Professional Documents
Culture Documents
4 INTRODUCTION 64 INTRODUCTION
69 DUCT LEAK OVERHEAT DETECTION SYSTEM ZONES
ENGINE FIRE DETECTION 26-10 70 OVERHEAT SENSING ELEMENT
7 INTRODUCTION 72 COMPARTMENT OVERHEAT DETECTION MODULE
15 FIRE DETECTION CONTROL UNIT 75 FUNCTIONAL DESCRIPTION
18 ENGINE FIRE DETECTORS
21 ENGINE AND APU FIRE CONTROL PANEL EQUIPMENT COOLING SMOKE DETECTION 26-19
24 FUNCTIONAL DESCRIPTION 78 INTRODUCTION
80 SMOKE DETECTOR
ENGINE FIRE EXTINGUISHING 26-21 83 TIMELINES
29 ENGINE FIRE EXTINGUISHING BOTTLES 84 FUNCTIONAL DESCRIPTION
PURPOSE EXTINGUISHING
The fire protection systems monitor the airplane for these conditions: The airplane has these fire extinguishing systems:
• Fire • Engine
• Smoke • APU
• Overheat • Lavatory
• Engine fire/overheat
• APU fire
• Lavatory smoke.
PURPOSE Fire detectors on the engine send signals to the FDCU. The FDCU supplies an aural and visual signal
to the flight compartment.
The engine fire detection system uses detectors on
the engines to monitor for overheat and fire The FDCU gives visual indications for detector faults on the module and the engine and APU fire
conditions. When the system senses an overheat control panel.
condition, visual alarm indications operate in the
The FDCU sends OVHT and FIRE signals to the onboard maintenance function (OMF) inside the
flight compartment. When the system senses a fire
network file server (NFS). The OMF generates maintenance messages. The maintenance messages
condition, visual and audible alarm indications
are viewable by maintenance personnel 30 seconds after landing.
operate in the flight compartment. The indications
are on the P7 glareshield panel and on the engine DUAL LOOP OPERATION
and APU fire control panel. The aural warning unit
Each engine fire detection system has two fire detection loops, A and B. A fire detection loop has
gives a bell sound in the flight compartment for an
seven fire detectors. The engine fire detection system is in dual loop operation when these
engine fire.
conditions are true:
GENERAL DESCRIPTION
• The OVHT DET switch is in the NORMAL position
These are the components for the engine overheat
• Both loops operate correctly.
and fire detection:
The FDCU needs an input from both loop A and loop B to supply an overheat and/or fire signal to
• Engine fire detector (loop A and loop B)
system indicators and the aural warning unit.
• Fire detection control unit (FDCU)
You use the TEST switch on the engine and APU fire control panel to run If an engine fire detector fails to operate, the FDCU changes to single
the overheat/fire test. When the switch is in the OVHT/FIRE position, the loop operation. In the single loop mode, only one loop must detect an
indications in the flight compartment are the same as for the real fire overheat or fire condition for the FDCU to give the alarm condition.
condition. If the test fails, use the FDCU to isolate the fault.
There is no indication in the flight compartment of single loop operation
NOTE: DURING THE OVHT/FIRE TEST, THE APU FIRE AND WHEEL WELL FIRE until you do the OVHT/FIRE test.
CIRCUITS ARE ALSO TESTED.
FAULT/INOP TEST
You use the TEST switch on the engine and APU fire control panel to run
the fault/inop test. When the switch is in the FAULT/INOP position, the
indications in the flight compartment are the same as a real fault
condition. If the test fails, use the FDCU to isolate the fault.
NOTE: DURING THE FAULT/INOP TEST, THE APU FIRE DETECTOR FAULT CIRCUIT
IS ALSO TESTED.
NOTE: THE FIRE BELL WILL STOP APPROXIMATELY 1.5 TO 4 SECONDS AFTER
YOU RELEASE THE OVHT/FIRE TEST SWITCH. THIS IS DUE TO THE NEW
SOFTWARE APPLICATION ON THE ENGINE AND APU DETECTION MODULE.
E N G I N E A N D A P U F I R E C O N T R O L PA N E L
C O N T R O L S TA N D
MASTER CAUTION SYSTEM
AURAL WARNING UNIT
FIRE DETECTION CONTROL UNIT
NETWORK FILE SERVER
FIRE DETECTION CONTROL UNIT
The FDCU monitors the detectors for overheat and During normal conditions, all front panel lights are off. When a fault condition occurs, the related
fire conditions on the engine. FAULT AREA light comes on. The FAULT DISPLAY lights show a fault code.
