FEATURES & FUNCTIONS
LCD Sync Fail LED
4 Lines X 20 Characters Backlight LCD This LED is on, when the phase angle difference between source-side
Setting & Configuration, Measurement & Monitoring Display voltage (Va) and load-side voltage (Vr) is beyond the preset value. Sync
With enclosure door closed, LCD & LED's are off to save power. Fail information as well as Open Line Detection is used together before
Close Control. In Sync Fail case, Close control command should be

RS232 Communication Port (DB9 Female)


inhibited.

Local operator can change setting and configuration or monitor the


current data through this port to setting tool with Notebook computer.
REMOTE CONTROL Button and LED
Control position is determined Local or Remote using this button.
MENU / UP / DOWN / ENTER Buttons LED is on when to Remote. Operation of this button is only possible
LCD Menu Operation Buttons (Setting & Display) locally but the status is monitored remotely as well. This scheme and
* 4 Setting Groups (Different setting values can be edited and saved for information is used for local operator's safety.
each group, and then an active setting group is selected to apply.)
BATTERY TEST Button and LED
RESET Button This button is used to test battery and charger circuit. When the test
Annunciator LED Reset Button (Fault Indication & System Error) result is OK, green color LED is on for 3 seconds and off thereafter.
Otherwise, LED is not on.
Run / Error / RX / TX / RTS /
AC On / Batt. Low LED's OPEN / CLOSE Buttons and LED's
Run : CPU Run
These buttons are used to locally control (Open / Close) the switch body.
Error : System Check
Before open or close control command, check first if the control position
(On in case that Self Diagnosis results in error)
is in Local.
RX : Communication Data Received
TX : Communication Data Transmitted CLOSE : Push this button to control the switch body manually to be closed.
RTS : Data Transmission Request
AC On : External AC power is being supplied to FRTU. OPEN : Manual open control opens the switch body
Batt.Low : Battery is overdischarged or charger circuit fails.

Fault Location Function


Gas Low(optional):Gas Pressure Low only for SF6 gas insulated switch

The distribution line has a lo


lot of load changes and not consistent impedance
A-phas
A-phase
se / B-phase / C-phase / due to its radial method itself.
itsel
nd Fault
Ground Fau lt (N)
ault ( & SEF LED's
Our solution, CALIPA-FLS provides
p the precise fault location using the suitable
F t Indication
Fault Indica
c tion
i LED's
L s for forr each
eeacch Phase
P asee andd Earth
Ph a Fault
F l SEF
E Indication
n a for algorithm
go m for thee distribution
t u line which has a lot of
o fluctuation in itself.
Ungrounded
Ungrroundded Network
Netwworkk (Residual
(Reesiduduuall or
or ZCT
CT Input)
ZC Innput)t
When
Whe eenn failure
faaailure
iluree occurs
occurs,
occccurs
urss, thee Fau
Fault
ult
u Location
o t Algorithm
A o m calculates the location of the
faultt by using
usinnng waveform
waaavef
veform information
foorm info t drawn
rmation w from
r EPIC-R300
EP
E and inputted line
Hot
Hot Line
Lin
ne (Source/Load)
(So
ou
urc
ce/
ce/Lo
oad
d)) LED's
LED'
D''s
s
ppara
aamettters..
parameters.

TThesehesse LED's
LE
ED'ss indicate
indiicatee if source-side
sourcce-side d andand load-side
load--sidee lines
linees are
arre energized
ennergizedd or
nnot.
ot. LED's
LED's
D arearre onn when
whhen each
eachh of theh line voltages
voltages
g goess up the preset presset
V oltaage On
Voltage On Level
Leveel andandd LED's
LE
ED's
D s are
are off
o when
whenn 3-phase
3-pphase voltages
vooltagegese gogo down
doown
Voltage
V oltaage Off
Offf Level.
evel. Voltage
LLeve l g On Level
Voooltage vell and
Leeve and Voltage
Volttage Off Level
V Leveeell are
arree also
alsssoo used
usssed
ed
ffor
or Open
Open Linee Detection
Deete
tect
cttion (Phase
(Phaase Loss),
Loso s), in which
whiichh function
ffunct
fuu tion source-side
ssourcce-side iid and
a d
load-side
load-
o -sidee lines
linees are
arre detected
deetectctted
e to
to bee open
opeen when
whenn theth linee voltage a
ggoes
oess down
dowwn Voltage
Voltltaaggee Off
Off Level,
Levevell, but
butt once
ooncce after
affter open
openn line,
neee, Open
line Opppenen Linee
D eteectionn is reset
Detection rreseet only
only when
whhen the he line
linee voltage
v ltaage goes
vo goess upp Voltage
Volt
Vooltttage
tag
age On Level. Levvel.
RECLOSER
Recloser Control

