Professional Documents
Culture Documents
Furthermore, the awaited SNI design can be completed satisfactorily with the title
“Earthquake Resistance Design Standard for Building Structures” , which is expected to
satisfy the challenge in building construction works, particularly concerning earthquake
resistance for building.
Finally, we would like to thank all parties who have helped in formulation of the Earthquake
Resistance Design Standard for Building Structures, particularly to the Authors led by Prof.
Dr. Ir. Wiratman Wangsadinata
SNI 03-1726-2002 i
TABLE OF CONTENTS
1 COVERAGE ........................................................................................................1
2 Reference ...........................................................................................................1
4 General requirements......................................................................................11
4.1 Design earthquake and building category..........................................................11
4.2 Regular and irregular building structure.............................................................12
4.3 Ductility of the building structure and nominal earthquake loading....................13
4.4 Factored load design and strength ....................................................................17
4.5 Capacity Design.................................................................................................17
4.6 Type of soil and propagation of earthquake wave .............................................17
4.7 Seismic zone and response spectrum ...............................................................19
4.8 Effect of vertical earthquake ..............................................................................24
SNI 03-1726-2002 ii
8 Building Structure Performance.....................................................................32
8.1 Service Limit Performance.................................................................................32
8.2 Ultimate Limit Performance................................................................................32
APPENDIX A: EXPLANATION
APPENDIX A:
B.1 Factored load and strength design for foundation.......................................61
B.2 Explanation of factored load and strength design for foundation..............62
SNI 03-1726-2002 iv
LIST OF TABLES
Figure 1 Indonesian Seismic zones with base rock peak acceleration with
a reoccurrence period of 500 years ................................................ 21
Figure 2 Design Earthquake Response Spectrum ........................................ 23
Figure P.1 Load-deflection diagram (V-δ) diagram of building structure .......... 42
Figure P.2 Distribution of the Bell-Shaped ln (Ru /Qu ) Component.................. 43
Figure P.3 Ideal collapsing mechanism of a building structure with plastic
joints formed on beam ends, column feet ....................................... 44
Figure P.4 Nominal level shear force diagram along the height of building ..... 54
Figure P.5 Moment – deflection diagram of a plastic joint at column feet or
shear wall feet................................................................................. 57
SNI 03-1726-2002 v
1 COVERAGE
1.1 This standard is intended as a replacement of Indonesian National Standard SNI-03-
1726-1989 to later become the minimum requirements of earthquake resistance design
for building structures, except for building structures defined in Article 1.2.
1.2 The design requirements of earthquake resistant building structures defined in this
standard do not apply for the following buildings:
- Building with uncommon structure system or buildings still requiring proving of their
worthiness.
- Buildings using base isolation system to absorb earthquake effect on the upper
structure.
- Civil Engineering Structures such as bridges, irrigation building, wall sand piers of
harbor, off-shore oil structure, and other non-buildings.
- One storey house and other non-technical buildings.
1.3 This standard has a purpose that the building structure which its earthquake resistance
is designed conforming to this standard can function:
- to prevent human casualties by the collapse of building because of a strong
earthquake;
- to reduce building damage due to light to medium earthquake, so the building is
repairable.
- to prevent tenant discomfort for building tenants during light to medium earthquakes;
- to maintain at all time vital services of building function.
2 Reference
This standard uses references of documents:
- SNI -03-1726-1989, “Earthquake Resistance Design Method for Houses and
Buildings”, the Office of the State Minister of Civil Works, The Directorate of
Technology Education, the Directorate General of Cipta Karya,No. 3 of 1997.
- National Earthquake Hazards Reduction Program (NEHERP) Recommended
Provisions for Seismic Regulation for New Buildings and Other Structures, 1997
Edition, Part 1 – Provisions, Part 2 – Commentary: FEMA 302, Feb. 1998
- Uniform Building Code (UBC), 1997 Edition, Volume 2, Structural Engineering
Design Provisions, International Conference of Building Officials, April 1997
3.1 Terms
Except for non conformity or there is no connection with those defined in this Standard,
the definitions apply in this standard are:
3.1.1.2
static push over analysis on a building structure
a 2 dimensional or 3 dimensional linier or non-linier static analysis method, where the effect
of Design Earthquake on the building structure is considered as static loads which catch at
each center of gravity of each floor, which values are increased slowly until exceeding the
loading capacity which first causes yield (plastic joint) in the building structure, and then
further load increase experiences large elasto-plastic shape change until reaching a
condition of about to collapse.
3.1.1.3
equivalent static earthquake load analysis on regular building structure
a 3 dimensional linier static analysis by reviewing equivalent earthquake static loads, related
to regular building structure properties which practically act as a 2 dimensional structure, so
its dynamic response is practically only determined by its first various response and can be
displayed as the result of equivalent static earthquake load.
3.1.1.4
equivalent static earthquake load analysis on irregular building structure
a 3 dimensional linier static analysis by reviewing equivalent earthquake static loads, which
have been described from distribution of dynamic maximum level shear force along the
height of the building received from a 3 dimensional linier elastic dynamic response analysis.
3.1.1.5
wave propagation analysis
an analysis to perform amplification of earthquake wave propagated from the base rock
depth to the soil surface, with data of soil above the base rock and input earthquake
movement on the base rock as the input data.
3.1.1.6
response spectrum order analysis
an analysis method to determine a 3 dimensional building structure dynamic response which
acts fully elastic on an earthquake effect through an analysis method known as the response
spectrum order analysis, where the total dynamic response of the building will result as a
superposition of maximum dynamic response of each order which will result through a
Design earthquake response spectrum.
3.1.1.7
linier time history dynamic response analysis
an analysis method to determine the history of dynamic response time of a 3 dimensional
building structure which acts fully elastic to ground movement due to the Design Earthquake
on nominal earthquake loading level as an input data, where the dynamic response in each
time interval is calculated using a direct integration method or can be through a order
analysis method.
3.1.2.2
nominal live load working on the building structure
load occurring due to occupation or usage of the building, by loads from people or moving
objects or machine and equipment and components which are not a fixed part of the building
which overall values are such as so the probability to exceed the value in a certain time
period is limited to a certain percentage. Generally, probability to exceed the load is in the
building life span of 50 years and is defined to be 10%. Nevertheless, designed live load
usually set in building structure loading standards can be considered as the nominal live
load.
3.1.2.3
nominal dead load
load from its own weight of all fixed building parts, including walls and partitions, columns,
beams, floor, roof, finishing, machines and equipment which are an inseparable parts of the
building which overall value is such so the probability to be exceeded in a certain life span is
limited on a particular percentage. Generally, the probability to exceed the load is in the
building life span of 50 years and is defined to be 10%. Nevertheless, designed dead load
usually set in building structure loading standards can be considered as the nominal dead
load.
3.1.3.2
ductility factor
ratio between the maximum deflection of the building structure when reaching the condition
of near collapsing and building structure deflection when the first yielding occurs on the
building structure.
3.1.3.3
fully ductile
a building structure ductility level, where the structure is capable of post elastic deflection
when reaching the condition of near the most severe collapse, which is by reaching a
ductility factor of 3.
3.1.3.4
partial ductility
all building structure ductility levels with intermediate ductility factors for fully elastic building
structure of 1.0 and for fully ductile building of 5.3.
3.1.4.2
Assembled reinforced concrete shear wall
a building structure subsystem which main function is to withstand shear load due to the
Design earthquake, consisting of two or more shear walls connected by connecting beams
which collapsing occurs with a certain ductility by the occurrence of plastic joints at both end
of the connecting beams and at the feet of all shear walls, where each yield moment can
experience almost all fully due to strain hardening. The ratio between breadth and height of
connecting beams may not exceed 4.
Ao Soil surface peak acceleration due to the Design Earthquake which depends on
Seismic zone and type of soil where the building structure is located.
b The largest horizontal magnitude of building structure map on the examined level,
measured perpendicular to earthquake loading direction, in subscript denotes the
lower structure.
dj Horizontal deflection of the ith floor from the results of 3 dimensional analysis of the
building structure due to equivalent static nominal earthquake load catching at the
center of gravity at storey floor levels.
Dn Nominal dead load which can be considered to be equal to the design dead load
set in building structure loading standard.
En Nominal earthquake load which value is defined by the probability to exceed the
load in a certain period, by the building ductility value µ it experiences and load
and material extra strength factor f1 included in the building structure.
f Total extra strength factor included in overall building structure, a ratio between
maximum earthquake load due to the Design Earthquake which can be absorbed
by the building structure when reaching the condition of near collapsing and
nominal earthquake load.
Fb Equivalent static nominal horizontal earthquake load due to own inertia force
catching at the center of gravity at the level of each basement floors of the building
basement structure.
Ln Nominal live load considered to be equal to designed live load defined in the
building structure loading standards.
Mgm Maximum rolling moment of the upper structure of a building working on the lower
structure at lateral clamping level when the upper structure is at the condition of
near collapsing due to implementation of total extra strength factor f contained in
the upper structure or due to final yield moment effect on plastic joints at the feet
of all columns and all shear walls.
My Initial yield moment of plastic joints occurring at the ends of building structure
components, column feet, and shear wall feet when the structure, due to the effect
of Design Earthquake, experiences the first yielding.
My,d Initial yield moment of plastic joint occurring on shear wall feet.
n Floor number of the top level (top floor), total floors of the building structure, in a a
subscript denotes nominal value.
N Result value of Standard Penetration Test on a soil layer; normal force in general
N Weighted average value of the Standard Penetration Test of soil layers above the
base rock with soil layer thickness as the weight value.
R Earthquake reduction factor, a ratio between maximum earthquake load due to the
Design Earthquake on the fully elastic building structure and nominal earthquake
load due to the effect of Design Earthquake on ductile building structure,
depending on ductility factor of the building structure; an irregular building
structure representative earthquake reduction factor.
Su Weighted average non flowing shear strength with soil layers as the weight value.
T Building structure natural frequency period stated in seconds which determines the
magnitude of Earthquake Response Factor of the building structure which curve is
displayed in the Design Earthquake Response Spectrum.
Tc Corner natural frequency period, which is the natural frequency period at the
changing point of diagram C from the flat line to hyperbolic curve at the Design
Earthquake Response Spectrum.
vs Weighted average propagation speed of shear waves with soil layer thickness as
the weight value.
V Equivalent static nominal basic shear load (force) due to the effect of Design
Earthquake working at the base level of regular building structure with general
ductility level, calculated based on fundamental natural frequency period of the
regular building structure.
Vn Effect of Design Earthquake at nominal loading level for building structure with
general ductility level; effect of Design Earthquake when the first yielding occurs
inside the structure which has been reduced with load and material extra strength
factor f1.
Vs Nominal basic shear force due to earthquake load working on a particular building
structure subsystem at the base level.
Vxo Nominal basic shear force due to the effect of Design Earthquake at nominal
loading level working at x-axis direction a the ground level of an irregular building
structure.
Vyo Nominal basic shear force due to the effect of Design Earthquake at nominal
loading level working at y-axis direction at the ground level of an irregular building
structure.
wn Nominal basic shear load working at the base level of irregular building
structure wit general ductility level, calculated based natural frequency period
of the building structure.
Wi Weight of the ith floor level of the upper structure of a building, including
corresponding live load.
zi Elevation of the ith floor of a building structure from lateral clamping level.
δy (delta – m) Deflection of the building structure by the effect of Design Earthquake when
the first yielding occurs.
ζ (zeta) Multiplying coefficient of total floors of the building structure limiting the
fundamental natural frequency of the building structure, according to Seismic
zone.
4 General requirements
4.1.2 For various building categories, depending on the probability of building structure
collapsing for the life of the and expected age of the building, the effect of Design
Earthquake on it must be multiplied with an significance factor I with the equation of:
Where I1 is the Significance Factor to adjust the reoccurrence period of the earthquake
related to probability adjustment of the earthquake occurrence for the life of the building,
while I2 is the Significance Factor to adjust earthquake reoccurrence period related to the
building age adjustment. The significance factors I1, I2, and I are defined according to
Table 1.
Significance factor
Building category
I1 I2 I3
General building, such as for residential, trade, and
1.0 1.0 1.0
office
Monument and monumental buildings 1.0 1.6 1.6
Post earthquake important buildings such as
hospital, clean water installation, power plant,
1.4 1.0 1.4
emergency rescue center, radio and television
facilities
Buildings for storing dangerous goods such as gas,
1.6 1.0 1.6
oil products, acid, toxic materials.
Chimneys, towered tanks 1.5 1.0 1.5
Note:
For all building structures which usage permit is issued prior to effectuation of this Standard,
the Significance Factor I can be multiplied by 80%.
- Height of the building structure measured from lateral clamping level may not be
more than 10 stories or 40 m.
- The building structure map does not show any corner notch, if there is a notch, the
length of the side of the notch does not exceed 15% of the largest size of the
building structure in the notch side direction.
- The building structure system does not show a leap of the front plane, if a leap of the
front plane, size of the structure map of the building protruding at each direction is
no less than 75% of the largest size of structure map of the lower building part. In
this case, roof house structure which is less than 2-storey tall is not necessarily
considered to cause front plane leap.
- The building structure system has regular lateral rigidity, without any soft level. Soft
level is a level, where its lateral rigidity is less than 70% of lateral rigidity of the levels
above or less than 80% of average lateral rigidity of 3 levels above. In this case,
lateral rigidity of a level is the shear force which if working at that level, will cause
one unit of inter-level deflection.
- The building structure system has regular floor weight, which means that each floor
has a weight of no more than 150% of floor weight of the floor above or below it.
Weight of roof or roof house does not need to satisfy this term.
- The building structure system has vertical components of continuous lateral load
support system, without shift of its center of gravity, except if the shift does not
exceed more than half the component size in the shift direction.
- The building structure system has continuous storey floors, without hole or opening
which area is 50% of all storey floors. If there is any level floor with such hole or
opening, the amount may not exceed 20% of total level floors.
For regular building structure, the effect of Design Earthquake can be examined as the effect
of equivalent static earthquake load, so according to this standard, its analysis can be done
based on equivalent static analysis.
4.2.2 Building structure which does not satisfy the terms according to Article 4.2.1, is
defined as an irregular building structure. For an irregular building structure, the effect of
Design Earthquake must be examined as a dynamic earthquake loading, so its analysis must
be done based on dynamic response analysis.
In equation (2), µ = 1.0, a ductility factor value for building structure acting fully elastic, while
µu is the maximum ductility factor value applicable by the respective building structure
system according to Article 4.3.4.
4.3.3 If Vn is the nominal earthquake loading due to effect of Design Earthquake which
must be examined in building structure design, the following relation applies:
Vy Vc
Vn = = (4)
f1 R
where f1 is the load and material extra strength factor included in the building
structure which value is defined as:
f1 = 1.6 (5)
In the equation (6), R = 1.6 is the earthquake reduction factor for fully elastic building
structure, while Rm is maximum earthquake reduction factor the respective structure
system can apply according to Article 4.3.4.
Table 2 shows the R values of various µ related values, with terms that the µ and R
values cannot exceed their maximum values conforming to Article 4.3.4.
Building structure µ R
performance level
Fully elastic 1.0 1.6
1.5 2.4
2.0 3.2
2.5 4.0
3.0 4.8
Partially elastic
3.5 5.6
4.0 6.4
4.5 7.2
5.0 8.0
Fully ductile 5.3 8.5
4.3.4 The building structure ductility factor µ in the building structure can be selected
according to needs, but may not be taken more than the maximum ductility factor
applicable by each building structure system or subsystem. Table 3 define µm
applicable by several building structure system and subsystem types, along the
corresponding maximum reduction Rm.
4.3.5 If in the direction of earthquake loading due to effect of Design Earthquake the
building structure consists of several different building structure subsystems, the
representative earthquake reduction factor of the building structure for the
earthquake loading can be calculated as a weighted average value with shear force
held by several subsystem types as the weight magnitude according to the equation:
R=
∑ Vs (7)
∑ Vs / Rs
Where Rs is the earthquake response factor of each building structure subsystem
and Vs is the basic shear force supported by each of the building structure
subsystem, with summing covering all existing building structure subsystem types.
This method can only be used if the ratio between earthquake response factors of
existing building structure subsystems does not exceed 1.5.
4.3.6 For building structure subsystem types not written in Table 3, its earthquake
response factor and ductility factor vales must be defined by rational method, for
example by defining them from static push over analysis).
Ru = φ Rn (8)
Qu = γ Qn (9)
Ru ≥ Qu (10)
4.4.2 By stating nominal dead load as Dn, nominal live load as Ln, and nominal
earthquake load as En, the Factored Load and Strength must be done by
examining the ultimate loading at the building structure as follows:
Qu = γD Dn + γL Ln (11)
Qu = γD Dn + γL Ln + γE En (12)
where γD, γL, and γE are load factors of nominal dead load, nominal live load, and
nominal earthquake load, which values are defined in the building structure loading
or in applicable concrete or steel standards.
4.4.3 Nominal dead load and nominal live load stated in Article 4.4.2 are loads which
values are such as, so probability of existence of heavier loads in the life span of
the building are limited to a particular percentage. Nevertheless, designed dead
load and designed live load defined in the building structure loading standard can
be considered as nominal loads.
4.6.2 Base rock is the rock layer below the soil surface that have the lowest N Standard
Penetration Test result of 60 and there is no other rock layer below it that has a
lower Standard Penetration Test value, or has a shear wave propagation speed vs
reaching 750 m/s or there is no other rock layer underneath which as a shear wave
propagation speed of less than that.
4.6.3 Soil types are determined as Hard Soil, Medium Soil, and Soft Soil, if for the
uppermost layer at a maximum thickness of 30 m the requirements in table 4 are
satisfied:
In table 4, v s ,N,andSu are weighted average values of the components with soil layer
thickness as the weight that must be calculated according to the following equations:
m
∑ ti
i=1
vs = m
(13)
∑ t j / v si
i=1
m
∑ ti
i=1
N= m
(14)
∑ t j / Ni
i=1
where ti is the ith soil layer, vsi is the shear wave propagation speed through the ith
soil layer, Ni is the standard penetration test result of the ith soil layer, Sui is the non
flowing shear strength of the ith soil lauer and m is total number of soil layers above
the base rock. Furthermore, in Table 4, PI is the plasticity index of clay, wn in the
soil natural water content and Su is the examined soil layer non flowing shear
strength,
4.4.4 Special Soil mentioned in Table 4 is types of soil that do not satisfy the
requirements written in the table. Besides, special soil also includes soil with high
liquification potential, very sensitive clay, fragile low cemented sand, turf, soil with
high organic content with thickness of more than 3 m, clay with 35 kPa <Su< 50
kPa with thickness of more than 30m. For special type soil, peak soil surface
acceleration must be determined from the analysis result of earthquake wave
propagation according to Article 4.6.1.
4.7.1 Indonesia is divided to 6 Seismic zone as shown in Figure 1, where Seismic zone 1
is the area with the lowest earthquake level, and Seismic zone 6 has the highest
earthquake level. This Seismic zone distribution is based on peak acceleration of the
base rock due to effect of Design Earthquake with a reoccurrence period of 500
years, which average values for each Seismic zone is defined in Figure 1 and Table
5.
4.7.2 If the soil surface peak acceleration A0 cannot be achieved from the wave
propagation analysis as mentioned in Article 4.6.1, the soil surface peak acceleration
or each Seismic zone and for each soil type is defined in Table 5.
4.7.4 To determine the effect of Design Earthquake on the building structure, which is the
equivalent static nominal basic shear load at a regular structure according to Article
6.1.2, nominal basic shear force as a dynamic response of the first order at irregular
building structure according to Article 7.1.3 and basic nominal shear force as a
dynamic response for all varieties participating on irregular building structure
according to Article 7.2.1, for each Seismic zone C-T Design Earthquake Response
Spectrum is defined as shown in Figure 2. In the figure, C is the Earthquake
Response Factor stated in gravity acceleration and T is the natural frequency period
of the building structure stated in seconds. For T = 0, the C equals A0, where A0 is
the peak acceleration of soil surface according to Table 5.
Am = 2.5 Ao (16)
and corner natural frequency period Tc of 0.5 second, 0.6 second, and 1.0 second for
hard, medium, and soft soil types respectively, then by considering Article 4.74 and
Article 4.7.5, the Earthquake Response Factor C is defined by the following equation:
- for T ≤ Tc
C = Am (17)
- for T >Tc
Ar
C= (18)
T
with
Ar = Am Tc (19)
In table 6, the values of Am and Ar are written for each Seismic zone and soil type.
(Soft soil)
(Medium soil)
(Soft soil)
(Hard soil)
(Medium soil)
(Hard soil)
(Hard soil)
(Hard soil)
4.8.1 Building structures that have high sensitivity to gravitational load sauce as balcony,
canopy, and long span cantilever beam, transfer beam at high raise building
structure supporting gravitational load from two or more levels above it and long span
pre-stressed concrete beam must be calculated against vertical movement of soils
surface due to effect of Design Earthquake, in form of equivalent static nominal
vertical earthquake load to be examined whether it works upward or downward which
value must be calculated as a multiplication C vertical Earthquake Response Factor ,
and gravitational load, including the corresponding live load.
4.8.2 The C1 vertical earthquake response factor mentioned in Article 4.8.1 must be
calculated by the equation:
Cv = ψ A0 I (20)
where the ψ coefficient depends on the Seismic zone where the building structure is
located and defined according to Table 7, and A0 is the peak acceleration of soil
surface according to Table 5, while I is the building Significance Factor according to
Table 1.
5.1.2 If soil-structure interaction analysis is not done, the upper structure and lower
structure of a building structure can be analyzed against the effect of Design
Earthquake separately, where the upper structure can be assumed to be laterally
clamped on base ground level. Furthermore, the lower structure can be considered
as a separate structure underground loaded by combination of earthquake loads
from the upper structure, the earthquake load from its own inertial force and
earthquake load from its surrounding soil.
5.1.2 On buildings without basement, clamping level of the upper structure can be
assumed to occur on the direct foundation footing, assembly foundation footing plane
and the upper plane of pile foundation heads,
5.1.5 In designing the upper structure or lower structure of a building on the effect of
Design Earthquake, the lower structure may not fail before the upper structure. For
this, on the effect of Design Earthquake , the lower structure must act fully elastic,
not depending of ductility level the upper structure has.
5.2.2 Ignoring the bearing of effect of Design Earthquake by one or more columns or
building structure subsystem mentioned in Article 5.2.1 is only allowed if bearing
participation of the earthquake effect is less than 10%. In this case, the component or
subsystem, other than to gravitational load, must also be designed against deflection
of building structure system due to effect of Design Earthquake on a fully elastic
building structure, which is against deflection of R/1.6 of deflection caused by
nominal earthquake load on the building structure, where R is the earthquake
reduction factor of the building structure and 1.6 is the earthquake reduction factor
for fully elastic structure (R=f1).
5.2.3 In a structure system consisting of combination of shear walls and open frames,
nominal basic shear load due to effect of Design Earthquake working on open frames
may not be less than 25% of total nominal shear load working in the direction of the
earthquake load.
5.3.2 Storey floors, concrete roof and floor system which are not rigid in their planes,
because they contain hole or opening which area is more than 50% of all storey floor
areas, will experience a deformation in their planes due to horizontal earthquake
load, which must be calculated for effect on the horizontal earthquake load
distribution at all existing storey structure system.
5.4 Eccentricity of center of gravity against the rotation center of storey floor.
5.4.1 The center of gravity of storey floor of a building structure is the resultant point of
dead load, including corresponding live load working at that floor. On the building
structure design, the center of gravity is the resultant point of equivalent static load or
dynamic earthquake force.
5.4.3 Between the center of gravity and the center of rotation, a designed eccentricity ed
must be examined. If the largest horizontal size of the building structure a the storey
floor, measured perpendicular to earthquake loading direction, is stated as b, the
designed eccentricity ed must be determined as follows:
- for 0 < e ≤ 0.3 b:
ed = 1.5 e + 0.05 b (21)
or
ed = e – 0.05 b (22)
and selected between both which effect is the most determining for the examined
building structure component or subsystem:
- for e > 0.3 b:
ed = 1.33 e + 0. 1 b (23)
or
ed = 1.17 e – 0.1 b (24)
and selected between both which effect is the most determining for the examined
building structure component or subsystem.
5.4.4 In designing a building structure against the effect of Design Earthquake, designed
eccentricity ed between the center of gravity and the center of rotation at the storey
floor according to Article 5.4.3 must be examined both in 3 dimensional static
analysis and dynamic analysis.
T 1<ζ n (25)
Seismic zone ζ
1 0.20
2 0.19
3 0.18
4 0.17
5 0.16
6 0.15
5.8.2 To simulate the direction of any effect of Design Earthquake on the building
structure, the effect of earthquake loading in the main direction defined by Article
5.8.1 must be assumed to be 100% effective and must be assumed to occur
simultaneously with the effect of earthquake loading in the perpendicular direction on
the main direction of the loading, but only with 30% effectiveness.
6.1.2 If a building category has a Significance Factor of 1 according to Table 1 and its
structure for a main axis of the structure map and loading direction of Design
Earthquake has a earthquake reduction factor R and fundamental natural frequency
period T1, the equivalent static nominal basic shear load V occurring at the base level
can be calculated according to the equation:
C1I
V= W1 (26)
R
where C1 is the Earthquake Response Factor received from the Design Earthquake
Response Spectrum according to Figure 2 for fundamental natural frequency period
T1, while W1 is the building total weight, including the corresponding live load.
6.1.3 Nominal basic shear load V according to Article 6.1.2 must be distributed along the
height of the building structure to be equivalent static nominal earthquake loads Fi
working at the center of gravity at the ith level according to equation:
Wi zi
Fi = n
(27)
∑ Wizi
i=1
where Wi is the floor weight of the ith floor including corresponding live load, zi is the
floor height of the ith floor measured from lateral clamping level according to Article
5.1.2 and Article 5.1.3, while n is the number of the topmost level floor.
6.1.4 If the ration between the height of the building structure and its map size in the
earthquake loading direction equals or exceeding 3, then 0.1 V must be considered
as a horizontal loads centralized at the center of gravity of the uppermost level, while
the remaining 0.9 V must be distributed along the height of the building structure to
be equivalent static nominal earthquake load according to Article 6.1.3.
6.1.5 On the tank above the tower, equivalent static nominal earthquake load V must be
considered to work at the center of gravity of all building structure and tank and its
contents.
where Wi and Fi have the same meaning as mentioned in Article 6.1.3, di is the
horizontal deflection of the ith floor stated in mm and ‘g’ is the gravitational
acceleration defined to be 9810 mm/sec2.
6.2.2 If the fundamental natural frequency period T1 of building structure for determination
of the Earthquake Response Factor C1 according to Article 6.1.2, defined using
empirical formulas or from a 3 dimensional free vibration analysis result, the values
cannot differ more than 20% of calculated values according to Article 6.2.1.
Where Rx and Vxo is the earthquake response factor and basic shear force for
earthquake loading in x direction ,while Rx and Vyo is the earthquake response factor
and basic shear load for earthquake loading in y direction. This method can only be
used if the ratio between earthquake response factor values for the 2 earthquake
loading directions do not exceed 1.5.
V ≥ 0.8 V1 (30)
where V1 is the nominal basic shear force as the first order response on due to effect
of Design Earthquake according to equation:
C1I
V1 = Wt (31)
R
with C1 is the Earthquake Response Factor resulting from the Design Earthquake
Response Spectrum according to Figure 2 for the first natural frequency period T1, I
is the Significance Factor according to Table 1, and R is the representative
earthquake reduction factor of the respective building structure, while W1 is total
weight of the building including corresponding live load.
7.2.2 Summing of order responses mentioned in Article 7.2.1 for irregular building structure
which has adjacent natural frequency periods, must be done using a method known
as the Complete Quadratic Combination (CQC). The natural frequency period must
be considered adjacent, if their difference is less than 15%. For irregular building
structure which has a significantly different natural frequency periods, summing of
the order responses can be done using a method called Square Root of the Sum of
Squares (SRSS).
7.2.3 To satisfy the requirements conforming to Article 7.1.3, the value nominal level shear
force due to effect of Design Earthquake along the height of the building structure
from the analysis of response spectrum in an particular direction, must be calculated
with a Scale Factor:
0.8V1
Scale Factor = ≥1 (32)
V1
where V1 is the nominal basic shear load as the first order dynamic response only
and Vt is the nominal basic shear force from the performed response spectrum order
analysis result.
7.3.1 If required, calculation of irregular building structure dynamic response on the effect
of Design Earthquake, can be done using a 3 dimensional dynamic analysis method
in form of time history linier and non-linier dynamic response with an earthquake
accelerogram quantified as the movement of input soil.
