Klasifikasi Besaran Tegangan

 LV (Low Voltage)
50 Volt - 1000 Volt (1KV)
 MV (Medium Voltage)
1KV - 35KV
 HV (High Voltage)
35KV – 245KV
 EHV (Extra High Voltage)
EHV > 245KV
AREA AMAN PENGOPERASIAN
MV Distribution
SM6 range 3 to 24 kV
Pengenalan Panel MV

Switching Function
1. DS (Disconnector Switch)
Suatu rangkaian peralatan yang dapat difungsikan pada keadaan
bertegangan dan tanpa beban.

2. LBS (Load Break Switch)


Suatu rangkaian peralatan yang dapat difungsikan pada keadaan
bertegangan dan berbeban.

3. CB (Circuit Breaker)
Suatu rangkaian peralatan yang dapat difungsikan pada keadaan
bertegangan, berbeban dan gangguan.
Pengenalan Panel MV
SM6 Panel MV Family
1. IM (LBS)
- Incoming / Outgoing Panel
2. CM (LBS)
- Metering Panel, Potential Transformer & Fuse
3. QM (LBS)
- Outgoing Panel, Fuse
4. DM1-A (Fixed Type) & DM1-W (withdrawable Type), (LBS + CB)
- Incoming / Outgoing Panel
5. DM2 (Double LBS & CB)
- Coupler Panel
6. GAM - LA
- Arrester Panel
Pengenalan Panel MV

Introduction
The SM6 range is made up of modular units containing
fixed or withdrawable metal enclosed SF6 switchgear,
including:
• switch-disconnectors;
• Fluarc SF1 or SFset circuit breakers;
• Disconnectors.
IM – Switch cubicle
1. Bus bar compartment
2. LV compartment
3. Switch & earthing switch
4. Operating mechanism compartment
5. Cable compartment
A. Earth bar connection
B. Bus bar connection
C. Cable connection
D. Voltage indicator
E. Capacitive divider
F. Front panel
G. Inspection windows
QM –
Fused switch combination cubicle

1. Bus bar compartment


2. LV compartment
3. Switch & earthing switch
4. Operating mechanism compartment
A. Earth bar connection
B. Bus bar connection
C. Voltage indicator
D. Tripping unit
E. Front panel
F. Cable connection
G. Inspection windows
H. Capacitive divider
I. Earthing switch
DM1A circuit breaker cubicle

1. Top busbar compartment


2. LV compartment
3. Switchgear compartment:
feeder disconnector
4. Operating mechanism
compartment
5. Cable connection or lower
busbar compartment

A. Earth bar connection pad


B. Top busbar connection pads
C. Inspection windows
D. SF1 type MV Circuit Breaker
E. Front panel
SM6 range - connection
Operating Instruction
IM & QM
Operating instructions IM and QM

Double-function operating Double-function operating


mechanism CIT mechanism CI1

Double-function operating
mechanism CI2
Operating instructions IM and QM

• Gas tightness: The enclosure filled with


SF6 gas satisfies <sealed pressure
system> requirements and seal tightness
is always checked in the factory.
• Operating safety: The switch may be in
one of three positions, “closed”, “open” or
“earthed”, representing s natural
interlocking system that prevents incorrect
operation. Moving contact rotation is driven
by a fasting mechanism that is independent
of the action of the operator.
SM6 switch-disconnector and
earthing switch and the SFset
and SF1 circuit breaker use
sulphur hexafluoride gas
(SF6) for insulation and
breaking.
Operating instructions IM and QM
Operating instructions IM and QM
Operating instructions IM and QM
Operating instructions IM and QM
Fuse indications on QM cubicles
Padlocking
Padlocking
Operating safety
Maintenance of
SM6 Cubicle
Maintenance of SM6 Cubicle

Grease - mechanical
 Description : Isoflex TOPAS L 152
 Part NB : 18 315 110
 Application : CB operating mechanism
Earthing switch operating mechanism
 Brand : Kluber, LAM
 Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle

Grease - electrical
 Description : Vaseline B5 (WP 70)
 Part NB : 18 317 103
 Application : CB fixed & moving contact
Earthing switch fixed & moving contact
 Brand : Motul, LAM
 Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle

 Vacuum cleaner
Tool
 Torque wrench (1 to 50 Nm)
 1/4 - 3/8 adapter
 6 mm extension fitting
 6 mm male hexagonal fitting
 10, 13, 17 and 19 mm ring wrench
 ( - ) screwdriver
 Three phases grounding jumper
 Multi meter
 Flashlight
 White cleaning cloth
 Alcohol 70% or 90%
Maintenance of SM6 Cubicle

• Never lubricate the operating mechanism


• No particular maintenance is required
under normal operating conditions
(temperature between –5 oC and 40 oC).
• For severe operating conditions
(aggressive environment, dust,
temperature below –5 oC or above 40 oC,
etc.), please consult Schneider Electric
Maintenance of SM6 Cubicle
Maintenance of SM6 Cubicle
Maintenance of SM6 Cubicle
Corrective maintenance
• Replacing the fuses
– The cubicle must be de-energized
– The switch must be opened
– The earthing switch must be closed
– Open the front panel for access to the fuses
• Important :
– Standard IEC 282.1 & 23.2 states that all three of
the MV fuses should be changed whenever one of
them blows.
Replacing a voltage indicator block

• Pull out the voltage indicator block. The


cubicle can remain energize.
Start-up Instruction
Check before energizing

• Check that nothing has been left in the


compartment, for all phases :
– Check that the fuse has been
properly fitted
– Check that the field distributor
covers have been properly closed on
all phases
– Check that the fault detector has
been properly connected
Operating test before energizing

Operate the switch several Operate the earthing switch


times several times
Voltage indicator

As soon as the cables have been energized, the


voltage indicator lamp should go on
Operating Instruction
DM1A
General description
DM1 circuit breaker cubicle

1. Top busbar compartment


2. LV compartment
3. Switchgear compartment:
feeder disconnector
4. Operating mechanism
compartment
5. Cable connection or lower
busbar compartment

A. Earth bar connection pad


B. Top busbar connection pads
C. Inspection windows
D. SF1 type MV Circuit Breaker
E. Front panel
General description
DM1A Version (cable incoming or outgoing)
(front panel removed)

F. Voltage indicator
G. Voltage transformers
H. Current transformer
K. Load-side earthing switch
L. Capasitive voltage diveders
M. CB control panel
N. Insulating shields
SF1 circuit breaker
SF1 circuit breaker
1. Enclosure
2. Bottom cover
3. Operating shaft
4. Main moving contact
5. Moving arching contact
6. Fixed arcing contact
7. Sealing system
8. Compression chamber
9. Moving piston
10. Valves
11. Insulating nozzle
SF1 circuit breaker
• Gas tightness: The enclosure filled with SF6 gas • Precompression: When the contacts begin to
satisfies “sealed pressure system” requirements opein, the piston slightly compress the SF6 gas in
and seal tightness is always checked in the the pressure chamber.
factory.
• Arching period: The arc then forms between the
• Operating safety: As for switch-units, accidental arcing contacts and the piston continues its
over-pressures are eliminated by the opening of downward movement. A small quantity of gas,
the safety membrane. directed by the insulating nozzle, is injected into
the arc. The cooling of the arc is thus achieved
• Breaking principle: The circuit breaker is based
through forced convection for the interruption of
on the SF6 gas autocompression principle. The
low currents, however during the interruption of
inherent qualities of SF6 and the soft break
low currents, thermal expansion is responsible for
resulting from this techniques reduce switching
the transfer of the hot gases toward the cold parts
over voltages.
of the pole unit.
Toward current zero, the distance
between the two arcing contacts is
sufficient for final interruption of the
current due to the dielectric-properties
of the SF6 gas.

• Sweeping over-stroke: The moving


parts finish their travel whereas the
cold gas injection continues until the
contacts are completely open.
Start-up & operating instructions
Feeder disconnector operating lever positions

Position the lever as indicated Position the lever as indicated


for downward (opening) for upward (closing) operations.
operations.
Start-up & operating instructions
CB no-load Operations
Start-up & operating instructions
De-energizing the load side of the installation

Initial status:
1. Open CBby 2. Lock the CB
The feeder open with key
pressing
disconnector is in in C by
pushbutton O.
closed position. pressing
CB is closed. pushbutton O.

3. Remove key 4. Set feeder


from C & disconnector
insert it in A. to open
Unlock lever position.
insertion point
E of feeder
disconnector.
Start-up & operating instructions
De-energizing the load side of the installation

5. Set feeder disconnector to


earthed position. The front
panel can be removed.
Note: in the case of a DM1A,
the load earthing switch
closes simultaneously.
Start-up & operating instructions
Operating safety

Operation is impossible when If the feeder disconnector is


CB is closed. in open or closed position,
the front panel can not be
The front panel can not be
removed.
removed or installed unless
the feeder disconnector is in If the front panel is removed,
earth position. the feeder disconnector can
be set to open position.
However it can not be set to
closed position.
Maintenance of
SM6 Cubicle
Maintenance of SM6 Cubicle

Grease - mechanical
 Description : Isoflex TOPAS L 152
 Part NB : 18 315 110
 Application : CB operating mechanism
Earthing switch operating mechanism
 Brand : Kluber, LAM
 Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle

Grease - electrical
 Description : Vaseline B5 (WP 70)
 Part NB : 18 317 103
 Application : CB fixed & moving contact
Earthing switch fixed & moving contact
 Brand : Motul, LAM
 Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle

 Vacuum cleaner
Tool
 Torque wrench (1 to 50 Nm)
 1/4 - 3/8 adapter
 6 mm extension fitting
 6 mm male hexagonal fitting
 10, 13, 17 and 19 mm ring wrench
 ( - ) screwdriver
 Three phases grounding jumper
 Multi meter
 Flashlight
 White cleaning cloth
 Alcohol 70% or 90%
Maintenance of SM6 Cubicle
Replacing a voltage indicator block

• Pull out the voltage indicator block. The


cubicle can remain energize.
Start-up & operating instructions
Checks before energising

Check that nothing has


been left in the connection
compartment.

Put the front panel back in place


Start-up & operating instructions
Energizing the load side of the installation

Initial status: 1. Set the feeder 2. Set the


disconnector to feeder
The feeder disconnector
open position
disconnector is in using the to closed
earth. CB is locked operating lever. position,
open position. Note: in the case then lock
Front panel in of a DM1A, the lever
load earthing insertion
place. point E of
switch opens
simultaneously. feeder
disconnector
with key to
3. Remove key from 4. Close
A. CB by
A,place in C and pressing
unlock the CB. pushbutton I.
Charge the CB (see The load side
CB instructions). of the
installation is
energized.
Start-up & operating instructions
Padlocking

With one to three 8 1. Padlocking 2. Padlocking


mm padlocks per feeder feeder
locking point. disconnector disconnector
in earth in open
position. position.

3. Padlocking 4. Padlocking
feeder of the front
disconnector panel.
in closed (1 padlock
position. only)