Technical Data
Fault Detection
Phase & Ground Fault Over Votage
Pickup Level : 10~2000A (step:1A) Pickup level : 1.05~1.50pu (step:0.01pu)
Fast TC Curve : 50 types (ANSI,IECmRecloser) Delay Time : 0.1~180.0 sec (step:0.1sec)
Fast Multiplier : 0.05~2.00 (step:0.01)
Fast Time Add : 0.00~1.00 (step:0.01sec) Under Frequency
Fast Min Responese : 0.00~1.00 (step :0.01sec)
Pickup level : 47.00~59.98Hz (step:0.01Hz)
Delay TC Curve : 50 types (ANSI,IECmRecloser)
Delay Time : 0.03~10.00sec (step:0.01sec)
Delay Multiplier : 0.05~2.00 (step:0.01)
Delay Time Add : 0.00~1.00 (step:0.01sec)
Over Frequency
Delay Min Responese : 0.00~1.00 (step :0.01sec)
Pickup level : 52.02~63.00Hz (step:0.01Hz)
Direction Detection Delay Time : 0.03~10.00sec (step:0.01sec)
3V1 threshold : 0~100% (step:1%)
3I1 threshold : 0~100% (step:1%) Negative Sequence Overcurrent(Broken conductor)
3I1 Angle : 0~359° (step:1°) Pickup I2 / I1 level : 30.0 ~ 100.0 (step: 1%)
I2 / I1 delay time : 0.01 ~ 100.0 (step : 0.01sec)
High Current Trip (HCT)
Phase-HCT Pickup Leve : 25~10000A (step:1A) 4 Setting Groups
Phase-HCT Adder : 0.01~1 (step:0.01sec)
Ground-HCT Pickup Leve : 25~10000A (step:1A) Each group saves individual setting values
Ground-HCT Adder : 0.01~1 (step:0.01sec) for different situations.
Active Setting Group Selection: 1~4
Delay Time Current Trip
Phase-HCT Pickup Leve : 25~10000A (step:1A) Inter lock
Phase-HCT Adder : 0.01~2 (step:0.01sec)
Live Load block
Ground-HCT Pickup Level : 25~10000A (step:1A)
Sync fail block
Ground-HCT Adder : 0.01~2 (step:0.01sec)

Sensitive Earth Fault (SEF)


Pickup I0 : 0.1~20A (step:0.1A) System Configuration
V0 : 10~80% (step:1%) AC Rating
Operating Angle : 0~345° (1°step)
Frequency : 50 or 60Hz
Opearting Time : 0.1~30 sec (step:0.1sec)
Rated Voltage on 4V input : 33.80~ 38 kV (step: 0.01 kV)
CT Ratio (1A nominal) : 1100~2000 (step: 10)
Cold Load
Loa
oad Pickup/Inrush
oad
oa Picckkup/Inrush Restraint
Pi ZCT Ratio (1A nominal) : 1100~2000 (step: 10)
Cold LoaLoad
oadd Phase
Phhas
asee Pickup Multiplier : 1.0~10 (step: 1)
Cold LoaLoadad Time Duration:
Dur
urat ion: 0~180 min (step: 1 min)
atio I/O
Inrush 2nd 2nd Harmonicc Level:
Leve
Le vel:l 1~50%
1~50% (step: 1%) DI Debounce Time : 110~500 msec (step: 5 msec)
Phase,
Ph Ground,
hhaseee,, G rroundd, S EF IInrush
SEF nrrussh BBlock
Bl
loc (yes)
ockk : 1 ((yes (no)
ss)) / 0 ((no
oo)) DO P
D Pulse
l e Width
Widddth : 110 2000
0 msec
10~2000 e ((step:
st 110 msec)

Openn Line
O LLin
innnee (Loss
(LLos
osss off Phase)
Phase) Detection
Deeete
teecct
ctio
tio
iionn Phase
Phas
P sse Rotation
Rotaaationn
R :A
A-B-C
C or A-C-B
C

