You are on page 1of 16

Seismic Performance Enhancement of Unreinforced Brick

Masonry Buildings by Retrofitting with Reinforced


Concrete Bands: Full Scale Experiments
Lakshmi Latha 1; Samit Ray-Chaudhuri 2; Suparno Mukhopadhyay, A.M.ASCE 3;
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

and Kunwar K. Bajpai 4

Abstract: This study was aimed to conduct a thorough experimental investigation on the seismic performance of semiconfined unreinforced
brick masonry (SC-URBM) building as a structural topology. Experiments were conducted on two identical full-scale single-story brick
masonry buildings: one is completely unreinforced (URBM), and the other is retrofitted with semiconfining horizontal and vertical reinforced
concrete (RC) elements (SC-URBM). Both buildings were subjected to FEMA 461 specified reverse slow-cyclic quasi-static loading protocol
to quantify the improved seismic performance of the SC-URBM building compared to the URBM building. From the experimental results,
ductility capacity, load carrying capacity, and energy dissipation capacity were evaluated, along with important observations such as failure
mechanisms from prepeak to postpeak regimes. The results and observation from the experiments demonstrate that the semiconfining
elements significantly enhance the energy dissipation capacity and ductility of the retrofitted SC-URBM building without compromising
its strength, thereby implying the superior performance of such buildings in comparison to URBM buildings. DOI: 10.1061/(ASCE)
ST.1943-541X.0003460. © 2022 American Society of Civil Engineers.

Introduction structures (ElGawady et al. 2004; Bhattacharya et al. 2014; Messali


et al. 2017). Some studies have considered the use of steel or fiber-
Unreinforced brick masonry (URBM) constructions form a signifi- reinforced mortar/concrete coating and engineered cementitious
cant portion of the entire spectrum of structural constructions composite overlays (Facconi and Minelli 2020; Lucchini et al.
around the world. The seismic response of the existing URBM 2021; Koutromanos et al. 2013) for strengthening masonry infill
buildings and the need for improvements in their seismic perfor- walls. Stainless steel reinforcing bars and high-strength steel cords
mance are of great concern. This is because URBM constructions have also been found to be useful for stabilizing and improving
do not provide adequate seismic performance and the seismic risk masonry wall performance (Corradi et al. 2018; Borri et al. 2019).
associated with such existing structures is very high. There are For load-bearing masonry structures, Indian standards [IS 4326
many factors that influence the seismic behavior of URBM build- (BIS 1993); IS 1893 (BIS 2002); IS 13935 (BIS 2009)] suggested
ings such as the geometry of the building, connection between RC elements and corner reinforcement for improving the seismic
walls, lateral stiffness, and nonstructural elements present (Murty performance in the absence of the relevant Indian standards for
et al. 2012). The seismic response of in-plane loaded walls is al- confined masonry (CM) constructions.
ways of major concern since they form the primary path for load Over the years, CM constructions have emerged to address the
transfer. Combinations of in-plane and out-of-plane damage may drawbacks of unconfined masonry and become an alternative for
also occur, causing damage to the corners, roof, and connection low-cost constructions (Brzev 2008). The main components of
between floor diaphragms and walls and often resulting in partial CM constructions include masonry walls (that act as gravity as well
or even total collapse of the structure (Lizundia et al. 2016). as lateral load-resisting system) and the confining elements. The
Different conventional strengthening techniques have been pro- confining elements do not require significant reinforcement and
posed so far to improve the seismic performance of existing URBM rigorous detailing, unlike reinforced concrete (RC) frame construc-
1
tions. As a result, the cost and labor involved in CM constructions
Ph.D. Scholar, Dept. of Civil Engineering, Indian Institute of Tech- are significantly less compared to RC frame constructions. With the
nology Kanpur, Kanpur, Uttar Pradesh 208016, India. Email: lakshmia@
superior merging of load-bearing walls and confining elements, it
iitk.ac.in
2
Professor, Dept. of Civil Engineering, Indian Institute of Technology
has been found that significant improvement in the structural
Kanpur, Kanpur, Uttar Pradesh 208016, India (corresponding author). behavior of CM constructions can be achieved, especially in terms
ORCID: https://orcid.org/0000-0003-0009-6201. Email: samitrc@iitk.ac.in of strength and ductility (Aguilar et al. 1996; Yoshimura et al. 1996,
3 2000; Brzev 2008). In particular, both vertical and horizontal RC
Assistant Professor, Dept. of Civil Engineering, Indian Institute of
Technology Kanpur, Kanpur, Uttar Pradesh 208016, India. Email: suparno@ (confining) elements accommodate the load transfer after the ma-
iitk.ac.in sonry panel reaches its maximum capacity, thus averting a sudden
4
Principal Scientific Officer, Dept. of Civil Engineering, Indian Institute disintegration of the walls.
of Technology Kanpur, Kanpur, Uttar Pradesh 208016, India. ORCID: Studies have also been carried out for understanding the perfor-
https://orcid.org/0000-0001-7141-230X. Email: kunwar@iitk.ac.in
mance of CM under cyclic lateral loads (Tomazevic and Klemenc
Note. This manuscript was submitted on September 29, 2021; ap-
proved on May 13, 2022; published online on September 23, 2022. Dis- 1997; Yoshimura et al. 2003; Zabala et al. 2004; Aguilar et al.
cussion period open until February 23, 2023; separate discussions must be 1996; Meli 1973; Marinilli and Castilla 2004; Kumazawa and
submitted for individual papers. This paper is part of the Journal of Ohkubo 2000; Meli et al. 2011; Chourasia et al. 2016; Cruz and
Structural Engineering, © ASCE, ISSN 0733-9445. Perez Gavilan 2021; Borah et al. 2021; Marques et al. 2020;

© ASCE 04022195-1 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

Fig. 2. Elevation and vertical section of an SC-URBM building.

