FOR NORTH SIDE

𝐾𝑉𝐴
I= = A
230𝑉

𝐾𝑉𝐴
d= x 100 = ft.
𝐾𝑉𝐴

24 ()()
AREA = = CM
230(0.05)

CM/3 = CM

USE: 3- 266800 ACSR, 50°C 60Hz @ 3ft. SPACING

R = 0.3831 Ω / CONDUCTOR/MILE
1𝑓𝑡.
OUTSIDE DIAMETER = 0.609 in. ( )
12𝑖𝑛.

= 0.508 ft.

OUTSIDE RADIUS = 0.0254 ft.

GMD = Dm = 3√(3)(3)(3) = 3ft.


3
GMR = Ds = √(0.7788)(0.0254)(0.0508)2

= 0.0371 ft.
3
XL∅ = 2π(60)(2x10)−7 ln( )(1609)
0.0371

XL∅ = 0.05329 Ω / CONDUCTOR/MILE

𝑋𝑇 0.5329
RATIO = = = 1.39
𝑅 0.3831

AC DROP FACTOR = 1.61

VDC = = V
3(266800)

VAC DROP = 1.61 x = V

V.R. = x 100% = %
230

3- 266800 ACSR, 50°C 60Hz @ 3ft. SPACING

BUNDLE CONFIGURATION:

3- 266800 ACSR, 50°C 60Hz @ 3ft. SPACING

BUNDLE CONFIGURATION:
FOR SOUTH SIDE
𝐾𝑉𝐴
I= = A
230𝑉

𝐾𝑉𝐴
d= x 100 = ft.
𝐾𝑉𝐴

24 ()()
AREA = = CM
230(0.05)

CM/3 = CM

USE: 3- 266800 ACSR, 50°C 60Hz @ 3ft. SPACING

R = 0.3831 Ω / CONDUCTOR/MILE
1𝑓𝑡.
OUTSIDE DIAMETER = 0.609 in. ( )
12𝑖𝑛.

= 0.508 ft.

OUTSIDE RADIUS = 0.0254 ft.

GMD = Dm = 3√(3)(3)(3) = 3ft.


3
GMR = Ds = √(0.7788)(0.0254)(0.0508)2

= 0.0371 ft.
3
XL∅ = 2π(60)(2x10)−7 ln( )(1609)
0.0371

XL∅ = 0.05329 Ω / CONDUCTOR/MILE

𝑋𝑇 0.5329
RATIO = = = 1.39
𝑅 0.3831

AC DROP FACTOR = 1.61

VDC = = V
3(266800)

VAC DROP = 1.61 x = V

V.R. = x 100% = %
230

3- 266800 ACSR, 50°C 60Hz @ 3ft. SPACING

BUNDLE CONFIGURATION: