SECONDARY CHILLED WATER PUMP HEAD LOSS CALCULA

Flow Pipe Size Friction Loss Length No. of Equivalent Length


Section (gpm) (inch) Description (ft/100 ft water) (ft) Fittings of fitting (ft)

pipe 3.8 25 0 0.00


butterfly valve 3.8 0 2 15.10
L-O 250 4
elbow 90 degrees 3.8 0 2 10.00
tee (branch flow) 3.8 0 1 21.00
pipe 3.8 20 0 0.00
elbow 90 degrees 3.8 0 2 7.50
butterfly valve 3.8 0 2 11.51
O-R 125 3 strainer 3.8 0 1 42.00
check valve 3.8 0 1 30.00
balancing valve 3.8 0 1 35.00
tee (branch flow) 3.8 0 1 15.00
pipe 3.8 25 0 0.00
R-T 250 4 elbow 90 degrees 3.8 0 1 10.00
tee (straight flow) 3.8 0 1 6.70
pipe 3.8 25 0 0.00
reducer 3.8 0 1 2.60
T-V 125 3 tee (branch flow) 3.8 0 1 15.00
gate valve 3.8 0 1 3.20
strainer 3.8 0 1 42

Pump Head (ft)


LOSS CALCULATION
Head Loss
Total Equivalent
(ft of
Length (ft)
water)
25.00 0.95
30.20 1.15
20.00 0.76
21.00 0.80
20.00 0.76
15.00 0.57
23.02 0.87
42.00 1.60
30.00 1.14
35.00 1.33
15.00 0.57
25.00 0.95
10.00 0.38
6.70 0.25
25.00 0.95
2.60 0.10
15.00 0.57
3.20 0.12
42.00 1.596

Pump Head (ft) 15.42