KSEB Electrical Equipment Specifications
KSEB Electrical Equipment Specifications
11KV,630A
20/5A LOAD BREAK SFU
11KV SUPPLY WITH S/T COIL
3X150SQMM
FROM EB 15VA CL:0.5 XLPE AL,3M
3X150SQMM 1A 40A
XLPE AL 11KV/110V
415V,3PH,50HZ,500kVA,DG SET
100VA,CL:0.5 [WITH ACCOUSTIC ENCLOSURE]
2A
2A R Y B
2A R Y B CL:590HP+30kW+185kVAR
51G 51G MD: 390KVA
MSB 800A 4P ACB
45-50 Hz
Vss V F
LOC:SUBSTATION SET AT 670A WITH 800A 4P ACB
52 3O/C+1E/F +U/V & S/T 52 SET AT 700A WITH
RELEASES 3O/C+1E/F +U/V & S/T
AMF RELEASES
A A
Signature of Client
800/5A 800/5A
MFDM KWH MFDM
15VA CL:1 15VA CL:1
2A 2A
800/5A
TO APFC RELAY
15VA CL:1 2x50X10MM AL FOR PH
2Cx1.5sqmm
1x50X10MM AL FOR N
400A TPN 250A TPN 250A TPN 250A TPN 500A TPN 250A TPN 250A TPN
35kA MCCB 35kA MCCB 35kA MCCB 35kA MCCB 35kA MCCB 35kA MCCB 35kA MCCB
SET AT SET AT SET AT SET AT SET AT
320A 200A 200A 200A 400A
400A TPN
ISO. Signature of Contractor& Supervisor
M 35KVAr
EQ.NO./FEEDER NO.
CAPACITOR
EQUIPMENT DESCRIPTION MOTOR 1 SSB1 SSB2 SSB3 PANEL SPARE SPARE
RATING IN KW /HP 150 HP+35 kVAr 145 HP+15 KW 145 HP+15 KW 150 HP 150kVAr
Signature of Contractor & Supervisor
RATED VOLTAGE IN VOLTS 415 415 415 415 415
SWITCH RATING IN AMPS 400 250 250 250 500
BACK UP FUSE IN AMPS 320 200 200 200 400
CABLE SIZE IN SQ.MM (AL) 3C X 300 3.5C X 240 3.5C X 240 3.5C X 240 1R X 3.5C X 400
LENGTH OF CABLE IN M -- -- -- -- --
EARTHING CONDUCTOR SIZE 25X3 25X3 25X3 25X3 25X3
LEGENDS
DRAWOUT TYPE SWITCH DISCONNECTOR
52 ISOLATOR FUSE UNIT[SFU] DOL STARTER CAPACITOR MFDM MULTI-FUNCTION DIGITAL
AIR CIRCUIT BREAKER[ACB] METER [It Includes
V,A,kVa,kW,PF METERS ]
FROM MSB
3.5X240 SQMM
XLPE --M
2A
RYB
CL:145HP+15KW
TYPICAL SSB 1 & 2 2A 45-55HZ
F Vss V 0-415V
DF:1.5
250A
TPN
ISO
200/5A A A A (0-200A)
15VA CL:1
80A 80A 80A 50A 50A 32A 80A 40A 32A 63A
25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN
SET AT 63A SET AT 63A SET AT 63A SET AT 40A SET AT 40A SET AT 25A SET AT 63A SET AT 32A
M M M M M M
EQ.NO./FEEDER NO.
Client
Title
Drawn by: Approved:
Checked by: Date:
Scale:NTS Drg. No:
For the use of Electrical Inspectorate
FROM MSB
3.5X240 SQMM
XLPE --M
2A RYB
CL:150HP
2A 45-55HZ
F Vss V 0-415V
DF:1.5
SSB 3 250A
TPN
ISO
200/5A A A A (0-200A)
15VA CL:1
50X6 MM AL FOR PH
25X6 MM AL FOR N
Signature of Client
80A 80A 80A 50A 50A 32A 80A 32A 32A 63A
25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN 25 kA TPN
SET AT 63A SET AT 63A SET AT 63A SET AT 40A SET AT 40A SET AT 25A SET AT 63A
M M M M M M
EQ.NO./FEEDER NO.
VDB:3
EQUIPMENT DESCRIPTION MOTOR 8 MOTOR 9 MOTOR 10 MOTOR 11 MOTOR 12 MOTOR 13
[VTPN MCB DB] SPARE SPARE SPARE
RATING IN KW /HP 25HP 25HP 25HP 15HP 15HP 10HP 35HP
RATED VOLTAGE IN VOLTS 415 415 415 415 415 415 415
SWITCH RATING IN AMPS 80 80 80 40 40 32 80
BACK UP FUSE IN AMPS 63 63 63 35 35 25 63
CABLE SIZE IN SQ.MM (AL) 3C X 25 3C X 25 3C X 25 3C X 10 3C X 10 3C X 6 3.5C X 35
LENGTH OF CABLE IN M 5 5 5 5 5 5 5
EARTHING CONDUCTOR SIZE 10 10 10 10 10 10 10
Client
Title
Drawn by: Approved:
Checked by: Date:
Scale:NTS Drg. No:
For the use of Electrical Inspectorate
FROM SSB1/SSB2
3.5C X 25SQMM
XLPE --M
TYPICAL CL:30HP
DF:1.5
VDB 1&2 100A
TPN
ISO
Signature of Client
8W VTPN MCB DB
M M M M M M
EQ.NO./FEEDER NO.