Voltage
Volt
V tag
agge On
O Level:
Leeevel
el:: 50~90%
5 ~~90%
50 % (step:
(stttep: 5%)
5% %) of rated
r d voltage
voltttage Sta
S atu
a us Monitoring
u
Status Mo
on
onito
n ori g
o
Voltage
Volt
V t gge Off
ltltag O Level:
LLeeevell: 35~75%
35 % (step:
35~~~75%
75% ((ssttep: 5%)%) off rated
% r t d voltage
voltltttage
Deelayy Time:
Delay
D Tim 0.1~30.0
me: 00.1~3
m 1 3030.00 secc (step:
((st ssec)
steeep: 00.11 seeec)
c) Opeeen / C
Op
Open
O Closed
Closssed : Swi
Sw
Switch
i Body
itch B Operated
p t St S
Status
Loca
Lo
LLocal
oca
caal / R Remote
Rem
Remmotee
mote : Con
Control
nntrol Position
s n
Synccchr
Synchronism
S h onism
hr
hro m Check
Cheecck Handle Lock
Handle
H Loccck : Sw
Switch
witch Body
w d Handle
a e Lock
Locking
o (Control Blocked)
Sync
S ync Fail
F il Phase
Phhaas
asee Difference:
Diffff rrenccce: 5~60°(step:
Diffe
Di
D 5~60°(
6 °(ste
60 °( teep: 1°)
1°)) Gas Pressure
G Preeessuuure LowL w : SF SF6
F6 Gas a Insulated
n a Switc Switch
t only(Control Blocked)
Delayy Time:
D Tim
me: 00.1
m 0.1~30.0 (step:
1~33300.00 secc (step
(ste
ep:
eep
p: 00.
0.11 se
sec)
eec) Door Open
Door
D Opppen : Co
Control
ntroll Boxx Enclosure
s Do Door Open
Opeeen Li
Open
O Line
ine (Loss
(Lossss of
o Phase
Phase)
Phhhaseee) Detected
D c d : A / B / C, R / S / T
Undeeer Voltage
Under
U Voltagee Hot (Live)
H (Livve) Line
L Tagg : Sourc
Source-side
r / Load-side
Pickup
P ickup level
levvvel : 0.03~0.95pu
0.0
.033~0.9995puu (step:0.01pu)
((steepp:00.0
.01p
011ppu)) Phasse Sync
Phase
P S c FailFaaail :VVa - VVr
Delayy Time
D Tim
me : 00.1
m 1~~180
180..00 sec
0.1~180.0 seeec (step:0
(s
ssteep::0.11ssec)
(step:0.1sec) FFI (Fault
(FFFault Indication)
Indddicaaationnn)
Technical Data
Control Recording
Local / Remote : Control Position (only locally changeable) Events
Open/Close : Switch Body Status Change Command Totally more than 32,000 events are stored and listed.
DO (Direct Operate) and SBO (Select Before Operate) are supported. I/O events (1024) / Functional events (1024,30000) / System events(256)
Reset : Annunciator Manual Reset Command Fault events (256) /PQM event(256) / Demand profile I,P,Q (6144) /
Battery Test : Battery & Charger Circuit Check Maximum demand profile (1024)

Protection Function Blocking Fault Waveform


Up to 4 faults are stored. (32 samples/cycle, 240 cycles/record)
User Configurable DO Points (reserved) : 2
Graphical Display in Analysis Tool : Ia, Ib, Ic, In, Va, Vb, Vc
Load Profiling
Measurement Demand & Daily Maximum Current: Ia, Ib, Ic, In

Current Demand & Daily Maximum Power: kW, kVAR (A/B/C/3-ph)

