Professional Documents
Culture Documents
A BOOK ON SEISMIC
RETROFITTING
Design and Techniques
Retrofitting Techniques
Construction Guidelines
Ready to Use examples:
From Preliminary Assessment to Retrofitting
Design
Case studies
Vulnerability Assessment
Retrofitting
Institute of Engineering
Tribhuvan University
Seismic Retrofitting Design and Techniques
DEDICATION
PREFACE
This Seismic Retrofitting Design and Techniques book is intended for professional practitioners with
enough background and experience on analysis, design and construction of new buildings. Along with
some knowledge on vulnerability evaluation of existing buildings, retrofitting practices and quality
control measures. The Book will be useful for civil engineering students and practitioner to have better
understanding of the retrofitting design and techniques such as vulnerability assessment, detail
analysis, retrofitting design & techniques, construction process etc. The book however will be useful
for general persons also to have better understanding of the vulnerability assessment, retrofitting
techniques, construction process.
This book contains step-by-step process and/or framework for vulnerability evaluation, retrofit design
and implementation of retrofit. However, is not recommended replicating the design values and
recommended measures as strengthening of existing building is unique for each building.
Generalizations of the design values have practical limitations.
The design values, drawings and other information have been checked thoroughly but there may be
discrepancies and typo errors. The intention of this book is to provide framework of calculation and
not the exact values. Therefore, the values should be checked and confirmed by professionals in case
they would like to use it for any further processing.
Different standards, state-of-the-art research results and professional judgment have been applied to
derive the final results. Change in the standards and state-of-the-art will not be reflected in these
results and professionals and users of this book are recommended to follow the recent knowledge in
this regard. Some examples and figures in this book are taken from Seismic Retrofitting Guidelines of
Buildings in Nepal.
Seismic Retrofitting Design and Techniques
ACKNOWLEDGEMENT
This Book is an outcome of the years of effort and dedication of many people from different
walks of life. I would like to extend our deepest gratitude to the UNDP Nepal and Department
of Urban Development and Building Construction. Similarly also would like to express my
sincere thanks to Civil Engineering Department, Pulchowk Campus, Institute of Engineering,
Tribhuvan University.
I greatly appreciate the contribution of Mr Vijay Singh, Mr. Man Thapa and Narwsh Giri from
UNDP Nepal, and Dr Ramesh Singh, Secretary Government of Nepal) for their contribution.
I indebted to Dr. Jishnu Subedi (Centre of Resilience Development, CoRD) and Mr Manohar
Rajbhandary, (MRB Associates) for their support and contributions. I would also like to thank
the team from Centre of Resilience Development (Cord), for their continuous contribution
and effort.
I would also like to express sincere gratitude to my family, brother Lok Darshan Shrestha, his
wife Melina Shrestha, my wife Sunita Shrestha and kids Aradhika Drashana, Tejaswini
Darshana, Shailab Darshan, Priyesh, Tejaswi Darshan, Suprit Darshan,
My greatest appreciation goes to Center of Resilient (CoRD) and all the people for their
interest and active support in publication of this book.
Seismic Retrofitting Design and Techniques
CONTENTS
1 INTRODUCTION ............................................................................................................................... 1
2 RETROFITTING GENERAL ................................................................................................................. 2
2.1 REALIZATION OF RETROFIT REQUIREMENT ............................................................................ 2
2.2 SELECTION OF ENGINEER/ARCHITECT .................................................................................... 2
2.3 NOTIFICATION TO MUNICIPALITY OR CONCERNED AUTHORITY ............................................ 2
2.4 ESTABLISH PERFORMANCE OBJECTIVES OR DESIGN REQUIREMENTS ................................... 4
2.5 REVIEW EXISTING CONDITION OF BUILDING .......................................................................... 4
2.6 CARRY OUT VULNERABILITY EVALUATION.............................................................................. 4
2.7 CARRY OUT PRELIMINARY DESIGN WITH COST ESTIMATE ..................................................... 5
2.8 DETAIL DESIGN ........................................................................................................................ 5
2.9 PREPARE CONSTRUCTION DOCUMENTS AND QUALITY ASSURANCE PLAN ........................... 5
2.10 SUBMISSION TO THE AUTHORITY ........................................................................................... 5
2.11 MONITORING AND QUALITY CONTROL .................................................................................. 5
2.12 QUALITY ASSURANCE .............................................................................................................. 5
3 HAZARD ASSESSMENT..................................................................................................................... 8
3.1 LIQUEFACTION ........................................................................................................................ 8
3.2 EARTHQUAKE INDUCED LANDSLIDE ....................................................................................... 9
MULTI-HAZARD CONSIDERATION IN REHABILITATION OF EXISTING BUILDINGS............................. 10
4 LOCAL SITE ASSESSMENT .............................................................................................................. 12
4.1 SOIL INVESTIGATION ............................................................................................................. 12
4.1.1 GENERAL ....................................................................................................................... 12
4.1.2 EXTENT OF SITE EXPLORATION ..................................................................................... 12
4.1.3 DEPTH OF EXPLORATION .............................................................................................. 12
4.1.4 ALLOWABLE BEARING PRESSURE.................................................................................. 13
5 REPAIR OF FOUNDATION WORK ................................................................................................... 14
5.1 CASE STUDY OF REPAIR OF FOUNDATION WORK OF A BUILDING ....................................... 15
6 REPAIR OF COLUMN...................................................................................................................... 16
Engineer shall provide detailed drawings of connection of the columns with foundation and Beam. . 16
7 REPAIR OF BEAM ........................................................................................................................... 18
8 REPAIR OF WALL ........................................................................................................................... 19
9 NON-STRUCTURAL COMPONENTS................................................................................................ 20
Seismic Retrofitting Design and Techniques
Section I................................................................................................................................................. 30
1. EXAMPLE –A 1 ............................................................................................................................... 32
PRELIMINARY VULNERABILITY ASSESSMENT OF BUILDING.................................................................. 32
1.1 INTRODUCTION ..................................................................................................................... 32
SUMMARY OF OBSERVATIONS: ........................................................................................................ 47
2. EXAMPLE – B1: BRICK MASONRY ................................................................................................. 49
EARTHQUAKE VULNERABILITY ASSESSMENT OF FIELD OFFICE BUILDING ........................................... 49
2.1 BACKGROUND ....................................................................................................................... 49
2.2 METHODOLOGY .................................................................................................................... 49
2.3 INTRODUCTION ..................................................................................................................... 50
2.4 DESCRIPTION OF THE EXISTING STRUCTURAL SYSTEM ........................................................ 50
2.5 BUILDING DRAWINGS ........................................................................................................... 52
2.6 PROBABLE DAMAGE GRADE OF THE EXISTING BUILDING TYPOLOGY AT DIFFERENT
INTENSITIES ....................................................................................................................................... 56
2.7 IDENTIFICATION OF VULNERABILITY FACTORS ..................................................................... 56
2.8 CONCLUSION ......................................................................................................................... 58
2.9 RECOMMENDATIONS............................................................................................................ 58
ANNEX 1: BUILDING TYPOLOGY IDENTIFICATION ........................................................................... 59
ANNEX 2: CLASSIFICATION OF DAMAGE GRADES:........................................................................... 60
ANNEX 3: MODIFIED MERCALLY INTENSITY SCALE (MMI Scale) ..................................................... 61
ANNEX 4: STRESS CHECK CALCULATIONS ........................................................................................ 64
2.9.1 CALCULATION OF BASE SHEAR ..................................................................................... 65
2.9.2 CALCULATION OF STOREY SHEAR ................................................................................. 67
2.9.3 SHEAR STRESS CHECK:................................................................................................... 67
2.9.4 ANNEX 5: CHECKLIST FOR FIELD ASSESSMENT ............................................................ 67
2.9.5 CHECKLIST FOR FIELD ASSESSMENT (TYPE 2: BRICK IN CEMENT MORTAR) ................. 68
3. EXAMPLE - B2: ADOBE BUILDINGS ............................................................................................... 72
EARTHQUAKE VULNERABILITY ASSESSMENT OF BUILDING ................................................................. 72
3.1 INTRODUCTION ..................................................................................................................... 72
3.2 DESCRIPTION OF THE EXISTING STRUCTURAL SYSTEM ........................................................ 72
3.3 BUILDING DRAWINGS ........................................................................................................... 74
3.4 PROBABLE DAMAGE GRADE OF THE EXISTING BUILDING TYPOLOGY AT DIFFERENT
INTENSITIES ....................................................................................................................................... 75
3.5 IDENTIFICATION OF VULNERABILITY FACTORS ..................................................................... 76
Seismic Retrofitting Design and Techniques
1 INTRODUCTION
Construction is very important aspect of retrofitting as each building requires unique technique and
duplicating similar approach may not always be the efficient way. An improper construction process
not only damages the structure but also will be unsafe for the workers. An example of bad construction
planning is shown in Figure 1 which shows that due to improper construction sequence an existing
building (which was supposed to be retrofitted) was damaged completely and new building had to be
constructed. Figure 1 (a) shows an existing structure which was supposed to be retrofitted. As the
dismantling process started, the workers dismantled all supporting elements of the structure and whole
structure became useless as see in Figure 1(c).
In order to establish a proper process for construction, the retrofitting design itself should provide
detailed process of Existing Building
construction along with
drawing as and when
required. This guideline Dismantle
process
shall be followed along
started
with the Design
Guidelines for (a)
(b)
Retrofitting.
Improper dismantling sequence
led to complete collapse of the
structure and only one unstable
column was left standing
Figure 1: Improper construction sequence led to complete collapse of the structure during retrofitting
1
Seismic Retrofitting Design and Techniques
2 RETROFITTING GENERAL
The process of seismic evaluation and retrofit is a risk reduction process and owners must understand
that the process aims to balance the relative risk rather than transferring risk to design professionals
and/or contractors and ‘guaranteed’ performance may not always be achievable.
A recommended step-by-step process to realize retrofitting is given in Figure 2. The process shall serve
only as guideline and depending upon the scope and size of the project, few steps from the process
may be skipped or few additional steps may be added.
1. Codal requirements to meet the prescribed requirements in NNBC 105 and other relevant
codes.
2. Change in use such as conversion of residential building to a school building
3. Functional change such as requirement of a large conference room or addition of additional
floors not included in the previous design
4. Upgrading performance of the building
In case such a competitive process cannot be justified from scope and size of the project, consultation
with the municipality or concerned authority should be carried out before selecting engineer/architect.
With the help of engineer, the owner shall give a preliminary notice to the municipality or the
concerned authority stating purpose of the retrofitting and get go-ahead letter from the authorities.
This is essential to record the intended purpose of the work and also to record the team of engineer(s)
involved
2
Seismic Retrofitting Design and Techniques
Is
Establish Performance Objectives or
Design Requirements Retrofitting
Feasible?
Detail design
Submit to
Any Municipality/Authority
Chang for Peer Review
Prepare Construction
Documents and Quality
Assurance Plan
3
Seismic Retrofitting Design and Techniques
In consultation with the owner/client and as per requirement of the relevant NNBC or other relevant
codes, the design team shall establish the seismic performance objectives and/or design requirements.
It should be noted that performance of a building may be different at different level of hazards and
attaining a certain level of performance objectives consist of achieving a certain level of performance
for a specific level of seismic hazard.
Similarly, the codal provisions for design requirements are different for different level of hazard. For
example, IS code adopts following specification of hazard and expected level of damage1.
The design approach adopted in this standard is to ensure that structures possess at least a
minimum strength to withstand minor earthquakes (<DBE), which occur frequently, without
damage; resist moderate earthquakes (DBE) without significant structural damage though
some non-structural damage may occur; and aims that structures withstand a major
earthquake (MCE) without collapse. Actual forces that appear on structures during
earthquakes are much greater than the design forces specified in this standard. However,
ductility, arising from inelastic material behavior and detailing, and overstrength, arising
from the additional reserve strength in structures over and above the design strength, are
relied upon to account for this different in actual and design lateral loads.
Some of the preliminary information are essential before proceeding to the decision of retrofitting.
Age of the building, design code (if any), existing condition of the building, change in use, buildings
and physical facilities in the neighborhood of the building which can have impact on safety of the
building, availability of drawings and other technical information such as geotechnical investigation
report and intended future use of the building.
The vulnerability evaluation of the building shall be carried out first as preliminary investigation and
then, if required, detailed investigation. Preliminary investigation such as geometrical properties and
existing condition of the building and detailed investigation can be carried out as suggested in the
guideline developed by DUDBC under ERRRP project2 or any other relevant guidelines.
1
IS 1893: 2002 Criteria for Earthquake Resistant Design of Structures: Part 1 General Provisions and Buildings
2
Seismic Vulnerability Evaluation Guideline Part I-final, DUDBC, GON
4
Seismic Retrofitting Design and Techniques
At this stage it is advisable that engineers decide on feasibility of retrofitting for the building. Although
detailed cost estimate requires detailed design, it is advisable to use engineering judgement on whether
or not to proceed for retrofitting of the building. The decision, it is underscored, may depend on many
other circumstances and economic viewpoint only may not be justified. For example, a historic
building may require retrofitting even though the project may not be advised on economic analysis.
If the retrofitting is decided to carry out, detailed design is required before construction intervention.
The detailed design shall be carried out according to the retrofitting guideline recommended for the
particular building type.
The detailed design of retrofitting along with necessary documents stating the need to retrofit and
works of vulnerability evaluation shall be submitted to the municipality or concerned authorities for
approval. The authorities may submit, if required, the design details to peer review before giving
approval.
Such changes shall be brought to the notice of the authority and approval shall be received before
preceding the construction work.
Quality assurance program must be put in place to assure appropriate approach during evaluation,
design and construction of all retrofit projects.
5
Seismic Retrofitting Design and Techniques
Vulnerability evaluation of each buildings require from preliminary visual assessment to detailed
structural analysis. Depending on the scope of the project, size of the structure and location, a detailed
geotechnical investigation may be required which should be decided by the engineer and the team.
Retrofit design shall be carried out only after detailed investigation of the existing structural system.
The retrofit options depend on building features, scope and objective of the project and cost. The
designer shall modify designs and drawings, if necessary, to reflect conditions encountered in the site
as the construction progresses.
The designer “shall be responsible for performing periodic structural observation of the rehabilitation
work. Structural observation shall be performed at significant stages of constrcution, and shall include
visual observation of the work for substantial conformance with the construction documents and
confirmation of conditions assumed during design. Structural observation shall be performed in
addition to any special inspection and testing that is otherwise required for the work3.”
Retrofit design should be peer reviewed by a team of engineers independent from the project.
The designer shall, along with design drawings and specifications, also prepare quality assurance plan
with provisions for special inspection and testing reports.
Construction planning and execution is the most critical part of any retrofit project. The importance of
construction quality on building performance in general and the likelihood of encountering unforeseen
conditions in retrofit construction in particular warrant special attention to construction monitoring
and quality assurance4.
3
FEMA 356
4
ATC-40
6
Seismic Retrofitting Design and Techniques
7
Seismic Retrofitting Design and Techniques
3 HAZARD ASSESSMENT
Local geotechnical investigation is always recommended before retrofitting. In case of small scale
projects such for individual residential buildings, enough information from secondary sources shall be
collected if detailed geotechnical investigation is not practical.
