KORADI TPS EXPANSION PROJECT – 3 x 660 MW L&T-S&L LIMITED

LARSEN & TOUBRO LIMITED


(UNIT #8, 9 & 10), KORADI, MAHARASHTRA
PART – I Rev.: 0
MAIN PLANT PACKAGE PLANT OPERATION AND CONTROL
PHILOSOPHY
L&T Project No. : C10901
Document No.: L555-00P-00101
L&T-S&L Job No.: L555000

ATTACHMENT 7.1.2
SYSTEM DISCRIPTION FOR
COLD REHEAT STEAM SYSTEM
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 3 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

TABLE OF CONTENTS

1. GENERL DESCRIPTION .................................................................................................................................... 4


1.1. INTRODUCTION................................................................................................................................................. 4

1.2. REFERENCE DRAWINGS & DOCUMENT .......................................................................................................... 4

2. SYSTEM DESCRIPTION..................................................................................................................................... 5
2.1. FLOW DESCRIPTION ........................................................................................................................................ 5

2.2. MAIN COMPONENTS ........................................................................................................................................ 5

3. TECHNICAL PARTICULARS ............................................................................................................................ 8


3.1. DESIGN & OPERATING PARAMETERS............................................................................................................. 8

3.2. DESIGNED DATA .............................................................................................................................................. 8

4. MODE OF OPERATION ...................................................................................................................................... 8


4.1. NORMAL OPERATION....................................................................................................................................... 8

4.2. ABNORMAL OPERATION .................................................................................................................................. 9

4.3. START-UP & SHUT DOWN OPERATION PHILOSOPHY .................................................................................... 9

5. INSTRUMENTATION & CONTROL................................................................................................................ 10


5.1. OPEN LOOP CONTROL: ................................................................................................................................. 10

5.2. CLOSE LOOP CONTROL: ............................................................................................................................... 14

5.3. ALARM CONDITIONS: .............................................................................................................................. 15


KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 4 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

1. GENERL DESCRIPTION

1.1. Introduction
Purpose :

Purpose of this document is to detail out the description & functions of Cold Reheat steam
system along with controls envisaged to ensure intended function of the system with regards
to the overall plant operation. This document also outlines brief operation philosophy of the
system.

Scope:
Cold reheat steam system starts from HP turbine exhaust and consists of all piping and
components upto Boiler reheater inlet.

1.2. Reference Drawings & Document


i. Mechanical drawings & documents

Authoring Document no. Sht Description


organization no.

L&T-S&L L555-08M-00202 2 P&IDs Cold Reheat Steam System

L&T-S&L L555-08M-00102 N/A Design Criteria For Reheat Steam System

ii. Vendor-Supplied Drawings and Documents

Authoring Document no. Sht Description


organization no.

LMTG - N/A Heat Balance Diagrams

LMTG T3106AAAA230 N/A Gland Steam And Drain Piping Diagram

LMTG T3106AYAC100 N/A SYSTEM DESCRIPTION FOR STEAM


TURBINE

LMB P10-0600-1 N/A Boiler P&I Diagram


KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 5 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

Authoring Document no. Sht Description


organization no.

LMB 97000-02-P10- N/A Control & Instrumentation Philosophy for


0600-1 Boiler P&ID

2. SYSTEM DESCRIPTION

2.1. Flow Description


The steam system mainly consists of following:-

 Two parallel Cold Reheat (CRH) lines (08LBC03BR001 & 08LBC03BR002) are
routed from HP turbine exhaust and connected to CRH common header
(08LBC03BR024). This common header is again bifurcated into two parallel lines
(08LBC03BR003 & 08LBC03BR004) near the Boiler area which are then routed to
the reheater inlet headers. The function of Cold Reheat steam line is to convey steam
from HP turbine exhaust to reheater inlet.

 HP bypass line (08MAN02BR005) downstream of the HP PRDS valve is connected to


the CRH common header.

