Minimum Storage Vessel Sizes and Pipe Sizing Calculations
Minimum Storage Vessel Sizes and Pipe Sizing Calculations
Thus for case 1, the minimum sizes of storage vessel Annex D (informative)
are given in table C.1.
Pipe sizing calculations
Table C.1 Minimum sizes of storage vessel for D.1 Determination of flow rates
case 1
D.1.1 General
Heat input to water Minimum storage capacity
In small, simple installations such as those in single
l dwellings, it is often acceptable to size pipes on the
kW With stratification With mixing basis of experience and convention. In all other cases
the probable flow rates and pipe sizes required should
be calculated using a recognized method of calculation,
3 109 122 such as the method given in this annex.
6 88 88 D.1.2 Assessment of probable demand
10 70 70 In most buildings all appliances are seldom in
15 70 70 simultaneous use. For reasons of economy a
simultaneous demand which is less than the maximum
Case 2. A dwelling with two baths installed and having demand from all appliances should be provided for.
a maximum requirement of 130 l drawn off at 60 ÊC This simultaneous demand can be estimated either
(2 baths + 10 l for kitchen use) followed by a further from data derived by observation and experience of
bath (100 l at 40 ÊC) after 30 min. similar installations, or by application of probability
theory using loading units.
The calculations follow the same procedures as for
case 1 and the results for case 2 are given in table C.2. D.1.3 Loading units (LU)
Loading units are factors which take into account the
Table C.2 Minimum sizes of storage vessel for flow rate at the appliance, the length of time in use
case 2 and the frequency of use. The number of each type of
Heat input to water Minimum storage capacity appliance, fed by the length of pipe being considered,
should be multiplied by the loading units, as given in
l
table D.1, and the total LU derived for the pipe. Using
kW With stratification With mixing figure D.1 the total number of LU can be converted
into the total simultaneous demand for the pipe in l/s.
Owing to the difference in rates of flow and pattern of
3 165 260 demand between hot and cold outlets, the LU
6 140 200 applicable also show some variation, but for most
10 130 130 practical purposes the same LUs can be used for both
hot and cold outlets.
15 120 130
Table D.1 is based on normal domestic usage and
customary (or statutory) provision of appliances. It is
These calculations, which may be carried out for any not applicable where usage is intensive, for example, in
particular situation, indicate the value of promoting theatres and conference halls; in such cases it is
stratification wherever possible and show the order of necessary to establish the pattern of usage and
savings in storage capacity that can be made without appropriate peak flow demand for the particular case.
prejudice to the quality of the service to the user by
increasing the heat input to the water.
BSI 1997 71
BS 6700 : 1997 Annex D
72 BSI 1997
Annex D
0.006
0.003
0.005
0.008
0.001
0.002
0.004
BSI 1997
0.01
0.02
0.03
0.04
0.05
0.06
0.08
0.07
0.1
0.2
0.3
0.4
0.5
0.6
0.8
10
1
2
3
4
5
6
8
Wall friction gradient (head loss) in kPa per metre
0.25
0.75
0.1
0.5
1.0
1.5
2.5
2
3
4
5
6
Lamont's smooth pipe formula S3
v = 0.5545 d 0.6935 i 0.5645
Velocity, metres per second
where: v is the velocity (m/s):
d is the diameter (mm); Formula applicable between these limits only
i is the hydraulic gradient;
0.05
0.06
0.08
v 1.7715
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1.0
10
20
30
40
50
and R = 10 0.5545 d 0.6935
2
3
4
5
6
8
where: R is the wall friction gradient (kPa) Flow, litres per second
15
18
22
28
35
67
42
12
54
6
15
55
5
10
20
25
30
35
40
45
50
60
65
70
75
80
BS 6700 : 1997
73
BS 6700 : 1997 Annex D
74 BSI 1997
Annex D BS 6700 : 1997
80
60
10
9
40 8 2
7
6
30
5
4
20 3
1 1/2
2
1 1/4
8 0.9
0.8
0.7
6 0.6 1
0.5
0.4
4
0.3
3 3/
4
0.2
0.1
0.09
0.08
0.07
1/
0.06 2
1.0 0.05
0.9
0.8 0.04
0.7 0.03
0.6
0.5
BSI 1997 75
76
BS 6700 : 1997
500
300
200
100
80
60
50
40
20
10
30
9
8
7
6
5
Pressure head of water, kPa
Based on
Q = AV 0.75
V = 0.2gH
where
Q is the flow (in L/s);
V is the velocity of flow (in m/s);
g is the acceleration due to gravity (in m/s2 );
H is the pressure head of water at the float valve (in kPa)
Diameter of orifice
millimetres
10
15
20
25
30
35
3
5
6
7
1/
5/
3/
1/
3/
1/
3/
15/
1
1 1/
16
8
4
8
16
inches
0.025
0.015
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.15
0.25
0.01
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.5
2.5
0.1
10
15
20
2
3
4
5
6
7
8
9
Annex D
Figure D.4 Head loss through float-operated valves
BSI 1997
Annex D BS 6700 : 1997
BSI 1997 77
BS 6700 : 1997 Annex D
78 BSI 1997
Annex D BS 6700 : 1997
7 5
C1 H1
H2
H4 6 C6
H7 C5
H3 H5 H6 C4
C2 C3
Sink WC Wash
basin
Bath
Cold water
storage
cistern
Hot water
cylinder
1
NOTE. This drawing is for pipe sizing example
Minimum pressure in water main only and does not include all necessary valves
for this example = 30 m head and backflow prevention devices.
