Professional Documents
Culture Documents
Bajpai Et Al 2022 Seismic Performance Enhancement of Unreinforced Brick Masonry Buildings by Retrofitting With
Bajpai Et Al 2022 Seismic Performance Enhancement of Unreinforced Brick Masonry Buildings by Retrofitting With
Abstract: This study was aimed to conduct a thorough experimental investigation on the seismic performance of semiconfined unreinforced
brick masonry (SC-URBM) building as a structural topology. Experiments were conducted on two identical full-scale single-story brick
masonry buildings: one is completely unreinforced (URBM), and the other is retrofitted with semiconfining horizontal and vertical reinforced
concrete (RC) elements (SC-URBM). Both buildings were subjected to FEMA 461 specified reverse slow-cyclic quasi-static loading protocol
to quantify the improved seismic performance of the SC-URBM building compared to the URBM building. From the experimental results,
ductility capacity, load carrying capacity, and energy dissipation capacity were evaluated, along with important observations such as failure
mechanisms from prepeak to postpeak regimes. The results and observation from the experiments demonstrate that the semiconfining
elements significantly enhance the energy dissipation capacity and ductility of the retrofitted SC-URBM building without compromising
its strength, thereby implying the superior performance of such buildings in comparison to URBM buildings. DOI: 10.1061/(ASCE)
ST.1943-541X.0003460. © 2022 American Society of Civil Engineers.
(a)
(b)
Fig. 3. Schematic diagram of (a) plan of both masonry buildings; and (b) details of section S-S’ (all dimensions in mm).
Fig. 4. Schematic diagram of SC-URBM building with horizontal and vertical RC bands at strategic locations (all dimensions in mm).
URBM and SC-URBM buildings. The buildings were cast on rec- the groove. Cementitious microconcrete [Renderoc RG of M/s
tangular RC strip footings on the laboratory’s strong floor. Each Fosroc, (Fosroc 2019)] was then poured into the grooves, with
footing was anchored to the strong floor using 12 bolts of 70 mm wooden plyboard shuttering, to create the RC bands. Figs. 6(b–d)
diameter (in shoulder) and made of high-strength steel (tensile illustrate the placing of steel bars, subsequent shuttering, and mi-
strength: 1,040 N), as shown in Fig. 3(a). Fig. 3(b) shows a sec- croconcreting process, respectively. A horizontal RC band was pro-
tional elevation of the building, highlighting the various vertical vided throughout at 0.5 m below the roof slab, i.e., in between the
dimensions. As can be seen from Fig. 3(a), with OP1 and OP2 in roof level and window sill level. Similarly, a horizontal band was
elevation, discontinuous lintel beams were provided just above the provided throughout at 0.5 m above the top of the foundation,
door and window levels, as is the common practice in nonengi- as shown in Fig. 4. The vertical RC bands were provided at some
neered URBM buildings found in India (Sinha and Brzev 2002; specific distances on the walls IP1 and IP2 (i.e., walls with no open-
Kaushik et al. 2006). ing), along the direction of the loading in order to create an approx-
The reinforcement details of the floor and roof slabs have been imately square confined panel. Also, for the walls OP1 and OP2
shown in Fig. 3(b). The detailing, including geometry and configu- (i.e., walls with one opening), the vertical bands were provided
ration, of the SC-URBM building after semiconfinement is shown in a way to get the maximum horizontal size of the confining
in Fig. 4. The sequence of construction works followed for both element considering the openings as shown in Fig. 4. The horizon-
building preparation is shown in Fig. 5. The buildings were con- tal bands are provided continuously through walls considering
structed side-by-side, followed by the placing of the precast roof the door opening and are also tied on both faces through 8 mm
slabs. Concrete blocks were placed on the top of both buildings {Fe 500 bar [IS 1786 (BIS 2008)]} bars, as discussed earlier.
for simulating live load as per relevant Indian standards [IS 875 All the vertical RC bands were connected to the roof and base slabs
(Part 2) (BIS 1987)]. by extending the grooves to the roof slab and the foundation,
although a full anchoring mechanism was not ensured. The full an-
choring mechanism may not be feasible for houses considered in
Strengthening Scheme Adopted for SC-URBM Building this work. The buildings considered for this retrofitting scheme
The strengthening scheme adopted with the RC bands for the usually have a layered brick foundation and a nominal plain cement
SC-URBM building is discussed in this subsection. The details concrete floor slab, where a proper anchoring may not be possible
of the construction scheme of the SC-URBM with vertical and hori- without adding external anchor blocks or a similar mechanism
zontal RC bands are illustrated in Fig. 6. At first, grooves of size (which may not be feasible and economical). So, in this case, the
50 mm × 50 mm were cut on both the inner and outer faces of the simple approach of drilling holes on the slab and extending the
walls, as shown in Fig. 6(a). Since the wall thickness was about bands was targeted.
230 mm, even after cutting the groves, the remaining portion of
the wall of size 130 mm was enough to provide stability at the con-
struction stage. On each groove, one 12 mm dia high yield strength Material Properties
deformed {HYSD, Fe500, [IS 1786 (BIS 2008)]} steel bar was The details of the material properties used in the construction are
placed centrally, and these bars were tied on both faces through provided in this subsection. The masonry buildings were con-
8 mm tor bars at a spacing of around 500 mm. Since a 50 mm × structed using solid clay burnt bricks, and mortar with a cement-
50 mm groove was adopted considering ease of constructability to-sand ratio of 1∶6. As one can notice, the chosen mortar represents
using the electric groove cutter, the diameter of the steel bar was a weak mortar for constructing masonry buildings. The purpose of
selected to provide a minimum clear cover (∼19 mm) within the choosing such weak mortar is to mimic the prevalent practice in
available groove size after placing the steel bar in the middle of commonly constructed nonengineered masonry buildings in rural
Fig. 5. Sequence of construction works: (a) side-by-side construction of URBM and SC-URBM buildings; (b) placing of roof slab; (c) test buildings
prepared for URBM and SC-URBM (with grooves for RC bands); and (d) final test buildings for both URBM and SC-URBM.
and suburban areas of India. The physical properties of masonry, and Rai (2014). Overall, the masonry sub-assemblage is weak in
constituent materials, and strengthening materials were evaluated tension, as is commonly known.
following relevant codal provisions. The average compressive
strength of the six mortar specimens was found to be 6.87 MPa Experimental Set-Up and Loading System
as per ASTMC109 [ASTM C109/C109M-11b (ASTM 2002)].
Table 1 provides the average test results of six pieces of brick units, The experimental program involved slow-cyclic tests of both
showing that the brick units follow Class A type brick as per Indian URBM and SC-URBM masonry buildings in the Pseudo Dynamic
Standard. The water absorption and compressive strength tests of Testing Facility of the Structural Engineering Laboratory, IIT
Kanpur. Displacement-controlled reverse cyclic loads were applied
brick units were conducted as per IS 3495 (Part 2) (BIS 1992c) and
laterally at the roof level of both buildings with the same boundary
IS 3495 (Part 1) (BIS 1992b).
conditions. The buildings were loaded with 1,000 k-N/500 mm
In order to understand the composite behavior of masonry walls,
stroke MTS servo-hydraulic actuators connected to the roof slabs
several other tests were conducted as per the relevant standards and
of the buildings and the strong (reaction) wall of the testing facility.
literature. These include the prism test, tension bond test, and
The details of the connection with the roof slab were done in such a
diagonal tensile test. Table 2 provides the average test results of
way that the load is transferred uniformly over the slab for both
six masonry sub-assemblages for the prism [IS 1905 (BIS 1998)]
loading and unloading sequences. The loading system used for
and diagonal tensile tests (ASTM 2007) and the average of nine test
the testing is as shown in Figs. 7(a and b). A steel beam section
results for the tension bond test (Khalaf 2005). One can notice that is used for load transfer, and the loading arrangement with the steel
the compressive strength of the masonry prism is about 4.18 MPa, beam section is further attached to steel plates for transferring load
while the Young’s modulus is about 1.24 GPa (COV 28%). The to the masonry roof slab.
secant modulus of elasticity at 75% of the ultimate compressive
strength of the masonry (usually considered between 40% and 75%
of the ultimate maximum compressive stress) is evaluated from the Instrumentation and Data Acquisition System
stress-strain curve and the average value is reported as Young’s The instrumentation system adopted for the slow-cyclic testing of
modulus. Further details about experiments can be found in Singhal both masonry buildings is shown in Fig. 8, and further details are
Fig. 6. Strengthening procedure adopted for SC-URBM building: (a) URBM building with 50 mm × 50 mm groove for RC bands; (b) building
with 12 mm dia HYSD bars in the groove and tie rods at a spacing of 500 mm; (c) shuttering for microconcreting; (d) SC-URBM building after
microconcreting with RC bands (on both sides); and (e) zoomed view of A.
Table 1. Geometric and mechanical properties of bricks shown in Fig. 9. In addition to the MTS actuator embedded with
Brick units (225 mm × 105.2 mm × 70.2 mm) Average values load cell and displacement transducer, linear variable differential
transformers (LVDTs) and wire potentiometers were used to mea-
Density (kg=m3 ) 1,885.49 (COV 3%)
Water absorption (%) 11.6 (COV 8.3%)
sure horizontal displacement and diagonal movement of the walls,
Compressive strength of bricks (MPa) 23.5 (COV 9.1%) respectively. As shown in Fig. 9, 10 LVDTs were used for the front
wall (wall OP1), 5 on each side of the wall. The purpose of putting
these LVDTs was to observe: (1) the deflection profile along the
Table 2. Results of masonry sub-assemblages test height of the wall, (2) if there is any slip between foundation and
wall, or between wall and roof slab, and (3) if there is any twisting
Masonry sub-assemblage tests Average values
or horizontal asymmetric movement developed due to application
Compressive strength (MPa) 4.18 (COV 9.3%) of the load. In the backwall (wall OP2), only one LVDT was used
Tension bond strength (MPa) 0.56 (COV 28%) at the roof level to measure the displacement in the middle of the
Diagonal tensile strength (MPa) 0.11 (COV 9.3%)
roof slab. In addition to the LVDTs, four wire potentiometers
(a) (b)
Fig. 7. Schematic diagram of (a) loading system used for testing; and (b) loading arrangement in the plan.
Loading Protocol
For testing the buildings, the loading history was adopted as per
FEMA 461 (FEMA 2007), which is suitable for the testing of hys-
Fig. 8. Global instrumentation system adopted.
teretic systems. Fig. 10(a) represents the loading history adopted
SC-URBM d6-LVDT_MIDDLE_SLAB
WALL-IP1
URBM
WALL-OP2
SC-URBM
URBM
WALL-OP1
WALL-OP1
URBM URBM
WALL-IP1
WALL-IP2
15 60
10 40
Displacement (mm)
Displacement (mm)
5 20
0 0
-5 -20
-10 -40
-15 -60
0 1000 2000 3000 4000 0 2000 4000 6000
(a) Time (Seconds) (b) Time (Seconds)
Fig. 10. Recorded loading history for: (a) URBM; and (b) SC-URBM buildings (as per FEMA 461).
200 200
100 100
Actuator Force (kN)
Actuator Force (kN)
SC-URBM
URBM Envelope Curve
0 0
Envelope Curve
-100 -100
-200 -200
-60 -40 -20 0 20 40 60 -60 -40 -20 0 20 40 60
(a) Roof Displacement (mm) (b) Roof Displacement (mm)
Fig. 11. Force-roof displacement behavior and envelope curve obtained from slow-cyclic tests on: (a) URBM building; and (b) SC-URBM building.
IP1_e IP1_i
~5 mm ~7 mm IP2_e
~ 12 mm
IP2_i
~ 12mm
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.
OP1_i
~ 10mm
OP2_e
OP1_e ~ 10mm
OP2_i
~ 8 mm ~ 12mm
IP2_i~
20 mm
No major
crack
No major OP2_e
crack OP1_e ~30 mm
~ 25mm
IP2_i
~50 mm
OP2_~
50mm
imminent if the displacement level was to be increased further. The the IP1 wall, which then again progressed in a stepped fashion.
test was therefore stopped for the URBM building at this stage. A similar type of failure was initiated on the interior side of the
For the SC-URBM building also, initially, horizontal flexural IP1 wall on lateral load reversal. Extensive cracking was observed
cracks appeared along the bed joint at the heel of the exterior of at the bottom of the sill level in the masonry panels of all walls till
(a) (b)
Fig. 14. Crack pattern observed for the (a) interior; and (b) exterior walls of URBM masonry system at ultimate displacement.
(a) (b)
Fig. 15. Crack pattern observed for the (a) interior; and (b) exterior walls of SC-URBM masonry system at ultimate displacement.
the SC-URBM reached its maximum capacity. Further damage was followed by rocking at the higher drift levels for the entire
observed at the end of the vertical bands since the band provided SC-URBM building (Fig. 13). The rocking of the SC-URBM
resistance against further crack propagation. So, the RC elements building seemed to continue until the band got separated from
(bands) of the SC-URBM suffered damage by resisting the further the foundation due to uplifting. Since the vertical band resisted fur-
developed stresses and holding the wall, while the walls continued ther developed stresses, there were no notable cracks on the ma-
to undergo deformation. Hence, the initial crack propagation was sonry blocks between the roof level and window sill level for
100 100
Lateral Load (kN)
-100 -100
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.
-200 -200
-60 -40 -20 0 20 40 60 -60 -40 -20 0 20 40 60
Peak Roof Displacement (mm) Peak Roof Displacement (mm)
(a) (b) (c)
Fig. 16. Envelope curve and bilinearization for (a) URBM building; (b) SC-URBM building; and (c) actual and idealized bilinear curve based on
ASTM (2011).
any of the in-plane walls of the SC-URBM building, thus prevent- and SC-URBM) are also shown in Figs. 16(a and b), along with the
ing the out-of-plane collapse even when the door opening was corresponding envelope curves. It is seen from these figures that both
present at the corner of the OP2 wall. Although vertical bands were idealizations are providing almost similar behavior.
not fully anchored to both roof slab and base slabs for the adopted
scheme, it actually helped to maintain the integrity of the super-
Ductility
structure to behave as a single unit along with the horizontal bands.