7.3.2 For designing a building structure through the time history linier dynamic analysis to
the effect of Design Earthquake on nominal earthquake level, the original soil surface
acceleration from the input earthquake must be scaled to the nominal earthquake
loading level, so its peak acceleration value A becomes:
A oI
A= (33)
R
7.3.3 To study the post-elastic properties of the building structure on effect of Design
Earthquake, a time history non-linier dynamic response analysis must be done,
where the original soil surface acceleration of the input earthquake must be scaled,
thus its peak acceleration value will equal AoI, where Ao is the peak acceleration of
soil surface according to Table 5 and I is the Significance Factor according to
Table 1.
7.3.4 Input earthquake accelerogram examined in the time history linier and non-linier
dynamic response analysis, must be taken from the soil movement record caused by
the earthquake received at a location with similar geological, topographical, and
seismotectonic condition with the location where the examined building is located. To
reduce the uncertainty about this location, at least 4 accelerograms of 4 different
earthquakes must be examined, one of which must be an accelerogram of the El
Centro N0S Earthquake recorded at May 15, 1940 in California.
8.1.2 To satisfy the requirements of building structure service limit performance, in all
aspects, inter-level deflection calculated from the building structure deflection
according to Article 8.1.1 may note exceed 0.03 of height of the respective level or 30
R
mm, whichever is lower.
8.2.1 The ultimate limit performance of the building structure is determined by the
deflection and maximum inter-level deflection of the building structure due to effect of
Design Earthquake when the building structure is near collapsing, to limit the
occurrence possibility of building structure collapsing which can cause human
casualties and to prevent dangerous collisions between buildings or between
earthquake load parts separated by separation space (dilatation clearance).
Conforming to Article 4.3.3., these deflection and inter-level deflection must be
calculated from the building structure deflection because of the effect of nominal
earthquake, multiplied by a factor ξ as follows:
- for regular building structure:
ξ = 0.7 R (34)
where R is the building structure earthquake reduction factor and the Scale Factor is
as defined in Article 7.2.3.
8.2.2 To satisfy the building structure ultimate limit performance requirements, in all
conditions, the inter-level deflection calculated from the building structure deflection
according to Article 8.2.1 may not exceed 0.02 of the respective storey height.
8.2.3 The separation distance between building must be determined at last equal to total
maximum deflection of each building structure at that level calculated using the
method in Article 8.2.1. In all conditions, each of the distances may not be les than
0.025 of height of that level measured from the lateral clamping level.
8.2.5 The separation clearance as mentioned in Article 8.24 must be designed in details
and performed in such a way, so it is always free from debris or obstructive objects.
Width of the separation clearance must satisfy all execution tolerance.
structure
R f f
performance µ
equation (6) (equation (37) (equation 39)
level
Fully elastic 1.0 1.6 1.00 1.6
Partially elastic 1.5 2.4 1.09 1.7
2.0 3.2 1.17 1.9
2.5 4.0 1.26 2.0
3.0 4.8 1.35 2.2
3.5 5.6 1.44 2.3
4.0 6.4 1.51 2.4
4.5 7.2 1.61 2.6
5.0 8.0 1.70 2.7
Fully ductile 5.3 8.5 1.75 2.8
9.1.2 With the equivalent static nominal earthquake load Fi on a building structure acting
on the ith storey floor center of gravity and at the elevation zi measured from lateral
clamping level according to Article 5.1.2 and Article 5.1.3, the maximum nominal
rolling moment loading from the upper structure on the lower structure acting fully
elastic conforming to Article 9.1.1 must be calculated according to equation:
n n
Mgm = f ∑ F1zi =f2 ∑ F1zi = (40)
i=1 i=1
In equation (40), R is the earthquake reduction factor for fully elastic structure (R=f1)
and n is the floor number of the highest level. This maximum nominal rolling moment
works on the lower structure along the corresponding normal load (vertical) and
shear load (horizontal).
9.1.3 Considering that on the upper structure of the building which due to effect of Design
Earthquake is in the condition of near collapsing a possibility of occurrence of plastic
joints at all column feet and all feet of the shear walls exists, the rolling moment
worked by the final yield moment of all the plastic joints must be examined as a
rolling moment loading possibility of the upper structure on the lower structure. In this
case, if My,k is the plastic joint initial yield moment on shear wall feet, each is
calculated for the respective normal force, where its interaction diagram N-M to
calculate yield moment of each is calculated based on cross section dimension and
strength of installed material, maximum nominal rolling moment loading of the upper
structure on the lower structure must be calculated using equation:
1 ⎛ ⎞
Mgm = ⎜ ∑ My,k + ∑ My,d ⎟ (41)
1.6 ⎝ column wall ⎠
In equation (41), 1.6 is the extra strength factor of load and material f1and summing
must be done covering all columns and all shear walls existing on the building upper
structure. Maximum nominal rolling moment according to equation (41) working on
the lower structure along the respective normal load (vertical) and shear load
(horizontal).
Ini equation (42), R is the earthquake reduction factor of the respective upper
structure and 1.6 is the earthquake response factor for fully elastic structure (R=f1).
9.1.5 Considering that the upper structure of a building in real situation due to the effect of
soil-structure interaction is not fully clamped on the lateral clamping level, it is
intended that this imperfect clamping effect can be calculated rationally, which
depends on soil type and existence of basement.
9.2.2 If the equivalent static nominal horizontal earthquake load due to own inertia Fb
working on the center of gravity of basement floor and lower structure acting fully
elastic cannot be determined using a more rational method, according to Article
9.2.1, it can be calculated from equation:
Fb = 0.10 Ao I Wb (43)
where Ao is the peak acceleration of soil surface due to effect of Design Earthquake
according to Table 5, I is the Significance Factor of the respective building according
to Table 1, and Wb is the weight of the basement floor, including corresponding live
load.
10.1.2 Objects stored in a museum and similar objects with high history or cultural values,
which are not structural components, must be tied and secured against the effect of
Design Earthquake. For details of the tie down, an advice from an expert is required.
10.2.2 Tie down components, including anchor bolts, must be rustproof, have sufficient
ductility and tie down power. In case of pre-cast concrete panels, their anchors must
be welded or tied to panel reinforcements.
10.5.3 The performance factor component P reflects the significance level of the component
or installation in its performance during or after the earthquake occurs. If not defined
using a more rational method, the performance factor component P is determined in
Table 10 and Table 11.
2. Ornaments pre-cast concrete panel and building external cover, along their 8
tie down equipment.
3
3. Ceiling system hung on the building structure with coverage plate which
weight exceeding 20 N per piece;
- over an important room (surgery room in a hospital), exit corridors and 2
public places or at places requiring a particular resistance against fire;
- over working areas and common residences:
4. Room equipment at the exit corridors or any equipment which will pose risk of
affected by an earthquake.
5. Clean water tank and chimneys integrated with building with weight not 2.5
exceeding 10% of the building weight.
6. Roof house structure or machine room on top of building. 2.5
A.1 Coverage
A.1.1 With this effectuation of this Standard, this article stresses on the cancellation of the
old standard, SNI 03-1726-1989. This is important, because according to this
standard, the Design Earthquake has a reoccurrence period of 500 years, while the
old standards states it as 200 years. It is known that if an earthquake reoccurrence
gets longer, its effect on a building structure gets worse. Furthermore, in this
standard, a new definition is given about types of soil which differs with those in the
old standard. Thus, it is clear that the old standard cannot be used any longer.