masonry wall. Although similar strengthening schemes have been


Fig. 1. 3D realization of semiconfinement of internal and external
suggested for good construction practice [IS 4326 (BIS 1993);
walls of a typical SC-URBM building with RC elements.
IS 1893 (BIS 2002); IS 13935 (BIS 2009)], as per the authors’
knowledge, no systematic experimental investigation has taken
place to evaluate the lateral load-resisting capacity and ductility
Hidalgo-Leiva et al. 2021). From these works, it was concluded that capacity of such retrofitted buildings. The proposed scheme is en-
CM systems perform better than conventional URBM systems. For visioned to be suitable for low-rise buildings of regular/irregular
CM wall panels, the common failure mode was found to be the geometry, which are particularly constructed with weak mortars
initial flexural failure followed by the shear failure. A distribution such as those commonly found in India and neighboring countries.
of cracks was observed in masonry walls during the shear failure The proposed scheme may prevent the sudden collapse of buildings
mode. The vertical RC elements however found to resist the devel- even during major earthquakes.
oped stresses, thus resisting a sudden collapse of the structure The in-plane failure modes of SC-URBM buildings may be gov-
(Tomazevic and Klemenc 1997). Also, unlike in URBM buildings, erned by shear or flexural failure mechanisms depending on the
the out-of-plane failure or overturning of the panel was not com- anchorage of the semiconfining elements, vertical load on walls,
monly observed in CM buildings. Instead, the two-way arching and aspect ratio. The flexural failure mechanism is governed by hori-
mechanism (reducing the strength of out-of-plane walls) was ob- zontal cracking at mortar bed joints present on the tension side of the
served (Meli et al. 2011; Brzev et al. 2010). walls. There can be extensive cracking at vertical semiconfining
Although CM constructions have been proven to provide supe- elements. The location of vertical bands and effective anchorage of
rior seismic performance, retrofitting an existing URBM building vertical semiconfining elements to both roof and foundation may fur-
to behave as a CM building remains unpopular due to various ther influence the rocking behavior. In shear behavior, the dowel
reasons. It may be noted that any retrofitting method for existing action effect may be provided by the vertical elements. The develop-
masonry constructions needs to be economic, reliable, minimally ment of flexural cracking at the corners under tension reduces the
intrusive, and can be adopted in a quick manner. Further, these resisting section of a wall and may be followed by shear sliding fail-
methods need to be simple and convenient so that local masons ure of the wall. The shear failure mechanism of a wall may also be
can be trained quickly. characterized by distributed diagonal cracking. This failure is due to
The objectives of this work are to consider a retrofitting scheme loss of bond at the interface of mortar-brick and can also be due to
for the semiconfinement of existing URBM buildings in order to tensile cracking of masonry units. The horizontal and vertical bands
enhance the seismic performance and to experimentally investigate can resist the formation of such diagonal cracking and thus have been
the effectiveness of the scheme through full-scale tests. The semi- adopted in the proposed scheme.
confinement scheme was developed to provide a better integral
action of the confining elements and load-bearing masonry walls.
In this scheme, horizontal and vertical semiconfining (SC) RC Scope of This Study
elements/bands are considered at strategic locations for improving
seismic performance. The locations of SC elements are considered An experimental investigation has been carried out in this work
in such a way that these bands (1) do not hinder the critical sections with two full-scale one-room identical buildings, one unreinforced
of wall-like corners, (2) provide maximum confinement to all wall (URBM building), and the other retrofitted with the aforemen-
surface areas, and (3) create SC panels with aspect ratio approxi- tioned semiconfining elements (SC-URBM building). Slow-cyclic
mately close to unity (∼1). Fig. 1 represents a 3D rendering of the lateral loading tests have been performed on both buildings to
URBM building retrofitted with RC horizontal and vertical ele- evaluate the in-plane behavior of the masonry walls under the same
ments (henceforth termed as SC-URBM building). The scheme is simulated gravity loads. The loading history is considered as per
different from that of CM constructions in a sense that, in SC- FEMA461 (FEMA 2007) such that the buildings tend to give
URBM constructions, the confining elements do not run through the deformations as experienced under earthquake excitations. In
the entire width of the wall. Rather, these bands are constructed on particular, the emphasis is given to understand the hysteretic behav-
both faces of an existing wall and connected by tie rods to provide a ior, strength, ductility, energy dissipation, stiffness degradation,
composite action, as shown in Fig. 2. The proposed SC-URBM and associated failure mechanisms, so as to quantify the influence
constructions essentially provide some confining action to the of semiconfining solution in the in-plane behavior of the masonry

© ASCE 04022195-2 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


walls with a particular layout of the vertical and horizontal control. Dimensional control is an important aspect as bricks with
semiconfining elements. It should be noted that the study presented significant variation in dimensions will require different mortar
herein does not consider the out-of-plane inertial effects. thicknesses at different locations of the wall and thus, such a wall
will have variation in the masonry strength as compared to the
situation where better dimensional control is achieved.
Experimental Program Two identical solid full-scale single-story masonry prototypes
were built in the same manner. Both buildings have a plan with
Description of Masonry Buildings exterior dimensions of 3,900 mm by 4,500 mm, and a clear height
Both masonry buildings were constructed at the Structural Engi- from base to roof slab of 3,000 mm. Two openings, one window
neering Laboratory of IIT Kanpur by the same skilled mason fol- and one door, as shown in Fig. 3(a), were provided to simulate a
one-room living unit. Walls for the buildings are designated using
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

lowing common construction practices prevalent in India. Brick


units used for the construction were Class A type bricks [IS 1077 alphanumeric symbols IP1, IP2, OP1, and OP2, respectively, as
(BIS 1992a)] as commonly used for housing construction and pro- shown on the plan of both buildings in Fig. 3(a) for better clarity
cured from a reputed local source. At first, the brick units were of presentation. The subscript IP represents parallel in-plane walls
verified to comply with dimensional control, since it affects the and OP represents parallel out-of-plane walls, while the numeric
overall strength of a masonry building. It may be noted that often symbols correspond to the in-plane and out-of-plane wall number-
the bricks available in the market come with significant variation in ing. Further, IP1_e, IP2_e, OP1_e, and OP2_e are used to denote
dimensions and warping. As per [IS 1077 (BIS 1992a)], it is essen- the exterior surfaces of the walls, while IP1_i, IP2_i, OP1_i, and
tial to ensure the bricks are of good quality including dimensional OP2_i are used for the interior surfaces of the walls, for both the

(a)

(b)

Fig. 3. Schematic diagram of (a) plan of both masonry buildings; and (b) details of section S-S’ (all dimensions in mm).

© ASCE 04022195-3 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

Fig. 4. Schematic diagram of SC-URBM building with horizontal and vertical RC bands at strategic locations (all dimensions in mm).

URBM and SC-URBM buildings. The buildings were cast on rec- the groove. Cementitious microconcrete [Renderoc RG of M/s
tangular RC strip footings on the laboratory’s strong floor. Each Fosroc, (Fosroc 2019)] was then poured into the grooves, with
footing was anchored to the strong floor using 12 bolts of 70 mm wooden plyboard shuttering, to create the RC bands. Figs. 6(b–d)
diameter (in shoulder) and made of high-strength steel (tensile illustrate the placing of steel bars, subsequent shuttering, and mi-
strength: 1,040 N), as shown in Fig. 3(a). Fig. 3(b) shows a sec- croconcreting process, respectively. A horizontal RC band was pro-
tional elevation of the building, highlighting the various vertical vided throughout at 0.5 m below the roof slab, i.e., in between the
dimensions. As can be seen from Fig. 3(a), with OP1 and OP2 in roof level and window sill level. Similarly, a horizontal band was
elevation, discontinuous lintel beams were provided just above the provided throughout at 0.5 m above the top of the foundation,
door and window levels, as is the common practice in nonengi- as shown in Fig. 4. The vertical RC bands were provided at some
neered URBM buildings found in India (Sinha and Brzev 2002; specific distances on the walls IP1 and IP2 (i.e., walls with no open-
Kaushik et al. 2006). ing), along the direction of the loading in order to create an approx-
The reinforcement details of the floor and roof slabs have been imately square confined panel. Also, for the walls OP1 and OP2
shown in Fig. 3(b). The detailing, including geometry and configu- (i.e., walls with one opening), the vertical bands were provided
ration, of the SC-URBM building after semiconfinement is shown in a way to get the maximum horizontal size of the confining
in Fig. 4. The sequence of construction works followed for both element considering the openings as shown in Fig. 4. The horizon-
building preparation is shown in Fig. 5. The buildings were con- tal bands are provided continuously through walls considering
structed side-by-side, followed by the placing of the precast roof the door opening and are also tied on both faces through 8 mm
slabs. Concrete blocks were placed on the top of both buildings {Fe 500 bar [IS 1786 (BIS 2008)]} bars, as discussed earlier.
for simulating live load as per relevant Indian standards [IS 875 All the vertical RC bands were connected to the roof and base slabs
(Part 2) (BIS 1987)]. by extending the grooves to the roof slab and the foundation,
although a full anchoring mechanism was not ensured. The full an-
choring mechanism may not be feasible for houses considered in
Strengthening Scheme Adopted for SC-URBM Building this work. The buildings considered for this retrofitting scheme
The strengthening scheme adopted with the RC bands for the usually have a layered brick foundation and a nominal plain cement
SC-URBM building is discussed in this subsection. The details concrete floor slab, where a proper anchoring may not be possible
of the construction scheme of the SC-URBM with vertical and hori- without adding external anchor blocks or a similar mechanism
zontal RC bands are illustrated in Fig. 6. At first, grooves of size (which may not be feasible and economical). So, in this case, the
50 mm × 50 mm were cut on both the inner and outer faces of the simple approach of drilling holes on the slab and extending the
walls, as shown in Fig. 6(a). Since the wall thickness was about bands was targeted.
230 mm, even after cutting the groves, the remaining portion of
the wall of size 130 mm was enough to provide stability at the con-
struction stage. On each groove, one 12 mm dia high yield strength Material Properties
deformed {HYSD, Fe500, [IS 1786 (BIS 2008)]} steel bar was The details of the material properties used in the construction are
placed centrally, and these bars were tied on both faces through provided in this subsection. The masonry buildings were con-
8 mm tor bars at a spacing of around 500 mm. Since a 50 mm × structed using solid clay burnt bricks, and mortar with a cement-
50 mm groove was adopted considering ease of constructability to-sand ratio of 1∶6. As one can notice, the chosen mortar represents
using the electric groove cutter, the diameter of the steel bar was a weak mortar for constructing masonry buildings. The purpose of
selected to provide a minimum clear cover (∼19 mm) within the choosing such weak mortar is to mimic the prevalent practice in
available groove size after placing the steel bar in the middle of commonly constructed nonengineered masonry buildings in rural

