MDP

Amperes
PB4
Amperes
GENERAL NOTES:
Circuit Load Description Circuit Breaker Circuit Load Description Circuit Breaker
VA Voltage Size of Conductor Size of Conduit VA Voltage Size of Conductor Size of Conduit
No. No.
Load Qty AB BC CA AT Pole AF Load Qty AB BC CA AT Pole AF
1. ALL ELECTRICAL WORKS INCLUDED HEREIN SHALL BE EXECUTED IN
1 Panel Board-1 1 23,050 104.77 220 125 2 150 2- 38mm2 THHN Cu. Wire 40 mm Dia PVC Conduit 1 8- Lighting Outlet 8 800 3.64 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE
2 Panel Board-2 1 14,900 67.72 220 100 2 100 2- 30mm2 THHN Cu. Wire 50 mm Dia PVC Conduit 2 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit PHILIPPINE ELECTRICAL CODE, IEEE, NEC, NEMA, THE RULES AND
3 Panel Board-3 1 4.300 81.59 220 60 2 100 2- 22mm2 THHN Cu. Wire 32 mm Dia PVC Conduit 3 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit REGULATION OF THE LOCALITY, AND THE REQUIREMENT OF THE POWER
4 Panel Board-4 1 16,700 19.54 220 100 2 150 2- 30mm2 THHN Cu. Wire 32 mm Dia PVC Conduit 4 2- Convenience Outlet 2 300 1.36 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
UTILITY COMPANY.

5 Panel Board-5 1 17,950 75.90 220 150 2 200 2- 50mm2 THHN Cu. Wire 50 mm Dia PVC Conduit 5 Spare 1,000 4.55 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 2. ALL ELECTRICAL WORKS INCLUDED HEREIN SHALL BE EXECUTED BY
EXPERIENCED MEN UNDER THE DIRECT SUPERVISION OF A FULL TIME
6 Panel Board-6 1 4,700 21.36 220 100 2 100 2- 30mm2 THHN Cu. Wire 50 mm Dia PVC Conduit 6 Spare 1,000 4.55 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
LICENSED ELECTRICAL ENGINEER, WORKS SHALL BE NEATLY PLACED.
TOTAL 81,600 124.31 143.62 102.95 TOTAL 4,300 5.0 7.27 7.27
SECURELY FASTENED PROPERLY FINISHED.
3. INCOMING VOLTAGE SYSTEM SHALL BE 220, THREE-PHASED 3 WIRE PLUS
ICB = 370.90 Amperes Therefore Use:
ICB = 19.54 Amperes Therefore Use: GROUND, 60HZ SYSTEM.
@ 80% DF 296.72 Amperes 3 - 300mm2 THHN Cu. Wire
@ 80% DF 15.63 Amperes 2 - 22mm2 THHN Cu. Wire
1 - 100mm Dia PVC/RSC
1 - 32mm Dia PVC/RSC
Therefore Use: 400AT/500AF, CB, 3P
Therefore Use: 60AT/100AF, CB, 3P
4. MATERIALS SHALL BE NEW AND SHALL CONFORM WITH THE STANDARD
BOLT-ON TYPE MCCB
IN NEMA 4X ENCLOSURE BOLT-ON TYPE MCCB
IN NEMA 1 ENCLOSURE
AMERICAN UNDERWRITER'S LABAROTORIES INC., IN EVERY CASE WHERE
SUCH STANDARDS HAS BEEN ESTABLISHED FOR THE PARTICULAR TYPE OF
MATERIAL IN QUESTION.