LOCATION Push and hold the FAULT/INOP TEST switch to test the fault detection circuitry. Faults are simulated
to do a check of the circuit ability to detect a fault. If the circuits operate correctly, all lights on the
The FDCU is in the electronic equipment
front panel come on. If a light does not come on, there is a fault in the module.
compartment on the E2-2 shelf.
The amber FAULT AREA lights show which engine and loop have a fault.
PHYSICAL DESCRIPTION
The red FAULT DISPLAY lights show the fault code for the associated engine and loop displayed by a
The control circuits for the engine overheat and fire,
FAULT AREA light.
and the APU fire detection are in the FDCU. The
FDCU front panel has these: The red ACTIVE & NVM DIPLAY light comes on with faults. If the light is blinking, the fault is active. If
the light is steady, the fault is not active (stale).
• Amber ENGINE 1 LOOP A fault light
FAULT AREA INDICATION
• Amber ENGINE 1 LOOP B fault light
When there are multiple engine loop faults (two or more amber lights on), this is the indication
• Amber ENGINE 2 LOOP A fault light
priority:
• Amber ENGINE 2 LOOP B fault light
HIGHEST PRIORITY Engine 1 Loop A
• Amber APU fault light
Engine 1 Loop B
• Four red FAULT DISPLAY lights
Engine 2 Loop A
• FAULT/INOP TEST switch. Engine 2 Loop B
The engine fire detectors monitor for high temperatures in the engine • Terminal stud
area.
FUNCTIONAL DESCRIPTION
LOCATION
Each engine has fourteen fire detectors. The detectors monitor seven
These are two engine fire detectors in each of these sections: sections of the engine. In each section, two detectors attach to a support
tube and make a fire detector assembly. An assembly has one detector
• Fan right
from loop A and one from loop B. There are seven engine fire detector
• Fan upper assemblies and two loops. This table shows the temperature
characteristics of the engine fire detectors.
• Fan mid
The engine fire detectors have these: LEFT CORE 650F (343C) 850F (454C)
• Overheat, fire, and fault pressure switches RIGHT CORE 650F (343C) 850F (454C)
FUNCTIONAL DESCRIPTION
• Fault
• Overheat
• Fire.
The engine and APU fire control panel provides fire protection for these • WHEEL WELL fire light
systems:
• Engine detector FAULT light
• Engine
• APU DET INOP light
• APU
• APU BOTTLE DISCHARGED light
• Wheel well.
• Engine L BOTTLE DISCHARGED light
LOCATION
• Engine R BOTTLE DISCHARGED light
The engine and APU fire control panel is on the P8 panel.
• EXT TEST lights.
PHYSICAL DESCRIPTION
FUNCTIONAL DESCRIPTION
These engine and APU fire control panel has these:
These are the indications on the engine and APU fire control panel:
• Engine and APU fire handles
• WHEEL WELL (red) fire warning light, comes on for a wheel well fire
• OVHT DET switches condition
• TEST switch • ENG OVERHEAT (amber) light comes on for an engine overheat
condition
• EXT TEST switch
• Fire handle switch lights (red) come on for an engine fire condition
• BELL CUTOUT switch
• BOTTLE DISCHARGED (amber) lights come on when an extinguisher
• ENG 1 OVERHEAT light
bottle is discharged
E N G I N E A N D A P U F I R E C O N T R O L PA N E L
FUNCTIONAL DESCRIPTION
PURPOSE OPERATION
The engine fire extinguishing bottles contain halon that extinguishes an The engine fire extinguishing bottle is pressurized to 800 psi. When an
engine fire. engine fire extinguishing bottle pressure is less than 250 psi, the bottle
pressure switch closes. The related BOTTLE DISCHARGE amber light on
LOCATION
the engine and APU fire control panel comes on.
The two engine fire extinguishing bottles are in the main wheel well. The
If the bottle temperature increases to 266F (130C), the safety relief port
bottles attach to brackets in the top aft left corner of the main wheel well.
ruptures. This releases halon into the wheel well.
PHYSICAL DESCRIPTION
TRAINING INFORMATION POINT
The engine fire extinguishing bottles are spherical. Each bottle contains
WARNING: MAKE SURE THERE ARE CAPS OR SHUNT PLUGS INSTALLED ON THE
halon and nitrogen at a pressure of 800 psi at a temperature of 70F (21C).