© ASCE 04022195-4 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

Fig. 5. Sequence of construction works: (a) side-by-side construction of URBM and SC-URBM buildings; (b) placing of roof slab; (c) test buildings
prepared for URBM and SC-URBM (with grooves for RC bands); and (d) final test buildings for both URBM and SC-URBM.

and suburban areas of India. The physical properties of masonry, and Rai (2014). Overall, the masonry sub-assemblage is weak in
constituent materials, and strengthening materials were evaluated tension, as is commonly known.
following relevant codal provisions. The average compressive
strength of the six mortar specimens was found to be 6.87 MPa Experimental Set-Up and Loading System
as per ASTMC109 [ASTM C109/C109M-11b (ASTM 2002)].
Table 1 provides the average test results of six pieces of brick units, The experimental program involved slow-cyclic tests of both
showing that the brick units follow Class A type brick as per Indian URBM and SC-URBM masonry buildings in the Pseudo Dynamic
Standard. The water absorption and compressive strength tests of Testing Facility of the Structural Engineering Laboratory, IIT
Kanpur. Displacement-controlled reverse cyclic loads were applied
brick units were conducted as per IS 3495 (Part 2) (BIS 1992c) and
laterally at the roof level of both buildings with the same boundary
IS 3495 (Part 1) (BIS 1992b).
conditions. The buildings were loaded with 1,000 k-N/500 mm
In order to understand the composite behavior of masonry walls,
stroke MTS servo-hydraulic actuators connected to the roof slabs
several other tests were conducted as per the relevant standards and
of the buildings and the strong (reaction) wall of the testing facility.
literature. These include the prism test, tension bond test, and
The details of the connection with the roof slab were done in such a
diagonal tensile test. Table 2 provides the average test results of
way that the load is transferred uniformly over the slab for both
six masonry sub-assemblages for the prism [IS 1905 (BIS 1998)]
loading and unloading sequences. The loading system used for
and diagonal tensile tests (ASTM 2007) and the average of nine test
the testing is as shown in Figs. 7(a and b). A steel beam section
results for the tension bond test (Khalaf 2005). One can notice that is used for load transfer, and the loading arrangement with the steel
the compressive strength of the masonry prism is about 4.18 MPa, beam section is further attached to steel plates for transferring load
while the Young’s modulus is about 1.24 GPa (COV 28%). The to the masonry roof slab.
secant modulus of elasticity at 75% of the ultimate compressive
strength of the masonry (usually considered between 40% and 75%
of the ultimate maximum compressive stress) is evaluated from the Instrumentation and Data Acquisition System
stress-strain curve and the average value is reported as Young’s The instrumentation system adopted for the slow-cyclic testing of
modulus. Further details about experiments can be found in Singhal both masonry buildings is shown in Fig. 8, and further details are

© ASCE 04022195-5 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

Fig. 6. Strengthening procedure adopted for SC-URBM building: (a) URBM building with 50 mm × 50 mm groove for RC bands; (b) building
with 12 mm dia HYSD bars in the groove and tie rods at a spacing of 500 mm; (c) shuttering for microconcreting; (d) SC-URBM building after
microconcreting with RC bands (on both sides); and (e) zoomed view of A.

Table 1. Geometric and mechanical properties of bricks shown in Fig. 9. In addition to the MTS actuator embedded with
Brick units (225 mm × 105.2 mm × 70.2 mm) Average values load cell and displacement transducer, linear variable differential
transformers (LVDTs) and wire potentiometers were used to mea-
Density (kg=m3 ) 1,885.49 (COV 3%)
Water absorption (%) 11.6 (COV 8.3%)
sure horizontal displacement and diagonal movement of the walls,
Compressive strength of bricks (MPa) 23.5 (COV 9.1%) respectively. As shown in Fig. 9, 10 LVDTs were used for the front
wall (wall OP1), 5 on each side of the wall. The purpose of putting
these LVDTs was to observe: (1) the deflection profile along the
Table 2. Results of masonry sub-assemblages test height of the wall, (2) if there is any slip between foundation and
wall, or between wall and roof slab, and (3) if there is any twisting
Masonry sub-assemblage tests Average values
or horizontal asymmetric movement developed due to application
Compressive strength (MPa) 4.18 (COV 9.3%) of the load. In the backwall (wall OP2), only one LVDT was used
Tension bond strength (MPa) 0.56 (COV 28%) at the roof level to measure the displacement in the middle of the
Diagonal tensile strength (MPa) 0.11 (COV 9.3%)
roof slab. In addition to the LVDTs, four wire potentiometers

(a) (b)

Fig. 7. Schematic diagram of (a) loading system used for testing; and (b) loading arrangement in the plan.

© ASCE 04022195-6 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


(WP0, WP1, WP2, and WP3) were used on both side walls (IP1
and IP2), i.e., the walls along the direction of loading, as shown in
Fig. 9. The purpose of these sensors were to measure the interstory
drift between the foundation and roof slab on the walls along the
loading direction. All the sensors used were of reputed make
(https://measurementsensors.honeywell.com/). Data from all sen-
sors were collected using a National Instrument (www.ni.com) data
acquisition system. In addition to these measurement sensors, high-
resolution images and videos were collected during the tests.
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

Loading Protocol
For testing the buildings, the loading history was adopted as per
FEMA 461 (FEMA 2007), which is suitable for the testing of hys-
Fig. 8. Global instrumentation system adopted.
teretic systems. Fig. 10(a) represents the loading history adopted

SC-URBM d6-LVDT_MIDDLE_SLAB
WALL-IP1

URBM
WALL-OP2

SC-URBM
URBM
WALL-OP1
WALL-OP1

URBM URBM
WALL-IP1
WALL-IP2

Fig. 9. Instrumentation system adopted in detail.

15 60

10 40
Displacement (mm)

Displacement (mm)

5 20

0 0

-5 -20

-10 -40

-15 -60
0 1000 2000 3000 4000 0 2000 4000 6000
(a) Time (Seconds) (b) Time (Seconds)

Fig. 10. Recorded loading history for: (a) URBM; and (b) SC-URBM buildings (as per FEMA 461).

© ASCE 04022195-7 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


for the URBM building. A predetermined pattern of slow-cyclic Observed Failure Modes
displacements with increasing amplitudes was applied to the test
Major crack patterns observed in walls of both URBM and SC-
buildings. For the SC-URBM building, the loading history fol-
URBM buildings have been represented in Figs. 12 and 13, respec-
lowed is shown in Fig. 10(b). For both buildings, the loading
tively. The pictures of the crack patterns at ultimate displacement
was applied at a very slow rate, ranging from 0.5 mm=min for early
are shown in Figs. 14 and 15, from both inside the room (interior
cycles to 1 mm=min for later cycles, in order to optimize the testing
view) and outside the room (exterior view). The crack progression
time while not missing any significant damage/failure modes. The
for both buildings at the initial stages followed similar behavior.
smallest deformation amplitude of the loading history is ensured to
Initially, flexural cracks were formed at the base of both buildings
be safely smaller than the amplitude at which the lowest damage
and propagated along the loading direction. For the URBM build-
state is observed. The initial displacement amplitude of 0.5 mm was
ing, the flexural cracking was followed by tension cracks at the top
repeated for 10 loading cycles to get a better understanding of
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

of the in-plane wall and then by horizontal cracks on the out-of-


behavior in the elastic range and also to ensure the working of
plane wall, suggesting an imminent out-of-plane wall failure due
all instruments and sensors properly. Then, the experiment was
to the extension of cracks. On the other hand, for the SC-URBM
continued with two loading cycles for each amplitude of 1 mm,
building, no major crack was observed in its masonry blocks
2 mm, 3 mm, etc., as per FEMA 461 (FEMA 2007). One can notice
between the roof and window sill levels for both in-plane and
however that for the URBM building, the testing was stopped ear-
out-of-plane walls, as shown in Fig. 13. Subsequently, the building
lier in comparison to the SC-URBM building. The reason for this is
started rocking motion under cyclic loading. The failure observed
explained in the next section.
in both masonry buildings is discussed in detail in the following
paragraphs.
Results and Discussions For the URBM building, horizontal flexural cracks appeared
along the bed joint at the heel of the exterior of the IP1 wall, which
then progressed in a stepped fashion. A similar type of failure was
Hysteretic Behavior initiated on the interior side of the same wall on the reversal of
Figs. 11(a and b) represent the roof displacement versus actuator lateral load. The flexural tensile cracking developed at the heel
force for the URBM and SC-URBM buildings, respectively. From and then propagated to the toe. Initially, a small amount of finite
these plots, it is evident that both buildings demonstrated a linear flexural tensile strength (provided by the bed-joint mortar) was
behavior at the initial stage. Once the force level reached the yield dominating the crack over the walls to resist shear forces. However,
force, both buildings started showing nonlinear hysteretic behavior. this flexural strength was poor, and as a result, the wall cracked
For the URBM building, the experiment was stopped at around under tension. Tension cracks were observed in a stepped fashion
12 mm roof displacement (i.e., about 0.4% roof drift ratio). This on the IP2 wall, which initiated at the roof slab to the IP2 wall
is because a large block slip pattern (along with cracks in the cor- connection, where the strength reduction as a result of cracking
ners and flexural cracks in the transverse walls) was observed that may be small and may exhibit ductile response. The horizontal
was seemingly posing a global failure mechanism, and the building cracks progressed to out-of-plane wall OP2 as well, where the door
appeared to be on the verge of failure due to an imminent out-of- opening is provided near the wall corner, and this actually hindered
plane wall failure. For the SC-URBM building, the test was stopped the flow of force from one wall to the other. The opening of cracks
at a roof displacement of about 50 mm (1.7% of roof drift ratio). through the joints over the door lintel can also be seen in Fig. 12 for
The building was still carrying the load without any significant the interior of the OP2 wall (OP2i ). There was no transfer of load
reduction of strength. The test on the SC-URBM building was because of opening, and as a result, vertical cracks at IP2 and OP2
stopped as there was complete separation of the building from the wall intersections were observed. Loss of connection between IP2
base due to the rocking motion/partial uplifting of the building and wall and OP2 wall was also seen since vertical cracks were devel-
no increment of the load was observed. Overall, one can conclude oping between the IP2i wall and the OP2i wall, as seen in Fig. 12.
that the SC-URBM building was able to provide much better hys- Further, the loss of connection between wall and roof slab was ob-
teretic performance compared to the URBM building. The details served too. Since the mortar was weak and the crack in the in-plane
of failure modes, energy dissipation, and ductility are provided in wall was not perfectly horizontal (creating a perfect horizontal slip
the following subsections. surface), it was felt that the failure of the out-of-plane wall is

200 200

100 100
Actuator Force (kN)
Actuator Force (kN)

SC-URBM
URBM Envelope Curve
0 0
Envelope Curve

-100 -100

-200 -200
-60 -40 -20 0 20 40 60 -60 -40 -20 0 20 40 60
(a) Roof Displacement (mm) (b) Roof Displacement (mm)

Fig. 11. Force-roof displacement behavior and envelope curve obtained from slow-cyclic tests on: (a) URBM building; and (b) SC-URBM building.

© ASCE 04022195-8 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


OP2_i~
12mm

IP1_e IP1_i
~5 mm ~7 mm IP2_e
~ 12 mm

IP2_i
~ 12mm
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

OP1_i
~ 10mm

OP2_e
OP1_e ~ 10mm
OP2_i
~ 8 mm ~ 12mm

Fig. 12. Major crack pattern observed in URBM building.

Rocking observed for SC-


URBM building
IP1_i
IP1_e ~ 12 mm
~5 mm

IP2_i~
20 mm

No major
crack
No major OP2_e
crack OP1_e ~30 mm
~ 25mm

IP2_i
~50 mm
OP2_~
50mm

Fig. 13. Major crack pattern observed in SC-URBM building.

imminent if the displacement level was to be increased further. The the IP1 wall, which then again progressed in a stepped fashion.
test was therefore stopped for the URBM building at this stage. A similar type of failure was initiated on the interior side of the
For the SC-URBM building also, initially, horizontal flexural IP1 wall on lateral load reversal. Extensive cracking was observed
cracks appeared along the bed joint at the heel of the exterior of at the bottom of the sill level in the masonry panels of all walls till

© ASCE 04022195-9 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

(a) (b)

Fig. 14. Crack pattern observed for the (a) interior; and (b) exterior walls of URBM masonry system at ultimate displacement.

(a) (b)

Fig. 15. Crack pattern observed for the (a) interior; and (b) exterior walls of SC-URBM masonry system at ultimate displacement.

the SC-URBM reached its maximum capacity. Further damage was followed by rocking at the higher drift levels for the entire
observed at the end of the vertical bands since the band provided SC-URBM building (Fig. 13). The rocking of the SC-URBM
resistance against further crack propagation. So, the RC elements building seemed to continue until the band got separated from
(bands) of the SC-URBM suffered damage by resisting the further the foundation due to uplifting. Since the vertical band resisted fur-
developed stresses and holding the wall, while the walls continued ther developed stresses, there were no notable cracks on the ma-
to undergo deformation. Hence, the initial crack propagation was sonry blocks between the roof level and window sill level for

© ASCE 04022195-10 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


200 200

100 100
Lateral Load (kN)

Lateral Load (kN)


Envelope Curve
ASTM (2011)
IBC (2008) Envelope Curve
0 0 ASTM (2011)
IBC (2008)

-100 -100
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

-200 -200
-60 -40 -20 0 20 40 60 -60 -40 -20 0 20 40 60
Peak Roof Displacement (mm) Peak Roof Displacement (mm)
(a) (b) (c)

Fig. 16. Envelope curve and bilinearization for (a) URBM building; (b) SC-URBM building; and (c) actual and idealized bilinear curve based on
ASTM (2011).

