Vision Battery Communication Fail Troubleshooting
Vision Battery Communication Fail Troubleshooting
1
Before correction, Battery communication fails and cannot check battery data on controller and SOC on iTower
Fig 1.0-Batteries 5 strings communication fails Fig 1.1-Incorrect battery capacity and string
2
Before correction, Battery communication fails and cannot check battery data on controller and SOC on iTower
Fig 1.2-Incorrect battery capacity and string Fig 1.3-Battery communication fail and SOC on
3
iTower
❖ Troubleshooting for vision battery communication fail
1. Check the batteries ID address(Dip switch)are correct or not and start from ID No-1
Fig-1.7
6
3.Check the batteries LAN cables status(RJ45)
Fig.1.8
7
4. Press menu –Go to configuration-Go to system setting-Modbus Devices-and must correct as below in
Fig,
Fig.1.9 Fig.2.0
8
Go to Modbus devices Go to Modbus number and check each number
Fig.2.1 Fig.2.2
9
Check each device and must correct as below number 1 to 5
3
1 2
4 5
Fig-2.3
10
4. First switch off the battery busbar breaker and as a second switch off the battery breaker about 5 sec or
10sec and switch on. Go to the Pluto plus controller configuration and press clear event and uninstall
equipment about 4 times. And check on controller for the battery communication status connected or not.
If not and still communication fail, press the reset button on battery 1 or 2 sec.After that go to controller
and enter configuration and press, clear event and uninstall equipment about 4 times.
And check again the battery communication status connected or not.
Note. During breaker on/off test make sure to run DG manual.
Fig-2.4
11
Thank You