You are on page 1of 32

.......

Document type : MT Discipline : EL


Project Title : MOPU Lease Contract for MAC Field Development
SPARE
NO DESCRIPTION QTY TOTAL UNIT REMARKS
10%
II BULK MATERIAL
A LIGHTING
1 Linear LED Lighting (AC) 123 12 135 Set

Outdoor Lighting, Industrial Type, Linear LED Type, White Light, 2x 26, 120 VAC, Single- Phase , 60 Hz,
Pendant/Stanchion Mounting, Suitable for Harsh, Salt Marine Environment and Corrosion resistant, IP 56, Suitable for
Hazardous Area, Class 1 Zone 2 Gas Group IIA, T3. Crouse Hind, Killark, Hubbel or Equivalent Product

2 Linear LED Lighting (AC - Emergency) 91 9 100 Set


Outdoor Lighting, Industrial Type, Linear LED Type, White Light, 2x 26, 120 VAC, Single- Phase , 60 Hz, c/w Battery Set,
Autonomy 90 minutes, Pendant/Stanchion Mounting, Suitable for Harsh, Salt Marine Environment and Corrosion
resistant, IP 56, Suitable for Hazardous Area, Class 1 Zone 1 Gas Group IIA, T3. Crouse Hind, Killark, Hubbel or
Equivalent Product

3 Lowbay LED Lighting 20 2 22 Set

Outdoor Lighting, Industrial Type, Lowbay LED Type, White Light, 62W, 120 VAC, Single- Phase , 60 Hz,
Pendant/Stanchion Mounting, Suitable for Harsh, Salt Marine Environment and Corrosion resistant, IP 56, Suitable for
Hazardous Area, Class 1 Zone 2 Gas Group IIA, T3. Crouse Hind, Killark, Hubbel or Equivalent Product

3 Floodlight LED Lighting (AC) 20 2 22 Set

Outdoor Lighting, Industrial Type, Floodlight LED Type, White Light, 112W (equivalent more than 13000 lumen) , 120
VAC, Single Phase 60 Hz, c/w Yoke Mounted, Suitable for Harsh, Salt Marine Environment and Corrosion resistant, IP
56, Suitable for Hazardous Area, Class 1 Zone 2 Gas Group IIA, T3. Crouse Hind, Killark, Hubbel or Equvalent Product

4 Exit Light 10 1 11 Set

Emergency Exit Lamp, Indoor, Industrial Type, 8 W, 120 VAC, Single Phase, 60 Hz, Pendant Type, Inlcluded NiCad
Battery 3 hours back up time.Suitable for Harsh, Salt Marine Environment and Corrosion resistant, IP 56, Suitable for
Hazardous Area, Class 1 Zone 1 Gas Group IIA, T3. Crouse Hind, Killark, Hubbel or Equvalent Product

Page 1+5 of 16
.......

Document type : MT Discipline : EL


Project Title : MOPU Lease Contract for MAC Field Development
SPARE
NO DESCRIPTION QTY TOTAL UNIT REMARKS
10%
5 Lighting Junction Box 276 28 304 Set

Junction Box For Lighting, Copper Free alluminum or GRP, Outdoor, gasketted, IP 56, certified for Class 1, Zone 1, Gas
Group IIA, Ex"e", ATEX Certified, Removable cover with -hinged door, Bottom cable entry with removable gland plate,
suitable for mounting on support, external mounting lug .Provided with breather/drain, internal/external earthing lug.
Terminal and DIN Rail Suitable for 2.5 mm2 to 10 mm2

6 Indoor - Linear LED Lighting (AC) 18 2 20 Set

Indoor Lighting, Linear LED Type, 2x 26 Watt, 120 VAC, 1 Phase, 60 Hz, pendant/recessed mounted, Industrial Type
(Non Hazardous). Philips or equivalent Product

7 Indoor - Lowbay LED Lighting 4 1 5 Set

Indoor Lighting, Linear LED Type, 62 Watt, 120 VAC, 1 Phase, 60 Hz, pendant/recessed mounted, Industrial Type (Non
Hazardous). Philips or equivalent Product

NOTES:
1 Electrical Material Take Off developed during FEED for Cost Estimate Purpose Only. EPCI Contractor Shall Responsible to Review, Verify and Update during Detail Design Engineering.
2 Quantity, rating and design configuration may vary depend on rating and type of manufacturer product, but not diminish the overall design and project requirement .
3 SPARE quantity to be reviewed.
REFERENCES:
1
2
3

Page 2+5 of 16
.......

Document type : MT Discipline : EL


Project Title : FEED Forel Bronang Development Project
SPARE
NO DESCRIPTION QTY TOTAL UNIT REMARKS
10%
B MISCELLANOUS

1 Welding Receptacle and Plug

Receptacle complete with Plug and Cover, Switch, 480 VAC, 60 Hz, 3 Phase + Earth (4 rounds pin type ),
63 Ampere rating, c/w Integrated Interlocking Switch, Outdoor Installation, Wall/Rack Mounted, IP 56 Minimum,
3 0 3 Set
Suitable for Harsh, Salt Laden and Marine Environment, GRP, UV and Oil Resistance Material,
Suitable for Hazardous Area, Ex "de", Class 1 Zone 2 Gas Group IIA, T3, Certified.