any of the in-plane walls of the SC-URBM building, thus prevent- and SC-URBM) are also shown in Figs. 16(a and b), along with the
ing the out-of-plane collapse even when the door opening was corresponding envelope curves. It is seen from these figures that both
present at the corner of the OP2 wall. Although vertical bands were idealizations are providing almost similar behavior.
not fully anchored to both roof slab and base slabs for the adopted
scheme, it actually helped to maintain the integrity of the super-
Ductility
structure to behave as a single unit along with the horizontal bands.
Further, the formation of sliding planes at the concrete-to-masonry Ductility ratio (μ) is given by the ratio of the ultimate displacement
interfaces was not observed. This may be due to the use of (Du ) to the yield displacement (Dy ) from the idealized bilinear
nonshrinkage high-strength concrete, which may have provided curve as shown in Fig. 16(c). The ultimate displacement (Du ) de-
enough frictional resistance at the interface. notes the displacement observed at load drop corresponding to 20%
of Fp or otherwise at the minimum strength degradation, which is
the last data point on the curve. Since the load drop did not exceed
Envelope Curves and Bilinearization
20% of Fp for both URBM and SC-URBM buildings, the last data
Figs. 16(a and b) show the envelope force-roof displacement curves point of the envelope curve was considered for the Du , and the cor-
for both buildings obtained by considering peak load during the responding load is the ultimate load denoted by Fu. Du is obtained
loading and unloading in the first loading cycle corresponding to as 12.53 and 48.85 mm for positive loading cycles, and 12.43 and
every displacement increment value. The strengths attained by the 48.2 mm for negative loading cycles, for the URBM and SC-
SC-URBM building are slightly higher than the URBM building. URBM buildings, respectively. For the URBM building, although
For the positive loading cycles, these values are 138.9 k-N for strength reduction due to cracking was not observed due to the
URBM and 157.9 k-N for SC-URBM buildings. For the negative ductile pattern of failure mode (flexural cracking followed by ten-
loading cycles, the corresponding values for URBM and SC- sion cracks in a stepped pattern), sudden out-of-plane wall collapse
URBM buildings are 135.4 k-N and 176.3 k-N, respectively. was imminent at higher displacement levels as described in the
Experimental force-displacement hysteretic behavior loops were observed failure modes of the URBM building. From Fig. 16(b),
fitted with envelope curves for both buildings in both positive and one can note that the SC-URBM building can sustain much larger
negative directions. The envelope curve was obtained from the deformations without posing any risk of collapse. In other words,
hysteretic force-displacement response by joining the displacement the ductility capacity (or post-yield deformation) of the SC-URBM
peaks of the first cycle of each amplitude in both positive and neg- building is significantly higher than that of the URBM building due
ative directions. In order to compare the experimental force- to the rocking mode. This behavior was seen even when the bars
deformation curve with the procedure available in various standards, were disconnected from the base of the SC-URBM building. In
bilinear idealization is adopted. This idealized force-deformation fact, the overall confining behavior provided the required integrity
curve is considered to derive the seismic performance parameters to make the superstructure behave as a single unit under the rocking
in the subsequent sections. It may be noted that the bilinear curve motion. This is of considerable importance from the seismic design
is an elastic-plastic curve that yields the same area as that of the point of view, as it indicates that the SC-URBM building can dis-
envelope curve till ultimate displacement (Du ). Two different ap- sipate a much higher amount of energy compared to the URBM
proaches are considered here to derive the bilinear force-deformation building.
curves. The procedure of bilinearization for the ASTM (2011) ap-
proach is as shown in Fig. 16(c), which is one of the well-recognized
Wall Stiffness Degradation
approaches. In this procedure, the force equal to 0.4 × the maximum
absolute load or peak load, denoted by Fp is considered as the first The initial stiffness of a wall is considered as the slope of the
cracking load (Fcr ). In the second approach, the bilinearization of envelope curve defined between the initial loading and the first
the envelope curve is based on IBC (2008), where the first cracking cracking load and can be estimated based on the idealization of
load (Fcr ) is assumed at 0.7 × Fp . The idealized bilinear curves IBC (2008) and ASTM (2011). Hence, the initial stiffness is
based on both procedures for both masonry buildings (i.e., URBM given by

© ASCE 04022195-11 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


K ie ¼ Fcr =Dcr ð1Þ performance of the SC-URBM building compared to the URBM
building, as already discussed in the preceding sections. The drift
where Fcr = first cracking load; and Dcr = displacement corre- corresponding to yield displacement, θy , is almost the same for both
sponding to Fcr as shown in Fig. 16(c). These idealizations are used buildings, which corresponds to their similar yield displacement
for practical considerations, even though masonry is an inelastic values. However, drift θu , corresponding to ultimate displacement,
material and even for small deformation it does not exhibit linear is comparatively higher for SC-URBM buildings due to the en-
elastic behavior. The stiffness degradation in a masonry wall rep- hanced deformation capacity.
resents its strength degradation, which occurs gradually during the
loading process by crack initiation and propagation. The effective
stiffness (K eff;i ) was considered using the equation: Slab Rotation

jFþ − Although the building was made symmetric along the loading di-
i j þ jFi j
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

K eff;i ¼ þ ð2Þ rection, the openings on the transverse walls were asymmetric
jDi j þ jD−
i j along the loading direction. So, in-plane loaded walls had different
where Fþ þ boundary constraints than the out-of-plane loaded walls. To detect
i = peak force with corresponding lateral displacement Di
for positive quadrant; and F− = peak force with corresponding lat- whether the buildings underwent any rotation, the rotation of the
i
eral displacement D− roof slab was estimated based on displacement measurements
i for negative quadrant for any ith loading
cycle. The SC-URBM building has relatively higher initial stiffness by the LVDTs attached to the left and right locations on the slab
[26.5% and 12% increase considering ASTM (2011) and IBC (i.e., the LVDTs d1 and d1’, as shown in Fig. 9). The rotation was
(2008) idealizations] compared to URBM due to the increase in obtained as the difference between these displacement mea-
strength by the incorporation of the confining elements. For the surements divided by the distance between the LVDTs. This slab
effective stiffness, the first stage of the stiffness degradation pattern rotation was computed for the various peak displacement ampli-
is observed to be the same for both buildings Fig. 17. However, the tudes, for both the negative and positive loading cycles. The varia-
SC-URBM building degraded to a much lower value of stiffness tion of this rotation with the corresponding story drift for both the
compared to the URBM building since the walls could undergo URBM and SC-URBM buildings is shown in Fig. 18. It is seen that
deformation even after reaching its strength due to the confining the rotation is slightly more for the URBM building compared to
elements.
Fp , Du , and drift corresponding to Du are listed in Table 3 for
both positive and negative loading cycles. The values of K ie , Dy , μ, Table 4. Bilinear parameters of buildings based on ASTM (2011)
and drift corresponding to Dy , based on ASTM (2011) and IBC Building K ie (k-N/mm) Dy (mm) μ θy (%)
(2008) idealizations, are given in Tables 4 and 5, respectively.
URBM(+) 121.82 0.97 12.92 0.03
The intersection point of two lines of the idealized bilinear
URBM(−) 132.55 1.08 11.51 0.04
envelope is considered, and the displacement corresponding to that SC_URBM(+) 128.69 1.07 45.65 0.04
point is the displacement at the elastic limit state (Dy ) as shown in SC_URBM(−) 217.58 0.81 59.51 0.03
Fig. 16(c). The bilinear parameters obtained based on both ap-
proaches, ASTM (2011) and IBC (2008), illustrate the improved

Table 5. Bilinear parameters of buildings based on IBC (2008)


400
Building K ie (k-N/mm) Dy (mm) μ θy (%)
URBM
SC-URBM URBM(+) 112.59 1.05 11.93 0.03
300 URBM(−) 110.83 1.1 11.3 0.04
Stiffness (kN/mm)

SC_URBM(+) 125.12 1.10 44.41 0.04


SC_URBM(−) 126.92 0.89 54.16 0.03
200

100
0.06
URBM
SC-URBM
0 0.04
0 20 40 60
Rotation (in degrees)

Peak Roof Displacement (mm) 0.02

Fig. 17. Stiffness degradation with lateral displacement, in URBM and 0


SC-URBM buildings.
-0.02

-0.04
Table 3. Peak load and ultimate displacement value of buildings
-0.06
Building Fp (k-N) Du (mm) θu (%) -0.4 -0.2 0 0.2 0.4
URBM(+) 138.90 12.53 0.42 Storey Drift (%)
URBM(−) 135.40 12.43 0.41
SC_URBM(+) 157.90 48.85 1.63 Fig. 18. Variation of rotation with story drift corresponding to peak
SC_URBM(−) 176.30 48.2 1.6 displacement amplitudes.