 A ventilator line connection (08LBC03BR025 & 08LBC03BR026) is provided from each


parallel lead of cold reheat lines upstream of pneumatically actuated check valve. These
lines combine to form a single line (08LBC03BR027). A ventilator valve
(08LBC03AA511) is provided on this line to dump the bottled up steam from HP turbine
casing into the condenser, whenever the temperature of the steam becomes very high
due to windage loss in the HP turbine at lower loads.

2.2. Main Components


Cold Reheat Steam system has the following major components:

2.2.1. Cold Reheat System Piping


2.2.2. Cold Reheat Piping Drains
2.2.3. Ventilator Line
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 6 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

2.2.1. Cold Reheat Steam System Piping


Two parallel Cold Reheat (CRH) lines (08LBC03BR001 & 08LBC03BR002) are routed
from HP turbine exhaust and connected to CRH common header (08LBC03BR024). This
common header is again bifurcated into two parallel lines (08LBC03BR003 &
08LBC03BR004) near the Boiler area which are then routed to the reheater inlet headers.

The cold reheat steam piping material is of alloy steel (ASTM A335 P11) from the HP
Turbine exhaust to the HP bypass connection to CRH common header and of carbon
steel (ASTM A106 Gr. B) from downstream of HP bypass connection to reheater inlet.

The design pressure of the Cold Reheat system is determined in accordance Design
Criteria Document (DCD). The Cold Reheat System Design Pressure is applicable for
the design of the Cold Reheat headers, branches, drain lines etc. Steam velocity is
maintained per velocity limits given in the Design Criteria Document (DCD).

Piping and piping components will be insulated with Rock Wool material for heat retention
and /or personnel protection. Each lead of Cold Reheat line consists of a pneumatically
actuated check valve near to the turbine (08LBC01AA701 & 08LBC01AA702). This
pneumatically actuated check valve prevents the back flow of steam to HP turbine during HP
Bypass valve operation.
Two (2) safety valves (08LBC99AA400, 08LBC99AA401 & 08LBC99AA402,
08LBC99AA403) are provided on each cold reheat steam lines near reheat inlet header
which acts as a safety protection device during over pressure or pressure surges in the cold
reheat steam lines.
The Cold Reheat Steam header also supplies Steam to Deaerator & BFP Turbine at low
loads, continuous to Feed water heater – 7, Auxiliary steam header and turbine gland
seal steam requirements of the steam turbine and also steam is supplied for the soot
blowers of boiler as per the requirement.

2.2.2. Cold Reheat Steam Piping Drains


The cold reheat steam piping is designed with draining facility which ultimately protects the
turbine from any ingress of accumulated water/condensate. The design of the cold reheat
steam system includes provisions for adequate drain at low point, in accordance with the
requirements of the ASME TDP-1.
Drain lines (08LBC03BR006 & 08LBC03BR009) with Motor operated drain valves
(08LBC03AA041 & 08LBC03AA042) are provided in each leads of cold reheat line on
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 7 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

upstream of pneumatically actuated check valves and are routed to condenser via Flash
tank. The operation of these drain valves is based on start-up/shut down sequence of the
turbine.
Manually operated Alternate drain valves (08LBC03AA104, 08LBC03AA105,
08LBC03AA106) are provided in the drain lines (08LBC03BR007, 08LBC03BR011 &
08LBC03BR015) which are routed to atmospheric flash tank. These drain valves are
operated only when respective motorized drain valves are closed. The operation of these
drain valves are based on operator’s discretion.
Low points in the cold reheat steam header are provided with drip leg. The drip leg
(08LBC03BR021) on the CRH common header is provided with motor operated drain valve
(08LBC03AA043) and drain is routed to condenser via turbine flash tank. The operation of
the drain valve is based on the level in the drip leg monitored by two level switches
(08LBC03CL201 & 08LBC03CL202)
Low points in ventilator line are provided with drip legs at upstream and down stream of
ventilator valve. Drip legs (08LBC03BR411 & 08LBC03BR415) are provided with dedicated
Solenoid operated drain valve (08LBC03AA417 & 08LBC03AA421) and drains are routed to
flash tank. The operation of these drain valves is based on level switches provided on the
drip legs.
CRH piping is designed to slope to these drains under all conditions of pipe expansion
from cold to hot positions. Manually-operated isolation valves are provided as a root valve
near to each drain connection. These manual valves are for maintenance purposes only
and should be LOCKED OPEN during unit operation. The motor-operated drain valve on
drain lines are operated in accordance with plant operation- Start-up and shutdown
sequences.