RMS & Phase Angle : Ia, Ib, Ic, In, I1, I2, I0
Averaging Interval: 5 / 10 / 15 min
Graphical Display in Analysis Tool
Tr u e RM S : I a, I b , I c
L ast Fau lt Current : I a, I b , I c, I n , I o
Accu r acy : 0.25% or 1A
Others
Read in g Ran g e : 4 ~1 2 5 0 0 A
RTC (Real Time Clock) : YYYY/MM/DD hh:nn:ss
Voltage
SOE (Sequence of Event) Time Resolution : 1 msec
RMS (Source, kV) & Phase Angle (Deg) : Va, Vb, Vc, Vo, V1, V2
Digital Filtering & Dead-band Setting for Analog Inputs
RMS (Load, kV) & Phase Angle (Deg) : Vr, Vs, Vt, Vo, V1, V2
Calibration (Correction Factor) : Factory Setting only
True RMS (Source & Load, kV): Va, Vb, Vc, Vr, Vs, Vt
Ia, Ib, Ic, In, Va, Vb, Vr, Vs, Vt
Va-Vr Phase Angle Difference (Deg)
Factor Magnitude aG0 U5 0 0 ~1 .5 0 0
L ast Fau lt ( V) :Vo
Phase Angle aG0 U0 0 0 ~3 5 9 .9°
Accu r acy : 0.25%
Power Factor
A-phase, B-phase, C-phase and 3-phase
L ead / L ag : L ead = 1
Accu r acy : 0.25% or 1°
Frequency : 45~65 Hz
Power
A-phase, B-phase, C-phase and 3-phase
Active (kW), Reactive (kVAR), Apparent (kVA)
Accuracy: 0.5%
Energy
A-phase, B-phase, C-phase and 3-phase: kWh, kVARh (Import & Export)
Counter
FRTU Restart Count, Switch Trip (Open) Count
Fault Count (A / B / C / N), Total Fault Count
Harmonics
Ia, Ib, Ic, In and I3ph THD (%)
Source-side Va, Vb, Vc and V3ph THD (%)
Load-side Vr, Vs, Vt and V3ph THD (%)
2nd~32nd Harmonics (A, kV) : Ia, Ib, Ic, In, Va, Vb, Vc, Vr, Vs, Vt
VOC (Value Of Change) : VOC (AI / Counter), VOC Limit (AI)
RECLOSER
Recloser Control

General Specifications
Power Source Inputs
AC 127 / 220V (50 or 60 Hz)
Transformer Output : AC 30V, 500VA
Power Supply Unit
Input Voltage : AC 30V, Output Voltage : DC 24V
Battery Charging Voltage : 27V (Temperature Compensated)
Block Overcharge : 32V, Block Overdischarge : 20V
Battery Check & Charger Circuit
Battery
Output : DC 24V
Capacity : 18 amp-hour at +25 C
Run Time : over 36 hrs without AC power
Switch Control : over 20 times without AC power
Recharging Time : within 10 hrs after full discharge
Life Guarantee : 5 years

RECLOSER Power Supply : DC 24V


Modem Power Supply : DC 13.8 / 24V (Factory Configurable)

Heater (optional) Power Consumption : 25W


Operating Temperature : -20 ~ +75 C (Ambient)
Humidity : 95 % RH
Altitude : up to 4000 m
Dimensions
Enclosure(Out-case only) : H760X W450 X D266 mm
FRTU : H340 X W260 X D91 mm
Weights
Control Box (Gross) : 60 kg
FRTU (only) : 3.8 kg
Enclosure Material : Stainless Steel, 2t (IP54)
Test Standards
Dielectric Strength : IEC 60255-5
Impulse : IEC 60255-5
1 MHz Burst : IEC 60255-22-1
Electrostatic Discharge : IEC 60255-22-2
Radiated Radio Frequency : IEC 60255-22-3
: IEEE C37.90.2 (1995)
Fast Transient : IEC 60255-22-4
Surge Withstand : IEEE C37.90.1 (1989)
Vibration : IEC 60255-21-1
Shock & Bump : IEC 60255-21-2
KSC 0220 : Low Temperature Test
KSC 0221 : High Temperature Test
Commmunication Interface
RS 232C Port #1 RS 232C Port #2
On FRTU left-side (inside the inner door) On FRTU Front Panel
SCADA or DA System Communication Interface Setting & Configuration, Maintenance, Recorded Data Analysis
Through Cable / Wireless / Fiber Optic Modems Through Setting & Analysis Tool
Functions
Remote Operation (Control, Status Monitoring, Tele-metering)
Functions
Remote Setting (optional) Setting and Configuration Change (Batch Job)
Time Synchronization between FRTU and Control Center System Protocol Monitor (Communication Frame Check)
File Transfer (Event & Fault Data; DNP protocol only) Real-time Display : Measurement and Status Data
Event List and Fault Oscillograph
Protocols
Demand Load Profiling & Graphical Display
DNP 3.0 (Level 2) or IEC60870-5-101 (optional)
FRTU Firmware Download
Baud Rate
1200 ~ 19200 bps Protocols Baud Rate Connector Type
Modbus 1200~19200 bps DB9 Female
Address
Master Address: 0 ~ 65534
Slave Address: 0 ~ 65534 Ethernet Port
Connector Type TCP/ IP 10/100 BASE-T
DB9 Female Protocol DNP3.0, IEC60870-5-101 / 104, IEC61850(option)

Construct
Enclosure of EPIC R300 is designed to operate normally under the high / low temperature and humid environmentst
by adopting duplicate and double structure with air gap and by adiabatic treatment. And, the inner door enhances operational
safety. Without opening the inner door, Recloser can be manipulated and operated. For the purpose of maintenance, with the inner doo
opened and hinged, batteries, modem, analog modules and other parts can be handled directly.

