You are on page 1of 1

2024 AREA FESTIVAL OF TALENTS (TECHNOLYMPICS)

SINGLE LINE DIAGRAM LOAD SCHEDULE


LEYECO , 60Hz RATING SIZE WIRE/PIPE
PROTECTION
230 VAC, 1 PHASE CKT. B. RATING
CIRCUIT NUMBER LOAD DESCRIPTION
VOLT - mm2 mm2
s3w s1 M AMPERE
VOLT AMPERE
(THHN) PIPE
A.T. POLE
s3 1 s3w
1 LIGHTING OUTLET 140 230 0.6 2.0 16 20 2
PANEL BOARD 2 CONVENIENCE OUTLET 1440 230 6.2 3.5 16 20 2
3 1.5 - HP AIR CONDITION UNIT 2300 230 10 5.5 16 30 2
40 AT TOTAL: 3880 230 16.87
COMPUTATIONS
20 AT
s2 20 AT 30 AT
1 L.O.
C.O. 2 3 A.C.U.
TOTAL NET COMPUTED LOAD: = 3880 VA
TOTAL NET CURRENT:
= 16.87 A
SERVICE FEEDER FOR ADMIN/OWNER
16.87 A
Lighting Layout USE 2 – 8.0 mm2 THHN @ 21 mmø EMT PIPE
SERVICE EQUIPMENT ADMIN/OWNER
16.87 A
USE 1 – 40 AT, 2 POLE, 230 VAC, MCB
2 3 A.C.U.
SPECIFICATIONS
1. ALL ELECTRICAL WORKS AND EQUIPMENT SHALL CONFORM WITH THE LATEST
EDITION OF THE PHILIPPINES ELECTRICAL CODE - PART, LEYECO II,
ALL INSTALLATION/CONSTRUCTION WORKS SHALL BE UNDER SUPERVISION OF A
REGISTERED ELECTRICAL ENGINEER (REE)/PROFESSIONAL
2. ELECTRICAL ENGINEER (PEE) OR REGISTERED ELECTRICIAN (RME)
3. MINIMUM SIZE WIRE SHALL BE 2 mm2 (No. 14 AWG) AND 3.5 mm2 (No. 12 AWG)
FOR LIGHTING AND CONVENIENCE OUTLETS, RESPECTIVELY
4. MAIN SERVICE ENTRANCE SHALL BE 325 mm2 THW at 80 mm ø RSC
5.UNLESS SHOWN IN THE PLAN, ALL WIRING SHALL BE IN STANDARD RSC. PIPE/EMT
INSTALLED INSIDE THE CEILING OR RUN EMBEDDED INSIDE WALLS OR UNDER FLOOR
Power Layout EQUIPMENT SHALL INSTALLATION:
LEGEND: SWITCHES/CONVENIENCE OUTLETS/ACU OUTLETS/
LOCATION PLAN s1
s2
- ONE GANG SWITCH
- TWO GANG SWITCH PANEL BOARD SHALL BE FLUSH MOUNTED
7. MOUNTING HEIGHT OF EQUIPMENT:
s3 - THREE GANG SWITCH
s3W - THREE WAY SWITCH
- 10 W ROUND SQUARE LED LIGHT
CONVENIENCE OUTLETS - 300mm ABOVE FINISH FLOOR LINE
s4W - FOUR WAY SWITCH
- 20 W CIRCLE LED LIGHT SWITCH OUTLETS - 1500mm ABOVE FINISH FLOOR LINE
- LIGHTING PANEL BOARD
- POWER PANEL BOARD - 10 W CIRCLE LED LIGHT ACU OUTLETS - LEFT HAND SIDE OF ACU UNIT
St
a .C
ru
z
St
.
N - WIRING IN CONDUIT, IN CEILING OR WALL
- CIRCUIT HOME RUN CONNECTION - CONVENIENCE OUTLET PANEL BOARD - 1500mm ABOVE FINISH FLOOR LINE
TH ? - CIRCUIT HOME RUN
IS - AIR CONDITION UNIT
AR
Ath

EA
A.C.U.
le tic

- SERVICE ENTRANCE
-GROUND/EARTH
Rd.

-CIRCUIT BREAKER M -KILOWATT-HOUR METER


Project Title and Location In - Charge of Installation Approved By Owner Sheet Content Sheet no.
NAME NAME LOAD SCHEDULE, LOCATION PLAN
REGISTERED ELECTRICAL ENGINEER REGISTERED ELECTRICAL ENGINEER
SINGLE LINE DIAGRAM, COMPUTATIONS E-1
SPECIFICATIONS, LEGEND
PRC NO. PTR NO. PRC NO. PTR NO.
LIGHTING LAYOUT, POWER LAYOUT
APOA NO DATE: APOA NO DATE: