téléchargement
Features
• Dual type, space saving
• Built-in temperature sensor for compensation
of cold-point-junction variations
• Available in different standard temperature
ranges adjusted by producer
Description
P-GA112/CE 2006-10-24
The GA-112 Functional Control
Fabric adjusts the amplifier and further The correct signal current can be calculated as
adjustment is normally not required. Functional follows:
control is carried out according to the following (20 - 4)*Tamb
I out =4+ (mA)
procedure: Range
1. Disconnect one of the sensor leads from
terminal no. 3 and 4. Example:
2. Short circuit the sensor input, terminal no. 3 GA-112/A, range 0 to 600 °C. Tamb = 30 °C.
and 4.
3. Connect a mA-meter in series with one of
I out =4+ (20 - 4)*30 = 4.8 mA
the leads to the power supply. 600
4. The signal current will correspond to the
ambient temperature of the amplifier (the Potentiometer for zero adjustment is accessible
thermo voltage is 0 µV). inside cover. This potentiometer cover
5. A 4 mA signal corresponds to 0 °C, while 20 approximately ±1 % of FRO* and should be
mA corresponds to full range. adjusted by fabric. Further adjustments are not
recommended.
Technical specifications
Bend part
of
Red 1 +
4 Power supply
K NiCr-NiAl
Therm ocouple 12-40VDC
6 R
Green 3 -
GA-112/-
Red 7 +
10
K NiCr-NiAl Power supply
12-40VDC
Therm ocouple 12 R
Green 9 -
Signal Load
4-20 m A resistance
Cable from
m easuring
equipm ent to
am plifier
K(NiCr/NiAl)
Therm ocouple Power supply
4-20 m A 12-35V DC
"Hot junction"
3
Red +
Input 2
Am pl.
- network
Green Load resistance
4
"Cold
junction "
KONGSBERG MARITIME AS