You are on page 1of 6

POWER QUALITY ASSESSMENT FROM A WAVE-POWER STATION

R G Alcorn, W C Beattie

The Queen’s University of Belfast

SUMMARY values from pre-recorded voltage data will be


A wave-power station produces electricity by presented. The method shown is the production
converting sea-wave energy into electrical energy. of a software flickermeter based on the IEC
This can be done by various methods, but the flicker standards.
method considered in this paper uses the
The flicker level is calculated using a statistical
oscillating water column principle. This system
method that produces a cumulative distribution
uses the oscillating wave motion to produce a
function from a flicker level classifier. This
reciprocating air flow which is rectified into
method of calculation easily lends itself to
useful torque by a Wells turbine. The station
implementation in software and can be tested
examined in this paper is the recently
against waveforms given in the IEC standard.
commissioned LIMPET station on Islay, a small
island off the West coast of Scotland. The Although the flickermeter model produced

LIMPET station has two contra-rotating Wells complies to the IEC standards, it will been shown

turbines which spin in the same direction that it is possible to greatly reduce the sample

irrespective of the direction of air flow across frequency of the device for wave-power

them. Each of these turbines is coupled to an applications without a reduction in accuracy. This

inverter controlled 250kW 415V 3-phase 6-pole is due to the fact that a wave-power station will

wound-rotor induction machine, giving the station only generate low frequency voltage fluctuations.

a rated capacity of 0.5MW. The major challenge This novel method of flickermeter implementation

of such a station is in producing an acceptable requires extra statistical manipulation in order to

quality of supply. This is due to the oscillating comply to the standards and this will be detailed

nature of the source as there are power variations in the paper.

with each wave and with each group of waves. Finally, several data sets collected from the

This paper will describe the assessment of power LIMPET station will be analysed and the results

quality from the LIMPET station with regard to will be presented. These will show that the

voltage flicker. The phenomenon of flicker will station is operating well within acceptable limits

be described, and a method of producing flicker of voltage flicker.


POWER QUALITY ASSESSMENT FROM A WAVE-POWER STATION

R G Alcorn, W C Beattie

The Queen’s University of Belfast

ABSTRACT turbines are specialised Wells turbines which spin in the


same direction irrespective of the direction of air flow
This paper describes the development and testing of a
across them. Each of these turbines is coupled to an
software based flickermeter used in order to assess the
inverter controlled 250kW 415V 3-phase 6-pole wound-
supply quality from the LIMPET (1,2) wave-power
rotor induction machine, giving the station a rated
station on Islay. It describes the phenomenon of voltage
capacity of 0.5MW. A schematic of the plant showing
flicker and the effect that a wave-power station has on
its layout and most important elements is shown in
this quantity. The paper also explains techniques
Figure 1.
developed in order to improve flickermeter performance
when used with pre-recorded data. It will also show There are regulations which must be observed for the
that the standard flickermeter sample frequency may be generation of electrical power (4,5). These are quite
reduced for wave-station applications. Finally the paper stringent when connected to an isolated point on the
will present flicker results from preliminary data grid. In the case of the LIMPET station, it is located at
collected from the LIMPET station and will show that the end of 10km of 11kV line. This paper discusses the
the device is operating well within acceptable limits. impact of a wave-power station on voltage flicker. It
also shows the development of a software flicker tool
INTRODUCTION
which may be use to analyse past voltage data.
The major challenge of a wave-power station is in
The software flickermeter was developed in such a way
producing an acceptable quality of supply. This is due to
that it could be included in system simulation in order to
the variable nature of the source as there are power
predict flicker performance or it could be used on data
variations with each wave and with each group of waves
previously collected from the station to assess power
(3). The difference between calm and rough seas
quality. This paper deals with only previously recorded
produces long-term variations in the average power
data from the recently commissioned LIMPET station.
output, but this presents few problems. However, the
At the time of publication, only limited data was
fluctuations caused by individual waves must be
available with the station operating below capacity, but
controlled and smoothed to provide acceptable power.
this will be updated in the future once a database has
The LIMPET station is mounted on an exposed western been assembled of the station in various operating
facing coastline on the island of Islay situated off the conditions.
West coast of Scotland. The station is of shoreline
FLICKER DEFINITION
oscillating water column (OWC) design. The incoming
wind waves produce an oscillation within the column. Voltage flicker is a systematic variation of the voltage
This oscillation drives air to and fro across a pair of envelope or a series of random voltage changes, the
contra-rotating turbines. magnitude of which does not normally exceed the
voltage regulations laid down by the supply authority
(4,5). Unlike harmonics, the distorted waveform
causing flicker contains frequencies below the
fundamental (typically below 25Hz) which makes even
a single-step voltage change classify as flicker. The
most important impact of these fluctuations is that they
cause variations in the light output of various lighting
sources. It is the human perceptibility to these
fluctuations that form part of the system of defining and
calculating the flicker severity.
The eye-brain chain is most sensitive at a frequency of
8.8 Hz. A sine modulated voltage wave at this
frequency with a modulation amplitude of 0.25% RMS
Figure 1 – LIMPET Schematic will correspond to a flicker level of 1. This definition
was made by exposing a group of people to a flickering
The water/air interface provides a gearing ratio from the tungsten-filament light at a set modulation frequency.
slow motion of the water column to much higher The amplitude of modulation was increased and when
velocity air motion suitable for driving turbines. The 50% of the people noticed flickering, the flicker level
was set to one. This was repeated over a range of flicker waveform to be analysed, the other parts must be
frequencies in order to obtain a perceptibility curve. removed.
The IEC perceptibility curve is shown in Figure 2.
Block 3 - Weighting Filters – the first filter removes
1.2 the dc component and the component at twice the mains
frequency present at the output of the demodulator. The
1
squaring function of the demodulator introduced this
higher frequency. The output of this filter is solely the
Perceptibility (p.u.)