Multi-Hazard mapping is essential before approaching for retrofitting. Retrofitting which contributes
positively to one hazard can behave adversely in another hazard. A CGI roof is recommended for
earthquake as it attracts less earthquake force and will not lead to fatal hazard in case of failure.
However, CGI roof, if not properly anchored, performs poorly in wind and is inconvenient for
occupants (particularly in schools) during rains.
Although seismic performance is the major criterion for retrofitting decision making, other potential
hazards at the site shall also be considered for the project. Retrofitting an important public building for
seismic safety, for example, may not guarantee against other potential hazards at the site. Other
potential hazards that need to be considered are fire, floods and landslides. Proper necessary measures
need to be adopted to ensure continued use of the facilities for those hazards also.
Besides hazards independent from earthquake, earthquakes also cause secondary hazards such as
landslide, liquefaction, surface fault rupture and fire. Measures to mitigate such hazards should be
included in the project design according to the scope and size of the project.
3.1 LIQUEFACTION
Liquefaction is the rapid loss of shear strength in cohesion less soils subjected to dynamic loading,
such as from an earthquake. Sometimes the shear strength falls to nearly zero, while other time it only
drops to a lower then a normal value. In a more general manner, soil liquefaction has been defined as
the transformation “from a solid state to liquefied state as a consequence of increased pore pressure
and reduced effective stress (Marcuson, 1978).”
8
Seismic Retrofitting Design and Techniques
Earthquake induced landslide of a slope can occur when earthquake and gravity forces within the slide
mass temporarily exceed slope stability. The value of ground acceleration within the slide mass
required to initiate slope instability is called the critical or yield acceleration.
For sites where earthquake induced landslide is possible, a geotechnical engineer should evaluate the
extent of landslide and its effect on the foundation of the building. Proper measures to mitigate the
effect of such landslides shall be adopted in design of the retrofitting work.
Whether landslide should be considered in the design depends on the site’s susceptibility to landslide,
which depends on the soil/geologic conditions, the slope angle, and the critical acceleration. Following
table gives guidance for determining when landslide should be considered. NNBC 108 has the
following provision for earthquake induced landslide.
Locating an important building on slopig ground in the mountainous terrain should be preceded by
examination of the hill slope stability conditions and identification of necessary structures for
counteracting the effects of the adverse conditions.
On a sloping ground, the location of all buildings should meet the requirements shown in Figure 3.2.2,
unless special slope stability measures are taken.
9
Seismic Retrofitting Design and Techniques
10
Seismic Retrofitting Design and Techniques
elements. Mitigation with elements or connections needed to complete the load path is necessary to
achieve the selected performance level.
3. Strong building material:
Reinforced concrete or reinforced masonry structural walls perform better for all hazards. They have
good performance for earthquake, flood, and fire when correctly designed and constructed.
4. Ductile structures:
Ductile detailing of steel and RC structure and proper connections provides better non - linear response
and a structure that is more resistant to collapse. Elements and connections need to be added so as to
increase ductile behavior of the structure in order to enhance performance of existing structures.
11
Seismic Retrofitting Design and Techniques
4.1.1 GENERAL
All site investigation should address the following basic questions:
i. Is there any danger of inherent natural susceptibility of the land to the process of sliding and
erosion?
ii. Will the construction adversely affect the existing conditions and trigger landslide, erosion,
land subsidence, poor pressure generation due to blockage of or otherwise the sub-surface flow
of water; will the construction adversely affect the water table?
iii. What will be the extent of settlement of the building?
iv. Is the sub-surface capable of taking the load to the proposed construction?
v. Is there any other natural/geological process likely to threaten the integrity of the building ?
(eg. Chances in a river course, flooding failure of an irrigation canal? )
vi. What are the possible engineering solutions for ensuring stability of the building foundation in
view of identified condition?
Answers to some of these questions can be found by examining the existing local knowledge, records
of any past exploration in the adjacent area and the behavior of existing similar structures. If
satisfactory answers to the questions can be found, it wil be necessary to undertake additional site
investigation including subsurface exploration , in-situ and laboratory testing, geophysical surveys and
testing, probing, etc.
The extent of exploration will depend upon the geological and geomorphological nature of the terrain,
and on the importance of the building and the scale of the project. Large scale engineering geological
mapping of the site and previous practices of construction in the adjacent area could form the basis for
deciding the extent of exploration for an important building.
The depth to be explored should be adopted based on the geological conditions at the site, e.g the depth
and type of subsurface soil, depth of weathering, the depth of ground water fluctuation, the depth of
12
Seismic Retrofitting Design and Techniques
frost action, etc. Generally, the exploration should be carried out to the depths at which the induced
stress due to the loads from the construction dissipates substantially and the strata can carry the load
without undesirable settlement and with an acceptable factor of safety against failure. Past experiences
and performance of adjacent buildings could be of prime importance in deciding about the depth of
exploration which shall not be less than one and a half times the estimated width or the lower dimension
of the footing below the foundation level. In hilly areas, exploration up to the depth sound bed rock
will generally be sufficient.
For the analysis of liquefaction susceptibility, 20 m should suffice as the depth of exploration.
The allowable bearing pressure should be calculated as per current good engineering practices.
13
Seismic Retrofitting Design and Techniques
The retrofitting of foundation, if required, shall be carried out in stages so that only a minimum of the
structure is left unsupported in the foundation.
A separate construction drawing showing the sequence of construction for foundation work shall be
prepared, if necessary.
1 6 3 5
4 2
2 4
5 3 6 1
Figure 4: Schematic diagram showing stage-wise retrofitting of foundation of load-bearing masonry walls
14
Seismic Retrofitting Design and Techniques
15
Seismic Retrofitting Design and Techniques
6 REPAIR OF COLUMN
In Moment Resisting Frame structure, Columns are the main structural element transferring the lateral
load to the ground. Weaker columns lead to formation of hinge during dynamic loading and a sway
mechanism is easily formed which leads to complete collapse of the structure. Therefore, earthquake
resistant building codes and the ductile detailing codes recommend ‘strong column, weak beam’
concept.
Repair of column, like repair of foundation and repair of wall in load bearing masonry structures, needs
special care as intervention in one column can lead to complete collapse of the structure.
Different techniques of column repair are commonly used and concrete jacketing is one of the most
widely used methods. In concrete jacketing, the lateral spaces of column need to be cleared in order to
accommodate additional reinforcement and concrete.
Engineer shall provide detailed drawings of connection of the columns with foundation and Beam.
The walls should be connected with the columns by inserting horizontals reinforcement bars if the
designer feels so.
16
Seismic Retrofitting Design and Techniques
17
Seismic Retrofitting Design and Techniques
7 REPAIR OF BEAM
18
Seismic Retrofitting Design and Techniques
8 REPAIR OF WALL
19
Seismic Retrofitting Design and Techniques
9 NON-STRUCTURAL COMPONENTS
Non-structural Components
The non-structural parts of a building include all parts of the building and its contents with the
exception of the structure, in other words: everything except the columns, floors, beams etc. Common
non-structural components include ceilings, windows, office equipment, computers, inventory stored
on shelves, file cabinets, water tanks, generators, transformers, heating, ventilating, and air
conditioning (HVAC) equipment; electrical equipment; furnishings; lights etc. Typically, non-
structural items are not analyzed by engineers and may be specified instead by architects, mechanical
engineers, electrical engineers, and interior designers. In most cases, they are purchased by the owners
after the construction is finished without the involvement of any design professional.
• Life safety
• Loss of functions
20
Seismic Retrofitting Design and Techniques
Figure 5: Non-structural damage in bed-room and sitting room (Source: Hospital Preparedness for Emergencies, Lectures)
The risk evaluation is based on the consequences of failure of the particular element:
1. Risk to Life: If loss of the element poses risk of loss of life or injury to hospital
occupants. Building occupants can be injured or killed by falling OFCs (non-structural
components).
2. Loss of Property: Those elements whose damage means a significant loss of asset to
the hospital. This can involve heavy costs because of the cost of OFCs (non-structural
components).
3. Loss of Function: If loss of element impairs the functioning of the hospital. Disruption
to normal functions will cause post-earthquake down time and loss of function just when the
community’s demand for hospital services may be extreme.
21
Seismic Retrofitting Design and Techniques
Each non-structural element should be evaluated for each of these criteria to determine its risk.
H High
M Moderate
L Low
Priority:
The priority rating should consider the combination of vulnerability and consequences. The following
matrix is recommended. The priority will be used to prioritize mitigation and cost-benefit evaluations.
Vulnerability Consequences
High (H) 1 4 7
Medium (M) 2 5 8
Low (L) 3 6 9
• Low Vulnerability means that are components is reasonably well restrained, and there
is a low probability of failure during a design earthquake (as specified in the performance
objective).
• Moderate Vulnerability means that the component is restrained, but there is a moderate
probability of failure during a design earthquake.
• High Vulnerability means that the identified component is either poorly restrained, or
not restrained at all, or there is a high probability of failure during a design earthquake.
• Low Consequences: failure of the component represents a low adverse impact on the
functional use of the building, and / or, the component is located where its failure presents a
22
Seismic Retrofitting Design and Techniques
low risk (no injury to minor injury) to the occupants of the building. An example is an air
conditioning unit on the ground in a locked compound behind a building.
• High Consequences: failure of the component represents a high adverse impact on the
functional use of the building, and / or, the component is located where its failure presents a
high risk (death or serious injury) to the occupants of the building. An example is an air
conditioning unit in the ceiling above an entrance corridor.
Mitigation Measures
Non-structural mitigation measures are easy and cost effective. For easy understanding and
remembrance, major mitigation measures can be assigned to 6R.
• Removal
• Relocation
• Restrain
• Reinforcement
• Replacement
• Reduction
Removal: Removal is probably the best mitigation option in many cases. In all hospitals, the survey
team found several examples of unnecessary or non-essential documents and materials stored near the
working place or near important equipment. One solution would be better fastenings or the use of
stronger supports, but the most effective solution would be removal and replacement.
Relocation: Relocation would reduce danger in many cases. For example, a very heavy object on top
of a shelf could fall and seriously injure someone as well as break thereby causing economic losses.
But by relocating heavy equipment and materials from upper shelves to lower shelves the risk could
23
Seismic Retrofitting Design and Techniques
be mitigated. This is the case in most of hospitals where the functionality of the stores of operation
theaters could be improved by doing so.
Cupboards and bookshelves kept near an exit door or passage, which can obstruct the way and cause
human death or injury during an earthquake event, are typical examples that were found in all hospitals.
These bookshelves and cupboards could easily be relocated to other places where the potential dangers
would be reduced.
Restrain: Restricted mobility for certain objects such as gas cylinders and power generators is a good
measure. It does not matter if the cylinders shift as long as they do not fall and break their valves.
Sometimes back-up power generators are mounted on springs to reduce the noise and vibrations when
they are working, but these springs would amplify ground motion. Therefore, restraining supports or
chains should be placed around the springs to keep the generator from shifting or being knocked off
their stands.
Reinforcement: Reinforcement is feasible in many cases. For example, an un-reinforced infill wall or
a chimney may be strengthened without great expense by covering the surface with wire mesh and
cementing it.
Replacement: Replace with something that does not represent a seismic hazard is appropriate in some
situations. For example, a heavy, tiled roof does not only make the roof of a building heavy, it is also
more susceptible to the movement of an earthquake. The individual tiles tend to come off thus creating
a hazard for people and objects. One solution would be to change it with a lighter, safer roofing
material.
Removal!!!
Anchorage
Strapping
Figure: Removal, strapping and anchorage reduces the risk due to non-structural components (Source:
Hospital Preparedness for Emergencies, Lectures)
24
Seismic Retrofitting Design and Techniques
Reduction: Redundancy or duplication of items is advisable. Emergency response plans that call for
additional supplies are a good idea. It is possible to store extra amounts of certain products providing
a certain level of independence from external supplies, which could be interrupted in case of an
earthquake.
Rapid response and repair is a mitigation measure used on large oil pipelines. Sometimes it is not
possible to do anything to prevent the rupture of a pipeline in a given place, therefore spare parts are
stored nearby and arrangements are made to enter the area quickly in case a pipe breaks during an
earthquake. A hospital should have spare plumbing, emergency power supplies and other necessary
components on hands, together with the suitable tools in order to ensure that repairs can be easily made
if something is damaged. For example, during an earthquake the water pipes may break; it may be
impossible to take prior measures to totally eliminate this risk, but it is possible to ensure that
everything necessary for quick repairs is at hand. With prior earthquake planning, it is possible to save
the enormous costs of water damage with a minimum investment in a few articles.
25
Seismic Retrofitting Design and Techniques
There are other easy-to-use mitigation measures also. Five of them are listed below:
1. Anchorage
2. Flexible couplings
3. Modification
4. Hooking
5. Strapping
1. Anchorage
Anchorage is the most widely used precaution. It is a good idea to use bolts, cables or other materials
to prevent valuable or large components from falling or sliding. The heavier the object, the more likely
it is that it will move due to the forces produced by an earthquake. Autoclave machines in all hospitals
are good example. They are heavy and can easily fall and break. The simple solution is to anchor the
feet of the machines to the concrete floor.
Some equipment and components of a system can easily be bolted to the floor. Transformers, water
treatment tanks, communication equipment and control panels of X-ray are typical examples of
equipment that can be anchored to the floor.
In most medical facilities and administration sections, cupboards, fridges and racks storing medical
equipment, books, documents or chemicals pose life safety hazards as well as functional and / or
property losses. This can easily be prevented by anchoring them to the wall using angles and nails as
this will stop them from overturning.
2. Flexible Couplings
If there is a tank outside the building with a rigid connection pipe joining the building and the tank
together, the tank will vibrate at various frequencies, in different directions and with amplitudes
different to those of the building all of, which will cause the pipe to break. A flexible pipe between the
two parts would prevent ruptures of this kind. Flexible couplings are necessary because separate
objects each move independently in response to an earthquake; some move quickly, others slowly.
Consequently, flexible piping is necessary near heavy equipment, at the joint of two buildings and in
seismic joints of the same building.
3. Modification
26
Seismic Retrofitting Design and Techniques
Modification is a possible solution for an object that represents a seismic hazard. For example, earth
movements twist and distort a building possibly causing the rigid glass in the windows to shatter and
launch sharp glass splinters onto the occupants and the passers-by around the hospital. Rolls of
transparent adhesive plastic may be used to cover the inside surfaces and prevent them from shattering
and threatening those inside. The plastic is invisible and reduces the likelihood of a glass window
causing injuries.
4. Hooking
In all hospitals, much equipment likes ECG monitors, suction units, ventilators, incubators, B.P.
monitors, resuscitation equipment, etc. were found on rollers or roller trolleys, and the roller systems
are necessary for better mobility. But this equipment on rollers can slide and impact with people, the
walls, beds or other things causing impact hazard to the other object or person and damage to the piece
of equipment itself.
Development of a proper hooking system using chains and hooks can protect the equipment and can
decrease the impact hazard the time of use or storage. Provision of a hooking system on beds could be
one way of hooking equipment at the time of use. At the time of storage, the equipment can be hooked
to the wall by chains.