2.2.3. Ventilator Line


Ventilator line is provided with an on/off MOV (08LBC01AA511) in the upstream of the
low point drains near to the turbine exhaust. Whenever the HP exhaust temperature
becomes very high due to the windage loss this ventilator line will dump the HP exhaust
steam into the condenser. A desuperheater is provided to control the temperature of
dump steam to condenser. Spray water supply to the desuperheater is provided from
CEP discharge. Associated logics for ventilator valve will be built in Turbine Control
System.
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 8 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

3. TECHNICAL PARTICULARS

3.1. Design & Operating Parameters

Particulars Units Design Operating


(100%TMCR;0%MU)
CRH Steam Flow Rate Kg/hr 1874416 1792114
CRH Steam Pressure Kg/cm2(g) 68.33 55.8
CRH Steam Temperature deg C 366 339.3

3.2. Designed Data

Piping Segment Pipe Nominal Selected


Diameter Minimum wall
thickness
CRH Steam Header(turbine end) 1050 41
CRH Steam Header (Reheater
1050 40
end)
CRH Steam individual Header
800 32
(turbine end)
CRH Steam individual Header
800 31.75
(Reheater end)

4. MODE OF OPERATION

4.1. Normal Operation

During normal operation steam from HP Turbine outlet flows to reheater through Cold
Reheat steam pipes. The Cold Reheat steam is supplied to Auxiliary steam header, HP
Feedwater Heater #7 and gland steam header.
Drip legs are provided at the low point of the cold reheat common header and ventilator line.
Drip leg drain actuator operated valves are operated based on the condensate level, sensed
by the respective level switches. Drain valves shall remain closed during normal operation.

Ventilator valve remains closed during normal operation.


KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 9 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

4.2. Abnormal Operation


Four safety valves are provided, two on each reheater inlet header near the Steam
Generator; for Reheater and Cold Reheat steam piping protection from overpressure.
High pressure is released through these safety valves. Overpressure could develop if the
reheat stop or intercept valves close without a corresponding opening of the LP bypass
valve.

Whenever the turbine-generator is tripped, the Cold Reheat drain valves and HP & LP
Turbine bypass Valves will be opened immediately and the Power actuated NRVs will be
closed.

4.3. Start-up & Shut down Operation Philosophy

4.3.1. Normal Plant Start-up


Normally during the start-up of the plant after achieving required paramaeters,
CRH steam flow is established through HP bypass system. After achieving
required parameters the cold reheat steam will supply the seal steam for turbine
and for the auxiliary steam header.
The Cold Reheat Steam system drain MOVs are used to drain condensate from the
Cold Reheat Steam piping. These drains will be kept open the unit is synchronized
with grid and carrying approximately 20% load. After 20% Load drain valves will be
closed and the level controlled drip leg drain MOV at downstream of Check valve will
be operated based on condensate level in the drip leg.

Power operated check valves will be operated to prevent back flow of steam to
the Turbine during Bypass/start-up operation.