2 Socket Outlet

Socket Outlet complete with Plug and Cover, Switch, 120 VAC, 60 Hz, Single Phase + Neutral + Earth (3 rounds pin type
), 16 Ampere rating, c/w Integrated Interlocking Siwtch, Outdoor Installation, Wall/Rack Mounted, IP 56 Minimum.
14 1 15 Set
Suitable for Harsh, Salt Laden and Marine Environment, GRP, UV and Oil Resistance Material,
Suitable for Hazardous Area, Ex "de", Class 1 Zone 2 Gas Group IIA, T3, Certified

3 LCS
Local Control Station, Including push buttons, HOA selector switch and indicating lights "RED" colour for running status,
and "GREEN" colour for stopped status. "Hand" switches shall be spring returned type. GRP , weatherproof – gasketed,
IP56, factory sealed. "Stop" or "Off"push buttons and HOA or ON/ OFF switches shall have pad locking provisions, Tag 12 2 14 Set
number shall be Stainless Steel SS316 material, Suitable for Class 1, Zone 1, Gas Group IIA, T3

Local Control Station, Including push buttons and indicating lights "RED" colour for running status, and "GREEN" colour
for stopped status. "Hand" switches shall be spring returned type. GRP , weatherproof – gasketed, IP56, factory sealed.
"Stop" or "Off"push buttons or ON/ OFF switches shall have pad locking provisions, Tag number shall be Stainless 14 2 16 Set
Steel SS316 material, Suitable for Class 1, Zone 1, Gas Group IIA, T3

4 Indoor Switch & Receptacle


Single Pole, Lighting Switch 120 V, 1PH, P+N+E, 16 A, Indoor,Flush Mounting, Industial Type 14 2 16 Set
Receptacle, 230 V, 1PH, 2P + E, 16A, Indoor, Flush Mounting (Non Hazardous), Industrial Type 14 2 16 Set

NOTES:

Page 1+7 of 16
.......

Document type : MT Discipline : EL


Project Title : FEED Forel Bronang Development Project
SPARE
NO DESCRIPTION QTY TOTAL UNIT REMARKS
10%
1 Electrical Material Take Off developed during FEED for Cost Estimate Purpose Only. EPCI Contractor Shall Responsible to Review, Verify and Update during Detail Design Engineering.

2 Quantity, rating and design configuration may vary depend on rating and type of manufacturer product, but not diminish the overall design and project requirement .

3 SPARE quantity to be reviewed.

REFERENCES:
1
2
3

Page 2+7 of 16
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%
A GTG RENTAL VENDOR'S SCOPE
A.1 MV POWER CABLES - FLAME RETARDANT - NON ARMOUR
A.1.1 3.6/6 kV, concentric stranded copper conductor class 2, XLPE Insulation with Insulation Screen, Individual Copper Tape Shielded,
Extruded Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat
A, Low Smoke/fume PVC compound, UV proof, Oil resistance, colour red and fully comply with doc. no. D-200-MAC-GEN-SPE-
002, "Specification for Power, Control & Earthing Cables".

Cu/XLPE/CTS/PVC, Flame Retardant, 3.3/6 kV


1 3C x 185 sqmm 510 102 612 m GTG to MV Switchgear

A.1.2 1.8/3 kV, concentric stranded copper conductor class 2, XLPE Insulation with Insulation Screen, Copper Tape Shielded, PVC
Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low Smoke/fume PVC
compound, UV proof, Oil resistance, colour red and fully comply with doc. no. D-200-MAC-GEN-SPE-002, "Specification for
Power, Control & Earthing Cables".

Cu/XLPE/CTS/PVC, Flame Retardant, 1.8/3 kV


1 1C x 120 sqmm 220 44 264 m GTG to NER

A.2 LV POWER AND CONTROL CABLES - FLAME RETARDANT - NON ARMOUR


A.2.1 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, Extruded Polypropylene Filler, PVC Compound Inner
Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low Smoke/fume PVC compound, UV proof, Oil
resistance, colour black and fully comply with doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing
Cables".

Cu/XLPE/PVC, Flame Retardant, 0.6/1 kV


1 2C x 1.5 sqmm 458 92 550 m

2 2C x 4 sqmm 29.5 10.5 40 m

3 2C x 6 sqmm 180 36 216 m

4 2C+E x 2.5 sqmm 835 167 1002 m

5 2C+E x 4 sqmm 140 28 168 m

6 2C+E x 6 sqmm 189 38 227 m

7 2C+E x 10 sqmm 52 11 63 m

8 3C+E x 4 sqmm 685 137 822 m

9 3C+E x 6 sqmm 137 28 165 m

10 4C x 1.5 sqmm 411 83 494 m

11 4C x 4 sqmm 135 27 162 m

Page 4 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%
12 4C+E x 4 sqmm 46 10 56 m For Space Heater from PLP-6202
to PDP-6101 and PDP-6203

13 6C x 1.5 sqmm 185 37 222 m

14 6C x 6 sqmm 135 27 162 m

15 7C x 1.5 sqmm 100 20 120 m

16 9C x 1.5 sqmm 0 0 0 m

17 30C x 1.5 sqmm 38 8 46 m

A.2.2 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, copper tape metallic overall screen / shield, Extruded
Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low
Smoke/fume PVC compound, UV proof, Oil resistance, colour black and fully comply with doc. no. D-200-MAC-GEN-SPE-002,
"Specification for Power, Control & Earthing Cables".

Cu/XLPE/OS/PVC, Flame Retardant, 0.6/1 kV


1 2C+Shield x 4 sqmm 315 63 378 m For GTG kW Load Share

A.2.3 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, copper tape metallic overall screen / shield, Extruded
Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low
Smoke/fume PVC compound, UV proof, Oil resistance, colour black and fully comply with doc. no. D-200-MAC-GEN-SPE-002,
"Specification for Power, Control & Earthing Cables", suitable for VFD application.

Cu/XLPE/OS/PVC, Flame Retardant, 0.6/1 kV


1 3C+E+Shield x 6 sqmm 171 35 206 m VFD Liquid Fuel Pump Motor
GTG

2 3C+E+Shield x 95 sqmm 171 10 181 m VFD DAC Start System GTG

Page 5 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%

A.3 LV POWER CABLES - FIRE RESISTANT - NON ARMOUR


A.3.1 0.6/1 kV, concentric stranded copper conductor class 2, mica tape conductor insulation with as per IEC 60331 with XLPE or EPR Applicable for Critical Loads such
Insulation, Extruded Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC as GTG Auxiliaries supply by
60332-3 Cat A, Low Smoke/fume PVC compound, UV proof, Oil resistance, Orange Colour outer sheath and fully comply with Battery backup.
doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing Cables".

Cu/XLPE/PVC, Fire Resistant, 0.6/1 kV


1 2C x 1.5 sqmm 96 20 116 m

2 2C x 25 sqmm 28 10 38 m

3 2C x 50 sqmm 206 42 248 m

4 2C+E x 2.5 sqmm 158 32 190 m

5 3C+E x 50 sqmm 136 28 164 m

A.4 EARTHING CABLES


A.4.1 600 V, concentric stranded copper conductor class 2, unarmoured, PVC sheathed, yellow / green outer sheath and fully comply
with doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing Cables".
Cu/PVC, Flame Retardant, 0.6 kV
1 1C x 6 sqmm 50 10 60 m For junction box earthing

2 1C x 16 sqmm 150 30 180 m For local control station earthing

3 1C x 35 sqmm 125 25 150 m For GTG auxiliary panel earthing


bar; for battery rack ;
For package skid, electrical motor
4 1C x 70 sqmm 150 30 180 m For GTG skid, MV Switchgear,
earthing.
Power Transformer, LV
Switchgear and NER Panel
earthing.

B CONTRACTOR'S SCOPE

Page 6 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%
B.1 LV POWER AND CONTROL CABLES - FLAME RETARDANT - NON ARMOUR
B.1.1 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, Extruded Polypropylene Filler, PVC Compound Inner
Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low Smoke/fume PVC compound, UV proof, Oil
resistance, colour black and fully comply with doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing
Cables".

Cu/XLPE/PVC, Flame Retardant, 0.6/1 kV


1 2C x 1.5 sqmm (Applicable for UPS battery temperature sensor) 40 8 48 m Applicable for UPS battery
temperature sensor - Supply by
UPS Vendor

2 2C x 1.5 sqmm 788 158 946 m

3 2C x 2.5 sqmm 80 16 96 m

4 2C+E x 2.5 sqmm 3223 645 3868 m Including for HVAC motor space
heater,
lenght = 250 m (estimation)

5 2C+E x 4 sqmm 1021 205 1226 m


6 2C+E x 6 sqmm 88 18 106 m
7 3C x 2.5 sqmm 30 10 40 m
8 3C+E x 2.5 sqmm 85 17 102 m
9 3C+E x 4 sqmm 3373 675 4048 m
10 3C+E x 6 sqmm 240 48 288 m Including for HVAC motor,
lenght = 150 m (estimation)

11 3C+E x 10 sqmm 396 80 476 m


12 3C+E x 25 sqmm 211 43 254 m
13 3C+E x 35 sqmm 334 67 401 m
14 3C+E x 50 sqmm 273 55 328 m For HVAC motor,
lenght = 50 m (estimation)

15 3C+E x 70 sqmm 228 46 274 m


16 3C+E x 185 sqmm 390 78 468 m
17 3C+E x 240 sqmm 297 60 357 m
18 4C x 1.5 sqmm 480 96 576 m For HVAC control,
lenght = 50 m (estimation)

19 4C x 2.5 sqmm 89 18 107 m

20 4C x 4 sqmm 89 18 107 m

21 4C+E x 4 sqmm 23 10 33 m For Space Heater from PLP-6202


to PDP-6201 and PDP-6202

Page 7 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%
22 4C+E x 6 sqmm 21 10 31 m

23 4C+E x 95 sqmm 14 10 24 m

24 4C+E x 150 sqmm 12 10 22 m

25 6C x 1.5 sqmm 30 10 40 m
26 7C x 1.5 sqmm 1724 345 2069 m

27 12C x 1.5 sqmm 3218 644 3862 m

B.1.2 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, copper tape metallic overall screen / shield, Extruded
Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low
Smoke/fume PVC compound, UV proof, Oil resistance, colour black and fully comply with doc. no. D-200-MAC-GEN-SPE-002,
"Specification for Power, Control & Earthing Cables", suitable for VFD application.

Cu/XLPE/OS/PVC, Flame Retardant, 0.6/1 kV


1 2C+Shield x 4 sqmm 84 17 101 m For Control GTC Current
Transmitter

2 3C+E+Shield x 4 sqmm 327 66 393 m

3 3C+E+Shield x 6 sqmm 152 31 183 m

4 3C+E+Shield x 10 sqmm 304 61 365 m

5 3C+E+Shield x 95 sqmm 134 27 161 m VFD DAC Start System GTC

B.1.3 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, copper tape metallic overall screen / shield, Extruded
Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low
Smoke/fume PVC compound, UV proof, Oil resistance, colour black and fully comply with doc. no. D-200-MAC-MOPU-SPT-104,
"Specification for Instrument and Telecom Cables".

Cu/XLPE/OS/PVC, Flame Retardant, 0.6/1 kV


1 3P x 1.5 sqmm (suitable for motor PTC cable application) 415 10 425 m For Cooler Motor RTD via VFD

2 3T x 1.5 sqmm (suitable for motor RTD cable application) 456 92 548 m For Cooler Motor RTD via VFD

3 6P x 1.5 sqmm 33 10 43 m Applicable for ACB Trip and Earth


Fault Alarm from 480V Low
Voltage Switchgear/MCC (PDP-
6201 and PDP-6202) to
Interposing Relay Panel (IRP-
6201) - Supply by Switchgear
Vendor

4 6T x 1.5 sqmm (suitable for motor RTD cable application) 150 10 160 m For Refrigerant Compressor via
Soft Starter

Page 8 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%
5 30P x 1.5 sqmm 264 10 274 m Applicable for Motor Start/Stop
Command and Status from 480V
Low Voltage Switchgear / MCC
(PDP-6201 and PDP-6202) to
Interposing Relay Panel (IRP-
6201) - Supply by Switchgear
Vendor

B.2 LV POWER CABLES - FIRE RESISTANT - NON ARMOUR


B.2.1 0.6/1 kV, concentric stranded copper conductor class 2, mica tape conductor insulation with as per IEC 60331 with XLPE or EPR Applicable for Critical Loads such
Insulation, Extruded Polypropylene Filler, PVC Compound Inner Sheath, PVC Outer Sheath Flame Retardant according to IEC as UPS and GTC Auxiliaries.
60332-3 Cat A, Low Smoke/fume PVC compound, UV proof, Oil resistance, Orange Colour outer sheath and fully comply with
doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing Cables".

Cu/XLPE/PVC, Fire Resistant, 0.6/1 kV


1 2C x 1.5 sqmm 160 32 192 m

2 2C x 6 sqmm 100 20 120 m

3 2C x 10 sqmm 20 10 30 m

4 2C x 16 sqmm 160 32 192 m

5 2C x 35 sqmm 100 20 120 m

6 2C x 120 sqmm 42 10 52 m

7 2C+E x 2.5 sqmm 80 16 96 m

8 2C+E x 4 sqmm 1561 313 1874 m

9 2C+E x 6 sqmm 460 92 552 m Include cable for battery charging


Fire Pump A/B= 150m

10 2C+E x 10 sqmm 528 106 634 m

11 2C+E x 16 sqmm 68 14 82 m

12 2C+E x 25 sqmm 80 16 96 m

13 4C+E x 10 sqmm 50 10 60 m

Page 9 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%

B.3 LIGHTING AND SMALL POWER CABLES - NON ARMOUR


B.3.1 0.6/1 kV, concentric stranded copper conductor class 2, XLPE Insulation, Extruded Polypropylene Filler, PVC Compound Inner
Sheath, PVC Outer Sheath Flame Retardant according to IEC 60332-3 Cat A, Low Smoke/fume PVC compound, UV proof, Oil
resistance, colour black and fully comply with doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing
Cables".

Cu/XLPE/PVC, Flame Retardant, 0.6/1 kV


1 2C+E x 2.5 sqmm 2382 477 2859 m For indoor lighting cable

2 2C+E x 4 sqmm 2385 477 2862 m For socket outlet cable, Flood
Lighting & HPS Lighting cable

3 3C+E x 2.5 sqmm 2240 448 2688 m For emergency lighting cable at
EER and Transformer Room and
outdoor emergency lighting cable
(estimation)

B.4 EARTHING CABLES


B.4.1 600 V, concentric stranded copper conductor class 2, unarmoured, PVC sheathed, yellow / green outer sheath and fully comply
with doc. no. D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing Cables".
Cu/PVC, Flame Retardant, 0.6 kV
1 1C x 6 sqmm 150 30 180 m For junction box earthing

2 1C x 16 sqmm 700 140 840 m For lighting fixture earthing and


including HVAC earthing
(estimated lenght = 50 m), For
local control station earthing

3 1C x 35 sqmm 475 95 570 m For cable tray/ladder bonding


jumper; for GTC auxiliary panel
and lighting transformer earthing
bar; for battery rack and raised
floor support earthing; including
HVAC earthing (estimated lenght
= 50 m).
For package skid, vessel,
electrical motor, welding outlet,
access stairway, cable tray/ladder,
lighting pole, skid package and
pipe support earthing

4 1C x 70 sqmm 300 60 360 m For GTC skid and LV Switchgear


earthing.

Page 10 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

SPARE
NO DESCRIPTION QUANTITY TOTAL UNIT REMARKS
20%

Page 11 of 11
Doc. No. .......
ELECTRICAL CABLE
D-200-MAC-MOPU-BME-002
MATERIAL TAKE OFF
Revision : C1 Job No.: 282
Document type : MTO Discipline : EL Doc. Status : Re-AFC Contract No. : 332004865
Project Title : MOPU Lease Contract for MAC Field Development Rev. Date : Draft-1

NOTES:

1 Electrical cable shall comply with D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing Cables".
2 Pair and Triad cable with shield shall comply with D-200-MAC-MOPU-SPT-104, "Specification For Instrument Cable".
3 For Approved Manufacturer List refers to Appendix A6 – Approved Manufacturer List.
4 For cable and termitaion installation detail, refer to drawing no. D-200-MAC-MOPU-46001, "Electrical Installation Details for Power".

REFERENCE DOCUMENTS:

1 D-200-MAC-GEN-SPE-002, "Specification for Power, Control & Earthing Cables"


2 D-200-MAC-MOPU-SPT-104, "Specification For Instrument Cable"
3 D-200-MAC-MOPU-SHE-001, "Electrical Cable Schedule (Power And Control)"
4 D-200-MAC-MOPU-44030, "Normal Lighting - Interconnection Wiring Diagram"
5 D-200-MAC-MOPU-44031, "Essential and Emergency Lighting - Interconnection Wiring Diagram"
6 D-200-MAC-MOPU-40301, "EER & IER Building Earthing Layout"
7 D-200-MAC-MOPU-40302, "Power Generation (Port) Earthing Layout"
8 D-200-MAC-MOPU-40303, "Power Generation (Starboard) Earthing Layout"
D-200-MAC-MOPU-40304, "Compressor & Scrubbers (Lower Deck) - Earthing Layout"
9
D-200-MAC-MOPU-40305, "Drill Deck - Earthing Layout"
10
D-200-MAC-MOPU-40306, "Coolers (Upper Deck) - Earthing Layout"
11
D-200-MAC-MOPU-40307, "TEG Regeneration & Flare KO Drum (Shale Shaker) - Earthing Layout"
12
D-200-MAC-MOPU-40308, "Skid Beam Area - Earthing Layout"
13
D-200-MAC-MOPU-40309, "DPCU (Port) - Earthing Layout"
14
D-200-MAC-MOPU-40310, "Flexible Jumper Balcony - Earthing Layout"
15
D-200-MAC-MOPU-40311, "Flare Boom Area - Earthing Layout"
16

Page 11 of 11
Doc. Title:

Doc. No:

Revision : 12 of 32+9......................................................

Rev. Date :

Page :

NO DESCRIPTION QTY SPARE 20% TOTAL UNIT REMARKS

F EARTHING MATERIAL
F.1 EARTHING MATERIAL

Earthing boss Ø30 x 40(L) mm c/w stud bolt size M10 x 60(L) mm, nut, spring and plate
1 227 45 272 ea
washer, SS 316L

2 Tinned copper cable lug, flat type, double compression, ring type, for cable size below :

- 6 Sqmm, for M10 stud hole (For Electrical Lighting Pole) 50 10 60 ea

- 16 Sqmm, for M10 stud hole (For Electrical Lighting Pole) 100 20 120 ea

- 35 Sqmm, for M10 stud hole (For Electrical Equipment) 150 30 180 ea

- 70 Sqmm, for M10 stud hole (For Electrical Equipment) 33 7 40 ea

Flame retardant & UV resistant, green/yellow colour, heat shrinkable sleeve suitable for the
3
following conductor / cable size below :

- 6 Sqmm, (1 Roll = 100 Meter) - (For Electrical Lighting Pole) 1 0 1 ea

- 16 Sqmm, (1 Roll = 100 Meter) - (For Electrical Lighting Pole) 1 0 1 ea

- 35 Sqmm, (1 Roll = 100 Meter) - (For Electrical Equipment) 1 0 1 ea

- 70 Sqmm, (1 Roll = 30 Meter) - (For Electrical Equipment) 1 0 1 ea

0.4
4 M8 x 30 SS 316L Hex. Head bolt c/w nuts, flat & spring washers 100 20 120 ea for lighting

M10 x 30 SS 316L Slotted Round Head bolt c/w nuts, flat & spring washers for cable tray
5 219 44 263 ea for earthing jumper cable tray
bonding / jumper

M10 Al / CU Bimetallic washers for cable ladder / tray bonding / jumper and cable ladder / tray for earthing jumper cable tray,
6 219 44 263 ea
earthing to the structure. note 3

Mild steel plate 100mm (L) x 50mm (H) x 5 mm thk., painted according to MHK-COMP-SPE- for lighting pole stanchion and
7 42 8 50 ea
EP-COR-0350 pendant earth tag

Notes:
1. This MTO is indicative and CONTRACTOR shall be responsible for review, verify and finalize base on actual data during detail design.
2. Electrical earthing material shall comply with :
- ID-SNB-SOME-1074-161003, "NSN - SPEC - Design of Earthing, Bonding and Lightning Protection Systems".
- ID-SNB-SOME-1074-161005, "NSN - SPEC - Electrical Cables".
- ID-SNB-SOME-1074-166002, "NSN - Electrical Typical Installation Standard Detail for Earthing".
In case Alumunium 5052H32 cable ladder / tray material will be used, Al / Cu bimetallic washer shall be be provided for cable ladder / tray bonding / jumper and cable ladder /
3.
tray earthing to the structure.

This document is the property of PT. Pertamina Hulu Mahakam and shall not be disclosed to third parties or reproduced without permission of the COMPANY.
Electronic Filename: 752293983.xlsx
13 of 32+9......................................................

This document is the property of PT. Pertamina Hulu Mahakam and shall not be disclosed to third parties or reproduced without permission of the COMPANY.
Electronic Filename: 752293983.xlsx
Doc. Title:

Doc. No:

Revision : 14 of 32+9......................................................

Rev. Date :

Page :

NO DESCRIPTION QTY SPARE 20% TOTAL UNIT REMARKS

H ELECTRICAL BULK MATERIAL

H.1 CABLE LUG

1 Tinned copper cable lug for 1.5 sqmm pin tube (ferrule) crimping type pre-insulated 3 1 4 box Each box contain 100 ea

2 Tinned copper cable lug for 2.5 sqmm crimping pre-insulated type with 4 mm dia. stud hole 4 1 5 box Each box contain 100 ea

3 Tinned copper cable lug for 4 sqmm crimping pre-insulated type with 4 mm dia. stud hole 1 0 1 box Each box contain 100 ea

4 Tinned copper cable lug for 6 sqmm compression type with 6 mm dia. stud hole 60 12 72 ea

5 Tinned copper cable lug for 10 sqmm compression type with 10 mm dia. stud hole 68 14 82 ea

6 Tinned copper cable lug for 16 sqmm compression type with 10 mm dia. stud hole 8 2 10 ea 0.4
7 Tinned copper cable lug for 35 sqmm compression type with 12 mm dia. stud hole 12 2 14 ea

8 Tinned copper cable lug for 50 sqmm compression type with 12 mm dia. stud hole 8 2 10 ea

9 Tinned copper cable lug for 70 sqmm compression type with 12 mm dia. stud hole 24 5 29 ea

10 Tinned copper cable lug for 95 sqmm compression type with 12 mm dia. stud hole 4 2 6 ea

11 Tinned copper cable lug for 120 sqmm compression type with 14 mm dia. stud hole 8 2 10 ea

12 Tinned copper cable lug for 150 sqmm compression type with 14 mm dia. stud hole 22 4 1 0 0 0

13 Tinned copper cable lug for 185 sqmm compression type with 14 mm dia. stud hole 10 2 12 ea

H.2 CABLE ACCESSORIES

1 Wire Identification / Marker

- Printer Machine Canon MK 2500 or equal c/w Tube, for Wire Marker 1 0 1 Set

- PVC sleeve tube for wire cross section 1.5 sqmm 10 2 12 m

- PVC sleeve tube for wire cross section 2.5 sqmm 14 3 17 m

- Tape Ink 9 1 10 ea

2 Cable Identification / Marker, 316L stainless steel embossed labels


- Cable Marker Machine to produce high quality embossed markers on 316L stainless steel
1 0 1 ea
material.
- Marker Strips, Size 95mm (L) x 12mm (H) 316LSS Material 100 20 120 ea

- Cable Ties 316LSS Material, Suitable for Fixing Marker Strips 100 20 120 ea

3 Self locking cable ties, PVC or nylon coated 316L SS material, for fixing cable

The Following Size :

- 300mm" (L) x 12mm" (W) Cable Ties, Quantity 100 Pcs/Pack 8 2 10 ea

- 300mm" (L) x 12mm" (W) Cable Ties, Quantity 100 Pcs/Pack 15 3 18 ea

- 450mm" (L) x 12mm" (W) Cable Ties, Quantity 100 Pcs/Pack 10 2 12 ea

Phase colour identifier elastic shrink sleeve over the cable core (Red, Black, Brown, Grey,
4 Blue, Green), UV Resistant, flame retardant suitable for 1000V cable with the following cable
cross section size:
- 2.5 sqmm 9 2 11 m

- 4 sqmm 2 1 3 m

- 6 sqmm 2 1 3 m

- 10 sqmm 2 1 3 m

- 16 sqmm 1 1 2 m

- 35 sqmm 1 1 2 m

- 50 sqmm 1 1 2 m

This document is the property of PT. Pertamina Hulu Mahakam and shall not be disclosed to third parties or reproduced without permission of the COMPANY.
Electronic Filename: 752293983.xlsx
- 70 sqmm 1 1 2 m

- 95 sqmm 1 1 2 m

- 120 sqmm 1 1 2 m
15 of 32+9......................................................
- 150 sqmm 2 1 3 m

- 185 sqmm 2 1 3 m

Name plate / Tag no. shall be Stainless Steel 316, screwed and affixed, with black letters
5 1 0 1 roll 1 roll = 10m
5mm height as a minimum

