ID/FD FAN LOGIC

SYSTEM

December 14,

PMI Revision 00

PURGE PERMISSIVES
All HFO nozzle valves closed
All pulverisers OFF
All feeders OFF
No MFT condition present
All scanners senses no flame
All Auxiliary Air dampers modulating

TO
FSSS

Both PA fans OFF


All Mill HAGs closed
Air flow more than 30% and less than 50%
HFO trip valve is closed
Wind box to furnace DP is adequate

December 14,

PMI Revision 00

Both FD fans OFF


Both ID fans OFF.
Inadequate water wall circulation for more than 5 seconds.
Loss of Reheat Protection for greater than 10 seconds.
All BFPs tripped.
Drum level very high for more than 10 seconds (2/3 logic)
Drum level very low for more than 10 seconds (2/3 logic)
Furnace pressure very high (2/3 logic)
Furnace pressure very low (2/3 logic)
Loss of all fuel.
All feeders OFF and loss of AC Supply to the elevation in service.
Unit flame failure.
Loss of Unit Critical Power for more than 2 seconds
Both Secondary APHs OFF.
Loss of 220 V DC Supply for more than 2 seconds.
Air flow less than 30% and boiler load not greater than 30%.
Manual Emergency trip.

December 14,

PMI Revision 00

Both FD fans OFF


Both ID fans OFF
Inadequate water wall circulation for more than 5 seconds
Loss of Reheat Protection for greater than 10 seconds
All BFPs tripped
Drum level very high for more than 10 seconds (2/3 logic)
Drum level very low for more than 10 seconds (2/3 logic)
Furnace pressure very high (2/3 logic)
Furnace pressure very low (2/3 logic)
Loss of all fuel

MFT
RELAY

All feeders OFF and loss of AC Supply to the elevation in service


Unit flame failure
Loss of Unit Critical Power for more than 2 seconds
Both Secondary APHs OFF
Loss of 220 V DC Supply for more than 2 seconds
Manual Emergency PB trip

14,30% and boiler load


PMI not
Revision
AirDecember
flow less than
greater00
than 30%

1. ALL ID FANS OFF

Arming:
Always armed
Logic:
Both ID Fans OFF Contact sensed by MFT panels
Purpose:
Anticipatory protection to prevent furnace pressurization

Loss of furnace pressure control and balanced draft


Protection Delay:
0 sec INSTANT.
Protection Check:
Simulate the signals from ID Fans Electrical Control Circuit

December 14,

PMI Revision 00

2. ALL FD FANS OFF

Arming:
Always armed
Logic:
Both FD Fans OFF Contact sensed by MFT panels
Purpose :
Anticipatory protection to prevent reducing firing condition

Loss of total air flow control and balanced draft


Protection Delay:
0 sec INSTANT.
Protection Check:

Simulate the signals from FD Fans Electrical Switchgear

December 14,

PMI Revision 00

3. LOSS OF ALL FUEL

Arming:
Any HFO/LFO nozzle valve NOT closed
Logic:
All LFO cut off AND All HFO cut off AND All Feeders OFF
Initiation of a mandatory purge cycle to restore furnace

Purpose:
Backup protection to trip remaining equipment (eg. PA Fans)
0 sec INSTANT.

Protection Check:
Keep oil manual isolating valves in any one elevation any one corner (done by OPN), simulate status of
manual valve (done by C&I), then give sequence start command to that corner

December 14,

PMI Revision 00

4. FLAME FAILURE

Arming:
Any Feeder Proven for 2 sec
Logic:
All Elevations A to K voted NO Flame

Eg. Elevation A voted no flame means


(AA 3/4 fireball scanners sense no flame AND AB 3/4 fireball scanners sense no flame AND AB 2/4 oil guns not proven in service)
Feeder A Not Proven for 2 sec

OR

Stop firing under unstable flame fireball conditions


Protection Delay:
0 sec INSTANT.
Protection Check:
Simulate feeder proven status without any oil in service

December 14,

PMI Revision 00

5. FURNACE PRESSURE VERY HIGH

Arming:
Always armed
Logic:

2 out of 3 pressure switches sense furnace pressure very high > +150 mmwc

Purpose:
To stop fuel firing under explosive tendency of furnace
Prevent furnace structural distortion

Protection Delay :
0 sec INSTANT.

Protection Check:

Simulate from protection instrument, or by actual


pressurization if agreed by Operation Head.
December 14,

PMI Revision 00

6. FURNACE PRESSURE VERY LOW

Arming:
Always armed
Logic:

2 out of 3 pressure switches sense furnace pressure very low <

-175 mmwc

Purpose:
To stop fuel firing under implosive tendency of furnace
Prevent furnace structural distortion
Protection Delay:
0 sec INSTANT.
Protection Check:
Simulate from protection instrument, or by actual
depressurization if agreed by Operation Head.