5. WHENEVER NECESSARY, PULLBOX OF PROPER SIZES AND DIMENSION


SHALL BE PROVIDED ALTHOUGH NOT INDICATED IN THE PLAN.
6. ALL CONDUIT SHALL BE PROTECTED AGAINST DAMAGES BY THE ENTRANCE
PB1 PB3 OF WATER NAD FOREIGN MATTER DURING CONSTRUCTION.
Circuit Load Description
VA
Amperes
Voltage
Circuit Breaker
Size of Conductor Size of Conduit
Circuit Load Description
VA
Amperes
Voltage
Circuit Breaker
Size of Conductor Size of Conduit
ALL ENDS OF CONDUITS SHALL BE PLUGGED TO EXECUTE MOISTURE AND
No. No.
Load Qty AB BC CA AT Pole AF Load Qty AB BC CA AT Pole AF DUST IMMEDIATELY AFTER THE CONDUITS ARE PLACED.
1 3- Lighting Outlet 3 300 1.36 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 1 8- Lighting Outlet 8 800 3.64 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
7. ALL CONDUITS BENDS SHALL BE FIELD MADE USING HYDRAULIC BENDERS.
2 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 2 8- Lighting Outlet 8 800 3.64 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit MINIMUM BENDING RADIUS SHALL BE IN ACCORDANCE WITH THE CODE.
2 2
3 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm THHN Cu. Wire 20 mm Dia PVC Conduit 3 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm THHN Cu. Wire 20 mm Dia PVC Conduit
8. ALL PIPES AND FITTINGS ON EXPOSED WORK SHALL BE SUPPORTED AND
4 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 4 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit SECURED BY MEANS OF C-CHANNELS, TUBULAR, ANGLE BAR AND CLAMPS.
5 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 5 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
9. ALL FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED
6 4- Lighting Outlet 4 400 1.81 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 6 8- Lighting Outlet 8 800 3.64 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
ON PLANS. INDIVIDUAL BRANCH CIRCUIT HOMERUNS SHALL NOT BE
7 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 7 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit COMBINED IN THE SAME RACEWAY UNLESS SO INDICATED.
8 3- Lighting Outlet 3 300 1.36 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 8 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
10. ROUTING OF CONDUIT SHOWN ON DRAWING ARE APPROXIMATELY ONLY
9 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 9 9- Lighting Outlet 9 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit CONTRACTOR SHALL ALLOW NECESSARY FIELD ADJUSTMENTS TO SUIT
10 10- Lighting Outlet 10 1,000 4.55 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 10 6- Convenience Outlet 6 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit ACTUAL CONDITION AT SITE.
11 7- Lighting Outlet 7 700 3.18 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 11 8- Convenience Outlet 8 1,200 5.45 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 11. ALL PANELBOARDS SHALL BE PROVIDED WITH GROUNDING BUS BAR THE
12 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 12 7- Convenience Outlet 7 1,050 4.77 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
GROUNDING BUS BAR SHALL BE CONNECTED TO THE SYSTEM GROUNDING.
13 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 13 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 12. ALL METALLIC CONDUIT, CABINET, BOXES AND EQUIPMENT SHALL BE
14 6- Lighting Outlet 6 600 2.72 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 14 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit PROPERLY GROUNDED AND BONDED.
15 5- Convenience Outlet 5 750 3.40 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 15 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 13. MOUNTING HEIGHT NOT SHOWN ON THE SCHEDULE ARE AS FOLLOWS:
16 8- Convenience Outlet 8 1,200 5.45 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 16 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit PANEL BOARD - 1.40 METER ABOVE FINISHED FLOOR TO CENTER OF PANEL.
17 10- Convenience Outlet 10 1,500 6.81 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 17 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 14. ALL ITEMS OF MATERIAL NOT FURNISHED BY REQUISITION AND REQUIRED
18 6- Convenience Outlet 6 900 4.10 220 20 2 50 2- 3.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 18 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit TO COMPLETE THE INSTALLATION IN A GOOD, WORKMANLIKE MANNER
SHALL BE PROVIDED BY THE CONTRACTOR. THESE ITEMS MAY CONSIST OF
19 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 19 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
MISCELLANEOUS STEEL SUPPORTS, CONDUIT STRAP, CONDUIT SUPPORTS
20 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 20 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit WIRE CONNECTORS, CONDUIT CAPS AND PLUGS, UNION INSULATIONS
21 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 21 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit TAPES SEALING FIBER AND COMPOUND, AND MASONRY ANCHORS, NUTS
22 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 22 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
AND BOLTS.

23 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 23 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 15. THE ELECTRICAL CONTRACTOR SHALL EXAMINE AND STUDY THE
24 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 24 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
ARCHITECTURAL DRAWING, LARGE SCALE AND FULL SIZE DETAILS.
APPROVED SHOP DRAWINGS FROM OTHER TRADERS, AND SHALL
25 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 25 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
FREQUENTLY CONSULT AND COORDINATE WITH OTHER TRADES TO AVERT
26 1 A/C unit (1.0 hp) 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 26 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit CONFLICT IN ACTUAL SITE INSTALLATION WORKS.
27 Spare 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 27 1 A/C unit (0.5 hp) 1 400 1.81 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit
16. THE PLANS AS DRAWN ARE BASED UPON THE ARCHITECTURAL PLANS AND
28 Spare 1 1,000 4.55 220 30 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit 28 Spare 1 1,000 4.55 220 20 2 50 2- 5.5mm 2 THHN Cu. Wire 20 mm Dia PVC Conduit THE DETAILS AND SHOWN CONDITION AS ACCURATELY AS IT IS POSSIBLE
TO INDICATE THEM IN SCALE. THE PLANS ARE DIAGRAMMATICAL AND DOES
TOTAL 23,050 39.1 34.16 32.5
NOT NECESSARILY SHOWN ALL FITTINGS NEEDED TO FIT THE BUILDING
TOTAL 17,950 29.54 26.43 25.66
ICB = 104.77 Amperes Therefore Use:
CONDITIONS THE LOCATIONS OF OUTLETS, APPARATUS AND APPLIANCES
@ 80% DF 83.81 Amperes 2 - 38mm2 THHN Cu. Wire ICB = 81.59 Amperes Therefore Use:
SHOWN ON THE PLANS ARE APPROXIMATE THE CONTRACTOR SHALL BE
1 - 40mm Dia PVC/RSC
@ 80% DF 65.27 Amperes
3 - 50mm2 THHN Cu. Wire
HELD RESPONSIBLE FOR THE PROPER LOCATION IN ORDER TO MAKE THEM
Therefore Use: 125AT, CB, 3P
BOLT-ON TYPE MCCB 1 - 50mm Dia PVC/RSC FIT WITH THE ARCHITECTURAL DETAILS AND INSTRUCTION FROM THE
IN NEMA 1 ENCLOSURE Therefore Use: 150AT/200AF, CB, 3P
BOLT-ON TYPE MCCB OWNER'S REPRESENTATIVE AT SITE.
IN NEMA 1 ENCLOSURE

LOAD SCHEDULE GENERAL NOTES


NOT TO SCALE NOT TO SCALE

CONTRACTOR ENGINEER PROJECT TITLE OWNER OWNER'S APPROVAL SHEET CONTENT SHEET NO.

GENERAL NOTES

PRC NO: VALIDITY:


LOAD SCHEDULES
SINGLE LINE DIAGRAM E1