H.3 LIGHTING ACCESSORIES

1 Galvanized Carbon Steel Pipe, dia. 50mm, (Ø 2") SCH-40 4 1 5 ea Standard length 6 m/ea

2 Galvanized Carbon Steel Pipe, dia. 76mm, (Ø 3") SCH-40 6 1 7 ea Standard length 6 m/ea

3 Fixing bracket for lighting pole 50mm OD (Ø 2"), HDG 26 5 31 ea

4 Insulated bushing suitable for lighting pole 50 mm OD (Ø 2") 26 5 31 ea

Nickel Plate Brass Blanking Plug, M20 x 1.5, ATEX certified or IECEx Scheme equivalent, Ex
5 45 9 54 ea
"d" and Ex "e", IP66 and IK08 for zone 1, gas group IIA, temp.T3

6 3" X 2" O.D Reducer SCH.40 26 5 31 ea

H.4 BOLT, NUT AND WASHER

1 M12 x 75L SS 316L hex head bolt, nut and flat, lock and insulating washers 100 20 120 ea

2 M8 x 25L SS 316L hex head bolt, nut and flat, lock and insulating washers 100 20 120 ea

3 M6 x 25L SS 316L hex head bolt, nut and flat, lock and insulating washers 100 20 120 ea

4 Full Threaded M6 x 1000(L) 10 2 12 ea Standard length 1 m/ea

H.5 STEEL MATERIAL

Steel Angle 50mm x 50mm x 6mm thk, painted according to painted according to MHK- Standard length 6 m/ea
1 86 17 103 ea
COMP-SPE-COR-0350 (included panel support)

Steel Channel 100 x 50 x 5mm thk, painted according to painted according to MHK-COMP- Standard length 6 m/ea
2 110 22 132 ea
SPE-COR-0350 (included panel support)

Steel Plate Standard Size 2.4mm(L) x 1.2mm (W) x 5mm Thk. painted according to MHK-
3 2 0 2 ea
COMP-SPE-COR-0350

Steel Plate Standard Size 2.4mm(L) x 1.2mm (W) x 10mm Thk. painted according to MHK-
4 2 0 2 ea
COMP-SPE-COR-0350

H.6 ACCESSORIES

1 U-bolt M10 for Ø1 1/2" pipe c/w 2 hex nuts & washer 316LSS with insulation 18 4 22 ea

2 Hanger Clevis for lighting pendant mounted 18 4 22 ea

3 Ø1" PVC pipe 15 3 18 ea Standard length 6 m/ea

4 Rigid conduit 1" 20 4 24 ea Standard length 6 m/ea

5 Rigid conduit 1 1/2" 10 2 12 ea Standard length 6 m/ea

6 Compound seal 20 4 24 kg Standard 1 kg/ea

Notes:
1. This MTO is indicative and CONTRACTOR shall be responsible for review, verify and finalize base on actual data during detail design.

This document is the property of PT. Pertamina Hulu Mahakam and shall not be disclosed to third parties or reproduced without permission of the COMPANY.
Electronic Filename: 752293983.xlsx
No. Rev. No. Cable Tag Number Voltage (V) From Tag No. From Description
37 C1 CC-PGCP-6101B-01 - GT-6101B GAS TURBINE GENER
19 C1 CC-PGCP-6101A-01 - GT-6101A GAS TURBINE GENER
From Location From Gland Hazardous From Gland Non Hazardous To Tag No.
MOPU TOP SIDE A M25 - PDP-6101
MOPU TOP SIDE A M25 - PDP-6101
To Description To Location To Gland Hazardous To Gland Non Hazardous Scope
3.6kV MV SWITCHGELECTRICAL EQ- M25 GTG RENT
3.6kV MV SWITCHGELECTRICAL EQ- M25 GTG RENT
Armour / Non-armour Fire Resistant
Voltage Grade Estimated Cable Length (Mtr.)
NON-ARMOUR FLAME RE0.6/1 kV 65
NON-ARMOUR FLAME RE0.6/1 kV 70
Cable OD (mm) Number of Core Cable Size (mm2)
15 6/C 6
15 6/C 6
Scope Voltage Grade Flame Retardant / Fire ReArmour / Number ofCable Si Sum of Estimated Cable Length (Mtr.)
CONTRACTOR
- 178
0.6/1 kV
FIRE RESISTANT
NON-ARMOUR
2/C
1.5 160
6 100
10 20
16 160
35 100
120 42
2/C+E
2.5 80
4 1501
6 310
10 528
16 68
25 80
4/C+E
10 50
FLAME RETARDANT
NON-ARMOUR
12/C
1.5 3218
2/C
1.5 828
2.5 80
2/C+E
2.5 2973
4 1021
6 88
2/C+SHLD
4 84
3/C
2.5 30
3/C+E
2.5 85
4 3373
6 240
10 396
25 211
35 334
50 223
70 228
185 390
240 297
3/C+E+SHLD
4 327
6 152
10 304
95 134
3/P+OS
1.5 415
3/T+OS
1.5 456
30/P+OS
1.5 264
4/C
1.5 430
2.5 89
4 89
4/C+E
4 23
6 21
95 14
150 12
6/C
1.5 30
6/P+OS
1.5 33
6/T+OS
1.5 150
7/C
1.5 1724
(empty)
(empty)
ARMOUR
(empty)
(empty) 45
GTG RENTAL VENDOR
- 80
0.6/1 kV
FIRE RESISTANT
NON-ARMOUR
2/C
1.5 96
25 28
50 206
2/C+E
2.5 158
50 136
FLAME RETARDANT
NON-ARMOUR
1/C
120 80
2/C
1.5 457.5
4 29.5
6 180
2/C+E
2.5 834.5
4 140
6 189
10 52
2/C+SHLD
4 315
3/C+E
4 685
6 137
3/C+E+SHLD
6 171
95 171
30/C
1.5 38
4/C
1.5 411
4 135
4/C+E
4 46
6/C
1.5 185
6 135
7/C
1.5 100
9/C
1.5 82
1.8/3 kV
FLAME RETARDANT
NON-ARMOUR
1/C
120 140
3.6/6 kV
FLAME RETARDANT
NON-ARMOUR
3/C
185 510
(empty)
(empty)
NON-ARMOUR
(empty)
(empty)
(empty)
(empty)
(empty)
(empty)
0.6/1 kV
FLAME RETARDANT
NON-ARMOUR
9/C
1.5 23.5
(empty)
9/C
1.5 21.5
(empty)
(empty)
(empty)
(empty)
.
(empty)
EARTHING CABLE
D-200- D-200- D-200-
MAC- MAC- MAC-
D-200-MAC-MOPU-40301
MOPU- MOPU- MOPU-
40302 40303 40304