December 14,

PMI Revision 00

10

7. DRUM LEVEL VERY HIGH

Arming:
Logic:

Always armed

2 out of 3 logic derived from hydrastep-left-1, hydrastep-right-1 and drum level transmitter > 250 mm

Purpose:

To prevent water carry over to superheater headers and subsequently to turbine

Protection Delay:
10 sec.
Protection Check:
Actual (increase feed water flow slowly until level
reaches trip limit).

December 14,

PMI Revision 00

11

8. DRUM LEVEL VERY LOW

Arming:
Always armed
Logic:

2 out of 3 logic derived from hydrastep-left-2, hydrastep-right-2 and drum level transmitter < -375 mm

Purpose:
To prevent waterwall tubes starvation
To prevent BCW pumps starvation
Protection Delay:
5 sec.
Protection Check:
Actual (decrease feed water flow slowly until level
reaches trip limit).

December 14,

PMI Revision 00

12

Arming:
Always armed
Logic:

9. ALL BFP OFF

Both TDBFPs sensed Not Working AND MDBFP sensed OFF

Purpose:
Anticipatory protection for Drum Level Very Low

To prevent economizer tubes starvation


Protection Delay :
10 sec.
Protection Check :
Simulate OFF contact of all BFP from BFP control panel

December 14,

PMI Revision 00

13

Arming:
Always armed
Logic:

10. ALL SAH OFF

Both Secondary Air Heaters: electric motor OFF AND air motor OFF

Purpose:
Preventing poor furnace combustion due to low secondary air temperature

Preventing flue gas damper isolation in all air heaters


Protection Delay:
5 sec.
Protection Check :
Actual.

December 14,

PMI Revision 00

14

11. WATERWALL CIRCULATION


INCORRECT

Arming:

Boiler ON

Logic :

All BCW OFF (OR) 2/3 running BCW DP < 0.68 ksc

Purpose:
Preventing damage to waterwall tubes due to insufficient cooling flow/circulation

Preventing DNB (departure from nucleate boiling)


Protection Delay:
5 sec.

Protection Check:
Equalizing DP transmitters to simulate DP low.

December 14,

PMI Revision 00

15

December 14,

PMI Revision 00

16

12. TOTAL AIR FLOW < 30%

Arming:

Always armed

Logic:

Total Air Flow (Primary Air + Secondary Air) < 30% of full load air flow (30% of 1800 Tph = 540
Tph)

Purpose:
Ensuring absolute minimum required quantity of air flow even during startup

Preventing localized accumulation of unburnt oil during startup

Protection Delay :
0 sec - INSTANT.

Protection Check :
Actual.

December 14,

PMI Revision 00

17

December 14,

PMI Revision 00

18

13. REHEATER PROTECTION

Arming:

HP bypass AND LP bypass charged for the first time > 2%

Logic:

Generator Circuit Breaker Open AND (HP bypass OR LP bypass Fail to Open)
OR
Reheater Inlet (HP) OR Outlet Path (IP/LP) Blocked

Purpose:

Ensuring absolute minimum required quantity of air flow even during startup

Preventing localized accumulation of unburnt oil during startup

Protection Delay:
10 sec.
Protection Check:
Actual.

December 14,

PMI Revision 00

19

December 14,

PMI Revision 00

20

December 14,

PMI Revision 00

21

Arming :

14. LOSS OF 24V DC

Always armed

Logic:

If 24V supply to any 2 MFT panels is lost, it will initiate a hardwired MFT protection through 220V
contactor circuit.

Purpose:
If 24V fails, the processors cannot execute any logic, leading to unsafe condition

Protection Delay :
0 sec INSTANT.

Protection Check :
By 24V breaker simulation in MFT panel.

December 14,

PMI Revision 00

22

Arming:

15. LOSS OF 220V DC

Always armed

Logic:

If 220V supply to any 2 MFT panels is lost, it will initiate a soft MFT protection through processor
logic.

Purpose:
If 220V fails, backup protection for 24V failure will be unavailable.

Protection Delay:
2 sec.

Protection Check:
By 220V breaker in MFT panel.

December 14,

PMI Revision 00

23

17 . 2/3 PROCESSORS FAIL/FROZEN

Arming:

Always armed

Logic:

If any 2 MFT processors out of 3 go into failed state, or if any 2 MFT processors go into frozen
output state, it will initiate MFT protection.

Purpose:

This ensures that at least 2 processors are in healthy condition at any point of time when boiler
is in service.

Failure of processors leads to unsafe condition

Protection Delay :
0 sec - INSTANT.

Protection Check:
By actually creating frozen output state in processors.

December 14,

PMI Revision 00

24

17. 2/3 PROCESSORS COMMN FAIL


Arming:

Always armed

Logic:

If any 2 MFT processors out of 3 stop communicating with the Ethernet network (redundant netA and net-B), they will initiate MFT protection

Purpose:

This ensures that at least 2 processors are communicating properly at any point of time when
boiler is in service.