EQUIPMENT DESCRIPTION MOTOR 14 MOTOR 15 MOTOR 16 MOTOR 17 MOTOR 18 MOTOR 19 SPARE SPARE
Signature of Contractor &Supervisor
RATING IN KW /HP 7.5HP 7.5HP 5HP 5HP 3HP 2HP
RATED VOLTAGE IN VOLTS 415 415 415 415 415 415
SWITCH RATING IN AMPS 40 40 32 32 25 16
BACK UP FUSE IN AMPS 32 32 25 25 16 10
CABLE SIZE IN SQ.MM (AL) 3CX6 3CX6 3CX4 3CX4 3CX4 3CX4
LENGTH OF CABLE IN M 5 5 5 5 5 5
EARTHING CONDUCTOR SIZE 10 10 10 10 10 10
Client
Title
Drawn by: Approved:
Checked by: Date:
Scale:NTS Drg. No:
For the use of Electrical Inspectorate
FROM SSB3/
3.5C X 25SQMM
XLPE --M
CL:35HP
DF:1.5
VDB 3 100A
TPN
ISO
M M M M M M M
EQ.NO./FEEDER NO.
EQUIPMENT DESCRIPTION MOTOR 14 MOTOR 15 MOTOR 16 MOTOR 17 MOTOR 18 MOTOR 19 SPARE SPARE
Signature of Contractor &Supervisor
RATING IN KW /HP 7.5HP 7.5HP 5HP 5HP 5HP 3HP 2HP
RATED VOLTAGE IN VOLTS 415 415 415 415 415 415 415
BACK UP FUSE IN AMPS 32 32 25 25 25 16 10
CABLE SIZE IN SQ.MM (AL) 3CX6 3CX6 3CX4 3CX4 3CX4 3CX4 3CX4
LENGTH OF CABLE IN M 5 5 5 5 5 5 5
EARTHING CONDUCTOR SIZE 10 10 10 10 10 10 10
Client
Title
Drawn by: Approved:
Checked by: Date:
Scale:NTS Drg. No:
For the use of Electrical Inspectorate
FROM SSB1/SSB2
4C X 6SQMM
XLPE --M
TYPICAL CL:15KW
VDB 32A DF:1.5
[LIGHTING & POWER]
TPN
ISO
4W VTPN MCB DB
Signature of Client
EQ.NO./FEEDER NO.
6A 16A/20A
SP SP
MCB MCB
FROM MSB
2A R Y B
CAPACITOR PANEL 150 KVAr
2A
VSS (0-500V)
400A TPN 2x 1.5 SQ. MM. CU. TO CT AT Y-PHASE
ISO.
2A IN MSB
APFCR
400/5A
CL:1, (0-400A)
50x10 MM AL- PH
50x6 MM AL- N 15VA
Signature of Client
80A 80A 80A 80A 63A 50A 20A 50A 63A
25 kA TP 25 kA TP 25 kA TP 25 kA TP 25 kA TP 25 kA TP 25 kA TP 25 kA TP 25 kA TP
SET AT 63A SET AT 63A SET AT 63A SET AT 63A SET AT 50A SET AT 40A SET AT 16A SET AT 40A
EQUIPMENT DESCRIPTION CAPACITOR-1 CAPACITOR-2 CAPACITOR-3 CAPACITOR-4 CAPACITOR-5 CAPACITOR-6 CAPACITOR-7 CAPACITOR-8 SPARE
RATING IN KW / HP/KVAr KVAr KVAr KVAr KVAr KVAr KVAr KVAr KVAr
CONNECTED LOAD 25 25 25 25 20 12.5 5 12.5
RATED CURRENT IN AMPS 35 35 35 35 28 17.5 7 17.5
SIZE IN SQ.MM 16 16 16 16 10 6 4 6
POWER
CABLE RUNS X NO: OF CORES 4 4 4 4 4 4 4 4 Signature of Contractor &Supervisor
A2XFY 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
LENGTH IN METERS
BACK UP FUSE IN AMPS 63 63 63 63 50 40 16 40
EARTHING CONDUCTOR IN SWGCU. 10SWG 10SWG 10SWG 10SWG 10SWG 10SWG 10SWG 10SWG
Client
Title
Drawn by: Approved:
Checked by: Date:
Scale:NTS Drg. No: