Professional Documents
Culture Documents
TRAINING COURSE
GROUP
POWER LINKERS
and
2
POWER SYSTEM CONSULTANTS GROUP
INDEX
1.0 INTRODUCTION
4.2 APPLICATIONS
6
POWER SYSTEM CONSULTANTS GROUP
15.0 REFERENCES
9
POWER SYSTEM CONSULTANTS GROUP
1.0 INTRODUCTION
OPERATED UNGROUNDED
10
POWER SYSTEM CONSULTANTS GROUP
11
POWER SYSTEM CONSULTANTS GROUP
ARCING GROUNDS
INSULATION FAILURE
12
POWER SYSTEM CONSULTANTS GROUP
• GROUNDING
14
POWER SYSTEM CONSULTANTS GROUP
• EARTHING
16
POWER SYSTEM CONSULTANTS GROUP
CHARGING CURRENTS N IB
Y
= IR + IY + IB = 0 IY
R
X
IR X X
C C C
NO RESULTANT CURRENT FIG_2
_1_A
TO EARTH
PHASOR DIAGRAM
B
VR = V Y = V B = 1.0
NEUTRAL VOLTAGE = IR VRY= V YB= V BR= 3
G,N
R
GROUND VOLTAGE = 0 IB
IY
IR+ IY+ IB= 0
VNG= V 0 = 0
Y
FIG_2
NEUTRAL SHIFT _1_B
17
POWER SYSTEM CONSULTANTS GROUP
PHASOR DIAGRAM
• FIG 2_2_A
B I F = ( I RY+ I RB )
V =V = 3
YR YG
OF HEALTHY PHASES 3
C
R
I YR+ I BR = 3 I = 3 / X
C
I BR I YR
I F = I RY + I RB
NO CHANGE V
GN
=V
0
= 1.0
FIG_2
_2_B
IRB B
IRB
IRY Y
IRY
R
IRY + IRB XC XC
IRY
IRB
19
POWER SYSTEM CONSULTANTS GROUP
DEFINITION OF NEUTRAL
21
POWER SYSTEM CONSULTANTS GROUP
• FIG 2_3
• NEUTRAL AND ZERO SEQUENCE VOLTAGE
ZERO SEQUENCE R
VOLTAGE AT Y
B
ANY POINT IN NETWORK
V RG V YG V BG
R R R R
N
NEUTRAL SHIFT AT
THAT POINT IN THE VNG
NETWORK FIG_2_3_A
CONDITION VR VRG
VRG = 1 0 ; G ,N R VY VYG
VYG = 1 -120 ; VB VBG
VBG = 1 120
Y
V D = V + V + V = 3V = 0
R Y B 0
VRG VYG VBG
VNG = V0 = V D / 3 = 0
= 3 VNG = 3 V0 = 0
VRG = 0 ; G
R
N
VYG 1 -120 ;
VBG 1 120
Y
25
POWER SYSTEM CONSULTANTS GROUP
FIG_SE_CO_8
26
POWER SYSTEM CONSULTANTS GROUP
FIG 13_4_A
FIG 13_4_B
MORAL
INDICATION OF UNBALANCE
30
POWER SYSTEM CONSULTANTS GROUP
VSOURCE X
C
• FIG 2_5
• FIG 2_5
RESIDUAL VOLTAGE ACROSS CAPACITIVE SYSTEM
( V RC +1 PU ) DECAYS AS PER ITS TIME CONSTANT
• FIG 2_5
BREAKER / ARC
R,X
L
VSOURCE X
C
33
POWER SYSTEM CONSULTANTS GROUP
34
POWER SYSTEM CONSULTANTS GROUP
35
POWER SYSTEM CONSULTANTS GROUP
F1 F2 F3 R
Y
B
FAULT
36
POWER SYSTEM CONSULTANTS GROUP
U/V O/V
39
POWER SYSTEM CONSULTANTS GROUP
XC : CHARGING CAPACITANCE
VN > 1.0
XE/XC = 1/3
1
VRG
VNG = --------------------- XE/XC ( IC/IEX ) x 0.001
0
1 (3 XEX / XC ) 10 100 1000
VN < 0.0
10000
-1
FIG_2_8
-2 41
49
POWER SYSTEM CONSULTANTS GROUP
1.0 R
G,N N'
Y 42
POWER SYSTEM CONSULTANTS GROUP
46
POWER SYSTEM CONSULTANTS GROUP
47
POWER SYSTEM CONSULTANTS GROUP
48
POWER SYSTEM CONSULTANTS GROUP
RESISTANCE GROUNDING
49
POWER SYSTEM CONSULTANTS GROUP
• FIG 3_2
50
POWER SYSTEM CONSULTANTS GROUP
DEFINITION
A SYSTEM OR PORTION OF THE SYSTEM CAN BE SAID TO
BE EFFECTIVELY GROUNDED WHEN FOR ALL POINTS IN THE
SYSTEM OR SPECIFIED PORTION THEROF,
( X0 / X1 ) < 3 AND ( R0 / X1 ) < 1
FOR ANY CONDITION OF OPERATION AND ANY AMOUNT
OF GENERATION CAPACITY.
