You are on page 1of 3

L&T CONSTRUCTION

Water & Effluent Treatment IC, EDRC


Project: Satna WSS Job No. Date:

Structure: OHT Location: Gadauli (OHT 69) - 26.4.24


Prepared Checked BH
Title: SBC calculation based on Shear Failure criterion
VNSN SNNS 1
Bearing Capacity Calculations as per G.S.F or L.S.F or Intermediate Shear failure Criteria

Description Symbol Dimension Unit

Ground level 0.00 m

Founding level RL -3.00 m


Type of Foundation envisaged Square Footing

Depth of Foundation with respect to G.L Df 3.00 m

Width of Foundation B 2.80 m

Length of Foundation L 2.80 m

Design parameters from Soil investigation Report

Cohesion C 2.20 t/m2

Actual Angle of internal friction of the soil φ 14.00 Deg.

Angle of internal friction for G.S.F φGSF 14.00 Deg.

Angle of internal friction for L.S.F φLSF 28.00 Deg.

Modfied Angle of internal friction for L.S.F φ'LSF 9.44 Deg.

Reduced Cohesion C' 1.47 t/m2


Bulk unit weight of soil g 1.722 t/m3

Inclination angle of load from vertical a 0.00


Reduced level of Ground Water level GWT (R.L) 0.00 m

Depth of Ground Water level Dw 0.00 m

Water table correction factor W' 0.500

Void ratio e 0.59

Factor of safety FOS 2.50


"General Shear failure"-

Nq =tan2(45+φ/2) xeπ tanφ 3.58


Page No 220 of Bowles
Nc =( Nq - 1) x Cot φ 10.34
5th edition
Ng =2 x (Nq+1) x tan φ 2.28
Bearing capacity factors considering G.S.F.

Shape Factor Sc Sq Sγ As per IS:6403-1981

Square Footing 1.30 1.20 0.80


Inclination factors As per IS 6403 - 1981
2
ic = iq= (1 -a / 90) 1.00

ig = (1 -a / f) 2
1.00
ic=iq=ig =1 1.00
Depth factors

Nφ 1.64

dc = 1 + 0.2 x (Df / B) x (Nφ)1/2 1.27

dq = dg=1 for φ <100

dq = dg=1+0.1x(Df / B) x (Nφ)1/2 for φ >100 1.14


Sensitivity: LNT Construction Internal Use
#
L&T CONSTRUCTION
Water & Effluent Treatment IC, EDRC
Project: Satna WSS Job No. Date:

Structure: OHT Location: Gadauli (OHT 69) - 26.4.24


Prepared Checked BH
Title: SBC calculation based on Shear Failure criterion
VNSN SNNS 1

Calculations
Surcharge at base level of foundation=γ x Df q 2.17 t/m2
Net Ultimate bearing capacity
CNcScdcic+q(Nq-1)sqdqiq+0.5gBNgSgdgigW' qnult 47.79 t/m2 AS per IS 6403
Factor of safety, FS 2.50
Net SBC for G.S.F qs 19.11 t/m2
"Local Shear failure"-
2 π tanφ'
Nq' =tan (45+φ'/2) xe 2.34
Nc' =( Nq' - 1) x Cot φ' 8.08
Ng' =2 x (Nq'+1) x tan φ' 1.11
Bearing capacity factors considering L.S.F.

Shape Factor Sc Sq Sγ As per IS:6403-1981

Square Footing 1.3 1.20 0.80


Depth factors 1.39
Nφ 1.39

dc = 1 + 0.2 x (Df / B) x (Nφ)1/2 1.25

dq = dg=1 for φ <100


dq = dg=1+0.1x(Df / B)x(Nφ)1/2 for φ >100 1.00
Inclination factors As per IS 6403 - 1981
2
ic = iq= (1 -a / 90) 1.00

ig = (1 -a / f)2 1.00

ic=iq=ig =1 1.00
Calculations
Surcharge at the base level of foundation = γ*Df q 2.17 t/m2
Net Ultimate bearing capacity

2/3CNcScdcic+q(Nq-1)sqdqiq+0.5gBNgSgdgigW' qnult 23.88 t/m2 AS per IS 6403


Factor of safety, FS 2.50
Net SBC for L.S.F qns 9.55 t/m2

Interpolation Factor based on Void Ratio I 0.81

Net SBC qns 17.30 t/m2

Recommended Net SBC qns 12.00 t/m2

Sensitivity: LNT Construction Internal Use


#
L & T Construction
Water & Effluent Treatment IC, EDRC
Project: Satna WSS Job No. Date:
Structure: OHT Location: Gadauli (OHT 69) - 26.4.24
Prepared Checked BH
Title: SBC calculation based on Settlement Failure criterion
VNSN SNNS 1
From To gbulk ɸ c SPT
Soil Classification
(m) (m) (T/m3) () (T/m2) ( N'' )
Silty Clay 0.00 3.00 -- -- -- 13
Silty Clay 3.00 12.80 1.722 14.00 2.20 13 to 86

Description DimensionUnit Remark


Ground level GL 0.00 m
Founding level in RL FL -3.00 m
Depth of Foundation below G.L Df 3.00 m
Type of footing Square Footing
Width of Foundation B 2.80 m
Length of Foundation L 2.80 m
Depth of Pressure Influence Zone Z 5.60 m (2B For Square Footing)
2
Stress at founding level (due to Structure) σ 12.00 t/m
Actual Load at Base of foundation P 94.08 Ton
Bulk density of soil ϒ 1.72 t/m3
SETTLEMENT CALCULATION
Stress on
Width of Length of Area of Young's
From To Thickness loaded Poisson's Average Average Average Modulus, Influence Settlement
Soil Layer loaded loaded loaded M = L/B N = H/B' I1 I2 mv (m2/t)
(m) (m) (m) area (s) ratio (m) N value CR value RQD value E (t/m2) factor, Is (mm)
area (m) area (m) area (m2) 2
(t/m )
Layer - 1 3.00 8.60 5.60 5.60 5.60 31.36 3.000 0.3 51 -- -- 6000 -- -- -- -- -- 0.00095 15.960
Uncorrected Total Settlement = 15.960 mm
Depth Factor, If = 0.73
Rigidity Factor, Isr = 1
Corrected Total Settlement, S = 11.662 mm

Sensitivity: LNT Construction Internal Use


#