Scrubbers (Lower Deck)


Power Generation

Power Generation

Compressor &
Battery Room

(Starboard)
(Port)
EER

IER
SIZE

TOTAL UNIT
1C - 6 → 0 M
1C - 16 → 40 M
1C - 35 → 0 M
1C - 70 → 0 M
1C - 120 → 0 M
MAC-

40305
Drill Deck

D-200-

MOPU-
MAC-

40306
Coolers (Upper Deck)
D-200-

MOPU-

TEG Reg. & Flare KO


MAC-

40307
D-200-

MOPU-

Drum (Shale Shaker)


MAC-

40308

Skid Beam Area


D-200-

MOPU-

Flexible Jumper
MAC-

40309
D-200-

MOPU-

Balcony
MAC-

40310

DPCU (Port)
D-200-

MOPU-
MAC-

40311

Flare Boom Area


D-200-

MOPU-

LCS

JOINT TRAY

PIN RAISER

POLE

JB
earth tag
LIGHTING CABLE LIGHTING CABLE

Outside Armoured Size Lenght

2C+e 2,5 2743

Size
2C+e

2653
4

4C+e 2,5 2043.5 2C+e 2,5

Armoured
2C+e 4

Un -
Armoured Size Lenght

2C+e 2,5 60.5 2C+e 2,5

Armoured
4C+e 2,5 262 2C+e 4

Inside 4C+e 2,5

Un -
Size Lenght
Armoured
2C+e 2,5 152
2C+e 4 96
comp. & drill SO

88 118 73
cooler SO

skid beam & gen port F & DCPU

125
gen port HPS

103
skid beam & gen stbd F

104

75
gen stbd HPS

TEG F

142

90
TEG HPS

skid beam F

132
skid beam HPS

93 92
flare HPS

comp. F1

comp. F2

136 116
comp. HPS

104
drill F
163
PLP-6201 (D-200-MAC-MOPU-44030)

drill HPS
90 111 cooler HPS1

cooler F1

cooler F2

cooler F3
133 154 160

cooler HPS2

TEG HPS
105 102
77
Dpcu HPS

EER F1

EER F2

74 64 64
TR F

EER SO1

EER SO2

35 35 35
TR SO

skid beam & DCPU - SO

comp. & srub. - SO

cooler - SO

WHP - HPS (to JB Interface)

108 73 73 78 78
WHP - SO (to JB Interface)
Lenght

TEG - F

skid beam & bridge - F

110 141
PLP-6202 (D-200-MAC-MOPU-44031)

79
skid beam & bridge - HPS

comp. & scrub. - F

drill - F

cooler - F1

cooler - F2
179 115 142 131

70

DCPU HPS

EER - F1
53 53

EER - F2
38

EER - SO
Nav. Aids CP (PNP-9901)

Nav. Aids CP (JB 2) - PNP-9902

Nav. Aids CP (JB 2) - PNP-9903

78 78 78 78
Nav. Aids CP (JB 2) - PNP-9904

gen port - F

DCPU port - F

gen STBD - F

TEG - F

skid beam & bridge - F1

skid beam & bridge - F2

comp. & scrub. - F1

comp. & scrub. - F2


PLP-6203 (D-200-MAC-MOPU-44031)

comp. & scrub. - F3

drill - F

cooler - F1

cooler - F2

cooler - F3

cooler - F4

WHP - JB 3

flare - HPS

TOTAL
105
202

121 134 143 187 131 131 109 141 107 138 145 163 133 133 78 92 2190
2230
2180
REV C

Selisih

192 10

105 0

2066 114

1892 338

2120 69.5