4.3.2. Normal Plant Shutdown


During unit shutdown, all system drain valves should be opened as the Cold
Reheat Steam system depressurizes, allowing steam and accumulated
condensate to drain to the condenser via turbine flash tank. These precautionary
measures are taken to prevent any accumulation of condensate formed in the cold
reheat steam piping and to assure that condensate will not enter the turbine
during hot restart resulting in damage to the turbine.
At approximately 15% of rated load, open all turbine drains except reheat steam
inlet piping drain. Ventilator valve will be operated based on HP turbine exhaust
temperature.
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 10 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

4.3.3. Ventilator Valve operation


The ventilator valve is opened in case of the turbine exhaust temperature goes
above 400°C (to be confirmed by LMTG) and is closed when the generator load is
above 10% and turbine exhaust temperature is below 360°C. The water spray
valve (08LCE13AA087) modulates to control the temperature downstream of
desuperheater. The spray valve receives signal from redundant temperature
transmitter located downstream of the desuperheater for opening and closing.

5. INSTRUMENTATION & CONTROL

5.1. Open Loop Control:

5.1.1. CRH drain valves (08LBC03AA041, 08LBC03AA042)

Purpose:
The Cold Reheat Steam system drain valves will be used to drain condensate from the
Cold Reheat Steam piping during start-up of the unit.
Functional Description:
The drain valves will be kept closed during normal operation of the turbine and will be
operated only during turbine start up, shutdown and turbine trip conditions through
sequence logic. This drain MOVs can also be operated from DCS in Auto/Manual based
on process requirement and operator judgement.
The following DCS control signals will be associated with the drain valves
(08LBC03AA041, 08LBC03AA042) at HP turbine exhaust:

Valve Number Start-Up Shut Down Normal Unit Trip


Operation
08LBC03AA041 Open Open Close Open
08LBC03AA042

5.1.2.1 Control & Monitoring


i. Permisssives
Open Permissive
 None
Close Permissive
 None
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 11 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

ii. Auto interlock


Auto Open Interlock
 Boiler flame ON
 Plant Load below 10% of rated load during start up and below 7% of rated load
during shut down.

Auto close Interlock


 Steam turbine load increases above 10% during start up
iii. Protective Commands
Override Open
 Turbine Trip

iv. References
This control description covers the process control functional logic requirement for
following equipment
 08LBC03AA041 CRH Steam Header (LHS) Drain MOV
 08LBC03AA042 CRH Steam Header (RHS) Drain MOV

Logic Diagram reference:


Equipment Tag Description Drawing Sheet
Number Number
08LBC03AA041 CRH STEAM HEADER (LHS) L555-00I- 041A-041B
DRAIN MOV 00200
08LBC03AA042 CRH STEAM HEADER (RHS) L555-00I- 042A-042B
DRAIN MOV 00200

5.1.2. Low point Drip pot drain valve (08LBC03AA053) on CRH Header

Purpose:
The Cold Reheat Steam system low point drain valves will be used to drain condensate
from the Cold Reheat Steam piping.
Functional Description:
The motor operated low point drain valve will be kept closed during normal operation of
the plant. It will be opened automatically upon detection of high water level in the
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 12 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

respective drip leg by the high level switch and will be closed automatically after
predetermined time period. This drain MOVs can also be operated from DCS in
Auto/Manual based on process requirement and operator judgement.
The following DCS control signals will be associated with the motor operated drain valves
(08LBC03AA053) at HP turbine exhaust.

Valve Number Start-Up Shut Down Normal Unit Trip


Operation
08LBC03AA053 Close Close Auto Auto

5.1.2.1 Control & Monitoring

i. Permisssives
Open Permissive
 None
Close Permissive
 None

ii. Auto interlock


Auto Open Interlock
 Dripleg level High
 Turbine Trip

Auto Close Interlock


 After predefined time OR
 Dripleg level is not High

iii. Protective command


This valve will be override open in case of drip leg level high high.

iv. References
This control description covers the process control functional logic requirement for
following equipment
 08LBC03AA053 CRH STEAM HEADER DRIPLEG MOV
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 13 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

Logic Diagram reference:


Equipment Tag Description Drawing Sheet
Number Number
08LBC03AA053 CRH STEAM HEADER DRIPLEG MOV L555-00I- 043A-
00200 043B

5.1.3. Low point Drip pot drain valves (08LBC03AA417 & 08LBC03AA421) on Ventilator
Line

Purpose:
The low point drain valves will be used to drain condensate from the ventilator valve
piping.
Functional Description:
Solenoid operated low point drain valves will be kept closed during normal operation of
the plant. It will be opened automatically upon detection of high water level in the
respective drip leg by the high level switch and will be closed automatically after
predetermined time period. This drain MOVs can also be operated from DCS in
Auto/Manual based on process requirement and operator judgement.
The following DCS control signals will be associated with the motor operated drain valves
(08LBC03AA417 & 08LBC03AA421) at HP turbine exhaust.

Valve Number Start-Up Shut Down Normal Unit Trip


Operation
08LBC03AA417 Auto Close Close Close
08LBC03AA421 Auto Close Close Close

5.1.2.2 Control & Monitoring

i. Permisssives
Open Permissive
 None
Close Permissive
 None
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 14 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

ii. Auto interlock


Auto Open Interlock
 Dripleg level High

Auto Close Interlock


 After predefined time
 Dripleg level is not High

iii. Protective command


This valve will be override open in case of drip leg level high high.

iv. References
This control description covers the process control functional logic requirement for
following equipment
 08LBC03AA017 Ventilator Valve Upstream Dripleg SOV
 08LBC03AA021 Ventilator Valve Downstream Dripleg SOV

Logic Diagram reference:


Equipment Tag Description Drawing Sheet
Number Number
08LBC03AA417 VENTILATOR VLV US DRPL SOV L555-00I- 044A-B
00200
08LBC03AA421 VENTILATOR VLV DS DRPL SOV L555-00I- 045A-B
00200

5.1.4. Turbine Exhaust NRVs:

Control description & logics will be provided by LMTG.s

5.2. Close Loop Control:

5.2.1. Ventilator Desuperheater Temperature Control Valve (08LCE13AA087)

Purpose:
To control the ventilator valve desuperheater downstream temperature.

Functional description:
KORADI TPS EXPANSION PROJECT – 3 x 660
LARSEN & TOUBRO LIMITED MW (UNIT #8, 9 & 10), KORADI, L&T-S&L LIMITED
MAHARASHTRA
SYSTEM DESCRIPTION, OPERATION & Rev.: C
MAIN PLANT PACKAGE CONTROL FOR COLD REHEAT STEAM Date: 05/07/12
SYSTEM
L&T Project No. : C10901 Page: 15 of 15
Document No.: L555-00M-00902
L&T-S&L Job No.: L555000

Whenever the ventilator valve is opened the spray control valve (08LCE13AA087)
receives signal from dual redundant temperature element (08LBC03CT007A/B) located
downstream of the desuperheater for modulating the valve.
Valve Number Start-Up Shut Down Normal Unit Trip
Operation
08LCE13AA087 Modulating Modulating Close Modulating

5.3. ALARM CONDITIONS:

Description Initiating KKS Tag Normal Alarm Trip


Device Number Value Value Value
CRH Steam Line Level 562.5
08LBC03CL201 - -
Dripleg Level HI Switch mm
CRH Steam Line Level 637.5
08LBC03CL202 - -
Dripleg Level HI HI Switch mm
Ventilator Valve
Level 562.5
Upstream Dripleg 08LBC03CL206 - -
Switch mm
Level HI
Ventilator Valve
Level 637.5
Upstream Dripleg 08LBC03CL208 - -
Switch mm
Level HI HI
Ventilator Valve
Level 562.5
Downstream Dripleg 08LBC03CL207 - -
Switch mm
Level HI
Ventilator Valve
Level 637.5
Downstream Dripleg 08LBC03CL208 - -
Switch mm
Level HI HI