Figure D.5 Example of pipe sizing for hot and cold water services, low pressure system
BSI 1997 79
BS 6700 : 1997 Annex D
H2 11 10
H5 9
T
H4 8
H1 H3
5 6 7
Wash
Sink WC
basin
T Bath
Minimum pressure in water main NOTE. This drawing is for pipe sizing example
for this example = 30 m head only and does not include all necessary valves
and backflow prevention devices.
Figure D.6 Example of pipe sizing for hot and cold water services, mains pressure
system
80 BSI 1997
Annex D
Table D.4 Example of pipe sizing calculations for cold water services 1)
BSI 1997
Pipe Flow rate Pipe Velocity Head Drop + Available Pipe length Head loss Residual head
reference Total Design size v loss R Rise2 head Actual Effective Pipe Valves2) Total Available Fitting Required Surplus
(7 + 14) (10 3 6) (11 + 12) (8 2 13) type
m LU l/s DN m/s kPa/m kPa kPa m m kPa kPa kPa kPa kPa kPa
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Main service pipe - for this example the minimum head in main = 300 kPa (3 bar)
122 9 + list 0.6 + 0.3 = 28 1.7 1.4 2 50 250 25 35 49 2 SV 70 180
0.9 = 21
223 6 + list 0.4 + 0.2 = 22 2.0 2.5 2 30 150 3 4.2 11 11 139
0.6
324 3 + list 0.2 + 0.1 = 15 2.2 5 2 30 109 3 4.2 21 21 88
0.3
425 3 + list 0.3 15 2.2 5 + 10 98 1 1.4 7 SV = 18 25 73
526 0.2 15 1.5 2.3 + 10 83 6 8.4 20 20 63 sink 5 58
527 0.1 15 0.75 0.6 25 68 1 1.4 1 1 67 float 30 37
valve
(5 mm f)
Cold water distributing pipes in flats
C1 2 C2 13.5 0.35 28 0.63 0.25 +20 20 4 5.6 1.4 Gate 1.4 18.6
valve
=0
C2 2 C3 11.5 0.32 22 1 0.8 Ð 18.6 1 1.4 1.2 1.2 17.4
C3 2 C4 10.0 0.30 22 0.9 0.65 26 11.4 1.5 2.1 1.4 1.4 10 bath 8 2
C3 2 C5 1.5 0.15 15 1.1 1.3 27 10.4 0.7 1.0 1.3 1.3 9.1 wash 8 1.1
basin
C2 2 C6 2.0 0.10 15 0.7 0.6 27 11.6 1 1.4 0.9 0.9 10.7 WC 10 0.7
cistern
(6.5 mm
f)
BS 6700 : 1997
81
82
BS 6700 : 1997
Table D.4 Example of pipe sizing calculations for cold water services1) (continued)
Pipe Flow rate Pipe Velocity Head Drop + Available Pipe length Head loss Residual head
reference Total Design size v loss R Rise2 head Actual Effective Pipe Valves2) Total Available Fitting Required Surplus
(7 + 14) (10 3 6) (11 + 12) (8 2 13) type
m LU l/s DN m/s kPa/m kPa kPa m m kPa kPa kPa kPa kPa kPa
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Hot water distributing pipes in flats
H1 2 H2 14.5 0.37 28 0.75 0.3 + 10 10 4.0 5.6 1.7 Gate 1.7 8.3
valve
=0
H2 2 H3 14.5 0.37 28 0.75 0.3 + 10 18.3 1.5 2.1 0.6 0.6 17.7
H3 2 H4 3.0 0.20 22 0.65 0.31 2 10 7.7 3.0 4.2 1.3 1.3 6.4 sink 5 1.4
H3 2 H5 11.5 0.32 28 0.65 0.24 17.7 3.0 4.2 1.0 1.0 16.7
H5 2 H6 10.0 0.30 22 0.9 0.65 2 6 10.7 1.5 2.1 1.4 1.4 9.3 bath 8 1.3
H5 2 H7 1.5 0.15 15 1.1 1.3 2 7 9.7 0.7 1.0 1.3 1.3 8.4 wash 5 3.4
basin
Annex D
BSI 1997
Annex D
Table D.5 Example of pipe sizing calculations for cold water services (mains supplied)1)
BSI 1997
Pipe Flow rate Pipe Velocity Head Drop + Available Pipe length Head loss Residual head
reference Total Design size v loss R Rise - head Actual Effective Pipe Valves1) Total Available Fitting Required Surplus
(7 + 14) (10 3 6) (11 + 12) (8 2 13) type
m LU l/s DN m/s kPa/m kPa kPa m m kPa kPa kPa kPa kPa kPa
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Supply pipes to flats - for this example the minimum head in main = 300 kPa (3 bar) All calculations based on water at 10 ÊC
122 93 1.17 28 2.3 2.1 2 40 260 24 33.6 71 2 SV 125 135
+CV
= 54
223 62 0.90 28 1.7 1.4 2 30 105 3 4.2 6 6 99
324 31 0.57 22 1.8 2.0 2 30 69 3 4.2 9 9 60
BS 6700 : 1997
83
84
BS 6700 : 1997
Table D.5 Example of pipe sizing calculations for cold water services (mains supplied)1)
Pipe Flow rate Pipe Velocity Head Drop + Available Pipe length Head loss Residual head
reference Total Design size v loss R Rise - head Actual Effective Pipe Valves1) Total Available Fitting Required Surplus
(7 + 14) (10 3 6) (11 + 12) (8 2 13) type
m LU l/s DN m/s kPa/m kPa kPa m m kPa kPa kPa kPa kPa kPa
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Hot water supply to top flat (charts used based on water at 10 ÊC)
4 2 H1 14.5 0.37 22 1.1 0.9 + 20 80 5.5 7.7 7 3 valves 27 53
= 20
H1 2 H2 3.0 0.20 15 1.5 1.7 2 10 43 3 4.2 7 7 36 sink 5 31
H1 ± H3 11.5 0.32 22 1.0 0.8 53 3 4.2 4 4 49
H3 2 H4 10.0 0.30 22 1.0 0.7 2 5 44 1.5 2.1 2 2 42 bath 8 34
H3 2 H5 1.5 0.15 15 1.1 1.4 27 42 0.7 1.0 2 2 40 wash 5 35
basin
1)
SV = stopvalve CV = check valve DCV = Double check valve 1 kPa = 0.1 metre head = 0.01 bar
Annex D
BSI 1997
BS 6700 : 1997
Normative references
BSI publications
BRITISH STANDARDS INSTITUTION, London
BS 417 : Specification for galvanized low carbon steel cisterns, cistern lids,
tanks and cylinders
BS 417 : Part 2 : 1987 Metric units
BS 699 : 1984 Specification for copper direct cylinders for domestic purposes
BS 853 Specification for vessels for use in heating systems
BS 853 : Part 1 : 1996 Calorifiers and storage vessels for central heating and hot water
supply
BS 864 Capillary and compression tube fittings of copper and copper
alloy
BS 864 : Part 2 : 1983 Specification for capillary and compression fittings for copper
tubes
BS 1010 Specification for draw-off taps and stopvalves for water services
(screw-down pattern)
BS 1010 : Part 2 : 1973 Draw-off taps and above-ground stopvalves
BS 1212 Float-operated valves
BS 1212 : Part 2 : 1990 Specification for diaphragm type float operated valves (copper
alloy body) (excluding floats)
BS 1212 : Part 3 : 1990 Specification for diaphragm type float operated valves (plastics
bodied) for cold water services only (excluding floats)
BS 1252 : 1991 Specification for domestic solid mineral fuel-fired, free-standing
cookers with or without boilers
BS 1394 : Stationary circulation pumps for heating and hot water service
systems
BS 1394 : Part 2 : 1987 Specification for physical and performance requirements
BS 1566 : Copper indirect cylinders for domestic purposes
BS 1566 : Part 1 : 1984 Specification for double feed indirect cylinders
BS 1566 : Part 2 : 1984 Specification for single feed indirect cylinders
BS 1710 : 1984 Specification for identification of pipelines and services
BS 1894 : 1992 Specification for design and manufacture of electric boilers of
welded construction
BS 1968 : 1953 Specification for floats for ballvalves (copper)
BS 2456 : 1990 Specification for floats (plastics) for float operated valves for cold
water services
BS 2494 : 1990 Specification for elastomeric seals for joints in pipework and
pipelines
BS 2580 : 1979 Specification for underground plug cocks for cold water services
BS 2871 : Specification for copper and copper alloys Ð Tubes
BS 2871 : Part 1 : 1971 Copper tubes for water, gas and sanitation
BS 2879 : 1980 Specification for draining taps (screw-down pattern)
BS 3198 : 1981 Specification for copper hot water storage combination units for
domestic purposes
BS 3377 : 1985 Specification for boilers for use with domestic solid mineral fuel
appliances
BS 3378 : 1986 Specification for room heaters burning solid mineral fuels
BS 3456 : Specification for safety of household and similar electrical
appliances
BS 3456 : Part 2 : Particular requirements
BS 3456 : Section 2.21 : 1972 Electric immersion heaters
BS 3456 : Part 102 : Particular requirements
BS 3456 : Section 102.21 : 1988 Storage water heaters
BSI 1997 85