Some equipment on roller trolleys can also be protected from falling by strapping the equipment to the
trolley and hooking the trolley to the wall. Some slender objects like oxygen cylinders can also be
hooked using chains.
5. Strapping
In most of the hospitals, the supplies and contents of laboratories, medical stores, general stores, CSSD
stores and OT stores are kept unsecured on shelves and in racks and would fall down and brake during
earthquakes. To mitigate this risk is not difficult; once the racks and cupboards have been anchored to
the wall, the contents can easily be secured by using strapping thus preventing chemical bottles and
medicine stored on the shelves from falling down.
Multi-Hazard Consideration
27
Seismic Retrofitting Design and Techniques
The following checklist can be used for decision making in strengthening of non-structural elements.
3 Anchorage/bracing of ducts 0
Non-structural Elements
1 Parapet X 0 0
4 Tile roofs X 0 X
28
Seismic Retrofitting Design and Techniques
Part – II
29
Seismic Retrofitting Design and Techniques
Section I
Vulnerability Assessment
A. PRELIMINARY ASSESSMENT
Example - A 1: School Building
B. DETAIL ASSESSMENT
Example - B1: Brick Masonry Building
30
Seismic Retrofitting Design and Techniques
A. PRELIMINARY ASSESSMENT
31
Seismic Retrofitting Design and Techniques
1. EXAMPLE –A 1
1.1 INTRODUCTION
This section includes the preliminary condition assessment of the existing buildings using a
multiple hazard retro-maintenance Safety Toolkits developed by the UN-Habitat in partnership
with UNISDR Asia Pacific Secretariat. The toolkit has been developed to facilitate the
assessment of the safety of critical infrastructures, focusing on schools and hospitals in South
Asia and available in UN Habitat. UN-Habitat Nepal in association with Centre of Resilient
Development (CoRD) has tested the Toolkit in two public schools of Lalitpur Sub-metropolitan
City, a government hospital of Bhaktapur Municipality and all the public schools of Kirtipur
Municipality.
Table 1: WEIGHTS
Hazard Weights
Category Weights
Issue Weights Planning 0.2 W seis 1
VI 3
Architectural 0.3 Wwind
I 2
Structural 0.3 Wflood
LOW 1
Non-structural 0.2 Wfire 1
32
Seismic Retrofitting Design and Techniques
Adarsha Kanya Secondary School has three buildings attached with the historic Patan Darbar
Square. The building is two storey adobe load bearing buildings with timber floor and CGI
roofing. The location, plan and elevation details are shown in the following figures:
33
Seismic Retrofitting Design and Techniques
B3 was
field
tested
34
Seismic Retrofitting Design and Techniques
35
Seismic Retrofitting Design and Techniques
Figure : The process of field test and some defects in Building B3 (Classrooms)
36
Seismic Retrofitting Design and Techniques
Class+ lab
Not Not Reinforced Brick Cement
B2 3 50 yrs Not known Not known Brick in mud mortar 3
known known Concrete plaster
8
GF: office
4
Bahadur Not Brick in cement
B5 3 FF: community 200 Not known Not known Wooden floor with tile Tile flooring
shah known surkhi Heritage building
special attention
TF: hall
37
Seismic Retrofitting Design and Techniques
** Type 1 if the building/ facility is in good condition - no need for maintenance, Type 2 if the building/ facility is in OK condition, need for routine maintenance, Type 3 if the building/ facility
needs minor repair, Type 4 if the building/ facility needs major repairs, Type 5 if the building/ facility is unsafe – to be replace
Furniture/ Equipment Total Nos Repair needs (nos) Replacement needs (nos) Supply of new (nos)
Desks 162+138 45
Chairs 28
Boards (white) 26
Tables 1+62+14=77
Photocopier 1
Almirah 14+19+4=37
Photocopier 1
Lab equipment 68
Funnel 15
Cubical flask 12
Microscope 2
Kerosene burner 16
Specimens 23
38
Seismic Retrofitting Design and Techniques
Anchorage → Type 1, Material of anchorage, Present condition of the Mention the level of
Location-- If yes, 0, if no type 1, where applicable anchor equipment/furniture
Type 1 if
If > GF(1)
protected
Furniture/ Age anchored, /FF(2)
Good as new (1), OK(2), Type 1, If PL > 300mm from high
Equipment (years) how many /SF(3)
At On At min. maint. (3), medium from HFE, Type 2, if wind, type 0
years back /TF(4) Metal Wood other
base top sides maint (4), major maint lower than HFE, Type 3, for no
/>TF(5)
(4),replacement (5) of < 300mm below HFE
Computers
Not
and 7 2 0 0 0 NA NA NA 1 1
anchored
attachments
Not
Acids in Lab 3 1 0 0 0 NA NA NA 1 1
anchored
Not
Photocopier 5 2 0 0 0 NA NA NA 1 1
anchored
Not
Almirah 23 1,2,3 0 0 0 NA NA NA 1 1
anchored
Lab Not
14 1 0 0 0 NA NA NA 1 1
equipment anchored
39
Seismic Retrofitting Design and Techniques
At several places in
15 sq m +15%
interior and exterior
4 Damaged plaster B3/R7,R9,R10,R1 of surface Important
damaged plaster to be
area
replaced
vertical crack on the wall- B3/R2, B3/R4
36 YEARS
5 Vertical cracks 13 ft Important
wider than 1mm B2/R5.
6 Floor cracks About 1.5mm wide crack B3A2/R8, B3B/R5. 10m Important
40
Seismic Retrofitting Design and Techniques
Compliance index 0 No safety as per norm, 1 100% Safety as per norms Figure VI.2: Weights considered
WEIGHTS
Compliance Index (cut off level 0.75): Seismic and Fire Fire Seismic
Issue Weights
Multi Hazard VI 3
compliance… 0.59
I 2
Non structural 0.35
0.25 LOW 1
Structural 0.25
0.68
41
Seismic Retrofitting Design and Techniques
Hazard Weights
The weights shown on the right were put forward by the Expert Group Meeting
W seis 1
th th
Held at Kathmandu (25 -26 March 2012). However, in any other context, the Wwind
country level experts may change these to suit the local conditions. Wflood
Wfire 1
The following two Tables show the retrofitting needs of building B3:
Table VI .5: Retrofitting actions to be taken to enhance SEISMIC SAFETY of School at Lalitpur, Nepal
SEISMIC
ISSUE NO ISSUES REFERENCES/ REMARKS
COMPLIANCE
PLANNING
ARCHITECTURAL ISSUES
42
Seismic Retrofitting Design and Techniques
SEISMIC
ISSUE NO ISSUES REFERENCES/ REMARKS
COMPLIANCE
Type 3, if the design is poor for evacuation of physically A special study to be undertaken by the community to
A3 0.1
challenged people make arrangements in this respect.
STRUCTURAL ISSUES
NS1 Type 0, if plumbing lines are not supported and braced 0.25
43
Seismic Retrofitting Design and Techniques
SEISMIC
ISSUE NO ISSUES REFERENCES/ REMARKS
COMPLIANCE
Type 0, if you have not provided flexible joints in lab and the
NS3 0.05
lines clamped at suitable points
Table VI .6: Retrofitting actions to be taken to enhance FIRE SAFETY of School at Lalitpur, Nepal
PLANNING
P3 Type 2, if there is open space, but not adequate for gathering 0.5
ARCHITECTURAL
A1 Type 0, if only one escape route exists in each classroom 0.05
Type 0, if there is no fire fighting water tank of adequate size
A6 0
nor a local source
This could be changed with least
A8 Type 0, if the doors open inside 0.05
investment
STRUCTURAL
S1 Type 0, if structural members not insulated 0.25
NON-STRUCTURAL
44
Seismic Retrofitting Design and Techniques
45
Seismic Retrofitting Design and Techniques
SUMMARY OF OBSERVATIONS:
The approach roads to the school are highly con gested and narrow. In a couple of places there are
sharp bends. One has to be very careful even when driving a small car. Access for fire engine will
be a problem even though there are two main access roads to the school. Very old buildings
surround the school and many of them are heritage buildings and need retrofitting need assessment.
Apart from that, in case of fire in these buildings, the approach road could become difficult for the
fire engine to access.
The masonry pillars of the building B3 are highly vulnerable to seismic forces. There is an urgent
need for reinforced skin around them to take lateral force safely. There are potential fire hazards
due to old wiring system and presence of timber as primary spanning system in many classrooms.
Apart from that lack of fire alarm and fire extinguisher, etc. were potential threats to the school.
The school did not have water reservoir for fire righting.
The condition assessment revealed that there were no evidence of regular housekeeping and routine
maintenance. The distresses were identified and recorded by the team consisting of a trainer and
the teachers from a few schools. The participants agreed that an increased awareness and capacity
building would have eliminated most of the defects. Because of long neglect on maintenance, the
rooms in B3 were damaged. The teachers involved in the survey, realized that it is they who can
keep up the school by close vigilance on the building and its facilities. The detailed list of distresses
is in Table VI .4
The lab needs immediate retrofitting of its pipe lines. The roof top water tank is highly vulnerable
and may fall down even with medium tremor.
The evacuation route of the school is very poor. However, it would not need much of money to find
out an emergency exist to the side lanes.
The B5 is a heritage building with exquisite ceiling pattern and spatial character. The two long
parallel walls have a differential settlement of more than 150mm, which is considerable. There is a
strong need for immediate detailed investigation on the foundation of B5 so that appropriate
underpinning actions could be taken.
The school is very poor for access of the physically challenged people.
The school teachers, education department’s representatives, a mason, etc. took part in the day long
exercise in the field testing. It had made them adequately aware on the way one should look after
a school to identify gaps and record data. The exercise was intended to enable the teachers and the
community members to monitor the building and facilities on a regular basis.
47
Seismic Retrofitting Design and Techniques
B. DETAIL ASSESSMENT
48
Seismic Retrofitting Design and Techniques
2.1 BACKGROUND
This report is based on the best engineering judgment arrived at from visual inspection and findings
during the site investigations. Also, non-destructive test to obtain the strength of the structural
members was carried out in the sites using Schmidt Hammer at possible locations.
This Report describes method and findings of the qualitative earthquake vulnerability assessment
done as per the requirement of the Client.
2.2 METHODOLOGY
This assessment is done based on visual inspection, drawings developed based on site
measurements, earthquake vulnerability factors identification, their qualitative analysis and short
mathematical calculations to check some vulnerability factors. For the assessment of the chosen
building structure, FEMA “Handbook for the Seismic Evaluation of Buildings" (FEMA 310) has
been followed. FEMA 310 suggests the procedure for the identification of deficiencies in the
building structure; however, it does not give the level of vulnerability if the building is non-
compliant. The checklists suggested by FEMA 310 were followed and other pertinent observations
necessary for the assessment were noted during the site survey. The details of the checklists are
given in each section.
49
Seismic Retrofitting Design and Techniques
2.3 INTRODUCTION
This section includes the qualitative earthquake vulnerability analysis of the structure: Field Office
Building. The analysis is based on available information and the information gathered during the
site survey of the existing structure.
The size of tie beam are different, at corner, size of tie beam are 250mm x 125mm up to 400mm
length, rest of other tie beams, size 150mm x 125mm around the wall.
Foundation Exploration
50
Seismic Retrofitting Design and Techniques
51
Seismic Retrofitting Design and Techniques
52
Seismic Retrofitting Design and Techniques
53
Seismic Retrofitting Design and Techniques
54
Seismic Retrofitting Design and Techniques
55
Seismic Retrofitting Design and Techniques
(Note: The description of different damage degrees is provided in Annex 2 and the details of the
MMI scale is given in Annex 3)
We can see from table 3.1 that weaker buildings in the type-2 category suffer a damage grade of 5
at an intensity of X whereas good buildings of this type-2 category suffer a damage grade of 4 at an
intensity of X.
The building in Nepalgunj can be categorized as a weak building in the type-2 typology as we can
already observe cracks in the structural system.
The influence of different vulnerability factors to the building on the basis of visual inspection for
building is tabulated below:
56
Seismic Retrofitting Design and Techniques
Table 3.2: Influence of Different Vulnerability Factors to the Structure of Field Office Building.
Load Path √
Weak Story √
Soft Story √
Geometry √
Vertical Discontinuity √
General
Mass √
Torsion √
Deterioration of Material √
Masonry Units √
Wall Anchorage √
Connection
Transfer of Shear Walls √
Plan Irregularities √
Diaphragm
Diaphragm Reinforcement at
√
Openings
57
Seismic Retrofitting Design and Techniques
2.8 CONCLUSION
After careful observation of the structures the following conclusions were reached. The existing
structure is likely to undergo heavy structural damage during earthquakes. The crack patterns
observed in the structure clearly indicates the lack of reinforcing of the walls. The cracks observed
in the corners and below slabs show that the structural components have not been properly
integrated for optimum structural performance during earthquakes. The beams are provided at
centre part of the building but at outer part ,beams are not provided , only lintel bands are provided
around the wall .
2.9 RECOMMENDATIONS
The existing cracks in the building indicate the necessity of retrofitting and rehabilitation work on
the structure. The following recommendations are made:
- Provision of water proofing layer and IPC Layer in roof slab as top layer (IPC layer) is cracked
all over the roof.
58
Seismic Retrofitting Design and Techniques
S
Building Types in Nepal Description
No.
Adobe Buildings: These are buildings constructed in
sun-dried bricks (earthen) with mud mortar for the
construction of structural walls. The walls are usually
more than 350 mm.
Adobe, stone in mud, brick-in-mud (Low Strength Stone in Mud: These are stone-masonry buildings
1 constructed using dressed or undressed stones with
Masonry).
mud mortar. These types of buildings have generally
flexible floors and roof.
Brick in Mud: These are the brick masonry buildings
with fired bricks in mud mortar
These are the brick masonry buildings with fired bricks
in cement or lime mortar and stone-masonry buildings
2 Brick in Cement, Stone in Cement
using dressed or undressed stones with cement
mortar.
These are the buildings with reinforced concrete
frames and unreinforced brick masonry infill in cement
mortar. The thickness of infill walls is 230mm (9”) or
Reinforced Concrete Ordinary-Moment-Resisting-
3 even 115mm (41/2”) and column size is predominantly
Frame Buildings
9”x 9”. The prevalent practice of most urban areas of
Nepal for the construction of residential and
commercial complexes is generally of this type.
These buildings consist of a frame assembly of cast-in-
place concrete beams and columns. Floor and roof
framing consists of cast-in-place concrete slabs.
Lateral forces are resisted by concrete moment frames
Reinforced Concrete Intermediate-Moment- that develop their stiffness through monolithic beam-
4
Resisting-Frame Buildings column connections. These are engineered buildings
designed without earthquake load or with old codes or
designed for small earthquake forces. Some of the
newly constructed reinforced concrete buildings are
likely to be of this type.
These buildings consist of a frame assembly of cast-in-
place concrete beams and columns. Floor and roof
framing consists of cast-in-place concrete slabs.
