Generator set data sheet

Model: C2500D5A
Frequency: 50Hz
Fuel type: Diesel
kVA rating: 2250kVA Data Center Continuous(DCC)

Spec sheet: EA_T_CC_19_EN


Sound data sheet MSP-4150
Cooling data sheet: MCP-2125
Prototype test summary data sheet PTS-675
Alternator data sheet: ADS-654,ADS-655,ADS-666

DCC
Fuel consumption kVA(kWe)
Ratings 2250(1800)
Load 1/4 1/2 3/4 Full
US gph 35.1 61.3 88.8 117.8
L/h 133 232 336 446

Engine
Engine manufacturer Cummins
Engine model QSK60-G8
Configuration 4-Cycle; 60° Vee; 16-Cylinder
Aspiration Turbocharged and Low TemperatureAftercooled
Fuel system Cummins HPI-PT
Gross engine power output, kWm (bhp) 1942(2604)
BMEP at set rated load, kPa (psi) 2579(374)
Bore, mm (in.) 159(6.25)
Stroke, mm (in.) 190(7.48)
Displacement, litre (in³) 60.2(3672)
Rated speed, rpm 1500
Compression ratio 14.5:1
Lube oil capacity, L (US gal) 280(74)
Overspeed limit, rpm 1725
Regenerative power,kWm(HP) 146(196)
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow .
Maximum fuel flow, L/hr (US gph) 1514(400)
Maximum fuel inlet restriction, kPa (in Hg)) 27(8)
Maximum fuel inlet temperature, °C (°F) 71(160)
Maximum Allowable Head on Injector Return Line, kPa (in Hg) 30.5(9)

©2023 Cummins Inc.| EA_S_CC_63_EN(11/23)


Air
Combustion air, scfm m³/min) 5156(146)
Maximum air cleaner restriction, kPa (in H2O) 3.7-6.2(15-25)

Exhaust
Exhaust flow at set rated load, CFM (m³/min) 12695(359.52)
Exhaust temperature, °C (°F) 478(892)
Maximum back pressure, kPa (in H2O) 6.8(1.1)

Standard radiator cooling


Ambient design, °C ( °F) 45(113)
Fan load¹, kWm (HP) 52(70)
Coolant capacity (with radiator), L (US gal) 543(143)
Cooling system air flow, m³/s (scfm) 33(68880)
Maximum cooling air flow static restriction, in H2O 0.5
Total heat radiated to room², MJ/min (Btu/min) 18.73(17757)
Total heat rejection³, MJ/min (Btu/min) 78.13(74061)

Enhanced high ambient radiator cooling¹


Ambient design, °C ( °F) 50(122)
Fan load¹, kWm (HP) 60(80)
Coolant capacity (with radiator), L (US gal) 543(143)
Cooling system air flow, m³/s (scfm) 40(85170)
Maximum cooling air flow static restriction, in H2O 0.5
Total heat radiated to room², MJ/min (Btu/min) 18.73(17757)
Total heat rejection³, MJ/min (Btu/min) 87.38(82827)
¹ With set-mounted shipping capability.Please note this option may not be available to certain countries.
²Total heat radiated to room includes engine radiated heat to ambient and alternator radiated heat to ambient,not include exhaust radiated heat to ambient
³Total heat rejection includes jacket water circuit, aftercooler circuit,fuel circuit and radiated heat to ambient(Engine ,alternator),not include exhaust radiated heat to ambient.

Weights Standard radiator cooling Enhanced high ambient radiator cooling


Unit dry weight, kgs 16767 16954
Unit wet weight, kgs 17441 17685
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length(A) Width(B) Height(C)


Standard open set dimensions mm 6206 2494 2800
* Dimensions didn't including isolator. See outline drawing for detail.

Genset outline
Open Genset

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

©2023 Cummins Inc.| EA_S_CC_63_EN(11/23)


Alternator data
Connection Temp rise ºC Duty* Winding No. Alternator Voltage

Wye, 3Phase 125 DCC 83 S9H1D-C41 10500V ,11000V


Wye, 3Phase 125 DCC 983 S9H1D-D41 11000V
Wye, 3Phase 125 DCC 312 S7L1D-J41 380-440V
Wye, 3Phase 125 DCC 983 HVSI804S1-D 10500V
* DCC:Data Center Continuous

Ratings definitions
Data Center Continuous (DCC):

Applicable for supplying power continuously to a constant or varying electrical load for unlimited hours in a data center application.

Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x SinglePhaseFactor x 1000


Voltage x 1.732 x 0.8 Voltage

For more information contact your local Cummins distributor

©2023 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry and InPower are trademarks of Cummins Inc. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.

EA_S_CC_63_EN(11/23)

You might also like