Failure of communication leads to malfunction of protection circuit

Protection Delay:
0 sec - INSTANT.

Protection Check:
By actually isolating network connections of the processors.

December 14,

PMI Revision 00

25

Arming:

18. EMERGENCY TRIP

Always armed

Logic:

If both Desk Emergency Push Buttons pressed together (OR)


If both Backup Panel Push Buttons pressed together (OR)
If MFT is confirmed through popup from any workstation PC

Purpose:

This facility allows the operation desk engineer to directly trip the boiler in case of any operational emergency eg. Boiler Tube
Leakage, Furnace excessive Clinkering, HFO oil leakage during startup, turbine related emergencies etc.

Protection Delay :
0 sec - INSTANT.

Protection Check :
By actually operating push buttons/through PC.

December 14,

PMI Revision 00

26

POST-TRIP PURGE FANS TRIP

Arming:

Boiler not firing fuel for 5 min (MFT may or may not be reset)

Logic:

If furnace pressure very high > 150 mmwc OR very low < -175 mmwc (AND)
Air Flow > 30% THEN
TRIP all ID Fans and FD Fans

Purpose:
This protection safeguards furnace against furnace pressure very high OR very low when boiler
is NOT firing.

Protection Delay :

0 sec INSTANT (5 min delay in arming circuit)

Protection Check:

By simulation at source.

December 14,

PMI Revision 00

27

RUNBACK GRADED MILL TRIP

Arming:

More than 4 mills in service

Logic:

If any major auxiliary (eg. ID, FD, PA, BFP) trips and standby is not available, unit load is
automatically reduced according to the new capability

Mills are tripped one by one starting from top running mill, at 2 sec delay, until 4 running mills
from bottom remain.

Purpose:

This interlock achieves the fastest possible load reduction, and requires NO intervention of desk
engineer

Protection Delay:

Varies from 1 sec to 1 min according to type of auxiliary

Protection Check:

Simulated at initiating point.

December 14,

PMI Revision 00

28

December 14,

PMI Revision 00

29

THANK YOU
QUESTIONS ?

December 14,

PMI Revision 00

30

P&I OF BOILER AUXILLARIES


A. FD FAN

START PERMISSIVES

Blade pitch position minimum.

Discharge damper fully closed.

Lube oil pressure adequate.

Control oil pressure adequate.

Oil tank level normal.

Bearing temperature not high.

One ID Fan running AND other FD fan not


running.
OR Both ID Fan running

December 14,

PMI Revision 00

31

TRIPS

Fan bearing temperature very high


Post purge furnace pressure very high/ very low
Outlet damper fail to open in set time

(3 min)

No ID fan running or one ID fan and one FD fan


already in service.

December 14,

PMI Revision 00

32

PA FAN
START PERMISSIVES

Blade pitch minimum


Lube oil pressure adequate
Control oil pressure adequate
Bearing temp. not high
Discharge damper closed.
Lube oil tank level adequate
No MFT & Cold air damper closed
At least one FD fan is running and
PAPH A/B in service & respective air inlet/ outlet
dampers are open

December 14,

PMI Revision 00

33

TRIPS
Fan bearing temperature very high.
Trip from FSSS (MFT).
Discharge damper fails to open.

December 14,

PMI Revision 00

34

ID FAN
START PERMISSIVES
Hyd. coupling Scoop position minimum.
Inlet guide vane position minimum.
Bearing temperature not high.
Oil temp. and oil level in Hyd. coupling OK.
Lube oil pressure adequate.
Both inlet and outlet dampers closed.
Other ID fan not running or Any FD fan running.

December 14,

PMI Revision 00

35

TRIP CONDITION
Fan/Motor bearing temperature very high.
Lube oil pressure very low.
Post purge furnace pressure Hi/Low from FSSS.
Discharge dampers/ suction damper fail to open
within specified time (3 min.)
Hydraulic coupling bearing temp. very high
Hydraulic coupling oil temp. very high.

December 14,

PMI Revision 00

36

SGWC PUMPS: (CC Pumps)

PERMISSIVES
Discharge valve 1 open.
Discharge valve 2 open.
Motor cavity temp. not high.
Pump cavity suction manifold differential
temp. not high.
Motor cooling water flow adequate.
December 14,

PMI Revision 00

37

TRIPS

Any of the discharge valves not fully open.


Motor cavity temp. high (60 deg. C) for more
than 5 Sec.
Electrical protection trip/ EPB pressed.

December 14,

PMI Revision 00

38

Run back operation


Tripping of PA Fan or FD Fan
PA header pressure low/very low
Sequential tripping of Mills/Feeders

December 14,

PMI Revision 00

39

December 14,

PMI Revision 00

40