Nevertheless, earthquake resistance of an existing building structure designed using
the old standard generally still applies. Several reasons will confirm this. First, the
earthquake reduction factor R according to the old standard is relatively lower than
the value in this standard. For example, for fully ductility structure, in the old
standard, R = 6, while in this Standard, R = 8.5, so the earthquake loads to consider
in the old and new standard do not differ much. Both, with new soil type definition,
many soil types which according to the old standard is considered as Soft Soil, in this
standard are categorized into Medium Soil, so the calculated earthquake load will
approach each other more. Third, existing buildings have run part of their ages, so
with the same risk of occurrence of building structure collapse in their remaining age,
the earthquake load to consider will be relatively lower than it is in this Standard for
new buildings.
A.1.2 This article states that this Standard does not apply for buildings mentioned in the
article. Nevertheless, main principles defined in this Standard also apply for the
buildings, as long as their ductility values and other specific properties are adjusted.
Evidently, definition of soil types, Indonesian seismic zone map and response
spectrum apply for both.
A.1.3 This article in short explains the philosophy of earthquake resistance design of a
building structure, which is because of a strong earthquake, a structure will
experience severe damage, but because it did not collapse, human casualties can be
prevented, while in light earthquake, the occupancy comfort is still guaranteed,
occurring damage is repairable and building function vital services can still run.
A.3.2 Notation
In this article, all important notations used in this standard is explained, so through
this article, the users of this Standard can easily find the meaning of a notation,
without finding the article that firstly include the notation.
A.4.1.2 This article adjusts the earthquake reoccurrence period which cause the buildings
to reach the condition of near collapsing with building category. Because multi
storey buildings, monuments and monumental areas have common functions,
without any specialty, particularity or other significance in usage, the probability of
occurrence of the earthquake in the life span of the building is defined as 10%, so
I1=1.0 applies. But building life span differs. Buildings up to 10 floors high, due to
various reasons and intentions generally have a life of less than 50 years, so I2 < 1
because the earthquake reoccurrence period is less than 500 years. Buildings
over 30 floors high, monument and monumental buildings have a long service life,
even must be preserved for the future generation, so I2 > I1 because the
earthquake reoccurrence period is more than 500 years. Post earthquake
important buildings (hospital, clean water installation, power plant, emergency
rescue center and radio and television facilities), building posing high risk to the
environment if damaged by an earthquake (storage for dangerous materials) or
endangering nearby buildings if it collapses because of an earthquake (chimney,
tank above a tower), have a similar usability age with general function buildings,
which is about 50 years, so I2 = 1.0. But the probability of occurrence of the
earthquake during the life span of the building must be differentiated and all must
be less than 10%, so I1>I because the earthquake reoccurrence period is more
than 500 years. The combination of I1 and I2 for several building categories is
defined in Table 1, including its I multiplication.
A.4.2.2 If a building structure does not satisfy the terms defined in Article 4.2.1, we are
dealing with an irregular building. For irregular building structure, the effect of
earthquake on the building must be analyzed dynamically. By implementing a
Order Analysis method, the response on dynamic earthquake is a superposition of
dynamic response of participating orders.
A.4.3.2 Assumptions adopted in this article, is that ductility building structure and fully
elastic building structure due to effect of Design Earthquake shows equal maximum
deflection δm in the condition of near collapsing (constant maximum displacement
rule), usually adopted in earthquake resistance design standards for building
structure, to get a simple correlation between Vy and Vc through µ. This assumption
is conservative, because in real condition, ductility building structure has a
relatively larger δm than elastic building structure, so it has a relatively larger µ than
the one assumed. The adopted assumption is visualized in the load-deflection
diagram (V-δ diagram) shown in Figure P.1.
ductile
4.3.3 In this article, nominal earthquake loading Vn is defined due to effect of Design
Earthquake that must be examined in building structure design. The Vn value is
certainly will be lower than Vy in such so the environment Vy/Vn ratio represents
extra strength factor and load and material f1 contained in a building structure. This
extra strength factor is formed by the installed strength of structure components to
plan through the Factored Load and Strength Design. Theoretically, the minimum
value of f1 is the multiplication of load factor and material factor used in the
Factored Load and Strength Design, which is f1 = 1.05 x 1.15 = 1.2. In this case,
the material factor is the reciprocal of capacity reduction factor (= 1/φ). In reality,
there is always excessive structure component strength, because total installed
reinforcements or profiles is more than necessary, so in general, f1 > 1.2. For
building structure in general, according to several researches, the actual
representative f1 value is about. Meanwhile, the earthquake response factor value
R changes following the change of µ value conforming equation (6). Table 2 shows
the R values for various µ values. Visually, the correlation among Vc, Vc, Vy, Vn, µ
and R is shown in Figure P.1.
Equation (4) is the basic equation to determine nominal earthquake loading at the
building structure. If Vy is known, for example by calculation of cross section
capacity of installed components or from static push load analysis of overall
structure, then Vn = Vy/f1. If Vc is known, for example from analytical calculation
through response spectrum dynamic response analysis, then Vn = Vc /R. For the
later, µ is certainly must be known first (see A.4.3.6).
A.4.3.4 This article defines Table 3 that contains the maximum ductility factor values µm
which can be given by several building structure system or subsystem types from
the results of various researches, along the respective Rm values. For each system
or subsystem written in Table 3, we can certainly select a µ value which is lower
than its µm value. A lower selected µ values shows a higher earthquake load to be
absorbed by the building structure, but the required detailing will be simpler in
correlation between components of the structure.
A.4.3.6 For uncommon structure system types, which generally have unknown µ value, the
value must be found first using rational methods, for instance through a static push
load analysis. From this analysis, δy and δm can be found, so µ can be calculated.
Furthermore, from the analysis, Vy is also known, so Vn can be calculated by
dividing it by f1.
Frequency distribution
Probability of
exceeding
A.4.4.3 Not many researches have been done about nominal value of dead load and live
load, because to get an accurate distribution system, the research will require a
long time (for the life of the building) to get an accurate distribution curve. Thus, as
long as the nominal values of both types of load are not yet available, their values
defined as the design load value in various loading standards can be used. In
European literature, nominal load is called characteristic load.
plastic joint
column
shear wall
beam
plastic joint
plastic joint
A.4.6.3 This article gives a definition of types of Hard Soil, Medium Soil, and Soft Soil
based on three criteria: the shear wave propagation speed vs, the result value of
the Standard Penetration Test N and non flowing shear strength Su. To determine
type of soil encountered, at least 2 of the 3 criteria must be available, where the
criterion that produces the softer soil is the determining one. If all 3 criteria are
available, the type of soil encountered must be supported by at least 2 criteria.
From various researches, it is apparent that only the 30 m uppermost layer will
decide the amplification of soil movement on the soil surface. Thus, the weighted
average value of the 3 criteria must be calculated until reaching the depth of 30 m
only. This determination of depth limit is also important to standardize the
calculation of average value according to equation (13), (14), and (15), considering
that more depth will result in higher average value.
A.4.6.4 This article gives a clue about which soil types are included in Special Soil.
Because the properties of these soil types cannot be formulated in general, all their
properties must be evaluated specifically at each location where the soil is found.
