A2-65 M/s CORDIAL

CLIENT

FROM UTILITY PANEL

PROJECT

LOC:ELECTRICAL ROOM
COMMON VDB CL.=27kW
CORDIAL RISE APARTMENT
MD.=18KW AT VAZHAYILA
63A
TPN
ISOLATOR FROM UTILITY PANEL
:PROJECT NO IBC - EL - 1210/20

25A 25A 32A 40A 40A 40A 32A 25A 25A LIFT PANEL 1&2 R Y B 2A CL.=10KW :DATE
TPN MCB TPN MCB TPN MCB TPN MCB TPN MCB TPN MCB TPN MCB DP MCB TPN MCB 16.03.2021

63A TPN
BUSBAR ISOLATOR :SCALE NTS
P-25X6mm AL
25A DP N-25X6mm AL :DIMS CMS
MCB ISO
40A FP 25A 2P :SHEET SIZE A-2
100mA 30mA
UPS RCBO RCBO
:DRAWN BY JERIN
25A DP
MCB ISO :CHECKED BY VIJAYAMOHAN
32A 6A 6A 6A 16A
25A 25A 32A 40A 40A 40A 25A SP SP SP
30mA SP
30mA 30mA 30mA 30mA 30mA 30mA 30mA NOTE: SIMILAR FOR

1Rx4Cx10sqmmALXLPEcable
MCB MCB MCB MCB :APPROVED BY Mr.M.RANJITH.
4P 4P 4P 4P 4P 4P 4P 4P LIFT 1 & LIFT 2
(CONSULTANT)

RCBO RCBO RCBO RCBO RCBO RCBO RCBO RCBO

DB/PKG1 DB/PK DB/PK DB/GYM DB/GAME DB/RECRE& UPSDB SPARE SUB PANELS
(3BF) (2BF)
+SUITEROOM
(GF) &HALL DB/COMMON, TERRACE 1KVA
(1BF&GF) (GF) P&S
FEEDER/EQUIPMENT NO: CLP/1 CLP/2 CLP/3 CLP/4 CLP/4 CLP/5 CLP/8 REVISIONS
RATING (KW/KVA/KVAR): 0.6KW 0.6KW 3KW 3KW 5KW 3KW 1KW
VOLTAGE (VOLTS): 415V 415V 415V 415V 415V 415V 415V TOLIFT TOLIFT POINTS No. Description Date
KW: 1KW 1KW 5KW 5KW 7KW 5KW 2KW MOTOR
CONNECTED R1 Tansformer Revised 09-11-2022
KVA: -- -- -- -- -- -- --
LOAD
KVAR:
CURRENT (AMPS):
R.P.M. OF MOTOR: -- -- -- -- -- -- --
SWITCH RATING (AMPS): 25A 25A 32A 40A 40A 40A 32A
BACK UP FUSE RATING (AMPS):
ISSUED TO
RELAY RANGE (AMPS): -- -- -- -- -- -- --
SUPPLY SIZE(RUNSxCORExSQ.MM): 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX10Sqmm 1RX4CX10Sqmm 1RX4CX10Sqmm 1RX4CX10Sqmm
No. Name Date
SIDE CABLE LENGTH (METRES):
EQUIPMENT SIZE(RUNSxCORExSQ.MM): -- -- -- -- -- -- --
SIDE CABLE LENGTH (METRES): -- -- -- -- -- -- --
EARTHING CONDUCTOR SIZE (SWG): 10CU 10CU 10CU 10CU 10CU 10CU 10CU
RATING (KVAR): -- -- -- -- -- -- --
CABLE SIZE(RNXCRXSQ): -- -- -- -- -- -- -- TITLE
CAPACITOR FROM GSB
CABLE LENGTH(METRES): -- -- -- -- -- -- --
EARTH.COND.SIZE(SWG): -- -- -- -- -- -- --