Further, the formation of sliding planes at the concrete-to-masonry Ductility ratio (μ) is given by the ratio of the ultimate displacement
interfaces was not observed. This may be due to the use of (Du ) to the yield displacement (Dy ) from the idealized bilinear
nonshrinkage high-strength concrete, which may have provided curve as shown in Fig. 16(c). The ultimate displacement (Du ) de-
enough frictional resistance at the interface. notes the displacement observed at load drop corresponding to 20%
of Fp or otherwise at the minimum strength degradation, which is
the last data point on the curve. Since the load drop did not exceed
Envelope Curves and Bilinearization
20% of Fp for both URBM and SC-URBM buildings, the last data
Figs. 16(a and b) show the envelope force-roof displacement curves point of the envelope curve was considered for the Du , and the cor-
for both buildings obtained by considering peak load during the responding load is the ultimate load denoted by Fu. Du is obtained
loading and unloading in the first loading cycle corresponding to as 12.53 and 48.85 mm for positive loading cycles, and 12.43 and
every displacement increment value. The strengths attained by the 48.2 mm for negative loading cycles, for the URBM and SC-
SC-URBM building are slightly higher than the URBM building. URBM buildings, respectively. For the URBM building, although
For the positive loading cycles, these values are 138.9 k-N for strength reduction due to cracking was not observed due to the
URBM and 157.9 k-N for SC-URBM buildings. For the negative ductile pattern of failure mode (flexural cracking followed by ten-
loading cycles, the corresponding values for URBM and SC- sion cracks in a stepped pattern), sudden out-of-plane wall collapse
URBM buildings are 135.4 k-N and 176.3 k-N, respectively. was imminent at higher displacement levels as described in the
Experimental force-displacement hysteretic behavior loops were observed failure modes of the URBM building. From Fig. 16(b),
fitted with envelope curves for both buildings in both positive and one can note that the SC-URBM building can sustain much larger
negative directions. The envelope curve was obtained from the deformations without posing any risk of collapse. In other words,
hysteretic force-displacement response by joining the displacement the ductility capacity (or post-yield deformation) of the SC-URBM
peaks of the first cycle of each amplitude in both positive and neg- building is significantly higher than that of the URBM building due
ative directions. In order to compare the experimental force- to the rocking mode. This behavior was seen even when the bars
deformation curve with the procedure available in various standards, were disconnected from the base of the SC-URBM building. In
bilinear idealization is adopted. This idealized force-deformation fact, the overall confining behavior provided the required integrity
curve is considered to derive the seismic performance parameters to make the superstructure behave as a single unit under the rocking
in the subsequent sections. It may be noted that the bilinear curve motion. This is of considerable importance from the seismic design
is an elastic-plastic curve that yields the same area as that of the point of view, as it indicates that the SC-URBM building can dis-
envelope curve till ultimate displacement (Du ). Two different ap- sipate a much higher amount of energy compared to the URBM
proaches are considered here to derive the bilinear force-deformation building.
curves. The procedure of bilinearization for the ASTM (2011) ap-
proach is as shown in Fig. 16(c), which is one of the well-recognized
Wall Stiffness Degradation
approaches. In this procedure, the force equal to 0.4 × the maximum
absolute load or peak load, denoted by Fp is considered as the first The initial stiffness of a wall is considered as the slope of the
cracking load (Fcr ). In the second approach, the bilinearization of envelope curve defined between the initial loading and the first
the envelope curve is based on IBC (2008), where the first cracking cracking load and can be estimated based on the idealization of
load (Fcr ) is assumed at 0.7 × Fp . The idealized bilinear curves IBC (2008) and ASTM (2011). Hence, the initial stiffness is
based on both procedures for both masonry buildings (i.e., URBM given by
jFþ − Although the building was made symmetric along the loading di-
i j þ jFi j
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.
K eff;i ¼ þ ð2Þ rection, the openings on the transverse walls were asymmetric
jDi j þ jD−
i j along the loading direction. So, in-plane loaded walls had different
where Fþ þ boundary constraints than the out-of-plane loaded walls. To detect
i = peak force with corresponding lateral displacement Di
for positive quadrant; and F− = peak force with corresponding lat- whether the buildings underwent any rotation, the rotation of the
i
eral displacement D− roof slab was estimated based on displacement measurements
i for negative quadrant for any ith loading
cycle. The SC-URBM building has relatively higher initial stiffness by the LVDTs attached to the left and right locations on the slab
[26.5% and 12% increase considering ASTM (2011) and IBC (i.e., the LVDTs d1 and d1’, as shown in Fig. 9). The rotation was
(2008) idealizations] compared to URBM due to the increase in obtained as the difference between these displacement mea-
strength by the incorporation of the confining elements. For the surements divided by the distance between the LVDTs. This slab
effective stiffness, the first stage of the stiffness degradation pattern rotation was computed for the various peak displacement ampli-
is observed to be the same for both buildings Fig. 17. However, the tudes, for both the negative and positive loading cycles. The varia-
SC-URBM building degraded to a much lower value of stiffness tion of this rotation with the corresponding story drift for both the
compared to the URBM building since the walls could undergo URBM and SC-URBM buildings is shown in Fig. 18. It is seen that
deformation even after reaching its strength due to the confining the rotation is slightly more for the URBM building compared to
elements.
Fp , Du , and drift corresponding to Du are listed in Table 3 for
both positive and negative loading cycles. The values of K ie , Dy , μ, Table 4. Bilinear parameters of buildings based on ASTM (2011)
and drift corresponding to Dy , based on ASTM (2011) and IBC Building K ie (k-N/mm) Dy (mm) μ θy (%)
(2008) idealizations, are given in Tables 4 and 5, respectively.
URBM(+) 121.82 0.97 12.92 0.03
The intersection point of two lines of the idealized bilinear
URBM(−) 132.55 1.08 11.51 0.04
envelope is considered, and the displacement corresponding to that SC_URBM(+) 128.69 1.07 45.65 0.04
point is the displacement at the elastic limit state (Dy ) as shown in SC_URBM(−) 217.58 0.81 59.51 0.03
Fig. 16(c). The bilinear parameters obtained based on both ap-
proaches, ASTM (2011) and IBC (2008), illustrate the improved
100
0.06
URBM
SC-URBM
0 0.04
0 20 40 60
Rotation (in degrees)
-0.04
Table 3. Peak load and ultimate displacement value of buildings
-0.06
Building Fp (k-N) Du (mm) θu (%) -0.4 -0.2 0 0.2 0.4
URBM(+) 138.90 12.53 0.42 Storey Drift (%)
URBM(−) 135.40 12.43 0.41
SC_URBM(+) 157.90 48.85 1.63 Fig. 18. Variation of rotation with story drift corresponding to peak
SC_URBM(−) 176.30 48.2 1.6 displacement amplitudes.
20000
1200 1200
800 800
10000
400 400
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.
0 0 0
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
(a) Peak Roof Displacement (mm) (b) Peak Roof Displacement (mm) (c) Average Displacement (mm)
Fig. 19. Dissipated energy versus peak roof displacement for (a) positive; (b) negative loading cycles; and (c) variation of cumulative dissipated
energy with average values of peak displacement.
the SC-URBM building. In other words, the presence of the RC The observed average damping at ultimate displacement is 12%
elements provided enhanced torsional rigidity to the building. The and 14% in positive loading cycles and 9.5% and 12% in negative
SC elements anchored in the roof slab inhibited the shear failure at loading cycles for the URBM and SC-URBM buildings, respec-
the roof-to-wall interface in the SC-URBM building and thereby tively. The higher value of damping for the URBM building is
reducing the torsional rotation. attributed to the fact that for this building, the damping observed
at higher displacements (10 mm to 12 mm) is higher due to the
extensive damage at those displacements. The testing of the URBM
Energy Dissipation and Equivalent Viscous Damping building was also stopped at that point where the building exhibited
From a seismic design point of view, it is crucial to have a better danger of collapse. However, the SC-URBM building could give
energy dissipation capacity for buildings. The energy dissipated for the same damping (10%) even for higher displacement amplitudes
a particular loading cycle can be calculated as the area enclosed by (till 19 mm) after initial elastic behavior. In this case, the experi-
the corresponding cycle of lateral load (actuator force) and roof ment continued till the ultimate displacement (50 mm) at which the
displacement from the hysteretic load-displacement plot of the damping observed was 8%. The SC-URBM building seemed not to
building. The average value of the energy dissipated for all loading pose a major danger of collapse even at this displacement level. So,
cycles of a particular peak displacement amplitude is considered the SC-URBM could give the same damping for higher displace-
here. The variation of the dissipated energy with different peak ment amplitudes compared to the URBM building, which enhanced
displacement amplitudes, both for positive and negative loading the energy dissipation capacity of the SC-URBM building consid-
cycles, is shown in Figs. 19(a and b), respectively. The variation erably as shown in Figs. 20(a and b).
of cumulative dissipated energy with average values of peak dis-
placement obtained for both loading cycles is shown in Fig. 19(c). Deformation Pattern
There is a linear increase in the energy dissipation for higher
In order to understand the deformation pattern along the height of
displacement values for both buildings. The energy dissipation
the buildings, the LVDT measurements obtained at various posi-
for SC-URBM building is significantly higher compared to URBM
tions along the height, as shown in Fig. 8, were analyzed. The aver-
building. URBM building appeared to be posing an imminent out-
age of the peak displacements from the LVDTs on both sides at a
of-plane wall failure at this displacement level. On the contrary, the
given height are used to generate the deformed shape. The de-
SC-URBM building behaved like a single unit and dissipated
formed shapes of the URBM and SC-URBM buildings are shown
energy through rocking motion even for the higher displacement
in Figs. 21(a and b), respectively. For both buildings, initially, the
amplitudes.
flexural deformation mode was dominating. However, for the
Since a narrower or wider hysteretic loop does not always help
SC-URBM building, from 1 to 3 mm displacement amplitudes,
in identifying how much energy is dissipated as it also depends on
a shear-type displacement profile was seen, which may be attrib-
lateral load resistance values, it is also important to compute the
uted to the lateral load resisting the action of SC elements after the
energy dissipation per loop or equivalent viscous damping ratio.
flexural cracking. The displacement at the base is comparatively
Based on the experimentally observed force-deformation behavior
higher for the SC-URBM building when compared to the URBM
from the slow-cyclic tests, the equivalent viscous damping ratio is
building. Shear sliding of the roof slab for displacement greater
evaluated for both URBM and SC-URBM buildings for comparing
than 1.27 mm can also be observed for the URBM building.
their performance. The equivalent damping ratio or specific damp-
ing factor is evaluated based on the dissipated energy and strain
energy of the buildings (Chopra 2012). For the corresponding ith Theoretical Prediction
positive and negative loading cycles, the equivalent viscous
damping ratio (ζ eq ) is based on the dissipated energy (Ei ) and The maximum horizontal shear that can be resisted by a rocking
strain energy of (Esi ) of the corresponding cycle and is given as brick masonry wall failing under static in-plane loading may
follows: be approximated by introducing a proper stress distribution for
the masonry in compression and neglecting the tensile strength
ζ eq ¼ ð1=4πÞ × Ei =Esi ð3Þ of the bed joints (Magenes and Calvi 1997). The relation proposed
30 30
20 20
10 10
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.
0 0
0 10 20 30 40 50 0 10 20 30 40 50
(a) Peak Roof Displacement (mm) (b) Peak Roof Displacement (mm)
Fig. 20. Equivalent damping versus peak displacement in (a) positive; and (b) negative loading cycles.
4000 4000
Height of Specimen (mm)
0 0
0 1 2 3 4 0 1 2 3 4
(a) Displacement w.r.t base (mm) (b) Displacement w.r.t base (mm)
Fig. 21. Deformed shape of (a) URBM building; and (b) SC-URBM building for various peak displacements.
by Magenes and Calvi (1997) is considered here for the in-plane horizontal and vertical RC elements (SC-URBM). Both buildings
strength calculation and is given as follows: were subjected to reverse slow-cyclic quasi-static loading protocol
(FEMA 461) to study the improvements in the seismic performance
V r ¼ ðD × t=αv Þ × ðp=2Þ × ð1 − p=ðK × fu ÞÞ ð4Þ of the SC-URBM building when compared to the URBM building.
where D, t, and H0 = length, thickness, and effective height of the However, the study focused on the evaluation of only the in-plane
wall, respectively; and αv ¼ H0 =D. Further, p and f u are mean behavior as the out-of-plane inertial effect could not be simulated in
vertical stress on the wall (here calculated as 0.1 MPa) and com- the experiment. Also, if full anchorage of the band with roof and
pressive strength of the masonry, respectively. K is a parameter floor slabs could have been achieved, the failure mode could have
(with a value of 0.85) to take into account the vertical stress dis- been different.
tribution at the compressed toe. The in-plane strength of the rocking From the experimental results of both buildings, the following
wall is obtained as 76.3 kN. The experimental value for the SC- conclusions can be made:
URBM wall was found to be 83.6 kN, (i.e., a deviation of about • The observed hysteretic behavior represented a significant en-
9.6% from the calculated value). The analytical evaluation consid- hancement in ductility and energy dissipation capacity of the
ered is particularly for masonry walls with a flexural rocking mode SC-URBM building with an approximate increase in strength
of failure. Here, the effect of semiconfining elements is however of 14% and 30% for both positive and negative loading cycles
neglected since it requires further investigations, and its contribu- when compared with the URBM building.
tion to the in-plane strength is nominal. Further, the in-plane • The behavior of SC-URBM observed at the ultimate displace-
strength of a single rocking wall of the SC-URBM building is con- ment was stable due to the rocking mode and out-of-plane
sidered half of the average peak load obtained for the positive and collapse was not seen, unlike URBM building.
negative loading cycles. • Although vertical bands were not fully anchored to the roof
and base slabs for the adopted scheme of the SC-URBM
building, it was actually observed to behave as a single unit
Conclusions even at significantly higher displacement levels compared to
the URBM building. Hence, it actually enhanced the capability
An experimental study was conducted on two identical full-scale of the SC-URBM building to have significantly higher ductility
single-story brick masonry buildings: one was completely unrein- and energy dissipation capacity as compared to the URBM
forced (URBM), and the other was retrofitted with semiconfining building.
building. shear resistance of vertical elements of the lateral force resisting sys-
• The roof rotation observed was lower in the SC-URBM tems for buildings. ASTM E 2126. West Conshohocken, PA: ASTM.
building, which showed that the confining elements provided Bhattacharya, S., S. Nayak, and S. C. Dutta. 2014. “A critical review
increased torsional rigidity to the building along with symmet- of retrofitting methods for unreinforced masonry structures.” Int. J.
Disaster Risk Reduct. 7 (Mar): 51–67. https://doi.org/10.1016/j.ijdrr
ric behavior.
.2013.12.004.
• Enhanced energy dissipation capacity of SC-URBM was ob- BIS (Bureau of Indian Standards). 1987. Code of practice for design loads
served, which is 2.54 and 2.35 times that of the URBM building (other than earthquake) for buildings and structures—Imposed loads.
for positive and negative loading cycles, respectively. The IS 875 (Part 2). New Delhi, India: BIS.
cumulative energy dissipation for SC-URBM is 6.5 times the BIS (Bureau of Indian Standards). 1992a. Common burnt clay building
energy dissipation by URBM building. A significant increase bricks—Specification. IS 1077. New Delhi, India: BIS.
in the energy dissipation capacity of the SC-URBM building BIS (Bureau of Indian Standards). 1992b. Indian standard methods of test
through a rocking motion for higher displacement amplitudes of burnt clay building bricks: Part 1—Determination of compressive
was observed when compared with the URBM building. strength. IS 3495 (Part 1). New Delhi, India: BIS.
• Hysteretic damping was observed almost the same for both BIS (Bureau of Indian Standards). 1992c. Indian standard methods of test
buildings, but the semiconfined building could maintain the of burnt clay building bricks: Part 2—Determination of water absorp-
tion. IS 3495 (Part 2). New Delhi, India: BIS.
same damping (10%) for higher displacements (up to 19 mm)
BIS (Bureau of Indian Standards). 1993. Indian standard code of practice
after initial elastic behavior, beyond which a slight decrease was for earthquake resistant design and construction of buildings. IS 4326.
observed. The damping observed at ultimate displacement was New Delhi, India: BIS.
8%. So the SC-URBM building seemed to take further loads, BIS (Bureau of Indian Standards). 1998. Code of practice for structural
even though the experiment was stopped earlier. But the URBM use of unreinforced masonry (third revision). IS 1905. New Delhi,
building suffered almost total collapse near 12 mm displace- India: BIS.
ment. There was no danger of collapse observed for SC-URBM BIS (Bureau of Indian Standards). 2002. Criteria for earthquake resistant
building even at 50 mm displacement amplitude, at which the design of structure. IS 1893. New Delhi, India: BIS.
experiment was stopped. BIS (Bureau of Indian Standards). 2008. High strength deformed steel bars
• Deformed shapes of both buildings illustrated the lateral load- and wires for concrete reinforcement—Specification (fourth revision).
resisting action of semiconfining elements, whereas shear sliding IS 1786. New Delhi, India: BIS.
BIS (Bureau of Indian Standards). 2009. Seismic evaluation, repair and
of the roof slab was observed for the URBM building.
strengthening of masonry buildings—Guidelines. IS 13935. New Delhi,
• In-plane strength for rocking flexural mode of failure of masonry India: BIS.
pier proposed by Magenes and Calvi (1997) gives a conservative Borah, B., V. Singhal, and H. B. Kaushik. 2021. “Assessment of seismic
estimate for rocking pier of SC-URBM building. design provisions for confined masonry using experimental and numeri-
In summary, for the adopted scheme, the semiconfining ele- cal approaches.” Eng. Struct. 245 (Oct): 112864. https://doi.org/10
ments were found to be very effective in improving the overall .1016/j.engstruct.2021.112864.
behavior of masonry walls. The enhanced ductility and energy dis- Borri, A., M. Corradi, G. Castori, and A. Molinari. 2019. “Stainless steel
sipation capacity along with integrity and stability observed for the strip—A proposed shear reinforcement for masonry wall panels.”
SC-URBM building were notable, especially at the higher drift Constr. Build. Mater. 211 (Jun): 594–604. https://doi.org/10.1016/j
levels. Thus, from this study, it is evident that the proposed scheme .conbuildmat.2019.03.197.
of retrofitting the existing deficient URBM buildings is minimally Brzev, S. 2008. Earthquake-resistant confined masonry construction.
Kanpur, India: National Information Center for Earthquake Engineer-
intrusive, easily implementable, and economic while rendering a
ing, Indian Institute of Technology Kanpur.
significantly better seismic performance as compared to these origi- Brzev, S., M. Astroza, and O. Moroni. 2010. Evaluation of confined
nal buildings. masonry guidelines for earthquake-resistant housing. Oakland, CA:
Earthquake Engineering Research Institute.
Chopra, A. K. 2012. Dynamics of structures: Theory and applications
Data Availability Statement to earthquake engineering. 4th ed. Upper Saddle River, NJ: Pearson-
Prentice Hall.
All data, models, or code that support the findings of this study are Chourasia, A., S. Bhattacharyya, N. Bhandari, and P. Bhargava. 2016.
available from the corresponding author upon reasonable request. “Seismic performance of different masonry buildings: Full-scale exper-
imental study.” J. Perform. Constr. Facil. 30 (5): 04016006. https://doi
.org/10.1061/(ASCE)CF.1943-5509.0000850.
Corradi, M., A. Di Schino, A. Borri, and R. Rufini. 2018. “A review
Acknowledgments of the use of stainless steel for masonry repair and reinforcement.”
Constr. Build. Mater. 181 (Aug): 335–346. https://doi.org/10.1016/j
The authors gratefully acknowledge and appreciate the logistic .conbuildmat.2018.06.034.
support provided by the Structural Engineering Laboratory, IIT Cruz, O. A. I., and J. J. Perez Gavilan. 2021. “Seismic performance of
Kanpur, for smooth conduction of the experiment. confined masonry walls with joint reinforcement and aspect ratio:
FEMA 461. Washington, DC: FEMA. retrofitting of hollow brick masonry walls with reinforced high perfor-
Fosroc. 2019. “Fosroc renderoc órg/micro concrete repair.” Accessed mance mortar coatings.” Constr. Build. Mater. 141 (Jun): 619–630.
