Rating HT Fusing HT Fusing Rated LV Fusing for Various Legs (Amps)
(kVA) (Amps) (Amps) Amps
Actual Available (LV)
33 11 33 kV 11 kV 1 2 legs 3 Legs 4 Legs 5 Legs 6 Legs 7 Legs 8 Legs
kV kV leg
50 0.87 2.6 1 2/3 67 63 --- --- --- --- --- --- ---
100 1.75 5.25 2 5/6 133 100 63 --- --- --- --- --- ---
200 3.5 10.5 3/5 10/8 267 200 100 *80/ 100 *63/ 80 --- --- --- ---
300 5.25 15.8 5/6 15/16 400 400 200 *100/ 200 100 80 63 --- ---
315 5.5 16.5 5/6 16 420 400 200 *100/ 200 100 80 *63/ 80 --- ---
400 7.0 21 6/8 20 533 --- *200/ 315 *100/ 200 *100/ 200 100 *80/ 100 --- ---
500 8.75 26.5 8/10 25 667 400 315 200 *100/ 200 *100/ 200 100 *80/ 100 *80/ 100
750 13.12 40 10/15 40 1000 --- 400 315 *200/ 315 200 *100/ 200 *100/ 200 *100/ 200
800 14 42 10/15 40 1067 --- 400 315 *200/ 315 200 *100/ 200 *100/ 200 *100/ 200
1000 17.5 52.5 16 40/60 1333 --- 400 400 315 *200/ 315 200 *100/ 200 *100/ 200
Note: * A combination of the fuse ratings. Formulae for choosing the fuses KVA = √3VLIL KW = √3VLILCOSɸ (COSΦ = 0.85)
KW = KVA COSɸ
MW = 16.2 × Amps (11KV) MW = 48.6 × Amps (33KV)
1000 1000