Panel
PENGALAMAN KERJA
LV (Low Voltage)
50 Volt - 1000 Volt (1KV)
MV (Medium Voltage)
1KV - 35KV
HV (High Voltage)
35KV – 245KV
EHV (Extra High Voltage)
EHV > 245KV
AREA AMAN PENGOPERASIAN
MV Distribution
SM6 range 3 to 24 kV
Pengenalan Panel MV
Switching Function
1. DS (Disconnector Switch)
Suatu rangkaian peralatan yang dapat difungsikan pada keadaan
bertegangan dan tanpa beban.
3. CB (Circuit Breaker)
Suatu rangkaian peralatan yang dapat difungsikan pada keadaan
bertegangan, berbeban dan gangguan.
Pengenalan Panel MV
SM6 Panel MV Family
1. IM (LBS)
- Incoming / Outgoing Panel
2. CM (LBS)
- Metering Panel, Potential Transformer & Fuse
3. QM (LBS)
- Outgoing Panel, Fuse
4. DM1-A (Fixed Type) & DM1-W (withdrawable Type), (LBS + CB)
- Incoming / Outgoing Panel
5. DM2 (Double LBS & CB)
- Coupler Panel
6. GAM - LA
- Arrester Panel
Pengenalan Panel MV
Introduction
The SM6 range is made up of modular units containing
fixed or withdrawable metal enclosed SF6 switchgear,
including:
• switch-disconnectors;
• Fluarc SF1 or SFset circuit breakers;
• Disconnectors.
IM – Switch cubicle
1. Bus bar compartment
2. LV compartment
3. Switch & earthing switch
4. Operating mechanism compartment
5. Cable compartment
A. Earth bar connection
B. Bus bar connection
C. Cable connection
D. Voltage indicator
E. Capacitive divider
F. Front panel
G. Inspection windows
QM –
Fused switch combination cubicle
Double-function operating
mechanism CI2
Operating instructions IM and QM
Grease - mechanical
Description : Isoflex TOPAS L 152
Part NB : 18 315 110
Application : CB operating mechanism
Earthing switch operating mechanism
Brand : Kluber, LAM
Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle
Grease - electrical
Description : Vaseline B5 (WP 70)
Part NB : 18 317 103
Application : CB fixed & moving contact
Earthing switch fixed & moving contact
Brand : Motul, LAM
Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle
Vacuum cleaner
Tool
Torque wrench (1 to 50 Nm)
1/4 - 3/8 adapter
6 mm extension fitting
6 mm male hexagonal fitting
10, 13, 17 and 19 mm ring wrench
( - ) screwdriver
Three phases grounding jumper
Multi meter
Flashlight
White cleaning cloth
Alcohol 70% or 90%
Maintenance of SM6 Cubicle
F. Voltage indicator
G. Voltage transformers
H. Current transformer
K. Load-side earthing switch
L. Capasitive voltage diveders
M. CB control panel
N. Insulating shields
SF1 circuit breaker
SF1 circuit breaker
1. Enclosure
2. Bottom cover
3. Operating shaft
4. Main moving contact
5. Moving arching contact
6. Fixed arcing contact
7. Sealing system
8. Compression chamber
9. Moving piston
10. Valves
11. Insulating nozzle
SF1 circuit breaker
• Gas tightness: The enclosure filled with SF6 gas • Precompression: When the contacts begin to
satisfies “sealed pressure system” requirements opein, the piston slightly compress the SF6 gas in
and seal tightness is always checked in the the pressure chamber.
factory.
• Arching period: The arc then forms between the
• Operating safety: As for switch-units, accidental arcing contacts and the piston continues its
over-pressures are eliminated by the opening of downward movement. A small quantity of gas,
the safety membrane. directed by the insulating nozzle, is injected into
the arc. The cooling of the arc is thus achieved
• Breaking principle: The circuit breaker is based
through forced convection for the interruption of
on the SF6 gas autocompression principle. The
low currents, however during the interruption of
inherent qualities of SF6 and the soft break
low currents, thermal expansion is responsible for
resulting from this techniques reduce switching
the transfer of the hot gases toward the cold parts
over voltages.
of the pole unit.
Toward current zero, the distance
between the two arcing contacts is
sufficient for final interruption of the
current due to the dielectric-properties
of the SF6 gas.
Initial status:
1. Open CBby 2. Lock the CB
The feeder open with key
pressing
disconnector is in in C by
pushbutton O.
closed position. pressing
CB is closed. pushbutton O.
Grease - mechanical
Description : Isoflex TOPAS L 152
Part NB : 18 315 110
Application : CB operating mechanism
Earthing switch operating mechanism
Brand : Kluber, LAM
Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle
Grease - electrical
Description : Vaseline B5 (WP 70)
Part NB : 18 317 103
Application : CB fixed & moving contact
Earthing switch fixed & moving contact
Brand : Motul, LAM
Remark : Recommended for all equipments :
VM6, SM6, Fluair, etc.
except HVDS
Maintenance of SM6 Cubicle
Vacuum cleaner
Tool
Torque wrench (1 to 50 Nm)
1/4 - 3/8 adapter
6 mm extension fitting
6 mm male hexagonal fitting
10, 13, 17 and 19 mm ring wrench
( - ) screwdriver
Three phases grounding jumper
Multi meter
Flashlight
White cleaning cloth
Alcohol 70% or 90%
Maintenance of SM6 Cubicle
Replacing a voltage indicator block
3. Padlocking 4. Padlocking
feeder of the front
disconnector panel.
in closed (1 padlock
position. only)