• Products released:
- REB670 bus bar protection
- REC670 bay control
- RED670 line differential protection
- REL670 line distance protection
- RET670 transformer protection and control
• IEC 61850-8-1
• Pre-configured and customized variants
1.1 Growth with increased offering
• New LHMI with graphic display, navigation keys, function keys for quick access,
push buttons for control operations, multi-color LEDs with alarm
• Improved EMC
• IEC 61850-8-1 Edition 1 and 2 without firmware change
• Forcing of binary outputs for efficient and fast testing and commissioning
• Cyber security support for compliance to NERC CIP and IEC 62351-8
• Improved IEC 60870-5-103
• Global base values for easier and faster settings of protection
• Disturbance recording binary channels
- REC670: 352 channels
- All others: 96 channels
• Application functions
- High speed distance protection (Quad), tested to IEC 60255-121
- Multipurpose filter for advanced applications like sub-synchronous measurement and protection
- Improved fault locator
- Flexible breaker monitoring functionality
- Frequency accumulative protection
- Voltage differential based fuse supervision
- Stator and Rotor overload functions
- Binary signal integrator
- Limit counter function
- Gas/Liquid medium supervision
- Improved pole slip functionality
Application functions
• Centralized busbar protection covering up to 6 zones (1ph)
• High speed line differential protection including charging current compensation using remote
voltage measurement
• Existing high-speed distance protection to now handle parallel-line application and supports up to 7 zones
• Increased number of functional instances in REL670 can protect two overhead lines (one as main and
another as backup) single IED.
• Extremely fast transient direction detection based on RALDA principle imple-mented in line distance protection
for series compensated line
• RET670 includes state-of-art differential protection for phase shifting transformer
• Railway protection functions covering 16,7/50/60 Hz system frequency
• Support for digital substation architectures with clear and logical separation of functionality when logical nodes
reside on process level devices
• Conditional blocking with only dependent functions blocked based on quality of SVs and thereby increasing the
availability of protection & control
• New Transformer insulation loss-of-life condition monitoring and through fault monitoring functions.
• New and novel earth fault protection for any grounding network type that can detect faults more accurately
and securely
• Complete set of current and voltage-based unbalance protection for shunt capacitor banks
• New distance to fault location function based on double end measurement
• Current/voltage harmonic monitoring functionality to monitor harmonic distortion up to 9th harmonics,
total harmonic distortion, and total demand distortion
• New fault component monitoring function captures peak and RMS current and voltage at the time of fault and
reports via IEC 61850
• Several math and logic functions added to develop additional application logics
Hardware enhancements
• New closed box casing with higher ingress protection class
• New numerical processor module enabling higher performance and capabilities in the IED
• New line data communication module (LDCM) that supports 2Mbps/64kbps. 2Mbps enables transfer of
9 Analogs and 192 Booleans simultaneously
• New optical Ethernet module to support Ethernet ports 5, 6
• Rear Ethernet ports can be freely chosen as optical LC or RJ45 connectors
• Electronic modules are conformal coated for higher reliability
• Additional Milliamp-Input-Module (MIM) – maximum of 6 MIM from earlier 4 modules
• Static Output Module (SOM) with enhanced breaking capacity
• System and cyber-security related
• Central account management supports Microsoft® Active Directory service for user man-agement and secure
communication via LDAP over SSL
• Higher cyber security data encryption levels
• IEC 61850 communication supervision now covers GOOSE and sample value
• Up to 200 disturbance records and 5000 events supported.
• Disturbance recorder supporting both COMTRADE-2019 and COMTRADE-2013 formats
Hitachi Energy We reserve the right to make technical changes or modify the We reserve all rights in this document and in the subject matter
© 2022 Hitachi Energy. All rights reserved. contents of this document without prior notice. With regard and illustrations contained therein. Any reproduction, disclosure
4CAE000226 to purchase orders, the agreed particulars shall prevail. Hitachi to third parties or utilization of its contents – in whole or in parts
Energy Ltd. does not accept any responsibility whatsoever for – is forbidden without prior written consent of Hitachi Energy Ltd.
www.hitachienergy.com potential errors or possible lack of information in this document.