Lateral forces are resisted by concrete moment frames
Reinforced concrete special-moment-resistant- that develop their stiffness through monolithic beam-
5
frames (SMRF) column connections. These buildings have joint
reinforcing, closely spaced ties, and special detailing to
provide ductile performance. Despite the fact that this
system should be adopted ideally for all new RC frame
buildings in Nepal, it is now only used as an exception.
Mixed buildings like Stone and Adobe, Stone and Brick
6 Others in Mud, Brick in Mud and Brick in cement etc. are
other building type in Nepal.
59
Seismic Retrofitting Design and Techniques
non-structural damage)
60
Seismic Retrofitting Design and Techniques
Grade 5: Destruction
Definitions of quantity
Can only be noticed or felt by people who are in the right situation and circumstance
Furniture's or things which are not correctly positioned may move or be slightly displaced
Things that are hanged on walls would slightly sway, shake or vibrate
61
Seismic Retrofitting Design and Techniques
Can be noticed and felt by more people inside homes or buildings especially those situated
at high levels. Some may even feel dizzy. The quake at this stage can be described as though
a small truck had passed nearby.
Things that are hanged on walls would sway, shake or vibrate a little more strongly.
The shaking or vibrations on water or liquid surfaces in containers would be more vigorous
and stronger
Can be noticed and felt by most people inside homes and even those outside. Those who are
lightly asleep may be awakened. The quake at this stage can be described as though a heavy
truck had passed nearby.
Things that are hanged on walls would sway, shake or vibrate strongly. Plates and glasses
would also vibrate and shake, as well as doors and windows. Floors and walls of wooden
houses or structures would slightly squeak. Stationary vehicles would slightly shake.
The shaking or vibrations on water or liquid surfaces in containers would be very strong. It
is possible to hear a slight reverberating sound from the environment
V. Strong Intensity
Can be felt and noticed by almost all people whether they are inside or outside structures.
Many will be awakened from sleep and be surprised. Some may even rush out of their homes
or buildings in fear. The vibrations and shaking that can be felt inside or outside structures
will be very strong.
Things that are hanged on walls would sway, shake or vibrate much more strongly and
intensely. Plates and glasses would also vibrate and shake much strongly and some may
even break. Small or lightly weighted objects and furniture would rock and fall off.
Stationary vehicles would shake more vigorously.
The shaking or vibrations on water or liquid surfaces in containers would be very strong
which will cause the liquid to spill over. Plant or tree stem, branches and leaves would shake
or vibrate slightly.
62
Seismic Retrofitting Design and Techniques
Many will be afraid of the very strong shaking and vibrations that they will feel, causing
them to lose their sense of balance, and most people to run out of homes or building
structures. Those who are in moving vehicles will feel as though they are having a flat tire.
Heavy objects or furniture would be displaced from original positions. Small hanging bells
would shake and ring. Outer surfaces of concrete walls may crack. Old or fragile houses,
buildings or structures would be slightly damaged.
Weak to strong landslides may occur. The shaking and vibrations of plant or tree stem,
branches and leaves would be strong and highly noticeable.
Almost all people will be afraid of the very strong shaking and vibrations that they will feel.
Those who are situated at high levels of buildings will find it very hard to keep standing.
Heavy objects or furniture would fall and topple over. Large hanging bells will sound
vigorously. Old or fragile houses, buildings or structures would most definitely be
destroyed, while strong or new structures would be damaged. Dikes, dams, fishponds,
concrete roads and walls may crack and be damaged.
Will cause confusion and chaos among the people. It makes standing upright difficult even
outside homes / structures.
Many big buildings will be extremely damaged. Landslides or lateral spreading will cause
many bridges to fall and dikes to be highly damaged. It will also cause train rail tracks to
bend or be displaced. Tombs will be damaged or be out of place. Posts, towers and
monuments may bend or completely be destroyed. Water and canal/drainage pipes may be
damaged, bend, or break.
63
Seismic Retrofitting Design and Techniques
surfaces whether from rivers, ponds or dams/dikes. Trees and plant life will very vigorously
move and sway in all directions.
People would be forcibly thrown/fall down. Chaos, fear and confusion will be extreme.
Most building structures would be destroyed and intensely damaged. Bridges and high
structures would fall and be destroyed. Posts, towers and monuments may bend or
completely be destroyed. Water and canal/drainage pipes may be damaged, bend, or break.
Landslides, liquefaction, lateral spreading with sand boil (rise of underground mixture of
sand and mud) will occur in many places, causing the land deformity. Plant and trees would
be damaged or uprooted due to the vigorous shaking and swaying. Large stone boulders
may be thrown out of position and be forcibly darted to all directions. Very-very strong
tsunami-like waves will be formed from water surfaces whether from rivers, ponds or
dams/dikes.
Widespread landslides, liquefaction, intense lateral spreading and breaking of land surfaces
will occur. Very strong and intense tsunami-like waves formed will be destructive. There
will be tremendous change in the flow of water on rivers, springs, and other water-forms.
All plant life will be destroyed and uprooted.
Assumptions:
64
Seismic Retrofitting Design and Techniques
LEVEL FLOOR AREA DEAD LOAD LIVE LOAD 25% LIVE LOAD SEISMIC WEIGHT
Based on IS 1893 (Part 1): 2002, Criteria for earthquake resistant design of structures,
I = Importance Factor
The total design lateral force or Design Seismic Base Shear (VB) along any principal direction is
determined by the following expression
VB = m1*Ah*W
The approximate fundamental natural period of vibration (Ta) in seconds, of all other buildings,
including moment-resisting frame buildings with brick infill panels, may be estimated by the
empirical expression:
Ta = 0.09h /d0.5
65
Seismic Retrofitting Design and Techniques
d = Base dimension of the building at the plinth level, in m, along the considered direction of the
lateral force
dx = 13.67m
dz = 10.238m
= 0.237 <0.55
= 0.274 <0.55
Therefore, Sa/g = 2.5 for medium soil (IS: 1893(Part 1): 2002
Z = 0.36
R = 1.5
Ah = ZISa/2Rg
= 0.45
= 442.577 KN
66
Seismic Retrofitting Design and Techniques
Vbz= 442.577 KN
67
Seismic Retrofitting Design and Techniques
(Note: C = Compliance to the statement; NC = Not Compliance to the statement; N/A = Not
Applicable, NK = Not Known)
The evaluation of different statements is made and is noted by Underlined Bold letter.
2.9.5.1 General
The structure system of building is load bearing system, which is around 10 years old. The structure
is being used as Field Office. The building is situated in a flat land.
C NC N/A NK WEAK STORY: The strength of the lateral-force-resisting system in any story shall not be
less than 80% of the strength in an adjacent story above.
The building is two and half storey. Top floor of the building does not meet this criterion.
This may suffer stress concentration
C NC N/A NK SOFT STORY: The stiffness of the lateral-force-resisting system in any story shall not be
less than 70% of the stiffness in an adjacent story above or below or less than 80% of the
average stiffness of the three stories above or below.
68
Seismic Retrofitting Design and Techniques
C NC N/A NK MASS: There shall be no change in effective mass more than 50% from one story to the
next.
C NC N/A NK TORSION: The distance between the story center of mass and the story center of rigidity
shall be less than 20% of the building width in either plan dimension.
C NC N/A NK MASONRY JOINTS: The mortar shall not be easily scraped away from the joints by hand
with a metal tool, and there shall be no areas of eroded mortar.
C NC N/A NK UNREINFORCED MASONRY WALL CRACKS: There shall be no existing diagonal cracks in
wall elements greater than 1/16" or out-of-plane offsets in the bed joint greater than
1/16".
C NC N/A NK PROPORTIONS: The height-to-thickness ratio of the shear walls at each story shall be less
than the following for Life Safety and Immediate Occupancy:
C NC N/A NK VERTICAL REINFORCEMENT: There shall be vertical reinforcement at all corners and T-
junctions of masonry walls and it shall be started from foundation and continuous to
roof.
69
Seismic Retrofitting Design and Techniques
C NC N/A NK HORIZONTAL BANDS: There shall be steel or wooden bands located at the plinth, sill and
lintel levels of the building in each floor.
C NC N/A NK CORNER STITCH: There shall be reinforced concrete or wooden elements connecting two
orthogonal walls at a vertical distance of at least 0.5m to 0.7m.
C NC N/A NK GABLE BAND: If the roof is slopped roof, gable band shall be provided to the building.
C NC N/A NK THROUGH-STONES: In case of stone building, the walls shall have plenty of through-
stones extending the whole width of the walls. The maximum spacing of such through-
stones shall be within 1.2m horizontally and 0.6m vertically.
C NC N/A NK REDUNDANCY: The number of lines of shear walls in each principal direction shall be
greater than or equal to 2.
C NC N/A NK SHEAR STRESS CHECK: The shear stress in the un-reinforced masonry shear walls shall be
less than 15 psi for clay units and 30 psi for concrete units.
Shear stress of Ground Floor = 3.53 psi, First Floor = 3.16 psi,Top Floor = 7.169 psi << 15
psi .Hence Safe .Refer Annex 4 for details.
Diaphragms
C NC N/A NK OPENINGS AT SHEAR WALLS: Diaphragm openings immediately adjacent to the shear
walls shall be less than 15% of the wall length.
C NC N/A NK PLAN IRREGULARITIES: There shall be tensile capacity to develop the strength of the
diaphragm at re-entrant corners or other locations of plan irregularities
70
Seismic Retrofitting Design and Techniques
C NC N/A NK DIAGONAL BRACING: If there is flexible diaphragms such as joists and rafters shall be
diagonally braced and each crossing of a joist/rafter and a brace shall be properly fixed.
C NC N/A NK LATERAL RESTRAINERS: For flexible roof and floor, each joists and rafters shall be
restrained by timber keys in both sides of wall.
Connections
C NC N/A NK WALL ANCHORAGE: Exterior concrete or masonry walls shall be anchored for out-of-
plane forces at each diaphragm level with steel anchors or straps that are developed into
the diaphragm.
C NC N/A NK TRANSFER TO SHEAR WALLS: Diaphragms shall be reinforced and connected for transfer
of loads to the shear walls and the connections shall be able to develop the shear
strength of the walls.
C NC N/A NK ANCHOR SPACING: Exterior masonry walls shall be anchored to the floor and roof
systems at a spacing 3 ft. or less.
71
Seismic Retrofitting Design and Techniques
3.1 INTRODUCTION
This section includes the qualitative earthquake vulnerability analysis public Building. The analysis
is based on available information and the information gathered during the site survey of the existing
structure.
The building is two storied with a storey height of 3 meters. The site is mildly sloped with gravel
mixed soil type. The construction in the building has been done in four phases. The building is in
two levels, the upper block is at 300mm above
the lower block. The ground floor of the upper
block was constructed 13 years ago, and then the
ground floor of the lower block was constructed
about 10 years ago. The first floor of the upper
block was then constructed 8 years ago, after
which, the first floor of the lower block was
constructed 2 years back. The structural system
Exploration of foundation
is the load bearing wall system. The ground floor
wall is 350mm thick and of brick in mud mortar masonry. The first floor wall is 230mm thick and
of brick in cement mortar. The slab of first floor is of reinforced brick concrete 100mm thick with
10mm bar @ 250mm center to center. The slab
of the roof is of reinforced cement concrete
100mm thick with 10mm bars @ 200mm center
to center. No tie beam, ceiling band, sill band and
lintel band has been provided at ground floor.
However, ceiling band has been provided at the
first floor. A 40mm thick damp proof concrete
has been provided at the plinth level. The internal
Void between masonry units
walls and ceilings are plastered and painted. The
front exterior wall is finished with cement plaster and painted. The rest of the exterior walls are
fair-faced.
72
Seismic Retrofitting Design and Techniques
The reinforcement is in exposed condition in many places due to insufficient cover. Deflections are
noticed in the beams in some places. Cracks are observed between slab and wall connection.
Dampness is observed in many places due to seepage. The beam reinforcement is exposed at the
end as a result of which it is susceptible to rusting.
73
Seismic Retrofitting Design and Techniques
74
Seismic Retrofitting Design and Techniques
From the visual observation and study of the available drawings of the building, the building under
study is identified as Type 1 or Adobe Brick in mud masonry as the walls are composed of brick in
mud mortar masonry in the ground floor and brick in cement masonry in the first floor. See Annex1
for details of the identification of different building typology.
75
Seismic Retrofitting Design and Techniques
(Note: The description of different damage degrees is provided in Annex 2 and the details of the
MMI scale is given in Annex 3)
We can see from table 1 that even the good buildings in the type-1 category suffer a damage grade
of 5 at an intensity of X. This building can be categorized as an average building in the type-1
typology as we can see cracks in the structural system of the building.
Different Vulnerability factors associated with the particular type of buildings are checked with a
set of appropriate checklist from FEMA 310, “Handbook for the Seismic Evaluation of Buildings”.
The basic vulnerability factors related to Building system, lateral force resisting system,
connections, and diaphragms are evaluated based on visual inspection and review of drawings. The
checklist used for checking different vulnerability factors of the assessed building is given in Annex
4 of this report. However, the critical vulnerability factors of the building required quantitative
checking. Some of the important calculation sheets are attached with Annex 4 of this report.
The influence of different vulnerability factors to the building on the basis of visual inspection for
the different buildings
Load Path √
Soft Story √
76
Seismic Retrofitting Design and Techniques
Geometry √
Vertical Discontinuity √
Mass √
Torsion √
Deterioration of Material √
Masonry Units √
Lateral Redundancy √
Force
Resisting
Shear Stress √
System
Wall Anchorage √
Connection
Transfer of Shear Walls √
Plan Irregularities √
Diaphragm
Diaphragm Reinforcement at
√
Openings
3.6 CONCLUSION
The existing structure is likely to undergo heavy structural damage during earthquakes of high
intensity. The presence of cracks between the roof and walls indicate that the diaphragm is not
attached to the load bearing wall system properly. The difference in levels of the two blocks might
attract stress during earthquakes due to the short column effect. Also, the fact that the building was
constructed at four different stages and four different time frames makes the building even more
vulnerable to earthquakes. The good part here, however, is that cracks are not observed at the
connection of the new and old constructions. The beam sections seem inadequate for the beam span
as the deflection of the beam is visible. Masonry in mud mortar are generally weak in shear hence,
77
Seismic Retrofitting Design and Techniques
proper strengthening should be provided to withstand the shear forces that are bound to be imposed
on the structure during earthquakes.
3.7 RECOMMENDATIONS
The following recommendations can be made to improve the structural performance of the building:
- The roofing system should be properly braced to the walls to withstand lateral loads.
- The beams should be checked for deflection and shear stress and jacketed if necessary.
78
Seismic Retrofitting Design and Techniques
1 Adobe, stone in mud, Adobe Buildings: These are buildings constructed in sun-dried bricks
brick-in-mud (Low (earthen) with mud mortar for the construction of structural walls. The walls
Strength Masonry). are usually more than 350 mm.
Stone in Mud: These are stone-masonry buildings constructed using dressed
or undressed stones with mud mortar. These types of buildings have
generally flexible floors and roof.
Brick in Mud: These are the brick masonry buildings with fired bricks in mud
mortar
2 Brick in Cement, Stone These are the brick masonry buildings with fired bricks in cement or lime
in Cement mortar and stone-masonry buildings using dressed or undressed stones with
cement mortar.