0.8

voltage flicker waveform. This filter comprises two


0.6
filters back to back, a first order high-pass filter with a
3dB cut-off at 0.05Hz and a low pass 6th order
0.4
Butterworth with 35Hz 3dB cut-off.
0.2
The second filter weights the voltage fluctuation
0
according to the lamp and human visual sensitivity
0 5 10

Frequency (Hz)
15 20 25
response. The transfer function for the block is shown in
the IEC standard.
Figure 2 - IEC Flicker Perceptibility Curve Block 4 – Squaring multiplier and sliding mean function
In most cases, flicker is caused by varying load – this performs two separate functions. Firstly the
characteristics. Arc furnaces, motor starting, sawmills, weighted flicker signal is squared to simulate the non-
and arc welding are typical sources of voltage linear eye-brain perception. Secondly the sliding mean
fluctuations. Usually, these plants will be fed by a averaging is performed to simulate the storage effect of
strong grid system and so flicker impact will be the brain and the thermal capacity of the filament. This
reduced. In the case of the wave station it is changes in has the transfer function of a first-order low-pass filter
the supply rather than the load which cause the voltage with a time constant of 300ms.
fluctuations. This coupled with the fact that an islanded Block 5 – Online statistical analysis – this block
system will normally have a weak grid system, makes it samples the instantaneous flicker waveform at a
more susceptible to flicker problems. suggested minimum of 50Hz. The flicker is classified
Figure 2 shows that for frequencies less than 1Hz, into a minimum of 64 class levels and a cumulative
voltage fluctuations have little effect on flicker level. probability function created. From this function it is
This is important in respect to a wave station whose possible to calculate a figure for the short term flicker
voltage flicker frequency caused by individual wind severity, PST, usually over 10 minute intervals. The long
waves would be of the order of 0.1Hz. However, the term flicker severity PLT is usually assessed over several
modulation of the voltage envelope by these individual days can be calculated from a successive of PST’s.
wave frequencies may just lie within the tolerable The final design of the flickermeter is left to the
voltage limits for a weak grid. These large voltage engineer, although the standard does give tests to check
excursions at low frequencies do have an effect on that the meter falls within specification.
voltage flicker which must be assessed. Another effect
of wind waves is that they tend to come in groups, SOFTWARE FLICKERMETER
producing a modulation effect on the individual waves. The purpose of the software flickermeter was to provide
IEC STANDARD METER online and offline flicker performance for the LIMPET
station.. The software flickermeter is divided into 2
The IEC have set standards for the measurement and parts, namely the instantaneous flickermeter model and
analysis of flicker severity. These are laid out in IEC the statistical analysis.
868 and show the design specifications of a
flickermeter(4,5). The meter is essentially composed of Instantaneous Flickermeter Model
several blocks, the purpose of each detailed as follows. The instantaneous flicker level is calculated by firstly
Block 1 – Input voltage transformer with automatic gain standardising (reduction to per unit value) and then
control– this accepts a wide range of nominal mains sampling the voltage waveform. This signal is squared,
voltages and adapts them to a maximum level simulating the lamp response, before being passed to
compatible with the operation of the following circuitry. several filters which simulate the eye-brain response.
The output of the block is the RMS voltage modulated This gives the instantaneous flicker sensation level. The
with the disturbance function. output of the system is the instantaneous flicker level
which must be further processed to give a value for PST.
Block 2 – Squaring Demodulator – this circuit gives a
component of its output a voltage linearly related to the Statistical Analysis
amplitude of the fluctuation modulating the input. It is The output of the instantaneous model produces a time
essentially simulating the flicker produced by a tungsten trace of flicker sensation which is passed to a function
filament lightbulb. Part of the output component is the that performs the statistical analysis. This must be done
in order to calculate the flicker sensation over a long methods employed to deal with the problems
enough period to allow for the build up of annoyance. experienced are shown below:
The statistical method is because flicker is made up of Logarithmic classes – The flicker level is sorted into
regular and irregular voltage anomalies. These can make classes or bands of flicker severity, these bands being
the instantaneous flicker level vary widely but perhaps spaced logarithmically. If a CPF was to be plotted solely
not perceptibly over the observed period. This means from this information it would form a staircase function.
that types of occurrence must be weighted. Also, it is This type of function cannot be used to accurately
important to know for what percentage of the observed interpolate the percentile points. Instead, the midpoint
period any given flicker level has been exceeded. of each class was found linearly and a curve fitted
between the points. This produced a smooth CPF for
In order to meet these requirements, a function was
more accurate interpolation.
written which sorted the instantaneous flicker into a
series of class levels, and then built up a probability Empty Classes – There is the possibility that there will
function of class level exceedence which could be used be class levels which have no flicker points in them.
to calculate the short term flicker severity. The short- When the CPF is constructed, even with the curve
term flicker severity may be evaluated in as short a time fitting described above, these empty classes produce flat
as 10 minutes as a 10 minute interval is long enough for spots, or part of a staircase function. If the required
an individual to notice the disturbance and its percentile happens to lie at this flat spot, the
persistence without giving too much importance to interpolation can have infinite solutions. To remove
isolated voltage changes. this possibility, any flat spots in the CPF are smoothed
by curve fitting using data either side of the flat spot.
Classification Method
The 0.1 percentile point – This is the point in the
For the software flickermeter, the classification method
function exceeded only by 0.1% of the flicker or 1 in
chosen was to have a 200 level logarithmic classifier.
1000 samples. If the maximum flicker occurs only
The percentage of time the flicker spends in each of
occasionally then this point will not be measured.
these levels is then calculated over the 10 minute test
Statistically it must exist, but over the given sample
period. A cumulative probability function (CPF) is
time it may not have been recorded. To ensure that this
established from the class level data. The probability
percentile point can be found from the CPF, several
function is defined as the probability that a level will be
points are used to extrapolate back to the 0.1 percentile
exceeded. The PST value is defined as
point. The weighting applied to this percentile
PST = K1P1 + K 2P2+....K n P n coefficient in the calculation of PST is small compared
with the other coefficients and so the accuracy of this
where P1, P2,.. Pn are CPF percentile points with an method is adequate.
assigned probability of being exceeded and K1, K2,..
Kn are weighting coefficients. In order to find the Flickermeter Sample Frequency
flicker level at a particular percentile point it is The IEC standard states that the flickermeter classifier
necessary to use an interpolation algorithm. Details of must have a sample rate of at least 50Hz. However, due
possible methods are given in the IEC standard. to the low frequency of sea waves and the inertia of the
The maximum flicker level was chosen to get a good turbine/generator system, the frequencies produced by a
spread of data throughout the levels, which in turn wave-power station are much lower.
produces a smoother CPF for PST calculation. The PST The drawback of the standard flickermeter for real time
could then be calculated using the equation with the analysis, is the high sample rate and the amount of
percentiles and weightings given in Table 1. processing required to produce a value for PST. To
Percentile (Pn) Weighting (Kn) store the voltage or power data for off-line analysis by
the flickermeter model consumes a lot of memory. The
0.1 0.0314 solution is to reduce the sample frequency of the
1 0.0525 flickermeter, so that less storage and processing is
3 0.0657 required. Although the flicker created by the wave-
10 0.28 power station is of a low frequency, reducing the sample
rate of the classifier will cause problems with the
50 0.08
percentile interpolation. Over a 10 minute interval at a
Table 1 – Percentiles and Weighting Coefficients frequency of 2Hz there will be only 2000 samples and
Percentile Interpolation this greatly reduces the number of samples per class
interval. This has a detrimental effect on how well the
There are several problems associated with the CPF can be produced and hence how accurately the
interpolation of the percentile points from the percentiles can be interpolated for PST calculation.
cumulative probability function. Interpolation is usually
necessary as it is unlikely that all the required percentile In order to understand the effect that the classifier
points lie exactly on the CPF at measured values. The sample frequency had on the accuracy of the
calculation, a test was devised to compare various
classifier set-ups at low frequencies. Several traces of flicker analysis can be performed on individual phases
voltage were processed with the flickermeter sample and this could highlight conditions of grid unbalance.
frequency ranging from 50Hz down to 1Hz. The results
are shown in Figure 3.
230