EMERGENCY PANEL R Y B 2A
SCHEMATIC DETAILS
CL.=60kW
DF.=1.5
100A TPN MD.=40KW
BUSBAR TYPE
ISOLATOR
100A AL
ELECTRICAL
32A TPN 32A TPN 32A TPN 32A TPN 32A TPN 32A TPN 32A TPN 32A TPN
MCB MCB MCB MCB MCB MCB MCB MCB
DRAWING NUMBER

IBC - EL - 1210/20-SCH-03
FROM UTILITY PANEL

PEOPLE
LOC:PUMP ROOM VASTUSHILPALAYA
WATER PUMP ARCHITECT : CONSULTANCY
R Y B 2A CL.=12kW
PANEL PVT LTD.
MD.=10KW SIGNATURE :
63A TPN
BUSBAR ISOLATOR
CONSULTANT : Mr. M.RANJITH
P-25x6MM AL
N-25x6MM AL SIGNATURE :
EDB1 EDB2 EDB3 EDB4 EDB5 EDB6 EDB7 EDB8
CLIENT : M/s CORDIAL
FEEDER/EQUIPMENT NO: EP1/1 EP1/2 EP1/3 EP1/4 EP1/5 EP1/6 EP1/7 EP1/8
32A 25A 32A 32A 16A 16A 25A 16A
FP FP FP FP DP DP FP FP
RATING (KW/KVA/KVAR): 5KW 5KW 5KW 5KW 5KW 5KW 5KW 5KW SIGNATURE :
MCB MCB MCB MCB MCB MCB MCB MCB VOLTAGE (VOLTS): 415V 415V 415V 415V 415V 415V 415V 415V
KW: 7.5KW 7.5KW 7.5KW 7.5KW 7.5KW 7.5KW 7.5KW 7.5KW
CONNECTED
KVA: -- -- -- -- -- -- -- -- ARCHITECT
LOAD
KVAR:
CURRENT (AMPS):
R.P.M. OF MOTOR: -- -- -- -- -- -- -- --
SWITCH RATING (AMPS): 32A 32A 32A 32A 32A 32A 32A 32A KOSHY K. ALEX & ZERIL S. JOSE
1Rx4Cx10sqmmALXLPEcable
1Rx4Cx10sqmmALXLPEcable

1Rx4Cx6sqmmALXLPEcable

1Rx4Cx6sqmmALXLPEcable

1Rx2Cx4sqmmALXLPEcable

1Rx2Cx4sqmmALXLPEcable

BACK UP FUSE RATING (AMPS): VASTUSHILPALAYA CONSULTANCY


RELAY RANGE (AMPS): -- -- -- -- -- -- -- -- PVT LTD.
SUPPLY SIZE(RUNSxCORExSQ.MM): 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm 1RX4CX6Sqmm ARCHITECTS, PLANNERS, ENGINEERS, INTERIOR DESIGNERS
KOWDIAR,TRIVANDRUM-3
SIDE CABLE LENGTH (METRES): Tel: 2311153, 2311154, 2311155
EQUIPMENT SIZE(RUNSxCORExSQ.MM): -- -- -- -- -- -- -- -- email: mail@vcpl.org.in

SIDE CABLE LENGTH (METRES): -- -- -- -- -- -- -- --


EARTHING CONDUCTOR SIZE (SWG): 10CU 10CU 10CU 10CU 10CU 10CU 10CU 10CU MEP CONSULTANT
RATING (KVAR): -- -- -- -- -- -- -- --
CABLE SIZE(RNXCRXSQ): -- -- -- -- -- -- -- --
CAPACITOR
CABLE LENGTH(METRES): -- -- -- -- -- -- -- -- INTEGRATED
EARTH.COND.SIZE(SWG): -- -- -- -- -- -- -- -- BUILDING
CONSULTANTS
Terrace Dewateringpit DWS FWS Sumppit STPpit SPARE SPARE 54/2477A,SUBASH CHANDRA BOSE ROAD,
BoosterPump Pump Pump Pump Pump Pump KADAVANTHRA P.O,
KOCHI-682020.
Phone : 0484-4010774 ,2205774.
e-mail : ibconsultants@rediffmail.com