3 Reinforced Concrete These are the buildings with reinforced concrete frames and unreinforced
Ordinary-Moment- brick masonry infill in cement mortar. The thickness of infill walls is 230mm
Resisting-Frame (9”) or even 115mm (41/2”) and column size is predominantly 9”x 9”. The
Buildings prevalent practice of most urban areas of Nepal for the construction of
residential and commercial complexes is generally of this type.
4 Reinforced Concrete These buildings consist of a frame assembly of cast-in-place concrete beams
Intermediate- and columns. Floor and roof framing consists of cast-in-place concrete slabs.
Moment-Resisting- Lateral forces are resisted by concrete moment frames that develop their
Frame Buildings stiffness through monolithic beam-column connections. These are
engineered buildings designed without earthquake load or with old codes or
designed for small earthquake forces. Some of the newly constructed
reinforced concrete buildings are likely to be of this type.
5 Reinforced concrete These buildings consist of a frame assembly of cast-in-place concrete beams
special-moment- and columns. Floor and roof framing consists of cast-in-place concrete slabs.
resistant-frames Lateral forces are resisted by concrete moment frames that develop their
(SMRF) stiffness through monolithic beam-column connections. These buildings
have joint reinforcing, closely spaced ties, and special detailing to provide
ductile performance. Despite the fact that this system should be adopted
ideally for all new RC frame buildings in Nepal, it is now only used as an
exception.
6 Others Mixed buildings like Stone and Adobe, Stone and Brick in Mud, Brick in Mud
and Brick in cement etc. are other building type in Kathmandu valley.
79
Seismic Retrofitting Design and Techniques
non-structural damage)
Grade 5: Destruction
80
Seismic Retrofitting Design and Techniques
Grade 5: Destruction
81
Seismic Retrofitting Design and Techniques
Can only be noticed or felt by people who are in the right situation and circumstance
Furniture's or things which are not correctly positioned may move or be slightly displaced
Slight shaking or vibrations will form on water or liquid surfaces in containers
Can be noticed and felt by more people inside homes or buildings especially those situated
at high levels. Some may even feel dizzy. The quake at this stage can be described as though
a small truck had passed nearby.
Things that are hanged on walls would sway, shake or vibrate a little more strongly.
The shaking or vibrations on water or liquid surfaces in containers would be more vigorous
and stronger
Can be noticed and felt by most people inside homes and even those outside. Those who are
lightly asleep may be awakened. The quake at this stage can be described as though a heavy
truck had passed nearby.
Things that are hanged on walls would sway, shake or vibrate strongly. Plates and glasses
would also vibrate and shake, as well as doors and windows. Floors and walls of wooden
houses or structures would slightly squeak. Stationary vehicles would slightly shake.
The shaking or vibrations on water or liquid surfaces in containers would be very strong. It
is possible to hear a slight reverberating sound from the environment
82
Seismic Retrofitting Design and Techniques
V. Strong Intensity
Can be felt and noticed by almost all people whether they are inside or outside structures.
Many will be awakened from sleep and be surprised. Some may even rush out of their homes
or buildings in fear. The vibrations and shaking that can be felt inside or outside structures
will be very strong.
Things that are hanged on walls would sway, shake or vibrate much more strongly and
intensely. Plates and glasses would also vibrate and shake much strongly and some may
even break. Small or lightly weighted objects and furniture would rock and fall off.
Stationary vehicles would shake more vigorously.
The shaking or vibrations on water or liquid surfaces in containers would be very strong
which will cause the liquid to spill over. Plant or tree stem, branches and leaves would shake
or vibrate slightly.
Many will be afraid of the very strong shaking and vibrations that they will feel, causing
them to lose their sense of balance, and most people to run out of homes or building
structures. Those who are in moving vehicles will feel as though they are having a flat tire.
Heavy objects or furniture would be displaced from original positions. Small hanging bells
would shake and ring. Outer surfaces of concrete walls may crack. Old or fragile houses,
buildings or structures would be slightly damaged.
Weak to strong landslides may occur. The shaking and vibrations of plant or tree stem,
branches and leaves would be strong and highly noticeable.
Almost all people will be afraid of the very strong shaking and vibrations that they will feel.
Those who are situated at high levels of buildings will find it very hard to keep standing.
Heavy objects or furniture would fall and topple over. Large hanging bells will sound
vigorously. Old or fragile houses, buildings or structures would most definitely be
destroyed, while strong or new structures would be damaged. Dikes, dams, fishponds,
concrete roads and walls may crack and be damaged.
Liquefaction (formation of quicksand), lateral spreading (spreading of soil surface creating
deep cracks on land) and landslides will occur. Trees and plants will vigorously shake and
vibrate.
83
Seismic Retrofitting Design and Techniques
Will cause confusion and chaos among the people. It makes standing upright difficult even
outside homes / structures.
Many big buildings will be extremely damaged. Landslides or lateral spreading will cause
many bridges to fall and dikes to be highly damaged. It will also cause train rail tracks to
bend or be displaced. Tombs will be damaged or be out of place. Posts, towers and
monuments may bend or completely be destroyed. Water and canal/drainage pipes may be
damaged, bend, or break.
Liquefaction and lateral spreading causes structures to sink, bend or be completely
destroyed, especially those situated on hills and mountains. For places near or situated at
the earthquake epicenter, large stone boulders may be thrown out of position. Cracking,
splitting, fault rupture of land may be seen. Tsunami-like waves will be formed from water
surfaces whether from rivers, ponds or dams/dikes. Trees and plant life will very vigorously
move and sway in all directions.
People would be forcibly thrown/fall down. Chaos, fear and confusion will be extreme.
Most building structures would be destroyed and intensely damaged. Bridges and high
structures would fall and be destroyed. Posts, towers and monuments may bend or
completely be destroyed. Water and canal/drainage pipes may be damaged, bend, or break.
Landslides, liquefaction, lateral spreading with sand boil (rise of underground mixture of
sand and mud) will occur in many places, causing the land deformity. Plant and trees would
be damaged or uprooted due to the vigorous shaking and swaying. Large stone boulders
may be thrown out of position and be forcibly darted to all directions. Very-very strong
tsunami-like waves will be formed from water surfaces whether from rivers, ponds or
dams/dikes.
84
Seismic Retrofitting Design and Techniques
C NC N/A NK WEAK STORY: The strength of the lateral-force-resisting system in any story shall not be
less than 80% of the strength in an adjacent story above.
C NC N/A NK SOFT STORY: The stiffness of the lateral-force-resisting system in any story shall not be
less than 70% of the stiffness in an adjacent story above or below or less than 80% of the
average stiffness of the three stories above or below.
C NC N/A NK MASS: There shall be no change in effective mass more than 50% from one story to the next.
C NC N/A NK SHAPE: The building shall be symmetrical in plan and regular in elevation.
C NC N/A NK PROPORTION IN PLAN: The breadth to length ratio of the building shall be within 1:3.
The breadth to length ratio of any room or area enclosed by load bearing walls inside
the building shall be also within 1:3. The building height shall be not more than three
times the width of the building.
C NC N/A NK FOUNDATION: The foundation width and depth shall be at least 75cm. Masonry unit shall
be of flat-bedded stones or regular-sized well-burnt bricks. Mortar joints shall not be
exceeding 20mm in any case. There shall be no mud-packing in the core of the
foundation.
Information about mud packing in the core of the foundation could not be obtained.
C NC N/A NK SLOPING GROUND: The slope of the ground where the building lies shall not be more
than 20o (1:3, vertical: horizontal)
C NC N/A NK PLUMBLINE: Walls of the foundation and superstructure shall be true to plumb line and
the width of the wall shall be uniform.
C NC N/A NK WALL CORE: There shall be no mortar packing in the core of the wall.
85
Seismic Retrofitting Design and Techniques
C NC N/A NK THROUGH-STONES/WYTHE CONNECTORS: In case of stone building, the walls shall have
plenty of through-stones extending the whole width of the walls. The maximum spacing
of such through-stones shall be within 1.2m horizontally and 0.6m vertically.
C NC N/A NK WALL THICKNESS: The minimum wall thickness for different storey heights shall not be
less than
No of Storey
Masonry Type
One Two
Stone 340-450 450
Brick 350 350
Adobe 350 450
C NC N/A NK UNSUPPORTED WALL LENGTH: The maximum length of unsupported wall shall not be
more than 8 times its thickness. If the length of unsupported wall is more than 12 times
its thickness, buttressing shall be provided.
C NC N/A NK HEIGHT OF WALLS: The thickness to height ratio of a wall shall not be more than 1:8 for
stone building, 1:12 for brick building and 1:10 for Adobe.
C NC N/A NK OPENINGS IN WALL: The maximum combined width of the openings on a wall between
two consecutive cross-walls shall not be more than 35% of the total wall length for one-
storey building and not more than 25% of the total wall length in two-storey building.
C NC N/A NK Maximum length of any openings shall not be longer than 1.2m.
C NC N/A NK POSITION OF OPENINGS: Openings shall not be located at corners or junctions of a wall.
Openings shall not be placed closer to an internal corner of a wall than half the opening
height or 1.5 times the wall thickness, whichever is greater. The width of pier between
two openings shall not be less than half of the opening height or 1.5 times the wall
thickness, whichever is greater. The vertical distance between two openings shall not be
less than 0.6m or half the width of the smaller opening, whichever is greater.
C NC N/A NK TORSION: The distance between the story center of mass and the story center of rigidity
shall be less than 20% of the building width in either plan dimension.
86
Seismic Retrofitting Design and Techniques
C NC N/A NK WALL CRACKS: There shall be no existing diagonal cracks in wall elements greater than
1/16" or out-of-plane offsets in the bed joint greater than 1/16".
C NC N/A NK MASONRY LAY-UP: Filled collar joints of multi-Wythe masonry walls shall have negligible
voids.
C NC N/A NK VERTICAL REINFORCEMENT: There shall be vertical reinforcement at all corners and T-
junctions of masonry walls and it shall be started from foundation and continuous to
roof.
C NC N/A NK HORIZONTAL BANDS: There shall be steel or wooden bands located at the plinth, sill and
lintel levels of the building in each floor.
C NC N/A NK CORNER STITCH: There shall be reinforced concrete or wooden elements connecting two
orthogonal walls at a vertical distance of at least 0.5m to 0.7m.
C NC N/A NK GABLE BAND: If the roof is slopped roof, gable band shall be provided to the building.
C NC N/A NK REDUNDANCY: The number of lines of walls in each principal direction shall be greater than
2.
3.9.1.1 Diaphragms
C NC N/A NK DIAGONAL BRACING: All flexible structural elements of diaphragms such as joists and
rafters shall be diagonally braced and each crossing of a joist/rafter and a brace shall be
properly fixed.
C NC N/A NK LATERAL RESTRAINERS: Each joists and rafters shall be restrained by restrainers in both
sides of the wall.
Connections
C NC N/A NK TRANSFER TO SHEAR WALLS: Diaphragms shall be reinforced and connected for transfer
of loads to the shear walls and the connections shall be able to develop the shear
strength of the walls.
C NC N/A NK ANCHOR SPACING: Exterior masonry walls shall be anchored to the floor and roof
systems at a spacing 3 ft. or less.
87
Seismic Retrofitting Design and Techniques
This report is based on the best engineering judgment arrived at from visual inspection and
structural calculations. Structural drawings, architectural drawings and other additional information
was collected wherever possible. Also, non-destructive test to obtain the strength of the structural
members was carried out in the sites using Schmidt Hammer at possible locations.
No. Description
88
Seismic Retrofitting Design and Techniques
Building Types in
Kathmandu Valley
Brick-in-mud are the brick masonry buildings with fired bricks in mud
mortar.
These are brick masonry buildings with fired bricks in cement or lime
Brick-in-Cement,
2 mortar and stone-masonry buildings using dressed or undressed
Stone-in-Cement
stones with cement mortar.
Mixed buildings like Stone and Adobe, Stone and Brick in Mud, Brick in
6 Others mud and brick in cement etc are other building type in Kathmandu
valley.
89
Seismic Retrofitting Design and Techniques
90
Seismic Retrofitting Design and Techniques
The building does not seem to incorporate earthquake resilience features such as seismic bands
etc. Also, at the topmost level, some of the columns are not tied to the beam system. The building
was not designed to meet seismic requirements. The other evidence of lack of seismic
consideration is the largely deficient configuration of the building.
91
Seismic Retrofitting Design and Techniques
Joint Eccentricity √
Connectivity
between
Connection different √
structural
elements
Diaphragm
√
Continuity
Plan
√
Irregularities
Diaphragm
Diaphragm
Reinforcement √
at Openings
Pounding Effect √
Others
Nonstructural
√
Elements
92
Seismic Retrofitting Design and Techniques
4.3 CONCLUSIONS
Based on the qualitative assessment done above on the basis of the available information about the
building, the architectural and structural drawings and the limited non destructive test that could be
carried, it is concluded that the assessed building is likely to undergo moderate structural damage
at large earthquakes of intensity IX MMI. Otherwise the building is most likely to undergo slight
to moderate structural damage at moderate earthquakes of intensity of VIII MMI. This is not in
compliance with the stipulation of the Nepal, National Building Code that requires: “Structures
should be able to resist moderate earthquakes without significant damage”; and “Structures should
be able to resist major earthquakes without collapse”. Moreover, the reinforcement provided in the
columns as per the structural drawings is insufficient to withstand the lateral load exerted on the
structure during earthquakes.
93
Seismic Retrofitting Design and Techniques
The selected columns should be provided with mild steel angles at corners and braced at
intervals. The columns are then wrapped with chicken wire mesh and plastered with 1:4 cement
plasters. The details are provided in Appendix 6. These columns are selected since the
reinforcement provided in these columns seems to be inadequate to withstand the load of the
structure.
Reinforced concrete shear walls should be added in the structure to increase the shear capacity
of the structure. The shear walls are especially provided in the staircase areas because it is the
staircases that are affected most during earthquakes. Providing the shear wall at the staircase
level also minimizes the effect of short column.
94
Seismic Retrofitting Design and Techniques
C NC N/A NK ADJACENT BUILDINGS: An adjacent building shall not be located next to the structure being
evaluated closer than 4% of the height for Life Safety and Immediate Occupancy.
C NC N/A NK WEAK STORY: The strength of the lateral-force-resisting system in any story shall not be less
than 80% of the strength in an adjacent story above or below for Life-Safety and Immediate
Occupancy.
C NC N/A NK SOFT STORY: The stiffness of the lateral-force-resisting system in any story shall not be less
than 70% of the stiffness in an adjacent story above or below or less than 80% of the average
stiffness of the three stories above or below for Life-Safety and Immediate Occupancy.
C NC N/A NK VERTICAL DISCONTINUITIES: All vertical elements in the lateral-force-resisting system shall be
continuous to the foundation.
C NC N/A NK MASS: There shall be no change in effective mass more than 50% from one story to the next
for Life Safety and Immediate Occupancy.
C NC N/A NK TORSION: The distance between the story center of mass and the story center of rigidity shall
be less than 20% of the building width in either plan dimension for Life Safety and Immediate
Occupancy.
95
Seismic Retrofitting Design and Techniques
C NC N/A NK INTERFERING WALLS: All infill walls placed in moment frames shall be isolated from structural
elements.
C NC N/A NK SHEAR STRESS CHECK: The shear stress in the concrete columns, calculated using the Quick
Check procedure of Section 3.5.3.2, shall be less than 100 psi or 2√f c for Life Safety and
Immediate Occupancy.
C NC N/A NK AXIAL STRESS CHECK: The axial stress due to gravity loads in columns subjected to overturning
forces shall be less than 0.10f' c for Life Safety and Immediate Occupancy. Alternatively,
the axial stresses due to overturning forces alone, calculated using the Quick Check
Procedure of Section 3.5.3.6, shall be less than 0.30f' c for Life Safety and Immediate
Occupancy.
C NC N/A NK FLAT SLAB FRAMES: The lateral-force-resisting system shall not be a frame consisting of
columns and a flat slab/plate without beams.
C NC N/A NK SHORT CAPTIVE COLUMNS: There shall be no columns at a level with height/depth ratios less
than 50% of the nominal height/depth ratio of the typical columns at that level for Life
Safety and 75% for Immediate Occupancy.
C NC N/A NK NO SHEAR FAILURE: The shear capacity of frame members shall be able to develop the
moment capacity at the top and bottom of the columns
C NC N/A NK STRONG COLUMN / WEAK BEAM: The sum of the moment capacity of the columns shall be
20% greater than that of the beams at frame joints.
96
Seismic Retrofitting Design and Techniques
C NC N/A NK BEAM BARS: At least two longitudinal top and two longitudinal bottom bars shall extend
continuously throughout the length of each frame beam. At least 25% of the longitudinal
bars provided at the joints for either positive or negative moment shall be continuous
throughout the length of the members for Life Safety and Immediate Occupancy.
C NC N/A NK COLUMN-BAR SPLICES: All columns bar lap splice lengths shall be greater than 35 d b for Life
Safety and 50 d b for Immediate Occupancy and shall be enclosed by ties spaced at or less
than 8 d b for Life Safety and Immediate Occupancy.
C NC N/A NK BEAM-BAR SPLICES: The lap splices for longitudinal beam reinforcing shall not be located
within l b /4 of the joints and shall not be located within the vicinity of potential plastic
hinge locations.
C NC N/A NK COLUMN-TIE SPACING: Frame columns shall have ties spaced at or less than d/4 for Life Safety
and Immediate Occupancy throughout their length and at or less than 8 d b for Life Safety
and Immediate Occupancy at all potential plastic hinge locations.
C NC N/A NK STIRRUP SPACING: All beams shall have stirrups spaced at or less than d/2 for Life Safety and
Immediate Occupancy throughout their length. At potential plastic hinge locations stirrups
shall be spaced at or less than the minimum of 8 d b or d/4 but no less than 100mm for
Life Safety and Immediate Occupancy.
C NC N/A NK JOINT REINFORCING: Beam-column joints shall have ties spaced at or less than 8d b for Life
Safety and Immediate Occupancy.
C NC N/A NK JOINT ECCENTRICITY: There shall be no eccentricities larger than 20% of the smallest column
plan dimension between girder and column centerlines. This statement shall apply to the
Immediate Occupancy Performance Level only.
C NC N/A NK STIRRUP AND TIE HOOKS: The beam stirrups and column ties shall be anchored into the
member cores with hooks of 135° or more. This statement shall apply to the Immediate
Occupancy Performance Level only.
4.4.3 Diaphragms
C NC N/A NK DIAPHRAGM CONTINUITY: The diaphragms shall not be composed of split-level floors. In wood
buildings, the diaphragms shall not have expansion joints.
C NC N/A NK PLAN IRREGULARITIES: There shall be tensile capacity to develop the strength of the
diaphragm at re-entrant corners or other locations of plan irregularities. This statement
shall apply to the Immediate Occupancy Performance Level only.
97
Seismic Retrofitting Design and Techniques
C NC N/A NK DIAPHRAGM REINFORCEMENT AT OPENINGS: There shall be reinforcing bars around all
diaphragms openings larger than 50% of the building width in either major plan dimension.
This statement shall apply to the Immediate Occupancy Performance Level only.
4.4.4 Connections
C NC N/A NK CONCRETE COLUMNS: All concrete columns shall be doweled into the foundation for Life
Safety and the dowels shall be able to develop the tensile capacity of the column for
Immediate Occupancy.
Assumptions:
Live load = 3 kN/m2; Live load at roof level without access= 1.5 kN/m2
Lateral load is solely carried by frame elements. Stiffness of the walls is not considered.
LOAD MULTIPLIER
Dead 1
Live 0.25
Based on IS 1893 (Part 1): 2002, Criteria for earthquake resistant design of structures,
98
Seismic Retrofitting Design and Techniques
I = Importance factor
The approximate fundamental natural period of vibration (Ta) in seconds, of all other buildings,
including moment-resisting frame buildings with brick infill panels, may be estimated by the
empirical expression:
Ta = 0.09h /d0.5
d = Base dimension of the building at the plint level, in m, along the considered direction of the
lateral force
Z = 0.36
Ah = ZISa/2Rg
Tax = 0.09*h/dx0.5
Tay = 0.09*h/dy0.5
R=5
The total design lateral force or design seismic base shear (VB) along any principal direction is
determined by the following expression
VB = Ah*W
99
Seismic Retrofitting Design and Techniques
The design base shear (Vb) is distributed along the height of the building as per the following
expression:
Where
Qi (kN) Vj (kN)
Where,
Ac = Summation of the cross sectional area of all columns in the storey under consideration
nc = Total no. of columns
nf = Total no. of frames in the direction of loading
Vavg = Average shear stress (psi) in the columns of concrete frames
1 nc V j
Vavg
m nc n f A
c
m = component modification factor = 2 for buildings being evaluated to the life safety performance
level
10
0
Seismic Retrofitting Design and Techniques
= 15.63 kN
Shear capacity of concrete section = 0.72 * 230 * 310 / 1000 = 51.34 kN>15.63kN
Hence, safe.
Where,
10
1
Seismic Retrofitting Design and Techniques
Calculation of Ml
deff = 332 mm
= 58.83 KN –m
M2 = 0
= 24.51 kN
Shear capacity of concrete section = 0.72 * 230 * 310 / 1000 = 51.34 kN>24.51kN
Hence, safe.
Where,
10
2
Seismic Retrofitting Design and Techniques
Ac = Summation of the cross sectional area of all columns in the storey under consideration =
4747 in2
Hence, Safe.
Checking eccentricity between centre of mass and centre of stiffness at different floors
CENTER OF
STORY CENTER OF MASS STIFFNESS % ECCENTRICITY WIDTH
Xm Ym Xr Yr Ex Ey L B
= 18.76 KN –m = M2
10
3
Seismic Retrofitting Design and Techniques
= 58.83 KN –m = M2
10
4
Seismic Retrofitting Design and Techniques
Can only be noticed or felt by people who are in the right situation and circumstance
I
Furniture or things which are not correctly positioned may move or be slightly displaced
- Can be noticed and felt by more people inside homes or buildings especially those
situated at high levels. Some may even feel dizzy. The quake at this stage can be described
as though a small truck has passed nearby
III
- Things that are hung on walls would sway, shake or vibrate a little more strongly
- Can be noticed and felt by most people inside homes and even those outside. Those who
are lightly asleep may be awakened. The quake at this stage can be described as though a
heavy truck has passed nearby
IV - Things that are hung on walls would sway, shake or vibrate strongly. Plates and glasses
would also vibrate and shake, as well as doors and windows. Floors and walls of wooden
houses or structures would slightly squeak. Stationary vehicles would slightly shake
- The shaking or vibrations on water or liquid surfaces in containers would be very strong.
It is possible to hear a slight reverberating sound from the environment
Strong Intensity
- Can be felt and noticed by almost all people whether they are inside or outside
V structures. Many will be awakened from sleep and be surprised. Some may even rush out of
their homes or buildings in fear. The vibrations and shaking that can be felt inside or outside
structures will be very strong
10
5
Seismic Retrofitting Design and Techniques
- Things that are hung on walls would sway, shake or vibrate much more strongly and
intensely. Plates and glasses would also vibrate and shake much more strongly and some
may even break. Small or lightly weighted objects and furniture would rock and fall off.
Stationary vehicles would shake more vigorously.
- The shaking or vibrations on water or liquid surfaces in containers would be very strong
which will cause the liquid surfaces in containers would be very strong which will cause the
liquid to spill over. Plant or tree stem, branches and leaves would shake or vibrate slightly.
- Many will be afraid of the very strong shaking and vibrations that they will feel causing
them to loose their sense of balance and most people to run out of homes or building
structures. Those who are in moving vehicles will feel as though they are having flat tyres.
VI
- Heavy objects or furniture would be displaced from original positions. Small hanging bells
would shake and ring. Outer surfaces of concrete walls may crack. Old or fragile houses,
buildings or structures would be slightly damaged.
- Weak to strong landslides may occur. The shaking and vibration of plant or tree stem,
branches and leaves would be strong and highly noticeable.
Damaging Intensity
- Almost all people will be afraid of the very strong shaking and vibrations that they will
feel. Those who are situated at high levels of building swill find it very hard to keep standing.
- Heavy objects or furniture would fall and topple over. Large hanging bells will sound
VII vigorously. Old or fragile houses, buildings or structures would most definitely be destroyed,
while strong or new structures would be damaged. Dikes, dams, fishponds, concrete roads
and walls may crack and be damaged.
10
6
Seismic Retrofitting Design and Techniques
- Many big buildings will be extremely damaged. Landslides or lateral spreading will cause
may bridges to fall and dikes to be highly damaged. It will also cause train rail tracks to bend
or be displaced. Thombs will be damaged or be out of place. Posts, towers and monuments
may bend or completely be destroyed. Water and canal/drainage pipes may be damaged,
bend or break.
Destructive Intensity
- People would be forcibly thrown/fall down. Chaos, fear and confusion will be extreme
- Most building structures would be destroyed and intensely damaged. Bridges and high
structures would fall and be destroyed. Posts, towers and monuments may bend or break.
IX
- Landslides, liquefaction, lateral spreading with sand boil (rise of underground mixture of
sand and mud) will occur in many places, causing the land deformity. Plant and trees would
be damaged or uprooted due to the vigorous shaking and swaying. Large stone boulders
may be thrown out of position and be forcibly darted to all directions. Very-very strong
tsunami-like waves will be formed from water surfaces whether from rivers, ponds or
dams/dikes.
Devastative Intensity
XI - Severe damage even to well built buildings, bridges, water dams and railway lines;
highways become useless; underground pipes destroyed.
10
7
Seismic Retrofitting Design and Techniques
(Vulnerability Table)
10
8
Seismic Retrofitting Design and Techniques
10
9
Seismic Retrofitting Design and Techniques
Grade 5: Destruction
a) Effects on humans
(Effects on ground and ground failure are dealt with especially in Section 7)
c) Damage to buildings
Introductory remark:
The single intensity degrees can include the effects of shaking of the respective lower intensity
degree(s) also, when these effects are not mentioned explicitly.
I. Not felt
b) No effect.
c) No damage.
a) The tremor is felt only at isolated instances (<1%) of individuals at rest and in a specially
receptive position indoors.
11
0
Seismic Retrofitting Design and Techniques
b) No effect.
c) No damage.
III. Weak
a) The earthquake is felt indoors by a few. People at rest feel a swaying or light trembling.
c) No damage.
a) The earthquake is felt indoors by many and felt outdoors only by very few. A few people are
awakened. The level of vibration is not frightening. The vibration is moderate. Observers feel a
slight trembling or swaying of the building, room or bed, chair etc.
b) China, glasses, windows and doors rattle. Hanging objects swing. Light furniture shakes visibly
in a few cases. Woodwork creaks in a few cases.
c) No damage.
V. Strong
a) The earthquake is felt indoors by most, outdoors by few. A few people are frightened and run
outdoors. Many sleeping people awake. Observers feel a strong shaking or rocking of the whole
building, room or furniture.
b) Hanging objects swing considerably. China and glasses clatter together. Small, top-heavy
and/or precariously supported objects may be shifted or fall down. Doors and windows swing
open or shut. In a few cases window panes break. Liquids oscillate and may spill from well-filled
containers. Animals indoors may become uneasy.
a) Felt by most indoors and by many outdoors. A few persons lose their balance. Many people are
frightened and run outdoors.
b) Small objects of ordinary stability may fall and furniture may be shifted. In few instances
dishes and glassware may break. Farm animals (even outdoors) may be frightened.
VII. Damaging
a) Most people are frightened and try to run outdoors. Many find it difficult to stand, especially on
upper floors.
11
1
Seismic Retrofitting Design and Techniques
b) Furniture is shifted and top-heavy furniture may be overturned. Objects fall from shelves in
large numbers. Water splashes from containers, tanks and pools.
b) Furniture may be overturned. Objects like TV sets, typewriters etc. fall to the ground.
Tombstones may occasionally be displaced, twisted or overturned. Waves may be seen on very
soft ground.
IX. Destructive
b) Many monuments and columns fall or are twisted. Waves are seen on soft ground.
X. Very destructive
11
2
Seismic Retrofitting Design and Techniques
XI. Devastating
a) All buildings of vulnerability class A, B and practically all of vulnerability class C are
destroyed. Most buildings of vulnerability class D, E and F are destroyed. The earthquake effects
have reached the maximum conceivable effects.
11
3
Seismic Retrofitting Design and Techniques
Section - II
Retrofitting Analysis
and Design
11
4
Seismic Retrofitting Design and Techniques
1. EXAMPLE - 1
ENGINEERED BUILDING
SEISMIC EVALUATION AND RETROFITTING DESIGN OF RC
FRAME BUILDING
1.1 BUILDING DESCRIPTION
The building is RC Frame structure in burnt clay bricks in cement mortar. The structure is
5-story + 1-Basement with storey height of 4m and 3.8m. The floor consists of reinforced
concrete slab system.
There are 230mm thick outer walls and light weight partition wall as inner walls.
Performance Level : 1
11
5
Seismic Retrofitting Design and Techniques
11
6
Seismic Retrofitting Design and Techniques
1. Assumptions:
Lateral load is solely carried by frame elements. Stiffness of the walls is not
considered.
11
7
Seismic Retrofitting Design and Techniques
∑ 46459.57 kN
Cd = C Z I K
I = Importance Factor
The total design lateral force or Design Seismic Base Shear (VB) along any principal direction is determined by
the following expression :
VB = Cd*Wt
Where,
11
8
Seismic Retrofitting Design and Techniques
The approximate fundamental natural period of vibration (Ta) in seconds, of all other buildings,
including moment-resisting frame buildings with brick infill panels, may be estimated by the
empirical expression:
Ta = 0.09h /d0.5
Where,
d = Base dimension of the building at the plinth level, in m, along the considered direction of the lateral
force
dx = 40.51m
dz = 33m
= 0.3617
= 0.4
11
9
Seismic Retrofitting Design and Techniques
Cd = C Z I K
= 0.08 X 1 X 1 X 1 = 0.08
The design base shear (VB) computed in 1.5 shall be distributed along the height of the building as per the
following expression:
Fi = V X Wi hi / Σ Wihi i
Where,
(Using IITK-GSDMA Guidelines for Seismic Evaluation and Strengthening of Buildings, 6.5.1)
Ʈcol = (nc/(nc-nf)) * (Vj / Ac)< min of 0.4 Mpa and 0.1 sq.rt.(fck)
0.1√fck = 0.45
nc= Total no. of Columns resisting lateral forces in the direction of loading
Ac = Summation of the cross- section area of all columns in the storey under consideration
12
0
Seismic Retrofitting Design and Techniques
12
1
Seismic Retrofitting Design and Techniques
Fo = 2/3 (Vb/nf) x (H / L)
= 337.89 kN
Axial Stress for z-direction loading,
σ = 337.89 X 1000 = 2.11 MPa
0.16
σ all =0.25 fck = 5 MPa
therefore σ < σ all OK
DCR = 0.422
Hence the check is satisfied
Recommended Actual
Wall
Wall Type Height/Thickness ratio Height/Thickness ratio Comments
Thickness
(0.24 < Sx ≤ 0.35) in building
Wall in
(3800-450)/230 =
ground 230mm 18 Pass
14.56
storey
The out of plain stability of ground floor wall and that for the upper stories are within the permissible limit,
hence the check is satisfied.
1.1 Check for Strong Column Weak Beam:
The flexure strengths of the columns shall satisfy the condition:
∑Mc ≥ 1.1 ∑Mb
Checking Capacity of Center Column at Ground Floor:
The longitudinal beam of size 300 X 550 is reinforced with 3-20dia. + 3-25dia. (i.e 2415.09mm2)
at top and 4-20 dia. (ie 1256.636mm2) at bottom.
Where,
b = 300mm; d= 515mm
The hogging and sagging moment capacities are evaluated as 303.406kNm and 194.225kNm
respectively.
Factored column axial load = 3860.19 kN
Pu / fck*b*D = 0.536 where column size is 600mmX600mm
The column is reinforced with 8-25dia. + 2-20dia.
Asc = 4555.278mm2 ; pt = 1.265%
Therefore,
Mu/fck*b*D2 = 0.05
Mu = 216 kNm
∑Mc = 216+216 = 432
∑Mb = 303.406 + 194.225 = 497.62kNm
1.1∑Mb = 547.382kNm
∑Mc< 1.1 ∑Mb
Hence, check is not satisfied.
12
2
Seismic Retrofitting Design and Techniques
2. Evaluation Summary:
· The building is safe in strength related checks such as shear stress capacity, axial stress, out of plane
stability.
· The computer analysis of the structure shows:
· Foundation: Safe
· Beam : Safe
· Column : Not Safe (The DCR lies in the range of 1.5 indicating more detailed analysis)
· Floor slab: Safe
· Thus, the above evaluations states that the frame has to be strengthened and retrofitted.
12
3
Seismic Retrofitting Design and Techniques
12
4
Seismic Retrofitting Design and Techniques
12
5
Seismic Retrofitting Design and Techniques
12
6
Seismic Retrofitting Design and Techniques
12
7
Seismic Retrofitting Design and Techniques
2.3 Shearwall Addition and Column Jacketing with approximate cost of NRs. 8,176,350
1.6 RECOMMENDATION
From the point of cost estimation and time of completion for the retrofitting, it is likely to
adopt option 3, i.e. shear wall addition with concrete jacketing of columns.
12
8
Seismic Retrofitting Design and Techniques
12
9
COMPARATIVE STUDY OF DIFFERENT OPTIONS
Parameter
Disturbance to
Disturbance Damagibility Effect on Requirement of
Options Time existing
to existing Cost after present foundation
Consumption function during
structure retrofitting aesthetic strengthening
construction
RC Jacketing on
** * *** *** *** * ** *
column
Steel Jacketing on
*** ** *** ** ** ** *
column
h
dium
Seismic Retrofitting Design and Techniques
0
13
Seismic Retrofitting Design and Techniques
13
1
Seismic Retrofitting Design and Techniques
2. EXAMPLE -2
OCCUPANCY CHANGE
Vulnerability evaluation and retrofitting of following buildings has been carried out using two
approaches.
13
2
Seismic Retrofitting Design and Techniques
13
3
Seismic Retrofitting Design and Techniques
13
4
Seismic Retrofitting Design and Techniques
Live load:
Dead Load:
~ 4.70 KN/m2
13
5
Seismic Retrofitting Design and Techniques
~ 4.50 KN/m2
Residential Building :
The following is a detail of quick check calculations based on FEMA 310 for the
Assumptions:
S.NO. FLOORS Total Dead Load Total Live Total Weight Remarks
(KN) Load (KN) ( KN )
The total design lateral force or design seismic base shear is given by
Based on IS 1893 (Part 1): 2002, Criteria for earthquake resistant design of structures,
13
6
Seismic Retrofitting Design and Techniques
I = Importance Factor
The total design lateral force or Design Seismic Base Shear (VB) along any principal direction is
VB = Ah*W
The approximate fundamental natural period of vibration (Ta) in seconds, of all other buildings, including
moment-resisting frame buildings with brick infill panels, may be estimated by the empirical expression:
Ta = 0.09h /d0.5
h = Height of Building in
Where, meter = 10.80 m
d = Base dimension of the building at the plinth level, in m, along the considered
direction of the lateral force
dx = 8.23 m
dz = 8.23 m
=0.338 <0.55
13
7
Seismic Retrofitting Design and Techniques
=0.338 <0.55
Sa/g = 2.5 (For Medium Soil ) (Refer IS 1893 (Part 1) :2002-Clause 6.4.5 and Fig.2 )
R = 3.0 (For Ordinary RC Moment Resisting Frame ) (Refer IS 1893 (Part 1) :2002-table 7 )
Ah = ZISa/2Rg
= 0.15
=0.15* 2468.34
370.251 kN
(Using IITK-GSDMA Guidelines for Seismic Evaluation and Strengthening of buildings 6.5.1)
The Total design lateral force or design seismic base shear is given by
13
8
Seismic Retrofitting Design and Techniques
Vb=Ah x W
Tcol = (nc/(nc-nf)) * (Vj / Ac)< min of 0.4 Mpa and 0.1 sq.rt.(fck)
nc= Total No. of Columns resisting lateral forces in the direction of loading
Ac = Summation of the cross- section area of all columns and shear wall in the storey under consideration
Shear Stress
Storey
Storey nc nf1 nf2 Ac T col T col
Shears (KN)
1(MPa) 2(MPa)
4 4 2 2 0.211 106.4 1.01 1.01
3 9 3 3 0.476 285.49 0.9 0.9
2 9 3 3 0.476 353.3 1.11 1.11
1 9 3 3 0.476 370.25 1.17 1.17
The following is a detail of quick check calculations based on FEMA 310 for the seismic evaluation
Assumptions:
13
9
Seismic Retrofitting Design and Techniques
FLOOR
LEVEL FLOORS LL 0.25LL Remarks
AREA sq.m
4 Third Floor 29.485 44.2275 11.056875
3 Second Floor 90.33 270.99 67.7475
2 FirstFloor 67.73 203.19 50.7975
1 Ground Floor 67.73 203.19 50.7975
∑ 180.39938
LUMP MASS CALCULATION
The total design lateral force or design seismic base shear is given by
Based on IS 1893 (Part 1): 2002, Criteria for earthquake resistant design of structures,
I = Importance Factor
The total design lateral force or Design Seismic Base Shear (VB) along any principal direction is
VB = Ah*W
14
0
Seismic Retrofitting Design and Techniques
The approximate fundamental natural period of vibration (Ta) in seconds, of all other buildings,
including moment-resisting frame buildings with brick infill panels, may be estimated by the
empirical expression:
Ta = 0.09h /d0.5
Where,
d = Base dimension of the building at the plinth level, in m, along the considered direction of the
lateral force
dx = 8.23 m
dz = 8.23 m
=0.338 <0.55
=0.338 <0.55
Sa/g = 2.5 (For Medium Soil ) (Refer IS 1893 (Part 1) :2002-Clause 6.4.5
and Fig.2 )
R = 3.0 (For Ordinary RC Moment Resisting Frame ) (Refer IS 1893 (Part 1) :2002-table 7 )
Ah = ZISa/2Rg
= 0.225
14
1
Seismic Retrofitting Design and Techniques
(Using IITK-GSDMA Guidelines for Seismic Evaluation and Strengthening of buildings 6.5.1)
The Total design lateral force or design seismic base shear is given by
Vb=Ah x W
Tcol = (nc/(nc-nf)) * (Vj / Ac)< min of 0.4 Mpa and 0.1 sq.rt.(fck)
nc= Total No. of Columns resisting lateral forces in the direction of loading
Ac = Summation of the cross- section area of all columns and shear wall in the storey under
consideration
14
2
Seismic Retrofitting Design and Techniques
Shear Stress
Storey Shears T col T col
Storey nc nf1 nf2 Ac
(KN) 1 2
(MPa) (MPa)
4 4 2 2 0.211 159.91 1.52 1.52
3 9 3 3 0.476 432.79 1.36 1.36
2 9 3 3 0.476 535.94 1.69 1.69
1 9 3 3 0.476 561.73 1.77 1.77
Tcol>>min of 0.4 MPa and 0.1sqrt(fck) = 0.45 MPa
Where,
b = 230
D = 350
The Moment Capacities are evaluated from STAADPro 2006, which is equal to 68.6 KN-m and
53.6 KN-m.
= 1.4*(68.6+53.6 )/2.7
= 63.36 KN
14
3
Seismic Retrofitting Design and Techniques
Fck = 20 N/mm2
Fy = 415 N/mm2
From SP 16 Table 61
= 30.94 kN
From SP 16 Table 62 :
= 46.5 kN >>32.42 KN
Hence, the Check for shear tie is satisfied for central column.
The axial stress due to gravity loads in the center column of Ground Floor = 711.289 kN
14
4
Seismic Retrofitting Design and Techniques
Fo = 2/3 (Vb/nf) x (H / L)
Fo = 2/3 (Vb/nf) x (H / L)
= 252.78 kN
0.05
DCR = 0.334
14
5
Seismic Retrofitting Design and Techniques
Fo = 2/3 (Vb/nf) x (H / L)
Fo = 2/3 (Vb/nf) x (H / L)
= 252.78 kN
0.05
DCR = 0.334
Recommended
Wall Actual Height/Thickness
Wall Type Height/Thickness Comments
Thickness ratio in building
ratio (0.24 < Sx ≤ 0.35)
230mm 18 (2700-350)/230 = 10.217 Pass
14
6
Seismic Retrofitting Design and Techniques
Wall in
ground storey
Wall in upper
230mm 16 (2700-350)/230 = 10.217 Pass
stories
Hence the check is satisfied
3. EXAMPLE - 2 (A)
ANALYSIS IN STAAD
14
7
Seismic Retrofitting Design and Techniques
WIRE FRAME
COLUMN
BEAM
14
8
Seismic Retrofitting Design and Techniques
3D Model in Staad
14
9
Seismic Retrofitting Design and Techniques
RETROFITTING DRAWINGS:
15
0
Seismic Retrofitting Design and Techniques
15
1
Seismic Retrofitting Design and Techniques
15
2
Seismic Retrofitting Design and Techniques
15
3
Seismic Retrofitting Design and Techniques
4. EXAMPLE – 2(B)
Performance Analysis of the structure with the given drawings was carried out for structural
performance evaluation. The performance evaluation of non-structural components and the
combined performance is not evaluated. Static Pushover Analysis is used to evaluate the
performance of the structure.
4.1 OUTPUT
The analysis is carried out for Design Basis Earthquake (DBE) and Maximum Considered
Earthquake (MCE) as defined in IS 1893 (2002). The main results for both DBE and MCE are given
below.
15
4
Seismic Retrofitting Design and Techniques
15
5
Seismic Retrofitting Design and Techniques
The analysis of the building was carried out using the static analysis and push over analysis in SAP
2000 and the buildings are found to be unsafe.
Demand base shear is 516.726KN but base shear obtain is less than required in both Basis
Earthquake (DBE) and Maximum Considered Earthquake (MCE)
Hence the building cannot be considered safe for the hospital purpose. It needs retrofitting
measures to increase capacity for the earthquake safety.
15
6
Seismic Retrofitting Design and Techniques
5. EXAMPLE – 2(C)
5.1 OUTPUT
The analysis is carried out for Design Basis Earthquake (DBE) and Maximum Considered
Earthquake (MCE) as defined in IS 1893 (2002). The main results for both DBE and MCE are given
below.
For Design Basis Earthquake (DBE), the performance point of retrofitted structure appears at Sa
(spectral acceleration) equal to 0.382 and maximum roof deflection (D) is 0.525 inches as shown
in the image below.
15
7
Seismic Retrofitting Design and Techniques
Plastic hinge formation for the building mechanisms has been obtained at different displacements
levels. The hinging patterns are as shown in figures
Thus the analysis of the building after RC jacketing of columns was carried out by modeling the
building in SAP 2000 and the results were found as mentioned above from the push over analysis.
The building is found to be safer in Push over analysis.
Hence the retrofitted building can be considered safe for the hospital purpose.
From the performance analysis of the retrofitted building according to the drawings provided and
field verification, the retrofitted building will be in damage control level. The performance objective
for DBE is expected at Life Safety level and for MCE it's expected at Structural stability. As the
performance of the building is realized at damaged control level (better performance than the
expected performance), the building is safe to use as per the requirements of IS 1893-2002.
15
8
Seismic Retrofitting Design and Techniques
6. EXAMPLE -3
A local building in Kathmandu was chosen for the Analysis. The plan and elevation of the building
is shown in figure 7 – 1.
The vertical structure is a single layer non retrofitted masonry made of brick masonry, while the
floor is of concrete slabs. In order to reduce the computational burden of the dynamic analyses
needed for the vulnerability assessment, only the facade wall was analysed using the proposed
SAP2000 v.14.0.0 model. The design values assumed for the mechanical properties are based on
the mean values measured in brick masonry from different researches conducted in Pulchowk
Campus, for brick masonry, fd=1.82N/mm2, E=509N/mm2, and G=203.6N/mm2. Only the in-plane
seismic performance of the wall was investigated, assuming that the wall was effectively connected
to the floors.
Laurent Pasticier, Claudio Amadio and Massimo Fragiacomao (July 2007) carried out Non Linear
Push over Analysis of masonry structure using SAP 2000 v.10. The study has established that the
equivalent frame method for the masonry could be adopted for Non - Linear Push over Analysis,
by providing different hinges at the different section in the members.
15
9
Seismic Retrofitting Design and Techniques
The masonry pier was modeled as elastoplastic. Hinges were determined according to the failure
mechanisms of masonry. The standard force-displacement curve that can be implemented in the
SAP 2000 plastic hinges in depicted in Figure 8-2(a) [24]. The masonry piers were modeled as
Figure 8-1. (a) Standard shape of the force vs displacement curve in SAP2000® v.10 for the plastic hinge element
[24]; (b) and (c): behaviour assumed, respectively, for the entire pier and the correspondent plastic hinge; (d)
and (e): behaviour assumed, respectively, for the entire spandrel beam and the correspondent plastic hinge.
elastoplastiv with final brittle failure (Figure 8-2 (b)) by introducing two 'rocking hinges' at the end
of the deformable parts and one ‘shear hinge’ at mid-height . A rigid- perfectly plastic behaviour
with final brittle failure was assumed for all these plastic hinges (Figure 8 - 2(c)).
16
0
Seismic Retrofitting Design and Techniques
Only shear hinge is assigned in spandrels at the mid span while piers are modeled with two flexural
hinges at the ends and one shear hinge at the mid span. Slight in base shear capacity was found but
performance point was not found.
Rigid diaphragm was assigned at the floor level but no increase in base shear capacity in found in
inplane analysis. No performance point was found.
16
1
Seismic Retrofitting Design and Techniques
Although the base shear capacity of the structure is lesser than while assigning RC columns, this
option seems to be more reliable as in this case the masonry structure is covered with wire mesh
which enable the masonry members to remain stable without the formation of the hinges
approximately upto the performance point.
16
2
Seismic Retrofitting Design and Techniques
400 No Retrofitting
300
Retrofitting with lintel
200
Lintel + Rigid diaphragm
100
0 Lintel+Rigid diaphragm +
0 0.01 0.02 0.03 0.04 Columns
Retrofitting with lintel + Columns are Increase in base Performance point of the building
rigid diaphragm + inserted in the walls shear capacity increases and as a whole
Columns structure remain stable but
masonry walls fails too earlier
although the whole structure is
stable, so this technique is not so
good
Retrofitting with lintel + Jacketing is done by Increase in base As each wall unit has been
rigid diaphragm + Wire wire meshing shear capacity strengthened, wall does not fail,
meshing so this technique seems to be
most reliable of all above
16
3
Seismic Retrofitting Design and Techniques
7. EXAMPLE -4
BUILDING DESCRIPTION
No. of stories =2
Size L= 6200 mm 6.2 m
B= 4000 mm 4 m
H= 6000 mm 6 m
Wall material= Brick in cement sand mortar (1:6)
Thickness of wall= 230 mm 0.23 m
Roof material= R.C.C
0.12
Thickness of roof= 125 mm 5 m
Earthquake Zone= V
Building Type= School
Window: B= 1000 mm 1 m
H= 1200 mm 1.2 m
No. of windows= 5 Per floor
Door:
D1 B= 1200 mm 1.2 m
16
4
Seismic Retrofitting Design and Techniques
H= 2100 mm 2.1 m
D2 B= 1000 mm 1 m
H= 2100 mm 2.1 m
Dead load and live loads:
Dead Load
Unit wt. or R.C.C= 25 KN/m3
Unit wt. of brick masonry= 19 KN/m3
Floor Finishing= 1 KN/m2
Live Load
Live Load for floor= 3 KN/m2
Live load for roof= 0 KN/m2
Earthquake Loads
Summary of lumped load calculation:
As per IS 1893 (Part 1):2002, cl 7.3,
table 8:
For imposed uniformly distributed floor loads up to 3KN/m2, % of imposed load =25%
Seismic Weight,
Live Load, LL Storey Level,
Storey Dead Load, DL Wi=DL+25%LL Story Height
(KN) hi(m)
(KN) (KN)
2 192.3436 0 192.3 3 6
1 298.5346 74.4 317.1 3 3
∑ 490.8782 509.5
School
Structure type Cl. 6.4.2, Table6
Building
16
5
Seismic Retrofitting Design and Techniques
Response
R Cl. 6.4.2, Table7 2.5
reduction factor
Height of the
h Refer drawing 6 m
building
Dimension of the
Dx Refer drawing 6.2 m
building Along X
Dimension of the
Dy Refer drawing 4 m
building Along Y
Average Response
acceleration (Sa/g)x Cl. 6.4.5, fig. 2 2.5
coefficients along X
Average Response
acceleration (Sa/g)y Cl. 6.4.5, fig. 2 2.5
coefficients along Y
Seismic Wt of the
W Cl. 7.4.1 509.5 KN
Building
Cl. 7.5.3, VB =Ah
Base Shear VB 137.6 KN
W
16
6
Seismic Retrofitting Design and Techniques
T= 0.216869219 secs
0.216869219
Hence, K= 1
Design
Storey
Seismic wt. Storey level Wihik lateral
Storey shear
Force
Wi (kN) hi(m) kNm Qi(kN) Vj(kN)
2 192.3436 6 1154 75.4 75.4
1 317.1346 3 951 62.159 137.6
2105 137.56
Lateral Coefficients:
16
7
Seismic Retrofitting Design and Techniques
Design of bandage
Assumed size of band:
d= 250 mm
t= 50 mm
Lever arm= z= 225 mm
fs of steel= 0.56*1.25*fy= 290.5 N/mm2
16
8
Seismic Retrofitting Design and Techniques
852.85
So, use 4.75 mm dia at a spacing of 7 c/c
Lateral Load:
Considering b= 1 m width of wall.
Lateral Load, w= C*(Wt. of wall of "b"
height)= 1.71306542 KN/m
Height of wall below lintel band= 1.2 m
M=wl^2/12= 0.20556785 KNm
Z=bt^2/6= 8816666.667
Bending stress,
fb=M/Z= 0.023 N/mm2
16
9
Seismic Retrofitting Design and Techniques
Design of stitches:
Lateral Load carried by stitch, w= C*(Wt. of triangular
portion of wall)= 3.854 KN
Count lintel and sill also as stitch band; therefore total
number of stitch considered= 3
Ast=W/(no. of stitches*0.56*fy)= 5.528 mm2
Since, for detailing requirement, we shall use 2 numbers of
8mm dia bars
(One on outside face and another in the inside face of the
wall).
In-Plane analysis and design of splint ( Vertical Band):
17
0
Seismic Retrofitting Design and Techniques
Pier analysis:
Lateral load on each wall (grid 1 and grid 2) Vi=VB/No. of walls= 68.78 KN
Masonry,E= 2400000 KN/m2
Proportion of
Lateral load
Stiffness (KN/m) lateral load carried
carried by pier
by pier
K= 12
p= K/∑K Fi=Vi*p
EI/[{1+2.4(d/h)2}h3]
38598.699 0.235 16.15
125798.692 0.765 52.63
164397.391 68.78
17
1
Seismic Retrofitting Design and Techniques
Overturning moment=
Mo=Q2/2*(h1+h2)+Q1/2*h1= 319.44 KNm
Centroid of pier P3 & P4= (A3X3+A4X4)/(A3+A3)= 1.914 m
h3= 1.186 m where h3 is the
h4= -0.914 distance between
M.O.I about centroid, IC=I3+A3h32+I4+A4h42= 9.05258E+11 mm^4 the centroid of P3
and centroid of the
grid 2
17
2
Seismic Retrofitting Design and Techniques
Overturning
Bending stress Vertical stress Net stress
stress
Points
Design of pier P4
Distance of NA from point A, x= 0.729024286 m
= 729.0242864 mm
Total tensile force, T=fn*A= 75637.9962 N
Ast
reqd=T/(0.56*fy)
= 325.4646997 mm2
Dia. Of rod
provided= 10 mm
NO. of rods reqd= 4.142277996 ≈ 5
Remarks: Safe
17
3
Seismic Retrofitting Design and Techniques
Section – III
Case Studies
17
4
Seismic Retrofitting Design and Techniques
A UNCRD project, with technical assistance from CDM-ITB, SDN padasuka II is located
at Kecamatan Soreang, Bandung County. The school has approximately 400 students. The
school building consists of 2 buildings with four rooms each, and the total area of the school
building is approximately 500 m2. The structural system before retrofitted is reinforced
concrete frames and masonry walls. The buildings were built in the early of 1990s, and still
in the expected life-time.
17
5
Seismic Retrofitting Design and Techniques
1.2 BACKGROUND
Many problems were found when the visual survey and structural investigation were
conducted. The problems found could be listed as follows:
2. Inadequate roof framing system, poor wall-roof connection, and poor roof truss element
and connection. The roof was in dire need of repair as the construction shown excessive
deformation on the top of the building.
3. Damages found on walls, with cracks and gaps found on some places, due to lack of
structural elements (beams and columns).
Structural Analysis
Using the results from structural investigation, the buildings were analyzed to evaluate the
structural performance under all applicable loads, including earthquakes. The structure was
modeled as such that the structural elements (beams and columns) formed the structural
frame, while masonry walls were modeled as plate elements. Both structural frame and
plate elements provided lateral resisting system for the structure. The foundation provided
support for the structural frames. The roof trusses were also modeled using truss elements.
Material properties used for the analysis were based on results of structural investigation.
17
6
Seismic Retrofitting Design and Techniques
The design criteria followed the performance based design, where the structure was
expected to have minor/limited damage under design earthquake (elastic behavior). The
seismic design level was obtained from the current building codes, with a pga of 0.24g. The
structural analysis was conducted using response spectra approach.
Results from structural analysis show that the structure did not have adequate capacity in
resisting lateral loads. Checking of connection capacity also revealed unsatisfactory results.
Moreover, the trusses required improvement to be able to support all applicable loads.
Combined with data obtained from visual and structural investigations, results from
structural analysis were then used to design appropriate retrofitting approach.
17
7
Seismic Retrofitting Design and Techniques
The buildings were retrofitted using iron wire mesh for strengthening wall elements, inserting
(a) Retrofitting
strategy
for columns of SDN Padasuka II
columns on building corners. The wire mesh was installed in the locations of ordinary beams
and columns, as well as diagonally on the perimeter walls. The wire mesh was installed on the
both side of the wall and anchored using iron wire. Tie beams were added underneath the walls
for strengthening the foundation system. The roof system was retrofitted using proper material
and detailing. Repair was conducted for nonstructural elements such as doors/windows and
ceilings. Finishing/cosmetic repair and improvement of sanitary facilities were also conducted
for the schools buildings.
17
8
Seismic Retrofitting Design and Techniques
17
9
Seismic Retrofitting Design and Techniques
Figure 1: Retrofitting works for the tie beam (inserting tie beam)
18
0
Seismic Retrofitting Design and Techniques
18
1
Seismic Retrofitting Design and Techniques
Figure Retrofitting works for the trusses and roof (providing proper materials and detailing)
18
2
Seismic Retrofitting Design and Techniques
1.4 IMPLEMENTATION
1.4.1 POST-EARTHQUAKE
CONDITION
Based on the survey conducted, there was no significant damage on SDN Padasuka II, with
only a few non-structural cracks occurred. From the post-earthquake condition, it can be
concluded that the retrofitting approaches adopted on SDN Padasuka II has successfully
prevented the buildings from major damage. As a comparison, there were some schools and
18
3
Seismic Retrofitting Design and Techniques
houses located near SDN Padasuka II that were strongly affected by the earthquake shaking.
Following figures show the post-earthquake condition of SDN Padasuka II.
18
4
Seismic Retrofitting Design and Techniques
2.1.1 INTRODUCTION
This is a project under Save the Children project, with design and technical assistance from
Syiah Kuala University. SDN 13 Syamtalira Arun is located at North Aceh. The school
building consists of 2 rooms. The school has approximately 400 students. In general, the
structural system before retrofitted was reinforced concrete frames with infill masonry walls.
existing
sloof beam 13/15
existing
sloof beam 18/20
1 2
Upper Sloof Beam Retrofitting
1 : 100
2.1.2 BACKGROUND
a. Status and Condition of Structure
From the initial survey, there were some major problems found in SDN 13 Syamtalira
Arun, i.e:
1. Cracks on walls
3. Poor workmanship
18
5
Seismic Retrofitting Design and Techniques
1) Visual Assessment
Evaluation of workmanship
18
6
Seismic Retrofitting Design and Techniques
2) Technical Assessment
Based on the results from the visual assessment, the technical assessment was conducted.
In the technical assessment, some of the physical verification and partial/non-destructive
tests were carried out, and the technical assessment measures included:
Comparison of size and quality between design drawing and state of the structure in
site
Check with code provision, mainly size of main structural member and reinforcement
bar
18
7
Seismic Retrofitting Design and Techniques
3) Results
Retrofitting strategy was decided based on the results of technical assessment. Due to the
approach of open frame system (walls were not considered as lateral resisting elements),
the retrofitting design required that structural element sizes (beams and columns) to be
increased to provide larger load resistance capacity. Hence, the following design
approaches were proposed:
- Foundation
18
8
Seismic Retrofitting Design and Techniques
- Beams
18
9
Seismic Retrofitting Design and Techniques
19
0
Seismic Retrofitting Design and Techniques
- Column
19
1
Seismic Retrofitting Design and Techniques
19
2
Seismic Retrofitting Design and Techniques
19
3
Seismic Retrofitting Design and Techniques
d. Retrofitting Process
19
4
Seismic Retrofitting Design and Techniques
19
5
Seismic Retrofitting Design and Techniques
2.4 IMPLEMENTATION
19
6
Seismic Retrofitting Design and Techniques
200000
180000
160000
140000
120000
100000
80000
60000
40000
20000
0
Initial Cost Replacement Cost Retrofit Cost
19
7
Seismic Retrofitting Design and Techniques
2. EXAMPLE - 3 (ADOBE)
One of the six buildings in the school had some earthquake damage up to G3. It is a typical
school building of the area with CGI sheet roof supported on stone masonry walls. The large-
scale casualties among school children in Pakistani Kashmir clearly points to the need for
vulnerability reduction in these structures. In addition, the building system is no different from
the typical houses of the area, so the lessons learnt in this case are also relevant to houses. The
building has three rooms in a line with a verandah in front and a roof supported on wood posts.
The roof is of CGI sheets with timber under-structure. The entire building has an attic floor
which keeps the winter cold out. Similar to other buildings in the area the openings are large
with small piers in between on front wall.
19
8
Seismic Retrofitting Design and Techniques
19
9
Seismic Retrofitting Design and Techniques
20
0
Seismic Retrofitting Design and Techniques
20
1
Seismic Retrofitting Design and Techniques
Figure Bond elements yet to be Figure Grouting no-shrink grout in Figure Corner crack splicing with
completed in RR wall crack with hand pump WWM
20
2
Seismic Retrofitting Design and Techniques
Figure Preparing WWM with 6 mm rebars Figure Installing WW mesh from aroll
After Deciding the Alignment of the Seismic Belt Details were Evolved to Ensure its
Figure Inserting dowel for belt to belt connection at Figure Belt continuity at corner behind wood post
corner obstruction
Figure Installing ‘L’ shaped dowel at corner to Figure plying cement-sand plaster
ensure continuity
20
3
Seismic Retrofitting Design and Techniques
Figure Installing vertical reinforcement in the corner Figure Vertical reinforcement concreting formwork
Figure Installing bolts and brackets for roof- Figure Installing bolts and brackets for roof-
wall connection wall connection
Figure Retrofitted building with belts, roof anchoring and diagonal timber bracings
20
4
Seismic Retrofitting Design and Techniques
To his credit there are numerous technical/research paper, book, guideline and manuals. He has given
his voices to unheard issues pertinent to create resilient communities in various TV channels and News
paper.
Paper Publication
Book/ Guideline/Manual
20
5