R -ph V oltage (V olts )


7
225
6

220
5
PST % Error

215
4 0 100 200 300 400 500 600 700 800 900 1000

3 230

Y -ph V oltage (V olts )


2
225

1
220

0
50 20 10 5 2 1
215
Flickermeter Sample Frequency 0 100 200 300 400 500 600 700 800 900 1000

240
Figure 3 – Classifier Sample Frequency Comparison

B -ph V oltage (V olts )


235
This shows the worst case error experienced by the
classifier over a range of classifier sample frequencies. 230

Although the errors at 1Hz and 2Hz are small, it is 225


0 100 200 300 400 500 600 700 800 900 1000
thought that running at sample frequencies lower than Tim e (s ec s )

5Hz would introduce unacceptable errors. This is ideal


in that this matches the data acquisition sample
Figure 4 - Voltage Traces from LIMPET
frequency on the LIMPET station.
In order to find the flicker causing frequencies produced
Testing and Calibration
by a wave-power station, a spectral analysis of the
With the flickermeter and statistical classifier set up as voltage signals in Figure 4 was performed. These are
described and with the sample frequency set to 5Hz, it shown in Figure 5. The spectra show that there is a
was then tested using frequency and modulation spread between periods of 10 – 20 seconds, which are
amplitude values specified in the IEC standard. The the naturally occurring wave periods at the LIMPET
flickermeter was tested with a range of frequencies from site. However, as the turbine/ generator combination
0.5Hz to 25Hz with modulation amplitudes set to give a has very high inertia, the effect of these individual
PST of 1. The results of the calibration test showed that waves is reduced. The spectra also show a frequency
for the standard input frequencies, the software content of the order of 60-90 seconds. This is a
flickermeter was performing to within 1% of the modulating wave period that occurs due to a build up
specification. and then decline of successive waves occurring in
groups. The inertia will have little effect on these
DATA ANALYSIS longer periods as it only deals with short term storage.
The data acquisition system on the LIMPET plant has
been set up to record various signals that describe
station operation. These are to monitor, control and
evaluate all aspects of the station’s performance. The
traces of interest for flicker measurement are the line
voltages returned from the inverter system.
At the time of publication, the LIMPET station has been
operational for a short period only, and hence the results
presented are only preliminary and have been taken
whilst the station has been operating below its installed
capacity of 0.5MW. The station in this commissioning
condition is not running system controls which have Figure 5 – Spectra of Voltage Signals
been designed to improve the quality of supply (6). Flicker analysis
Figure 4 shows an example of the phase voltages The voltage spectra of Figure 5 show that there are a
measured whilst the station was producing an average range of flicker causing frequencies at various
power of 60kW, with peaks reaching 120kW. The data intensities. Each of the phase voltages requires flicker
acquisition system for analysis purposes saves data in analysis for each of the data sets under investigation.
sets of between 10 and 15 minute periods which are The instantaneous flicker produced by the flickermeter
ideal for flicker analysis. It must also be noted that for a single voltage trace is shown in Figure 6.
9
x 10
-7
seen that the standard deviation is small, meaning that
for the files analysed the flicker performance is similar.
8

7
Phase Flicker PST
R-Phase 0.125
Ins tantaneous Flic k er Level

5
Y-Phase 0.152
4
B-Phase 0.144
3 Mean flicker Standard Deviation
2 0.140 0.034
1 Table 2 – Flicker Results
0
0 100 200 300 400 500 600 A further result of the analysis is that the flicker values
Tim e (sec s )
produced for each phase are slightly different. The
Figure 6 – Instantaneous Flicker with class levels values shown in Table 2 give the phase average over all
the data analysed. The difference is to be expected
This shows the variation in flicker intensity and the since an islanded system such as Islay is unlikely to
class levels used in order to classify it. The nature of have a balanced grid and hence the phase susceptibility
the flicker variations show that the trace is more often at to flicker will be different for each phase.
lower levels than at higher levels therefore being better
suited to a logarithmic classifier. CONCLUSIONS

The resultant cumulative probability function produced It has been shown that it is possible to create and test a
from the classified instantaneous flicker sensation trace software flickermeter that complies to the IEC
in Figure 6 is shown in Figure 7. This shows a smooth standards. Furthermore it has been shown that this
and complete function, a result of the having adequate meter can be used to assess impact on the grid that a
data along with a logarithmic classifier. This type of wave-power station has.
CPF produces confidence in the interpolated percentile Frequency analysis of the voltage waveforms measured
points used in the final calculation of PST. at LIMPET have shown that the frequencies
CP F of s ignal perm anenc e in c lass es contributing to flicker are those of the individual waves
100
and a low frequency modulated wave. The frequency
90 analysis also showed that because the voltage waveform
80 was subject to only low frequency fluctuations, the
Cum ulative P robability Func tion %

70
flickermeter sample frequency could be reduced without
loss of accuracy.
60

50
The work to date has shown that the LIMPET station is
working well within acceptable limits of flicker.
40
Although the data was taken when the station was
30
working below its installed capacity, it is thought that its
20 flicker performance at rated output will be similar since
10 a control strategy based on quality of supply will be
0
used once the station has been fully commissioned
-11 -10 -9 -8 -7 -6
10 10 10 10 10 10
Clas s Num ber REFERENCES
Figure 7 – CPF with percentiles 1. Heath T.V., The History and Status of the LIMPET
Project, IMechE Seminar, November 1999
RESULTS
2. Description of Limpet Wave Station and Technical
A range of 3 phase voltage traces were available from Specifications available on WaveGen’s website:
the LIMPET station taken from the station operating at 3. www.wavegen.co.uk
average power levels just under 100kW with peak
power output reaching 150kW. The files were taken on 4. Beattie W.C., Sprevak D., Alcorn R.G., Producing
successive days but all displayed similar frequency acceptable electrical supply quality from a wave-power
content of that shown in Figure 5. Also, since the station, Proc Conference OMAE 98 Greece, 1998
station was in a commissioning mode when the data was 5. IEC 868, Flickermeter – Function and Design
being taken, all the power levels are very similar. This specifications, IEC, Geneva 1986 (BS EN 60868-0)
allows the files to be used as a group and average flicker 6. IEC 868-0, Flickermeter – Evaluation of Flicker
levels to be found. The results are given in Table 2. Severity, IEC, Geneva 1991 (BS EN 60868-0)
The results show that for the range of data analysed, the 7. Alcorn R.G., Beattie W.C., Control strategy
flicker is well within acceptable limits, having an development for remote Wave-Power Stations, UPEC
average of 14% of maximum tolerance. It can also be 2000 Conference, Belfast.

You might also like