Professional Documents
Culture Documents
R G Alcorn, W C Beattie
LIMPET station has two contra-rotating Wells complies to the IEC standards, it will been shown
turbines which spin in the same direction that it is possible to greatly reduce the sample
irrespective of the direction of air flow across frequency of the device for wave-power
them. Each of these turbines is coupled to an applications without a reduction in accuracy. This
inverter controlled 250kW 415V 3-phase 6-pole is due to the fact that a wave-power station will
wound-rotor induction machine, giving the station only generate low frequency voltage fluctuations.
a rated capacity of 0.5MW. The major challenge This novel method of flickermeter implementation
quality of supply. This is due to the oscillating comply to the standards and this will be detailed
with each wave and with each group of waves. Finally, several data sets collected from the
This paper will describe the assessment of power LIMPET station will be analysed and the results
quality from the LIMPET station with regard to will be presented. These will show that the
voltage flicker. The phenomenon of flicker will station is operating well within acceptable limits
R G Alcorn, W C Beattie
0.8
Frequency (Hz)
15 20 25
response. The transfer function for the block is shown in
the IEC standard.
Figure 2 - IEC Flicker Perceptibility Curve Block 4 – Squaring multiplier and sliding mean function
In most cases, flicker is caused by varying load – this performs two separate functions. Firstly the
characteristics. Arc furnaces, motor starting, sawmills, weighted flicker signal is squared to simulate the non-
and arc welding are typical sources of voltage linear eye-brain perception. Secondly the sliding mean
fluctuations. Usually, these plants will be fed by a averaging is performed to simulate the storage effect of
strong grid system and so flicker impact will be the brain and the thermal capacity of the filament. This
reduced. In the case of the wave station it is changes in has the transfer function of a first-order low-pass filter
the supply rather than the load which cause the voltage with a time constant of 300ms.
fluctuations. This coupled with the fact that an islanded Block 5 – Online statistical analysis – this block
system will normally have a weak grid system, makes it samples the instantaneous flicker waveform at a
more susceptible to flicker problems. suggested minimum of 50Hz. The flicker is classified
Figure 2 shows that for frequencies less than 1Hz, into a minimum of 64 class levels and a cumulative
voltage fluctuations have little effect on flicker level. probability function created. From this function it is
This is important in respect to a wave station whose possible to calculate a figure for the short term flicker
voltage flicker frequency caused by individual wind severity, PST, usually over 10 minute intervals. The long
waves would be of the order of 0.1Hz. However, the term flicker severity PLT is usually assessed over several
modulation of the voltage envelope by these individual days can be calculated from a successive of PST’s.
wave frequencies may just lie within the tolerable The final design of the flickermeter is left to the
voltage limits for a weak grid. These large voltage engineer, although the standard does give tests to check
excursions at low frequencies do have an effect on that the meter falls within specification.
voltage flicker which must be assessed. Another effect
of wind waves is that they tend to come in groups, SOFTWARE FLICKERMETER
producing a modulation effect on the individual waves. The purpose of the software flickermeter was to provide
IEC STANDARD METER online and offline flicker performance for the LIMPET
station.. The software flickermeter is divided into 2
The IEC have set standards for the measurement and parts, namely the instantaneous flickermeter model and
analysis of flicker severity. These are laid out in IEC the statistical analysis.
868 and show the design specifications of a
flickermeter(4,5). The meter is essentially composed of Instantaneous Flickermeter Model
several blocks, the purpose of each detailed as follows. The instantaneous flicker level is calculated by firstly
Block 1 – Input voltage transformer with automatic gain standardising (reduction to per unit value) and then
control– this accepts a wide range of nominal mains sampling the voltage waveform. This signal is squared,
voltages and adapts them to a maximum level simulating the lamp response, before being passed to
compatible with the operation of the following circuitry. several filters which simulate the eye-brain response.
The output of the block is the RMS voltage modulated This gives the instantaneous flicker sensation level. The
with the disturbance function. output of the system is the instantaneous flicker level
which must be further processed to give a value for PST.
Block 2 – Squaring Demodulator – this circuit gives a
component of its output a voltage linearly related to the Statistical Analysis
amplitude of the fluctuation modulating the input. It is The output of the instantaneous model produces a time
essentially simulating the flicker produced by a tungsten trace of flicker sensation which is passed to a function
filament lightbulb. Part of the output component is the that performs the statistical analysis. This must be done
in order to calculate the flicker sensation over a long methods employed to deal with the problems
enough period to allow for the build up of annoyance. experienced are shown below:
The statistical method is because flicker is made up of Logarithmic classes – The flicker level is sorted into
regular and irregular voltage anomalies. These can make classes or bands of flicker severity, these bands being
the instantaneous flicker level vary widely but perhaps spaced logarithmically. If a CPF was to be plotted solely
not perceptibly over the observed period. This means from this information it would form a staircase function.
that types of occurrence must be weighted. Also, it is This type of function cannot be used to accurately
important to know for what percentage of the observed interpolate the percentile points. Instead, the midpoint
period any given flicker level has been exceeded. of each class was found linearly and a curve fitted
between the points. This produced a smooth CPF for
In order to meet these requirements, a function was
more accurate interpolation.
written which sorted the instantaneous flicker into a
series of class levels, and then built up a probability Empty Classes – There is the possibility that there will
function of class level exceedence which could be used be class levels which have no flicker points in them.
to calculate the short term flicker severity. The short- When the CPF is constructed, even with the curve
term flicker severity may be evaluated in as short a time fitting described above, these empty classes produce flat
as 10 minutes as a 10 minute interval is long enough for spots, or part of a staircase function. If the required
an individual to notice the disturbance and its percentile happens to lie at this flat spot, the
persistence without giving too much importance to interpolation can have infinite solutions. To remove
isolated voltage changes. this possibility, any flat spots in the CPF are smoothed
by curve fitting using data either side of the flat spot.
Classification Method
The 0.1 percentile point – This is the point in the
For the software flickermeter, the classification method
function exceeded only by 0.1% of the flicker or 1 in
chosen was to have a 200 level logarithmic classifier.
1000 samples. If the maximum flicker occurs only
The percentage of time the flicker spends in each of
occasionally then this point will not be measured.
these levels is then calculated over the 10 minute test
Statistically it must exist, but over the given sample
period. A cumulative probability function (CPF) is
time it may not have been recorded. To ensure that this
established from the class level data. The probability
percentile point can be found from the CPF, several
function is defined as the probability that a level will be
points are used to extrapolate back to the 0.1 percentile
exceeded. The PST value is defined as
point. The weighting applied to this percentile
PST = K1P1 + K 2P2+....K n P n coefficient in the calculation of PST is small compared
with the other coefficients and so the accuracy of this
where P1, P2,.. Pn are CPF percentile points with an method is adequate.
assigned probability of being exceeded and K1, K2,..
Kn are weighting coefficients. In order to find the Flickermeter Sample Frequency
flicker level at a particular percentile point it is The IEC standard states that the flickermeter classifier
necessary to use an interpolation algorithm. Details of must have a sample rate of at least 50Hz. However, due
possible methods are given in the IEC standard. to the low frequency of sea waves and the inertia of the
The maximum flicker level was chosen to get a good turbine/generator system, the frequencies produced by a
spread of data throughout the levels, which in turn wave-power station are much lower.
produces a smoother CPF for PST calculation. The PST The drawback of the standard flickermeter for real time
could then be calculated using the equation with the analysis, is the high sample rate and the amount of
percentiles and weightings given in Table 1. processing required to produce a value for PST. To
Percentile (Pn) Weighting (Kn) store the voltage or power data for off-line analysis by
the flickermeter model consumes a lot of memory. The
0.1 0.0314 solution is to reduce the sample frequency of the
1 0.0525 flickermeter, so that less storage and processing is
3 0.0657 required. Although the flicker created by the wave-
10 0.28 power station is of a low frequency, reducing the sample
rate of the classifier will cause problems with the
50 0.08
percentile interpolation. Over a 10 minute interval at a
Table 1 – Percentiles and Weighting Coefficients frequency of 2Hz there will be only 2000 samples and
Percentile Interpolation this greatly reduces the number of samples per class
interval. This has a detrimental effect on how well the
There are several problems associated with the CPF can be produced and hence how accurately the
interpolation of the percentile points from the percentiles can be interpolated for PST calculation.
cumulative probability function. Interpolation is usually
necessary as it is unlikely that all the required percentile In order to understand the effect that the classifier
points lie exactly on the CPF at measured values. The sample frequency had on the accuracy of the
calculation, a test was devised to compare various
classifier set-ups at low frequencies. Several traces of flicker analysis can be performed on individual phases
voltage were processed with the flickermeter sample and this could highlight conditions of grid unbalance.
frequency ranging from 50Hz down to 1Hz. The results
are shown in Figure 3.
230
220
5
PST % Error
215
4 0 100 200 300 400 500 600 700 800 900 1000
3 230
1
220
0
50 20 10 5 2 1
215
Flickermeter Sample Frequency 0 100 200 300 400 500 600 700 800 900 1000
240
Figure 3 – Classifier Sample Frequency Comparison
7
Phase Flicker PST
R-Phase 0.125
Ins tantaneous Flic k er Level
5
Y-Phase 0.152
4
B-Phase 0.144
3 Mean flicker Standard Deviation
2 0.140 0.034
1 Table 2 – Flicker Results
0
0 100 200 300 400 500 600 A further result of the analysis is that the flicker values
Tim e (sec s )
produced for each phase are slightly different. The
Figure 6 – Instantaneous Flicker with class levels values shown in Table 2 give the phase average over all
the data analysed. The difference is to be expected
This shows the variation in flicker intensity and the since an islanded system such as Islay is unlikely to
class levels used in order to classify it. The nature of have a balanced grid and hence the phase susceptibility
the flicker variations show that the trace is more often at to flicker will be different for each phase.
lower levels than at higher levels therefore being better
suited to a logarithmic classifier. CONCLUSIONS
The resultant cumulative probability function produced It has been shown that it is possible to create and test a
from the classified instantaneous flicker sensation trace software flickermeter that complies to the IEC
in Figure 6 is shown in Figure 7. This shows a smooth standards. Furthermore it has been shown that this
and complete function, a result of the having adequate meter can be used to assess impact on the grid that a
data along with a logarithmic classifier. This type of wave-power station has.
CPF produces confidence in the interpolated percentile Frequency analysis of the voltage waveforms measured
points used in the final calculation of PST. at LIMPET have shown that the frequencies
CP F of s ignal perm anenc e in c lass es contributing to flicker are those of the individual waves
100
and a low frequency modulated wave. The frequency
90 analysis also showed that because the voltage waveform
80 was subject to only low frequency fluctuations, the
Cum ulative P robability Func tion %
70
flickermeter sample frequency could be reduced without
loss of accuracy.
60
50
The work to date has shown that the LIMPET station is
working well within acceptable limits of flicker.
40
Although the data was taken when the station was
30
working below its installed capacity, it is thought that its
20 flicker performance at rated output will be similar since
10 a control strategy based on quality of supply will be
0
used once the station has been fully commissioned
-11 -10 -9 -8 -7 -6
10 10 10 10 10 10
Clas s Num ber REFERENCES
Figure 7 – CPF with percentiles 1. Heath T.V., The History and Status of the LIMPET
Project, IMechE Seminar, November 1999
RESULTS
2. Description of Limpet Wave Station and Technical
A range of 3 phase voltage traces were available from Specifications available on WaveGen’s website:
the LIMPET station taken from the station operating at 3. www.wavegen.co.uk
average power levels just under 100kW with peak
power output reaching 150kW. The files were taken on 4. Beattie W.C., Sprevak D., Alcorn R.G., Producing
successive days but all displayed similar frequency acceptable electrical supply quality from a wave-power
content of that shown in Figure 5. Also, since the station, Proc Conference OMAE 98 Greece, 1998
station was in a commissioning mode when the data was 5. IEC 868, Flickermeter – Function and Design
being taken, all the power levels are very similar. This specifications, IEC, Geneva 1986 (BS EN 60868-0)
allows the files to be used as a group and average flicker 6. IEC 868-0, Flickermeter – Evaluation of Flicker
levels to be found. The results are given in Table 2. Severity, IEC, Geneva 1991 (BS EN 60868-0)
The results show that for the range of data analysed, the 7. Alcorn R.G., Beattie W.C., Control strategy
flicker is well within acceptable limits, having an development for remote Wave-Power Stations, UPEC
average of 14% of maximum tolerance. It can also be 2000 Conference, Belfast.