SQUIBS WHEN YOU TOUCH OR MOVE THE SQUIBS. THE SQUIB IS AN
These are the components of each bottle:
EXPLOSIVE DEVICE AND CAN CAUSE INJURY IF IT IS ACCIDENTALLY FIRED.
• Pressure gage and switch
The discharge outlet fittings from the two fire extinguisher bottles are
• Safety relief port different sizes. Also the tubing has colored tape, yellow for engine 1 and
blue for engine 2.
• Two electrical connections
• Two squibs.
Each bottle has two squibs connected to discharge outlets. The tubing
downstream of the discharge outlet has a check valve that lets halon go
to the left or right engine from each bottle.
ENGINE FIRE EXTINGUISHING BOTTLES
ENGINE FIRE EXTINGUISHING BOTTLES
E N G I N E F I R E E X T I N G U I S H I N G - O P E R AT I O N
E N G I N E A N D A P U F I R E C O N T R O L PA N E L
INTRODUCTION
GENERAL DESCRIPTION
LOCATION
PHYSICAL DESCRIPTION
PURPOSE OPERATION
The APU fire extinguishing bottle contains halon that When you pull up and turn the APU fire handle in any direction or move the toggle switch on the
extinguishes an APU fire. panel in the wheel well, you operate the squib. The squib breaks a seal in the bottle. This causes the
bottle to release halon into the APU compartment. If the bottle temperature increases to 266F
PHYSICAL DESCRIPTION
(130C) or bottle pressure to approximately 1800 psi, the safety relief port breaks open. This blows
The APU fire extinguishing bottle is spherical. The out the disc and discharges the halon into the accessory compartment.
bottle contains halon under a nitrogen pressure of
800 psi at a temperature of 70F (21C). These are the
components of the APU fire extinguishing bottle:
LOCATION
PURPOSE The fire extinguisher bottles contain halon 1301 fire extinguishing agent pressurized with nitrogen.
The HRD bottle is 630 cubic inches and filled with 25 lbs of halon. The LRD bottle is 378 cubic inches
The cargo fire extinguishing system sends halon to
and filled with 13 lbs of halon. Tubing connects the bottles to discharge nozzles in the forward and
the forward and aft cargo compartments.
aft cargo compartments.
GENERAL DESCRIPTION
The DMUs remove moisture, filters debris, and meters the flow of halon during release from the
The cargo fire extinguishing system has these low rate discharge (LRD) fire extinguishing bottle. The discharge nozzles spray halon into the fwd or
components: aft cargo compartments. There are 2 discharge nozzles in the ceiling of the forward cargo
compartment and 3 in the ceiling of the aft cargo compartment.
• Cargo fire control panel
OPTION: The ETOPS LRD bottle is 800 cubic inches and filled with 33 lbs of halon.
• High-rate discharge (HRD) fire extinguisher bottle
The fire extinguisher bottle holds halon fire The discharge assembly has an explosive squib that releases the halon through the discharge port.
extinguishing agent pressurized with nitrogen to The squib is discharged when the DISCH switch on the cargo fire control panel is pressed.
extinguish fires in the forward and aft cargo
The pressure switch monitors the pressure in the bottle. When the bottle pressure is less than 250
compartments.
psi, the switch sends a signal to the flight compartment and the amber DISCH light comes on.
LOCATION
The safety relief and fill port is a fitting on the bottle. The safety relief opens to make sure the bottle
The fire extinguisher bottles are in the air does not break if internal pressure is too high.
conditioning distribution compartment.
WARNING: BE CAREFUL WHEN YOU MOVE THE FIRE EXTINGUISHER BOTTLE. THE FIRE EXTINGUISHER
PHYSICAL DESCRIPTION BOTTLE IS HIGHLY PRESSURIZED AND HAS AN EXPLOSIVE CARTRIDGE AS A COMPONENT. ACCIDENTAL
DISCHARGE OF THE FIRE EXTINGUISHER BOTTLE CAN CAUSE INJURY TO PERSONS OR DAMAGE TO
The fire extinguisher bottle has these components:
EQUIPMENT.
• Safety relief and fill port
WARNING: PUT A PROTECTIVE CAP ON THE SQUIB. IF YOU DO NOT PUT A PROTECTIVE CAP ON THE SQUIB,
• Two handles THE FIRE EXTINGUISHER BOTTLE CAN RELEASE ITS CONTENTS SUDDENLY AND CAUSE INJURY TO PERSONS.
• Stowage for the electrical protective caps for the There are three different size fire extinguisher bottles for the airplane. The HRD bottle is 630 cubic
squibs. inches. The basic LRD bottle is 378 cubic inches and the ETOPS LRD bottle is 800 cubic inches. All
bottle components are the same.
FIRE EXTINGUISHER BOTTLE
C A R G O F I R E C O N T R O L PA N E L
AIR CONDITIONING DISTRIBUTION
C O M PA R T M E N T
C A R G O F I R E C O N T R O L PA N E L
INTRODUCTION
The wheel well overheat detection system uses two Fire (overheat) sensing elements in the main wheel well supplies the wheel well fire detection
sensing elements in the main wheel well. It monitors signal. The signal goes to the compartment overheat detection controller. This unit supplies the fire
the wheel well for a fire condition. When the system alarms.
senses a fire condition, alarm indications operate in
These are the flight compartment indications of a wheel well fire:
the flight compartment. The indications are on the
glareshield panel P7 and on the engine and APU fire • Two red FIRE WARN lights on P7 panel come on
control panel P8. The aural warning unit also gives a
• Bell sounds in the aural warning unit
bell sound.
• Red WHEEL WELL light on engine and APU fire control panel comes on.
PHYSICAL DESCRIPTION
If the wheel well fire alarms come on due to a real fire or a fault, the MAINT ADV light on the
These are the components for the wheel well fire
compartment overheat detection controller comes on. Use the module to do a check for real alarm
detection:
or a fault condition.
• Main wheel well fire (overheat) sensing element
You use the test switch on engine and APU fire control module panel to the OVHT/FIRE position to
(loop A and loop B)
do a test of the wheel well sensing element. If the test passes, the indications in the flight
• Compartment overheat detection controller compartment are the same as for a real fire condition. If the test fails, use the compartment
overheat detection controller to isolate the fault.
• P7 glareshield panel
NOTE: DURING THE WHEEL WELL FIRE TEST, THE ENGINE OVERHEAT, THE ENGINE FIRE, AND THE APU FIRE
• Engine and APU fire control panel
SYSTEMS ALSO DO A TEST.
• Aural warning unit.
W H E E L W E L L O V E R H E AT D E T E C T I O N
E N G I N E A N D A P U F I R E C O N T R O L PA N E L
C O M PA R T M E N T O V E R H E AT D E T E C T I O N M O D U L E
O V E R H E AT S E N S I N G E L E M E N T
The overheat sensing element monitors for high The sensing element is a thermistor type with resistance inversely proportional to temperature. As
temperature conditions in the main wheel well. the element temperature increases, the resistance decreases. If any portion of the sensing element
is above alarm temperature of 400F (205C), the element resistance decreases sharply. The single
LOCATION
wire in the center of the core is the power lead and the outside tube is electrically grounded. The
The sensing element is in the ceiling of the left and insulating resistance of the core material decreases suddenly at the alarm temperature. Current
right main wheel wells. flows through the core material to ground when alarm temperature is sensed.
The sensing element attaches to the ceiling of the TRAINING INFORMATION POINT
wheel well by quickrelease fasteners.
The minimum bend radius for the sensing elements is one inch (2.5 cm). If possible, do not bend
PHYSICAL DESCRIPTION the element in a radius less than three inches (8 cm).
The sensing element is a single strand of nickel wire Sensing elements are in clamps with color-coded bushings. The element end brackets have collars
embedded in insulation. The sensing element has that prevent the element from twisting when the electrical connectors are put on.
these components:
CAUTION: DO NOT MAKE THE PERMITTED DENTS OR KINKS STRAIGHT. DAMAGE TO THE TUBING CAN
• Nickel wire OCCUR.
• Insulation NOTE: MAKE SURE THERE IS AT LEAST 0.50 INCH (1.5 CM) BETWEEN THE ELEMENT AND THE STRUCTURE
EXCEPT AT THE MOUNTING CLIPS.
• Tube
• Electrical connector.
O V E R H E AT S E N S I N G E L E M E N T
O V E R H E AT S E N S I N G E L E M E N T
C O M PA R T M E N T O V E R H E AT D E T E C T I O N M O D U L E
PURPOSE MEM READ (memory read switch), accesses the non-volatile memory.