August 26, 2021. https://fosroc.com/api/datasheets/781/3. https://doi.org/10.1016/j.conbuildmat.2017.03.112.
Hidalgo-Leiva, D. A., A. Picado-Arguedas, and N. Sanchez-Vargas. 2021. Murty, C., R. Goswami, A. Vijayanarayanan, and V. Mehta. 2012. Some
“In-plane cyclic performance of confined partially grouted masonry concepts in earthquake behaviour of buildings, 9. Gandhinagar,
walls with joint and vertical reinforcement.” Eng. Struct. 245 (Oct): Gujarat: Gujarat State Disaster Management Authority.
112881. https://doi.org/10.1016/j.engstruct.2021.112881.
Singhal, V., and D. C. Rai. 2014. “Suitability of half-scale burnt clay bricks
IBC (International Building Code). 2008. International building code. Falls
for shake table tests on masonry walls.” J. Mater. Civ. Eng. 26 (4):
Church, VA: International Code Council.
644–657. https://doi.org/10.1061/(ASCE)MT.1943-5533.0000861.
Kaushik, H. B., K. Dasgupta, D. R. Sahoo, and G. Kharel. 2006. “Perfor-
Sinha, R., and S. N. Brzev. 2002. Housing report: Unreinforced brick
mance of structures during the Sikkim earthquake of 14 February
masonry building with reinforced concrete roof slab. India: World
2006.” Curr. Sci. 91 (4): 449–455.
Housing Encyclopedia, Earthquake Engineering Research Institute
Khalaf, F. M. 2005. “New test for determination of masonry tensile
(International Association for Earthquake Engineering) [EERI (IAEE)].
strength.” J. Mater. Civ. Eng. 6 (725): 725–732. https://doi.org/10
.1061/(ASCE)0899-1561(2005)17:6(725). Tomazevic, M., and I. Klemenc. 1997. “Seismic behaviour of confined
Koutromanos, I., M. Kyriakides, A. Stavridis, S. Billington, and P. B. masonry walls.” Earthquake Eng. Struct. Dyn. 26 (10): 1059–1071.
Shing. 2013. “Shake-table tests of a 3-story masonry-infilled RC frame https://doi.org/10.1002/(SICI)1096-9845(199710)26:10%3C1059::AID
retrofitted with composite materials.” J. Struct. Eng. 139 (8): 1340– -EQE694%3E3.0.CO;2-M.
1351. https://doi.org/10.1061/(ASCE)ST.1943-541X.0000689. Yoshimura, K., K. Kikuchi, M. Kuroki, L. Liu, and L. Ma. 2000. “Effect
Kumazawa, F., and M. Ohkubo. 2000. “Non linear characteristics of con- of wall reinforcements applied lateral force and vertical axial loads on
fined masonry walls with lateral reinforcement in mortar joints.” In seismic behaviour of confined concrete masonry walls.” In Proc., 12th
Proc., 12th World Conf. on Earthquake Engineering. Upper Hutt, World Conf. on Earthquake Engineering. Upper Hutt, New Zealand:
New Zealand: New Zealand Society for Earthquake Engineering. New Zealand Society for Earthquake Engineering.
Lizundia, B., et al. 2016. EERI earthquake reconnaissance team report: Yoshimura, K., K. Kikuchi, M. Kuroki, H. Nonaka, K. Kim, Y. Matsumoto,
M7.8 Gorkha, Nepal earthquake on April 25, 2015, and its aftershocks. T. Itai, W. Reezang, and L. Ma. 2003. “Experimental study on reinforc-
Oakland, CA: Earthquake Engineering Research Institute. ing methods for confined masonry walls subjected to seismic forces.”
Lucchini, S. S., L. Facconi, F. Minelli, and G. Plizzari. 2021. “Cyclic test In Proc., 9th North American Masonry Conf., 89–100. Boulder, Co:
on a full-scale unreinforced masonry building repaired with steel fiber- Masonry Society.
reinforced mortar coating.” J. Struct. Eng. 147 (6): 04021059. https:// Yoshimura, K., K. Kikuchi, T. Okamoto, and P. Sanchez. 1996. “Effect
doi.org/10.1061/(ASCE)ST.1943-541X.0003020. of vertical and horizontal wall reinforcement on seismic behavior of
Magenes, G., and G. M. Calvi. 1997. “In-plane seismic response confined concrete masonry walls.” In Proc., 11th World Conf. on Earth-
of brick masonry walls.” Earthquake Eng. Struct. Dyn. 26 (11): quake Engineering. Oxford: Pergamon.
1091–1112. https://doi.org/10.1002/(SICI)1096-9845(199711)26:11<1091 Zabala, F., L. Bustos, A. Masanet, and J. Santalucia. 2004. “Experimental
::AID-EQE693>3.0.CO;2-6. behaviour of masonry structural walls used in Argentina.” In Proc., 13th
Marinilli, A., and E. Castilla. 2004. “Experimental evaluation of confined World Conf. on Earthquake Engineering. Vancouver, BC: 13 WCEE
masonry walls with several confining-columns.” In Proc., 13th World Secretariat.