Professional Documents
Culture Documents
InTech-December-2021_16
InTech-December-2021_16
Relative flow
Installed gain
3.0
factor at the high end of the range. The 0.6 2.5
Pressure
80
a 10-inch high-performance butterfly 70
60
valve would cost approximately one- 50
P2
Flow capacity, C V
0.6 2000
between linear and equal percentage.
The upper right graph in figure 5 0.4
1000
3.0
and maximum design flows. The gain
Installed gain
0.6 2.5
1.0
the butterfly valve is 1.4:1, where the 0.2
0.5
Which pressure drop? The ideal situation is where the person ered, and the one that allows satisfac-
A question arose regarding the pres- selecting the control valve has a say tory controllability while minimizing
sure drop to use when sizing a control in determining what the control valve energy consumption will be selected.
valve. Assuming a system that has al- pressure drop will be, most often by Curves of P1, the pressure just upstream
ready been designed, the sizing pres- specifying the pump that will be used. of the valve, are shown for each of the
sure cannot be arbitrarily assigned, Using an installed gain analysis of vari- three pumps, along with the power re-
but the values of P1 and P2 need to be ous pumps that might be suitable can quired by each at a normal flow rate of
obtained by an analysis of the friction- be helpful. 400 gpm. These curves slope downward
al pressure losses and static pressure To demonstrate how this can be in proportion to the flow squared from
changes in the system both upstream done, three possible pumps for the sys- the 100 gpm pump head (45, 60, and 75
and downstream of the control valve. tem shown in figure 6 will be consid- psig, respectively, for pumps A, B, and
Pressure losses 5 15 5
@600 gpm
Pump head
6” Sch 40
drops 5 psi
from 100 gpm 70°F
to 600 gpm 10
Water P1 P2
TC
80 75 P1 (Pump C) 29 hp*
70 65
60 P1 (Pump B) 23 hp*
60
50
65 50 45 P1 (Pump A) 17 hp* 35
35 20 Pressure units: psig
50 40
5
35 30
20 P2 30
=% Inherent 10
10
characteristic
0
0 100 200 300 400 500 600
* At 400 gpm
Installed GainGain
Installed flow Installed
Installed gain
1.0 40
4.0
5 psi, 17 hp *
600 gpm
100 gpm
3.5
3..5
5 6” valve 35 psi, 29 hp *
0.8 3” valve
)/dh
30
3.0
Relative flow
* At 400 gpm
0.4 1.5
1.5
Gain, Gain,
20 psi, 23 hp *
10
1.0 3” valve
0.2
0.5
0.5
* At 400 gpm
0.0
0
0.0
0 0.1
0.1 0
0.2
.2 0
0.3
..3
3 0
0.4
0..4 0
0.5
.5 00.6
..6
6 0
0.7
..7
7 0
0.8
.8 0
0.9
.9 1 1.1
1.1 1.2
1..2
2
0.0 0.2 0.4 0.6 0.8 1.0
Q/Qmax
Relative travel
Relative Travel Q/Q max
Figure 6. Control valve installed gain analysis helps balance pumping energy and process controllability.
Segment valve graphic courtesy of Neles
C) to a pressure 10 psi lower due to the difference between P1 and P2) are indi- three cases. What is interesting is the
combined effect of the 5 psi pressure cated in the figure by the arrows at the installed gain graphs.
loss in the upstream piping and the 5 left side of the figure for 100 gpm and at With the 17-hp pump, besides requir-
psi decrease in pump head from 100 the right side of the figure for 600 gpm. ing a more expensive 6-inch valve, the
gain graph looks terrible. The installed
gain is the highest of the three (meaning
a larger flow error for the same valve posi-
The ideal situation is where the person selecting the tion error), it drops to 0.4 as it approach-
control valve has a say in determining what the control es the maximum design flow (the red
vertical line at 1.0 on the Q/Qmax scale),
valve pressure drop will be, most often by specifying the and the variation in gain over the flow
pump that will be used. range is almost 7:1, much greater than
the recommendation of 2:1. This is large
enough that it would be difficult to come
gpm to 600 gpm stated in the figure. The analysis is performed based on up with proportional-integral-derivative
The curve for P2, the pressure at the con- using a segment ball valve. The graph (PID) tuning parameters that would pro-
trol valve outlet, starts with the 10 psig in the lower left of figure 6 shows the vide good and stable control over the en-
static head of the tank at very low flows calculated installed flow characteris- tire required flow range. The gain graphs
and increases in proportion to the flow tics. Keep in mind the installed flow of the 23-hp and 29-hp pumps fall within
squared to 30 psig as the downstream graphs generated by the worksheet of the recommended gain criteria, but the
piping and heat exchanger pressure the reference 4 graph is relative flow, 23-hp pump is the winner, because its
losses increase to their 600 gpm values. so 1.0 is 100 percent of the fully open gain is closer to 1.0, and it also is the more
The control valve pressure drops (the flow, which is different for each of the economical of the two to operate. n