The compartment overheat detection module (CODM) monitors sensing MEM CLEAR (memory clear switch), clears the non-volatile memory. The
elements for overheat conditions in the wheel well and the wing and existing faults and alarms can not be cleared until corrected.
body areas.
LOC TEST (local test switch), initiates a test sequence of the control
LOCATION circuits and detector elements. This is a system test that shows current
configuration and faults. These are the possible wheel well overheat
The CODM is in the electronic equipment compartment on the E1-4 rack.
display messages:
PHYSICAL DESCRIPTION
• MWW LPA OVHT, SHORT, OPEN
The control circuits for wheel well overheat detection are in the CODM.
• MWW LPB OVHT, SHORT, OPEN.
The front panel has these components:
Pressing LOC TEST and viewing a MWW fault deactivates the failed loop
• MAINT ADV (maintenance advisory) light
and puts the wheel well overheat system into single loop operation. This
• LED display allows flight deck initiated tests to pass and improves airplane availability.
• BITE instructions DISP TEST (display test switch), verifies correct operation of the control
circuits. MAINT ADV (maintenance advisory light), is on when a fault or an
• Four BITE control switches (MEM READ, MEM CLEAR, LOC TEST and alarm is stored in the non-volatile memory. MAINT ADV also shows in the
DISP TEST). display window until the LOC TEST button is pushed to view the fault or
BITE TEST SWITCHES AND INDICATIONS alarm. The MAINT ADV light stays on until the detected condition is
removed and the non-volatile memory is cleared. When doing manual
The non-volatile memory provides a storage area for ten fault/alarms. wheel well overheat detection tests from the flight compartment, the
Failure of the control cards, power supply card, loss of ac or dc power are CODM display window shows EXTERNAL TEST.
not stored. Short circuit faults are stored as alarm codes.
C O M PA R T M E N T O V E R H E AT D E T E C T I O N M O D U L E
C O M PA R T M E N T O V E R H E AT D E T E C T I O N M O D U L E
FUNCTIONAL DESCRIPTION
FUNCTIONAL DESCRIPTION
PURPOSE These are the flight compartment indications of a duct leak overheat:
The duct leak overheat detection system (DLODS) uses sensing elements • Left or right amber WING-BODY OVERHEAT light on the air
adjacent to the pneumatic ducts. It monitors the pneumatic distribution conditioning panel comes on MASTER CAUTION and AIR COND
system ducts for overheat conditions. When the system detects an annunciator lights come on.
overheat condition, alarm indications turn on in the flight compartment.
WING AND BODY OVERHEAT TEST
The indications are on the P7 glareshield panel and on the P5 air
conditioning/bleed air controls panel. The duct leak overheat detection test is with the OVHT TEST switch on the
air conditioning bleed air controls panel. If the test passes, the
GENERAL DESCRIPTION
indications in the flight compartment are the same as for a real overheat
These are the major components of the duct leak overheat detection condition. If the test fails, use the compartment overheat detection
system: module to isolate the fault.
The duct leak overheat detection system uses a single overheat sensing
loop. The detector loops in the left and right wing/body area supplies
overheat and fault signals to the CODM. The CODM uses the signals to
give overheat or fault indications in the flight compartment on the air
conditioning bleed air controls panel. The fault signals show on the
CODM.
D U C T L E A K O V E R H E AT D E T E C T I O N S Y S T E M
A I R C O N D I T I O N I N G PA N E L
MASTER CAUTION SYSTEM
C O M PA R T M E N T O V E R H E AT D E T E C T I O N M O D U L E
D U C T L E A K O V E R H E AT D E T E C T I O N S Y S T E M Z O N E S
GENERAL DESCRIPTION All zone overheat detector elements are monitored by the compartment overheat detection
module (CODM). The sensing elements sense wheel well fire (dual loop), and overheats caused by
These are the zones of the duct leak overheat
pneumatic duct leaks (single loop).
detection system:
The overheat sensing elements monitor for high temperature conditions • Nickel wire
in the wing and lower aft body of the airplane.
• Insulation
LOCATION
• Tube
The sensing elements are located in these areas:
• Electrical connector.
• Left and right engine strut
FUNCTIONAL DESCRIPTION
• Left and right wing leading edge
The sensing element is a thermistor type with resistance inversely
• Left and right air conditioning compartment proportional to temperature. When element temperature increases, its
resistance decreases. If any part of the sensing element is more than the
• Keel beam
alarm temperature of 310F (154C) in the strut or 255F (124C) in other
• Aft cargo compartment areas, the element resistance decreases quickly. The wire in the center of
the core is the power lead and the external tube is electrically grounded.
• Section 46 and 48. The insulating resistance of the core material decreases quickly at the
The sensing element attaches to the airplane structure by quickrelease alarm temperature. Current flows through the core material to ground
fasteners. when alarm temperature is sensed.
The sensing element has a single strand of nickel wire in insulation. The minimum bend radius for the sensing elements is one inch (2.5 cm).
If possible, do not bend the element in a radius less than three inches (8
cm).
O V E R H E AT S E N S I N G E L E M E N T
PURPOSE The MEMORY READ switch gets access to the non-volatile memory. The
MEMORY CLEAR switch clears the non-volatile memory. The existing
The compartment overheat detection module (CODM) monitors sensing
faults and alarms can not be cleared until corrected. The LOCAL TEST
elements for overheat and fire conditions in the wheel well and the
switch, initiates a test sequence of the control circuits and detector
wing/body areas.
elements. This is a system test that shows current configuration and
LOCATION faults. These are the possible duct leak overheat detection display
messages:
The CODM is in the electronic equipment compartment on the E1-4 rack.
• L WNG STR OVHT, SHORT, OPEN
PHYSICAL DESCRIPTION
• L WNG LE OVHT, SHORT, OPEN
The control circuits for the wing/body overheat detection are in the
CODM. The front panel has these components: • L WNG LE 2 OVHT, SHORT, OPEN
• MAINT ADV (maintenance advisory) light • L AC PACK BAY OVHT, SHORT, OPEN
• Four BITE control switches (MEMORY READ, MEMORY CLEAR, LOCAL • AFT BDY CGO OVHT, SHORT, OPEN
TEST and DISP TEST).
• AFT BODY APU OVHT, SHORT, OPEN
BITE TEST SWITCHES AND INDICATIONS
• R WNG LE OVHT, SHORT, OPEN
The non-volatile memory provides a storage area for ten fault/alarms.
• R WING LE 2 OVHT, SHORT, OPEN
Failure of the control cards, power supply card, and loss of ac or dc
power are not stored. Short circuit faults are stored as alarm codes. • R WNG PACK BAY OVHT, SHORT, OPEN
C O M PA R T M E N T O V E R H E AT D E T E C T I O N M O D U L E
FUNCTIONAL DESCRIPTION
PURPOSE Smoke clearance mode operation has an interface with these operations
in the air conditioning system:
The equipment cooling system has two subsystems, the equipment
cooling supply system and the equipment cooling exhaust system. The • Flow control and shutoff valve
equipment cooling smoke detection system monitors for smoke in the
• Recirculation fans
supply system and the exhaust system. If there is smoke, the detection
system gives an indication in the flight compartment. • Equipment cooling fans
The detection system also starts the automatic reconfiguration of the • Overboard exhaust valve.
smoke clearance mode.
A test panel on the J23 junction box in the EE compartment lets you do a
GENERAL test of the smoke detectors and system operation.
The supply system and the exhaust system have a smoke detector. The
detectors monitor for smoke. Relays give the logic that controls the
operation of the smoke detection system.
PURPOSE OPERATION
The smoke detectors monitor for smoke in the Air goes into one port and exits the other port. In the detector, it goes through a light beam. When
equipment cooling supply and exhaust systems. particles are in the air, the light beam is deflected to a circuit. The circuit energizes a relay. The relay
gives a ground to the connector. The ground is the alarm signal.
LOCATION
PHYSICAL DESCRIPTION
• Electrical connector
• Two ports
• Mounting flange.
GENERAL • R1185. It has a five-minute time delay. It de-energizes five minutes after R1150 de-energizes.
The graphic shows the different timelines for these: • R1183. It has a 10-second internal timer. It energizes for ten seconds when R645 de-energizes.
• Supply or exhaust smoke detected NOTE: THIS PAGE SHOWS A GENERAL SEQUENCE OF THE TIMELINES TO HELP UNDERSTAND THE
FUNCTIONAL DESCRIPTION PAGE.
• EQUIP SMOKE light operation
GENERAL
SMOKE ALARM
• Energize R1185
• Energize R1185.
RECONFIGURATION
• R1186 de-energizes
• R1184 de-energizes
FUNCTIONAL DESCRIPTION
PURGE MODE
TEST
DFDAU