This article stresses that at each Special Soil, earthquake movement at the soil
surface must be determined from the analysis result of earthquake wave
propagation. In the this earthquake wave propagation analysis, earthquake
accelerograms must be taken from vibration record caused by existing earthquake
or from a location with geological, topographical and seimotonic conditions similar
to location where the examined special soil is found. Considering that soil
movement due to earthquake at a location cannot be predicted precisely, as an
input earthquake, simulated earthquake vibration can be used. Determining
parameters in this simulated earthquake vibration among else are predominant
vibration period, response spectrum configuration, vibration time period, and its
earthquake intensity.
A.4.7.2 Average base rock accelerations for Seismic zone 1 to 6, after determination are
respectively 0.03 g, 0.10 g, 0.15 g. 0.20 g, 0.25 g, and 0.30 g. With this base rock
acceleration, the soil surface peak acceleration (Ao) is determined for Hard Soil,
Medium Soil, and Soft Soil, are determined according to Table 5, one and another
as a result of comparative study with foreign standards, among else are the
National Earthquake Hazards Reduction Program of 1997 (NEHRP 1997) and
Uniform Building Code of 1997 (UBC 1997). For instance, if we examine the
NEHRP 1997, base rock is about equivalent to S1, while Hard Soil, Medium Soil,
and Soft Soil is about equivalent to S2, S3, and S4 respectively.
A.4.7.5 From various investigations, it is apparent that for 0 ≤ T ≤ 0.2 second, there are
various uncertainties, both in the soil movement characteristic itself or in ductility
properties of the respective Single Freedom Degree system. Thus, for 0 ≤ T ≤0.2
second, it is defined the C must be taken equal to Am. Thus, for T ≤ Tc, the
response spectrum correlates with the maximum response acceleration which has
a fixed value, while T >Tc correlates with mc response speed which has a fixed
value.
A.4.7.6 Various investigation results show that Am ranges between 2 A0 and 3 Ao, so Am =
2.5 A0 is an average value considered suitable for design. Then, from various
investigation result, it is also apparent that as a good approach, for Hard Soil,
Medium Soil, and Soft Soil types, the corner natural frequency period Tc can be
taken 0.5 second, 0.6 second, and 1.0 second respectively.
A.4.8.2 It can be understood that the vertical component of soil movement due to the effect
of the earthquake will relatively gets bigger if the examined location is closer to the
epicenter. In this article, soil movement vertical acceleration is defined as a
multiplication of a coefficient ψ with soil surface peak acceleration Ao. As the
seismic of an area gets higher, the area is closer to the epicenter, so the value of
the coefficient ψ increases from 0.5 to 0.8, for Zone Area from 1 to 6, according to
Table 7. Equation (20) shows that in the vertical direction, the structure is assumed
to completely follow soil vertical movement, not depending on its natural frequency
period and ductility. In this equation, the earthquake response factor is considered
to have been calculated. Later, the factor I is to be determined by the category of
building we deal with.
A.5.1.2 By separating the examination of upper structure and lower structure, the upper
structure can be considered to be clamped to the ground floor level, while the lower
structure can be examined as a separate 3D structure underground which
experiences a loading from the upper structure, from its own inertia force and from
the surrounding soil.
A.5.1.3 This article defines the lateral clamping level of the upper structure, if there is no
basement.
A.5.1.5 At each earthquake event, it is impossible for a building upper structure to show a
good behavior, if its lower structure has failed earlier. To prevent the occurrence of
such phenomenon, the lower structure must be designed to act fully elastic all the
time. Thus, nominal load on the lower structure as the effect of Design Earthquake,
must be defined based on µ = 1 and R = f1 = 1.6, as applies for fully elastic
structure.
A.5.2.3 This article repeats the terms in Table 3 for double system. It means that the open
portals which have a relatively low lateral rigidity still have a particular minimum
installed strength, to give a better guarantee of good resistance against
earthquake.
A.5.4.2 The rotation center of level floors according to this article is unique foe each
building structure and does not depend on earthquake load distribution along the
height of the building structure. Due to the earthquake load working at the center of
gravity located eccentrically on the level floor rotation center, the level floor shows
3 types of deflection, they are translations in each direction of coordinate axis and
rotation through the level floor rotation center, according to the degrees of freedom
the building has (see A.5.3.1). Thus, the effect of Design Earthquake on a building
structure must be analyzed in 3 D, both in static and dynamic analysis.
Rotation center is not the center of rigidity or the center of shear as also known in
structure engineering. The center of rigidity of a building structure is a point at each
level (between two floors) which if shear load of all levels working on the building
jointly, all the building structure (which means all levels and floors) does not rotate,
but only translates. Thus, the center of rigidity is not unique for a building structure,
but depends on earthquake load distribution along the height of the building
structure. Examination of the center of rigidity is not relevant in the context of level
floor rotation movement.
A.5.4.3 This article defines a design eccentricity between the center of gravity and the
center of rotation at each level floor, considering that in reality, the eccentricity can
divert far from the theoretically calculated value. There are 2 sources of this
diversion. The first source is a dynamic amplification due to non-linier structure
behavior on post elastic earthquake loading step. The second source is the
existence of rotation component of soil movement through a vertical axis,
difference in structure rigidity value, steel yield strength value, dead load value, and
live load value and distribution, between the theoretically calculated and real
condition values. Correlated to the 2 aforementioned sources of diversion, the
design eccentricity ed consists of 2 component. The first component which is a
function of theoretical eccentricity e is to handle the effect of first source. The
second component which is a function of the largest horizontal magnitude of
building structure map, perpendicular to earthquake load direction b is to handle
the second effect source. The effect of the first source is more dominant at low
eccentricity (0<e≤ 0.3b), while the second source is more dominant at high
eccentricity ( e > 0.3 b). At the limit of e = 0.3, the resulting design ed is certainly
equal.
A.5.5.2 This article provides the terms about modulus elasticity of concrete Ec and modulus
elasticity of steel Es.
A.5.5.3 This article stresses that the effective moment of inertia as defined in Article 5.5.1
applies both in static analysis and dynamic analysis to calculate deflection and
natural frequency period of the building structure. It is considered not reasonable to
differentiate rigidity calculation into the two types of analysis.
In this article, the fundamental frequency period limit values of a building structure is
defined as a multiplication of a coefficient ξ and total level n owned by the building. In
Table 8, the coefficient ξ is defined as the function of Seismic zone seismic where
the building structure resides. This is considering that the lower the seismic, the less
determining the earthquake load on gravitational load, so the effect of limitation of
fundamental frequency period will decrease. Giving penalty to a very flexible building
structure by a prerequisite minimum C value on in the C-T response spectrum can
actually add comfort, but will not change its behavior.
A.6.1.3 Equation (27) is a part of equivalent static earthquake load description result
mentioned in A.6.1.1, simultaneously giving the terms on how to distribute nominal
base shear load V along the building structure height to be equivalent static
nominal earthquake loads Fi.
A.6.1.4 This article correlates with a relatively very flexible building structure in the
earthquake direction (a “thin” building), which frequently shows a whip effect. The
centralized load 0.1 V installed at the top floor level simulates this whip effect.
A.6.1.5 With the terms in this article, calculation of over-the-tower tank is conservative. For
a more accurate calculation, distribution of its structure mass can definitely be
calculated.
A.6.2.2 To determine equivalent static nominal earthquake load, natural frequency period
calculated with the Rayleigh formula is determined as the standard. The natural
frequency period can be determined by other ways, as long as the result will not
divert (upward or downward) more than 20 % of values calculated with the
Rayleigh formula.
A.7.2.2 Response each order defined through the Planned Earthquake Response
Spectrum is the maximum response. Generally, the response of each order will
reach maximum value at different times, so the maximum response of the orders
cannot be summed easily. This article defines how to superposition maximum
response of the orders based on the result of various researches. There are 2
superposition methods defined in this article, which are methods known as
A.7.2.4 By using this article, response spectrum order analysis is only used to determine
dynamic nominal level shear force due to effect of Design Earthquake. Internal
forces in the building structure components come from common 3D static analysis
based on equivalent static earthquake loads described from distribution of nominal
level shear force received from prior dynamic response analysis, which if
necessary, is modified first conservatively to get a better distribution of nominal
earthquake load distribution along the height of the building structure (see Figure
P4). This way, we can get a certainty about sign (work direction) of internal forces
in building structure components.
(design)
modified
A.7.3.2 For nominal earthquake loading level where structure response still acts fully
elastic, peak acceleration of input earthquake must be scaled to be A as I equation
(33). In this equation, the factor I is to calculate the earthquake loading to be
nominal earthquake loading.
A.7.3.4 This article stresses, that each accelerogram contains uncertainty to be used at a
location. Thus, at least 4 accelerograms from separate earthquakes must be
examined. The El Centro Earthquake is taken as the standard, because its
accelerogram contains a wide frequency, recorded at medium distance from the
epicenter and with medium (not extreme) amplitude.
A.7.3.5 As an alternative, this article allows usage of soil acceleration simulated as input
earthquake movement in time history dynamic response analysis.
A.8.1.2 This response spectrum defines quantitatively the criteria of service limit
performance of building structure.
A.8.2.2 This article stresses quantitatively the criteria limit of building structure ultimate
performance.
A.8.2.3 This article is intended to prevent collision of 2 neighboring buildings. From the
experience with various strong earthquake occurrences in the past time, many
building severe damage occur because neighboring buildings collide. This must be
prevented by providing a sufficient intermediate space, as defined in this article.
A.8.2.4 This article is intended to prevent collision between 2 building structure parts
separated by a dilatation clearance. The size of the clearance must definitely be
sufficient to prevent collision between parts which is not only will cause heavy
damage, but can also change the calculated structure response.
A.9.1.2 The highly dominant load worked by the upper structure on the lower structure is
the rolling moment, along the respective normal (vertical) load and shear
(horizontal) load. Maximum nominal rolling moment from the upper structure on the
lower structure which acts fully elastic is received form the maximum rolling
moment by dividing it with R = f1, which is the earthquake response factor for fully
elastic structure as defined by equation (40) (see Figure P.1).
A.9.1.3 Other possibility is the occurrence of rolling moment worked by the yield moment
working on plastic joints at the foot of all columns and on the foot of all shear walls.
Since the building structure, due to effect of Design Earthquake, experiences the
first yield until reaching the condition of near collapsing, plastic joints, particularly
on column foot and shear wall foot, experience rotation, while their yield moments
increase from the initial yield moment My to final yield moment f0 My, due to strain
hardening of steel, with f0 as the strain hardening factor. This process is visualized
in the moment-deflection diagram of a plastic joint at the column foot or shear wall
foot as shown in Figure P.5. For fully ductile building structure (µ = 5.3), according
to various researches f0 = 1.25, while for a fully elastic building structure (µ = 1),
automatically f0 = 1.00, because yielding just about to occur. To make the rolling
moment due to plastic joint yield moment to the nominal rolling moment, the f0 value
is not required, because nominal moment can be calculated directly from the initial
yield moment by dividing it with load and material extra strength factor f1 = 1.6 as
stated by equation (41) (see Figure P.5.). Nominal rolling moment according this
equation (41) certainly occurs along the respective normal (vertical) load and shear
(horizontal) load.
plastic joint
plastic joint
A.9.1.4 From the two possibilities of the aforementioned rolling moment, the definitive one
is the smallest value, because with the formation of plastic joint at all column feet
and all shear wall feet, nominal rolling moment according to earthquake (40) will
not be mobilized fully. But in all aspects, the maximum nominal rolling moment
value is not necessarily taken more than that occurring due to effect of Design
Earthquake on the building upper structure acting fully elastic, as stated by
equation (42) (see Figure P.1 and P.5).
A.9.1.5 Imperfect clamping on column feet and shear wall feet may be calculated. How it is
done is left to the planner, as long as it is rationally accountable.
A.9.3.2 This article gives a clue how soil-structure interaction must be examined to a
limited extent. The critical part in this analysis is the determination of compression
spring and shear spring quantitative properties, which represents the back, side,
and bottom soil (foundation).
A.10.1.2 Historical articles is certainly must be saved against damage for the interest of the
future generation.
B.1.2 Along the strength design of upper structure and lower structure, building foundation
strength can be designed based on Factored Load and Strength Design Method.
B.1.3 Nominal load Qn working on the foundation is nominal load working on lower
structure, continued directly to the supporting ground such as pad and raft
foundation, or continued through pile or bore pile foundation to the supporting ground
as on post foundation type. The nominal load Qn multiplied by the corresponding
load factor γ is the ultimate load Qu which works on the foundation conforming to
Article 4.4.1, Article 4.4.2, and Article 4.4.3.
B.1.4 According to Factored Load and Strength Design the following foundation ultimate
limit requirements must be satisfied:
Ru ≥ Qu (P.1)
where Ru is the foundation ultimate strength or ultimate support capacity, which is a
multiplication of capacity reduction factor φ and foundation nominal strength Rn
according to equation:
Ru ≥ φ Rn (P.2)
B.1.5 Capacity reduction factor φ for foundation is defined according to Table P.1 for pad
and raft foundation type, and according to Table P.2 for pile and bore pile foundation
type.
Table P.1 Capacity reduction factor φ for pad and raft foundation type
Soil Type φ
Sand 0.35 – 0.55
Clay 0.50 - 0.60
Rock 0.60
B.2.2 Design of upper structure and lower structure component strength using Factored
Load and Strength Design, has been followed for a long time in practice in
Indonesia. But for foundation strength design, there is a strong tendency to keep
using allowable tension or load. This inconsistency should certainly be eliminated
as early as possible. Thus, the Appendix of this Standard is intended to socialize
the Factored Load and Strength Design as an alternative, which is expected to
replace the old method as soon as possible.
B.2.3 Basically, nominal load at the lower structure is also the nominal on foundation
transmitted to the supporting soil. Thus, load factors γ which must be multiplied with
nominal load Qn get ultimate load Qu on the Foundation, must taken equal to the
one that applies for building upper structure and lower structure.
B.2.5 The capacity reduction factor φ highly depends on several things, like foundation
work quality, variation distribution of soil parameters, calculation method of nominal
strength or ultimate strength, reliability of soil parameter and test method used to
get them, load properties (compression, tension, moment, shear). Because a φ
value cannot be determined, but in a range, as shown in Table P.1 and Table P.2.
Generally, the φ value in the range is taken if in nominal supporting capability the
correlation with the Standard Penetration Test value is used. The average φ value
in a range is taken if shear strength parameters from lab result test or direct load
test until failure is used.