FRTU

Power SW

Door Open SW
Power/Control
Receptacle
RECLOSER
Recloser Control

Enclosure Dimensioned Drawings

450
435
27 266 22
268
225 137
182
BACK SUPPORT
18
15

DOOR
93

PACKING
150

193
313

INNER PANEL
447

569
610

BODY
669

A-A”
760

906

12

MS CONNECTOR

MODEM
A-A” CABLE
HOLE
50

475 315

Side Panel Connector Pin Position

RS232C(SCADA PORT)
V6 V4 V_COM V_COM V2

V5 V_COM V_COM V3 V1 AI1 AI2 AICOM


RS232C(SCADA PORT)
VOLTAGE AI(4~20mA)

Control Source Connector


AI(4~20mA) Connector
DI (Status) Connector

RS232C RS232C
RS485 Port (SCADA Port)

DO (Control) Connector

ETHERNET Connector
AI(Voltage) Connector CURRENT

IN(0)- IN(0)+ Icom IC IB IA

AI(Current) Connector CONTROL STATUS POWER

DO6- DO6+ DI10 DI_COM2 DI9 DI_COM1 DI8 DI7


DO10- DO10+ DO9- DO9+ DO8- DO8+ DO7- DO7+ (Rec Close) (Rec Close) DI_COM3 (Spare2) (Spare1) (Gas Low) (Handle Lock) 24G 24VIN
9

DO5- DO5+ DO4- DO4+ DO3- DO3+ DO2- DO2+ DO1- DO1+ DI6 DI5 DI_COM1 DI4 DI3 DI2 DI1
(Rec Open) (Rec Open) (Bat Test-) (Bat Test+) (Close-) (Close+) (Open-) (Open+) (Door Open) (Charger Fail) (Batt Low) (AC Loss) (Close) (Open) FG FG
Technical Data
Epic R300 have a dedicated setting & configuration, operation, and analysis tool, FRTU_SET_TOOL. This tool is used for setting
value change, FRTU firmware download, SCADA communication monitor, recorded data upload & graphical display (event, fault,
and demand), and monitoring (staus and measurement) & control, especially in local site, through RS232 port on FRTU front panel
using Modbus protocol. Besides, for remote operation before SCADA or DA system installation, one-to-one connection between
the tool and FRTU, In this sense, the remote operation purpose is simple SCADA implementation for tele-metering, status
monitoring, and remote control of switches through RS232 SCADA port on the left side of FRTU using DNP or IEC protocol, and
modem control & dial-up functions are also supported.

Setting & Configuration


Status/ Control TC Curve

Measurement

Fault Waveform Event

Connection to FRTU Sample Recording Window


- Graphical Display of Recorded Fault Waveform or Text List-up of
Before connecting a communication cable between RS232C port and Fault Data
Notebook, FRTU type, protocol, and other communication options - Clear (Removal) of all fault data is possible.
should be firstly configured. And click [CONNECT] button.
Setting Window Status Window
- DWONLOAD (existing setting values display stored in FRTU) - On-line Monitoring View of Status Data, FRTU F/W Version, Model ID,
- UPLOAD (setting change and update to FRTU) and Modem Control Data
- 4 Setting Groups - Local / Remote Control of Switch, Annunciator Reset, and Battery
Test Command: Password-protected
Config Window
- I/O Configuration Window, Communication Configuration Window, Protocol Monitor Window
and Application Object Configuration Window Real-time SCADA communication frame data are listed and analyzed.
- According to protocol selection, communication configuration Buffer size is configurable, and the frame data can be saved in a log
windows are different. file and printed out.
Event Window TC Curve Window
- Recorded Events List-up (all events or by event type) Time-Current Characteristic Curves of 48 types are separately
- Clear (Removal) of all event data is possible. displayed graphically. And a curve changes the shape as Time
Demand Window multiplier or Adder is entered.
- Load Profiling with Demand Load Current, Maximum Current,
Demand Power, and Maximum Power Other Functions
- List-up in Text mode - FRTU Firmware Upload
- Modem Control and Dial-up
Measurement Window
On-line Measurement Data View of Electric Values