© ASCE 04022195-12 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


2000 2000 30000

Cumulative Dissipated Energy (kNmm)


URBM
URBM URBM
SC-URBM
SC-URBM SC-URBM

Dissipated Energy (kNmm)


Dissipated Energy (kNmm)
1600 1600

20000
1200 1200

800 800
10000

400 400
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

0 0 0
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
(a) Peak Roof Displacement (mm) (b) Peak Roof Displacement (mm) (c) Average Displacement (mm)

Fig. 19. Dissipated energy versus peak roof displacement for (a) positive; (b) negative loading cycles; and (c) variation of cumulative dissipated
energy with average values of peak displacement.

the SC-URBM building. In other words, the presence of the RC The observed average damping at ultimate displacement is 12%
elements provided enhanced torsional rigidity to the building. The and 14% in positive loading cycles and 9.5% and 12% in negative
SC elements anchored in the roof slab inhibited the shear failure at loading cycles for the URBM and SC-URBM buildings, respec-
the roof-to-wall interface in the SC-URBM building and thereby tively. The higher value of damping for the URBM building is
reducing the torsional rotation. attributed to the fact that for this building, the damping observed
at higher displacements (10 mm to 12 mm) is higher due to the
extensive damage at those displacements. The testing of the URBM
Energy Dissipation and Equivalent Viscous Damping building was also stopped at that point where the building exhibited
From a seismic design point of view, it is crucial to have a better danger of collapse. However, the SC-URBM building could give
energy dissipation capacity for buildings. The energy dissipated for the same damping (10%) even for higher displacement amplitudes
a particular loading cycle can be calculated as the area enclosed by (till 19 mm) after initial elastic behavior. In this case, the experi-
the corresponding cycle of lateral load (actuator force) and roof ment continued till the ultimate displacement (50 mm) at which the
displacement from the hysteretic load-displacement plot of the damping observed was 8%. The SC-URBM building seemed not to
building. The average value of the energy dissipated for all loading pose a major danger of collapse even at this displacement level. So,
cycles of a particular peak displacement amplitude is considered the SC-URBM could give the same damping for higher displace-
here. The variation of the dissipated energy with different peak ment amplitudes compared to the URBM building, which enhanced
displacement amplitudes, both for positive and negative loading the energy dissipation capacity of the SC-URBM building consid-
cycles, is shown in Figs. 19(a and b), respectively. The variation erably as shown in Figs. 20(a and b).
of cumulative dissipated energy with average values of peak dis-
placement obtained for both loading cycles is shown in Fig. 19(c). Deformation Pattern
There is a linear increase in the energy dissipation for higher
In order to understand the deformation pattern along the height of
displacement values for both buildings. The energy dissipation
the buildings, the LVDT measurements obtained at various posi-
for SC-URBM building is significantly higher compared to URBM
tions along the height, as shown in Fig. 8, were analyzed. The aver-
building. URBM building appeared to be posing an imminent out-
age of the peak displacements from the LVDTs on both sides at a
of-plane wall failure at this displacement level. On the contrary, the
given height are used to generate the deformed shape. The de-
SC-URBM building behaved like a single unit and dissipated
formed shapes of the URBM and SC-URBM buildings are shown
energy through rocking motion even for the higher displacement
in Figs. 21(a and b), respectively. For both buildings, initially, the
amplitudes.
flexural deformation mode was dominating. However, for the
Since a narrower or wider hysteretic loop does not always help
SC-URBM building, from 1 to 3 mm displacement amplitudes,
in identifying how much energy is dissipated as it also depends on
a shear-type displacement profile was seen, which may be attrib-
lateral load resistance values, it is also important to compute the
uted to the lateral load resisting the action of SC elements after the
energy dissipation per loop or equivalent viscous damping ratio.
flexural cracking. The displacement at the base is comparatively
Based on the experimentally observed force-deformation behavior
higher for the SC-URBM building when compared to the URBM
from the slow-cyclic tests, the equivalent viscous damping ratio is
building. Shear sliding of the roof slab for displacement greater
evaluated for both URBM and SC-URBM buildings for comparing
than 1.27 mm can also be observed for the URBM building.
their performance. The equivalent damping ratio or specific damp-
ing factor is evaluated based on the dissipated energy and strain
energy of the buildings (Chopra 2012). For the corresponding ith Theoretical Prediction
positive and negative loading cycles, the equivalent viscous
damping ratio (ζ eq ) is based on the dissipated energy (Ei ) and The maximum horizontal shear that can be resisted by a rocking
strain energy of (Esi ) of the corresponding cycle and is given as brick masonry wall failing under static in-plane loading may
follows: be approximated by introducing a proper stress distribution for
the masonry in compression and neglecting the tensile strength
ζ eq ¼ ð1=4πÞ × Ei =Esi ð3Þ of the bed joints (Magenes and Calvi 1997). The relation proposed

© ASCE 04022195-13 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


Equivalent viscous damping ratio (%)
50 50

Equivalent Viscous Damping Ratio (%)


URBM URBM
SC-URBM SC-URBM
40 40

30 30

20 20

10 10
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

0 0
0 10 20 30 40 50 0 10 20 30 40 50
(a) Peak Roof Displacement (mm) (b) Peak Roof Displacement (mm)

Fig. 20. Equivalent damping versus peak displacement in (a) positive; and (b) negative loading cycles.

4000 4000
Height of Specimen (mm)

Height of Specimen (mm)


3000 3000

2000 0.09 2000 0.09


0.43
0.76 0.26
1.27 1.04
2.47 1.51
3.2 2.46
3.45
1000 1000

0 0
0 1 2 3 4 0 1 2 3 4
(a) Displacement w.r.t base (mm) (b) Displacement w.r.t base (mm)

Fig. 21. Deformed shape of (a) URBM building; and (b) SC-URBM building for various peak displacements.

by Magenes and Calvi (1997) is considered here for the in-plane horizontal and vertical RC elements (SC-URBM). Both buildings
strength calculation and is given as follows: were subjected to reverse slow-cyclic quasi-static loading protocol
(FEMA 461) to study the improvements in the seismic performance
V r ¼ ðD × t=αv Þ × ðp=2Þ × ð1 − p=ðK × fu ÞÞ ð4Þ of the SC-URBM building when compared to the URBM building.
where D, t, and H0 = length, thickness, and effective height of the However, the study focused on the evaluation of only the in-plane
wall, respectively; and αv ¼ H0 =D. Further, p and f u are mean behavior as the out-of-plane inertial effect could not be simulated in
vertical stress on the wall (here calculated as 0.1 MPa) and com- the experiment. Also, if full anchorage of the band with roof and
pressive strength of the masonry, respectively. K is a parameter floor slabs could have been achieved, the failure mode could have
(with a value of 0.85) to take into account the vertical stress dis- been different.
tribution at the compressed toe. The in-plane strength of the rocking From the experimental results of both buildings, the following
wall is obtained as 76.3 kN. The experimental value for the SC- conclusions can be made:
URBM wall was found to be 83.6 kN, (i.e., a deviation of about • The observed hysteretic behavior represented a significant en-
9.6% from the calculated value). The analytical evaluation consid- hancement in ductility and energy dissipation capacity of the
ered is particularly for masonry walls with a flexural rocking mode SC-URBM building with an approximate increase in strength
of failure. Here, the effect of semiconfining elements is however of 14% and 30% for both positive and negative loading cycles
neglected since it requires further investigations, and its contribu- when compared with the URBM building.
tion to the in-plane strength is nominal. Further, the in-plane • The behavior of SC-URBM observed at the ultimate displace-
strength of a single rocking wall of the SC-URBM building is con- ment was stable due to the rocking mode and out-of-plane
sidered half of the average peak load obtained for the positive and collapse was not seen, unlike URBM building.
negative loading cycles. • Although vertical bands were not fully anchored to the roof
and base slabs for the adopted scheme of the SC-URBM
building, it was actually observed to behave as a single unit
Conclusions even at significantly higher displacement levels compared to
the URBM building. Hence, it actually enhanced the capability
An experimental study was conducted on two identical full-scale of the SC-URBM building to have significantly higher ductility
single-story brick masonry buildings: one was completely unrein- and energy dissipation capacity as compared to the URBM
forced (URBM), and the other was retrofitted with semiconfining building.

© ASCE 04022195-14 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


• The parameters used for representing the building behavior References
under earthquakes are sensitive to bilinear idealization assump-
tions. The IBC (2008) idealization is found to give lower elastic Aguilar, G., R. Meli, R. Diaz, and R. Vazquez-Del-Mercado. 1996. “Influ-
stiffness and ductility as compared to the ASTM (2011) ence of horizontal reinforcement on the behaviour of confined masonry
walls.” In Proc., 11th Conf. on Earthquake Engineering. Oxford:
idealization.
Pergamon.
• The initial stiffness for the SC-URBM building is observed to be ASTM. 2002. Standard test method for compressive strength of hydraulic
higher [26.5% and 12% increase considering ASTM (2011) and cement mortars (using 2-in. or [50-mm] cube specimens). ASTM C109/
IBC (2008) idealizations] than the URBM building due to the C109M-11b. West Conshohocken, PA: ASTM.
addition of semiconfining elements. Linear degradation with a ASTM. 2007. Standard test method for diagonal tension (shear) in ma-
much lower slope was obtained for the higher displacements due sonry assemblages. ASTM E 519-07. West Conshohocken, PA: ASTM.
to the enhanced deformation capacity of the SC-URBM ASTM. 2011. Standard test methods for cyclic (reversed) load test for
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

building. shear resistance of vertical elements of the lateral force resisting sys-
• The roof rotation observed was lower in the SC-URBM tems for buildings. ASTM E 2126. West Conshohocken, PA: ASTM.
building, which showed that the confining elements provided Bhattacharya, S., S. Nayak, and S. C. Dutta. 2014. “A critical review
increased torsional rigidity to the building along with symmet- of retrofitting methods for unreinforced masonry structures.” Int. J.
Disaster Risk Reduct. 7 (Mar): 51–67. https://doi.org/10.1016/j.ijdrr
ric behavior.
.2013.12.004.
• Enhanced energy dissipation capacity of SC-URBM was ob- BIS (Bureau of Indian Standards). 1987. Code of practice for design loads
served, which is 2.54 and 2.35 times that of the URBM building (other than earthquake) for buildings and structures—Imposed loads.
for positive and negative loading cycles, respectively. The IS 875 (Part 2). New Delhi, India: BIS.
cumulative energy dissipation for SC-URBM is 6.5 times the BIS (Bureau of Indian Standards). 1992a. Common burnt clay building
energy dissipation by URBM building. A significant increase bricks—Specification. IS 1077. New Delhi, India: BIS.
in the energy dissipation capacity of the SC-URBM building BIS (Bureau of Indian Standards). 1992b. Indian standard methods of test
through a rocking motion for higher displacement amplitudes of burnt clay building bricks: Part 1—Determination of compressive
was observed when compared with the URBM building. strength. IS 3495 (Part 1). New Delhi, India: BIS.
• Hysteretic damping was observed almost the same for both BIS (Bureau of Indian Standards). 1992c. Indian standard methods of test
buildings, but the semiconfined building could maintain the of burnt clay building bricks: Part 2—Determination of water absorp-
tion. IS 3495 (Part 2). New Delhi, India: BIS.
same damping (10%) for higher displacements (up to 19 mm)
BIS (Bureau of Indian Standards). 1993. Indian standard code of practice
after initial elastic behavior, beyond which a slight decrease was for earthquake resistant design and construction of buildings. IS 4326.
observed. The damping observed at ultimate displacement was New Delhi, India: BIS.
8%. So the SC-URBM building seemed to take further loads, BIS (Bureau of Indian Standards). 1998. Code of practice for structural
even though the experiment was stopped earlier. But the URBM use of unreinforced masonry (third revision). IS 1905. New Delhi,
building suffered almost total collapse near 12 mm displace- India: BIS.
ment. There was no danger of collapse observed for SC-URBM BIS (Bureau of Indian Standards). 2002. Criteria for earthquake resistant
building even at 50 mm displacement amplitude, at which the design of structure. IS 1893. New Delhi, India: BIS.
experiment was stopped. BIS (Bureau of Indian Standards). 2008. High strength deformed steel bars
• Deformed shapes of both buildings illustrated the lateral load- and wires for concrete reinforcement—Specification (fourth revision).
resisting action of semiconfining elements, whereas shear sliding IS 1786. New Delhi, India: BIS.
BIS (Bureau of Indian Standards). 2009. Seismic evaluation, repair and
of the roof slab was observed for the URBM building.
strengthening of masonry buildings—Guidelines. IS 13935. New Delhi,
• In-plane strength for rocking flexural mode of failure of masonry India: BIS.
pier proposed by Magenes and Calvi (1997) gives a conservative Borah, B., V. Singhal, and H. B. Kaushik. 2021. “Assessment of seismic
estimate for rocking pier of SC-URBM building. design provisions for confined masonry using experimental and numeri-
In summary, for the adopted scheme, the semiconfining ele- cal approaches.” Eng. Struct. 245 (Oct): 112864. https://doi.org/10
ments were found to be very effective in improving the overall .1016/j.engstruct.2021.112864.
behavior of masonry walls. The enhanced ductility and energy dis- Borri, A., M. Corradi, G. Castori, and A. Molinari. 2019. “Stainless steel
sipation capacity along with integrity and stability observed for the strip—A proposed shear reinforcement for masonry wall panels.”
SC-URBM building were notable, especially at the higher drift Constr. Build. Mater. 211 (Jun): 594–604. https://doi.org/10.1016/j
levels. Thus, from this study, it is evident that the proposed scheme .conbuildmat.2019.03.197.
of retrofitting the existing deficient URBM buildings is minimally Brzev, S. 2008. Earthquake-resistant confined masonry construction.
Kanpur, India: National Information Center for Earthquake Engineer-
intrusive, easily implementable, and economic while rendering a
ing, Indian Institute of Technology Kanpur.
significantly better seismic performance as compared to these origi- Brzev, S., M. Astroza, and O. Moroni. 2010. Evaluation of confined
nal buildings. masonry guidelines for earthquake-resistant housing. Oakland, CA:
Earthquake Engineering Research Institute.
Chopra, A. K. 2012. Dynamics of structures: Theory and applications
Data Availability Statement to earthquake engineering. 4th ed. Upper Saddle River, NJ: Pearson-
Prentice Hall.
All data, models, or code that support the findings of this study are Chourasia, A., S. Bhattacharyya, N. Bhandari, and P. Bhargava. 2016.
available from the corresponding author upon reasonable request. “Seismic performance of different masonry buildings: Full-scale exper-
imental study.” J. Perform. Constr. Facil. 30 (5): 04016006. https://doi
.org/10.1061/(ASCE)CF.1943-5509.0000850.
Corradi, M., A. Di Schino, A. Borri, and R. Rufini. 2018. “A review
Acknowledgments of the use of stainless steel for masonry repair and reinforcement.”
Constr. Build. Mater. 181 (Aug): 335–346. https://doi.org/10.1016/j
The authors gratefully acknowledge and appreciate the logistic .conbuildmat.2018.06.034.
support provided by the Structural Engineering Laboratory, IIT Cruz, O. A. I., and J. J. Perez Gavilan. 2021. “Seismic performance of
Kanpur, for smooth conduction of the experiment. confined masonry walls with joint reinforcement and aspect ratio:

© ASCE 04022195-15 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195


An experimental study.” Eng. Struct. 242 (Sep): 112484. https://doi.org Conf. on Earthquake Engineering. Vancouver, BC: 13 WCEE
/10.1016/j.engstruct.2021.112484. Secretariat.
ElGawady, M., P. Lestuzzi, and M. Badoux. 2004. “A review of conven- Marques, R., J. M. Pereira, and P. B. Loureno. 2020. “Lateral in-plane seis-
tional seismic retrofitting techniques for URM.” In Proc., 13th Int. Brick mic response of confined masonry walls: From numerical to backbone
and Block Masonry Conf. Amsterdam, Netherlands. Eindhoven: Tech- models.” Eng. Struct. 221 (Oct): 111098. https://doi.org/10.1016/j
nische Universiteit Eindhoven. .engstruct.2020.111098.
Facconi, L., and F. Minelli. 2020. “Retrofitting RC infills by a glass fiber Meli, R. 1973. “Behaviour of masonry walls under lateral loads.”
mesh reinforced overlay and steel dowels: Experimental and numerical In Proc., 5th World Conf. on Earthquake Engineering. Rome, Italy:
study.” Constr. Build. Mater. 231 (Jan): 117–133. https://doi.org/10 Edigraf.
.1016/j.conbuildmat.2019.117133. Meli, R., et al. 2011. “Seismic design guide for low-rise confined masonry
FEMA. 2007. Interim testing protocols for determining the seismic perfor- buildings.” Accessed August, 2011. www.confinedmasonry.org/.
mance characteristics of structural and nonstructural components. Messali, F., G. Metelli, and G. Plizzari. 2017. “Experimental results on the
Downloaded from ascelibrary.org by "Indian Institute of Technology, Kanpur" on 09/29/23. Copyright ASCE. For personal use only; all rights reserved.

FEMA 461. Washington, DC: FEMA. retrofitting of hollow brick masonry walls with reinforced high perfor-
Fosroc. 2019. “Fosroc renderoc órg/micro concrete repair.” Accessed mance mortar coatings.” Constr. Build. Mater. 141 (Jun): 619–630.
August 26, 2021. https://fosroc.com/api/datasheets/781/3. https://doi.org/10.1016/j.conbuildmat.2017.03.112.
Hidalgo-Leiva, D. A., A. Picado-Arguedas, and N. Sanchez-Vargas. 2021. Murty, C., R. Goswami, A. Vijayanarayanan, and V. Mehta. 2012. Some
“In-plane cyclic performance of confined partially grouted masonry concepts in earthquake behaviour of buildings, 9. Gandhinagar,
walls with joint and vertical reinforcement.” Eng. Struct. 245 (Oct): Gujarat: Gujarat State Disaster Management Authority.
112881. https://doi.org/10.1016/j.engstruct.2021.112881.
Singhal, V., and D. C. Rai. 2014. “Suitability of half-scale burnt clay bricks
IBC (International Building Code). 2008. International building code. Falls
for shake table tests on masonry walls.” J. Mater. Civ. Eng. 26 (4):
Church, VA: International Code Council.
644–657. https://doi.org/10.1061/(ASCE)MT.1943-5533.0000861.
Kaushik, H. B., K. Dasgupta, D. R. Sahoo, and G. Kharel. 2006. “Perfor-
Sinha, R., and S. N. Brzev. 2002. Housing report: Unreinforced brick
mance of structures during the Sikkim earthquake of 14 February
masonry building with reinforced concrete roof slab. India: World
2006.” Curr. Sci. 91 (4): 449–455.
Housing Encyclopedia, Earthquake Engineering Research Institute
Khalaf, F. M. 2005. “New test for determination of masonry tensile
(International Association for Earthquake Engineering) [EERI (IAEE)].
strength.” J. Mater. Civ. Eng. 6 (725): 725–732. https://doi.org/10
.1061/(ASCE)0899-1561(2005)17:6(725). Tomazevic, M., and I. Klemenc. 1997. “Seismic behaviour of confined
Koutromanos, I., M. Kyriakides, A. Stavridis, S. Billington, and P. B. masonry walls.” Earthquake Eng. Struct. Dyn. 26 (10): 1059–1071.
Shing. 2013. “Shake-table tests of a 3-story masonry-infilled RC frame https://doi.org/10.1002/(SICI)1096-9845(199710)26:10%3C1059::AID
retrofitted with composite materials.” J. Struct. Eng. 139 (8): 1340– -EQE694%3E3.0.CO;2-M.
1351. https://doi.org/10.1061/(ASCE)ST.1943-541X.0000689. Yoshimura, K., K. Kikuchi, M. Kuroki, L. Liu, and L. Ma. 2000. “Effect
Kumazawa, F., and M. Ohkubo. 2000. “Non linear characteristics of con- of wall reinforcements applied lateral force and vertical axial loads on
fined masonry walls with lateral reinforcement in mortar joints.” In seismic behaviour of confined concrete masonry walls.” In Proc., 12th
Proc., 12th World Conf. on Earthquake Engineering. Upper Hutt, World Conf. on Earthquake Engineering. Upper Hutt, New Zealand:
New Zealand: New Zealand Society for Earthquake Engineering. New Zealand Society for Earthquake Engineering.
Lizundia, B., et al. 2016. EERI earthquake reconnaissance team report: Yoshimura, K., K. Kikuchi, M. Kuroki, H. Nonaka, K. Kim, Y. Matsumoto,
M7.8 Gorkha, Nepal earthquake on April 25, 2015, and its aftershocks. T. Itai, W. Reezang, and L. Ma. 2003. “Experimental study on reinforc-
Oakland, CA: Earthquake Engineering Research Institute. ing methods for confined masonry walls subjected to seismic forces.”
Lucchini, S. S., L. Facconi, F. Minelli, and G. Plizzari. 2021. “Cyclic test In Proc., 9th North American Masonry Conf., 89–100. Boulder, Co:
on a full-scale unreinforced masonry building repaired with steel fiber- Masonry Society.
reinforced mortar coating.” J. Struct. Eng. 147 (6): 04021059. https:// Yoshimura, K., K. Kikuchi, T. Okamoto, and P. Sanchez. 1996. “Effect
doi.org/10.1061/(ASCE)ST.1943-541X.0003020. of vertical and horizontal wall reinforcement on seismic behavior of
Magenes, G., and G. M. Calvi. 1997. “In-plane seismic response confined concrete masonry walls.” In Proc., 11th World Conf. on Earth-
of brick masonry walls.” Earthquake Eng. Struct. Dyn. 26 (11): quake Engineering. Oxford: Pergamon.
1091–1112. https://doi.org/10.1002/(SICI)1096-9845(199711)26:11<1091 Zabala, F., L. Bustos, A. Masanet, and J. Santalucia. 2004. “Experimental
::AID-EQE693>3.0.CO;2-6. behaviour of masonry structural walls used in Argentina.” In Proc., 13th
Marinilli, A., and E. Castilla. 2004. “Experimental evaluation of confined World Conf. on Earthquake Engineering. Vancouver, BC: 13 WCEE
masonry walls with several confining-columns.” In Proc., 13th World Secretariat.

© ASCE 04022195-16 J. Struct. Eng.

J. Struct. Eng., 2022, 148(12): 04022195

You might also like