SYSTEM
A B C
Y
GROUNDED
SYSTEM MAY BE EFFECTIVELY GROUNDED FOR FAULT AT 'B'
• FIG 3_3
52
POWER SYSTEM CONSULTANTS GROUP
• TRANSFORMER : X0 X1
53
POWER SYSTEM CONSULTANTS GROUP
54
POWER SYSTEM CONSULTANTS GROUP
55
POWER SYSTEM CONSULTANTS GROUP
G FIG_4_1_A
56
[ {20% to 80%} ; {10% to 40%} ]
POWER SYSTEM CONSULTANTS GROUP
57
POWER SYSTEM CONSULTANTS GROUP
58
POWER SYSTEM CONSULTANTS GROUP
NO BEARING 1 0 1 0
1 120 1 0
1 240 1 0
O 3 0
COMPONENT : DEPENDS
+VE HALF
CYCLE
4.2 APPLICATIONS
LV (415V)
IE RULES
61
POWER SYSTEM CONSULTANTS GROUP
LV (415V)
FIG_4_3
LV (415V)
CONCLUSIONS
MV ( 3.3, 6.6, 11 KV )
65
POWER SYSTEM CONSULTANTS GROUP
CABLE UE GRADE
USUALLY,
68
POWER SYSTEM CONSULTANTS GROUP
I Y
UNGROUNDED SYSTEM : RY
IUG = 9 90
R I
RY
I +I
RY RB
R
I I X X
N F C C
HRG SYSTEM : I
N
I
RY
B
IF I
RY
+ I
RB
IUG I
F
IN
N I
N
69
POWER SYSTEM CONSULTANTS GROUP
VOL
I UG
IF
PHI = 450
PHI = 90 0
70
POWER SYSTEM CONSULTANTS GROUP
N
RG = 635
71
POWER SYSTEM CONSULTANTS GROUP
N
R'G = 0.9
11/3 kV / 240V
USUALLY ADOPTED
CHEAPER SOLUTION, RESISTOR : LOW , LOW VOLTAGE,
HIGH CURRENT
TURNS RATIO = TR = VP / VS [ e.g. (11000/3) / 240V = 26.5 ]
RG = R'G x TR2 [ 635 = 0.9 x 26.52 ]
( RANGE 1% to 10 %)
1A RELAY :
RANGE 10 MILLIAMPS to
100 MILLIAMPS
73
POWER SYSTEM CONSULTANTS GROUP
FROM TRANSFORMER OR
GENERATOR NEUTRAL
FIG_5_3
BUSHING
SHEET STEEL
RESISTOR ENCLOSURE
STACKS
INSULATOR
INSULATOR
TO TO
EARTH EARTH
GRID GRID
75
POWER SYSTEM CONSULTANTS GROUP
76
POWER SYSTEM CONSULTANTS GROUP
IRB B
IRB
IRY Y
GFN IRY
XL IRY + IRB
R
IN F XC XC
IN IRY
IRB 77
POWER SYSTEM CONSULTANTS GROUP
78
POWER SYSTEM CONSULTANTS GROUP
• FIG_6_1_A
• FIG_6_1_B
IN = IYR + IBR
1 3 1 1
-- = ----- L = ----- L = -----------
xL xC 3c 3 2 c
79
POWER SYSTEM CONSULTANTS GROUP
81
POWER SYSTEM CONSULTANTS GROUP
82
POWER SYSTEM CONSULTANTS GROUP
• FIG 7_1_A
83
POWER SYSTEM CONSULTANTS GROUP
85
POWER SYSTEM CONSULTANTS GROUP
E/3
E/3
E/3
B Y
E 87
POWER SYSTEM CONSULTANTS GROUP
GROUNDING TRANSFORMER
RATING (MVA) = 3 E I0 = (E/3) IF
CONVERSE FIG_13_4_A
89
POWER SYSTEM CONSULTANTS GROUP
SUMMARY
TYPE : ZIG ZAG GROUNDING TRANSFORMER
VOLTAGE : 11 KV (L to L)
MVA RATING : 2.6
TIME RATING : 10 SEC
ZERO SEQUENCE REACTANCE : 60%
I0
I0
R
IF = 3I 0
93
POWER SYSTEM CONSULTANTS GROUP
D SIDE UNLOADED, 0
0 0 0
NOT SERVING
ANY LOAD
0
R 0
CURRENT DRAWN IF =0
ONLY EXCITING CURRENT
VERY LOW
FOR (+VE) AND (-VE) SEQUENCE QUANTITIES
IMPEDANCE OFFERED IS EXCITING IMPEDANCE
VERY HIGH
94
POWER SYSTEM CONSULTANTS GROUP
I0
I0 I0 I0
PATH AVAILABLE FOR FLOW
OF ZERO SEQUENCE I0
R I0
CURRENT FLOW
IF =3I0
I0 FLOWS IN THREE PHASES OF STAR
EQUIVALENT I0 CAN FLOW IN CLOSED DELTA
IMPEDANCE OFFERED Z L CONVENTIONAL LEAKAGE
REACTANCE
Z(+ve) = Z(-ve) = ; Z(zero) = Z L
GROUND FAULT CURRENT LIMITED BY PROVIDING NGR
95
POWER SYSTEM CONSULTANTS GROUP
• FIG_7_4_A
TURNS RATIO = I0 I0 I0 I0
I0
I0 ON DELTA SIDE
I0
= 5.1 x 9.18
IF = 3I 0
= 46.8 A
99
POWER SYSTEM CONSULTANTS GROUP
100
POWER SYSTEM CONSULTANTS GROUP
TABLE 9_1
101
POWER SYSTEM CONSULTANTS GROUP
ADVANTAGES T1 T2
G1 G2
GROUND FAULT CURRENT
N1 N2
SUPPLIED BY THE
STATION LIMITED BY NGR
T1 T2
G1 G2
N1 N2
NGR
DISADVANTAGE
103
POWER SYSTEM CONSULTANTS GROUP
GT1 GT2
G1 G2
N1 N2
NGR NGR
104
POWER SYSTEM CONSULTANTS GROUP
G1 G2
N1 N2 NGR
ZIG ZAG
GROUNDING
TRANSFORMER 105
POWER SYSTEM CONSULTANTS GROUP
G1 G2
N1 N2
ISOLATING DEVICE
106
POWER SYSTEM CONSULTANTS GROUP
G1 G2
N1 N2
ISOLATING DEVICE
107
POWER SYSTEM CONSULTANTS GROUP
G1 G2
N1 N2
ISOLATING DEVICE
108
POWER SYSTEM CONSULTANTS GROUP
FIG_11_1
109
POWER SYSTEM CONSULTANTS GROUP
CONDITION
PHASE VOLTAGES
G
VR = VY = VB = 1.0 N R
LINE VOLTAGES
VRY = VYB = VBR = 3
Y
110
POWER SYSTEM CONSULTANTS GROUP
CHANGES IN BOTH :
PHASE VOLTAGES VY AND VB
LINE VOLTAGES VRY AND VBR
N
LINE VOLTAGE VYB NO CHANGE G
R
• FIG 11_3
115
POWER SYSTEM CONSULTANTS GROUP
116
POWER SYSTEM CONSULTANTS GROUP
138
POWER SYSTEM CONSULTANTS GROUP
S NETWORK
F
(+VE)
S F 118
POWER SYSTEM CONSULTANTS GROUP
(-VE)
119
S P F
POWER SYSTEM CONSULTANTS GROUP
120
POWER SYSTEM CONSULTANTS GROUP
Ia TA IA
IN TC
Ta
Ib Tb
Tc IC
TB
I IB
c
IF 121
POWER SYSTEM CONSULTANTS GROUP
Ia TA IA
IN TC
Ta
Ib Tb
Tc IC
TB
Ic IB
IF 122
POWER SYSTEM CONSULTANTS GROUP
CASE 1
ABSENCE OF PRIMARY NEUTRAL GROUNDING
NO CURRENT CAN FLOW ON SECONDARY SIDE
FAULT CURRENT IS ZERO EVEN WHEN NEUTRAL IS GROUNDED !!
BEHAVES LIKE UNGROUNDED SYSTEM
SOURCE TRANSFORMER
123
POWER SYSTEM CONSULTANTS GROUP
CASE 2
F 124
POWER SYSTEM CONSULTANTS GROUP
CASE 2
F 125
POWER SYSTEM CONSULTANTS GROUP
CASE 3
BOTH PRIMARY AND SECONDARY NEUTRALS GROUNDED
AND SOURCE ALSO GROUNDED
CURRENTS CAN FLOW IN BOTH THE SECONDARY AND
PRIMARY SIDES OF TRANSFORMER AND SATISFY :
AMPERE TURNS BALANCE AND KCL
BEHAVES LIKE TRULY GROUNDED SYSTEM
SOURCE TRANSFORMER
0 0
0 0
Ia IA
126
149
IF
POWER SYSTEM CONSULTANTS GROUP
CASE 4
TRANSFORMER SECONDARY NEUTRAL GROUNDED
THROUGH RESISTANCE
TRANSFORMER PRIMARY NEUTRAL AND SOURCE SOLIDLY
GROUNDED
CURRENTS CAN FLOW IN BOTH THE SECONDARY AND
PRIMARY SIDES OF TRANSFORMER
SOURCE TRANSFORMER
0 0
0 0
Ia R IA
127
F 150
POWER SYSTEM CONSULTANTS GROUP
CASE 4
0 0
Ia R IA
128
F 151
POWER SYSTEM CONSULTANTS GROUP
CASE 4
EXAMPLE : TRANSFORMER 11 KV / 6.6 KV, NGR = 38
GROUND FAULT CURRENT
ON SECONDARY SIDE = (6600 /3) / 38 = 100 A
EQUIVALENT CURRENT
ON PRIMARY SIDE = 100 * 6.6 / 11 = 60A
SOURCE TRANSFORMER
0 0
0 0
Ia R IA
129
60 A 100 A IF 152
POWER SYSTEM CONSULTANTS GROUP
CASE 5
SOURCE TRANSFORMER
0 0
0 0
Ia R IA
I F130
155
POWER SYSTEM CONSULTANTS GROUP
CASE 5
GROUND FAULT CURRENT ON SECONDARY SIDE LIMITED
BY NGR VALUE
THE EQUIVALNT REFLECTED CURRENT ON THE PRIMARY
SIDE ENCOUNTERS ANOTHER NGR ON SOURCE SIDE
OVERALL EFFECT : FAULT CURRENT REDUCES
SUBSTANTIALLY
SOURCE TRANSFORMER
0 0
0 0
Ia R IA
I 131
F 156
POWER SYSTEM CONSULTANTS GROUP
CASE 5
0 0
Ia R IA
100 A
37 A 62 A I132
F
157
POWER SYSTEM CONSULTANTS GROUP
CASE 6
TRANSFORMER D - STAR GROUNDED
Ia 0 0
IN 0
0
IA
IF
133
POWER SYSTEM CONSULTANTS GROUP
CASE 6
RELAYS RESPONDING TO FAULT
STAR SIDE
PHASE RELAY ON FAULTED PHASE
GROUND RELAY
DELTA SIDE
PHASE RELAYS ON TWO PHASES
[ GROUND RELAY DOES NOT PICK UP ! ]
Ia 0 0
IN 0
0
IA
134
IF 159
POWER SYSTEM CONSULTANTS GROUP
CASE 6
VOLTAGE VECTORS
CASE 7
TRANSFORMER
STAR GROUNDED [P] D [T] STAR GROUNDED [S]
D - TERTIARY WINDING, USUALLY DESIGNED TO CARRY ONLY
ZERO SEQUENCE CURRENTS UNDER NORMAL
CONDITIONS – UNLOADED – NO CURRENT
SOURCE UNGROUNDED OR PRIMARY NEUTRAL UNGROUNDED
RESULTS SAME
TRANSFORMER
SOURCE P T S
0 0
0
136
POWER SYSTEM CONSULTANTS GROUP
CASE 7
SOURCE UNGROUNDED
TRANSFORMER
SOURCE P T S
2 2 1 1
0 0
0 3
1 1 3
1 1
1
IF137
=3
162
POWER SYSTEM CONSULTANTS GROUP
CASE 7
RELAYS RESPONDING TO FAULT
SECONDARY SIDE
PHASE RELAY ON FAULTED PHASE
GROUND RELAY
PRIMARY SIDE
PHASE RELAYS ON ALL THREE PHASES
[ GROUND RELAY DOES NOT PICK UP ]
TRANSFORMER
SOURCE P T S
2 2 1 1
0 0
0 3
1 1 3
1 1
1 138
IF = 3 163
POWER SYSTEM CONSULTANTS GROUP
CASE 8
FIG13_5_B
TRANSFORMER
STAR GROUNDED [P] D [T] STAR GROUNDED [S]
139
POWER SYSTEM CONSULTANTS GROUP
CASE 8
BECAUSE OF PRESENCE OF D TERTIARY
CURRENT(PU) THROUGH PRIMARY NEUTRAL
LESS THAN
CURRENT(PU) THROUGH SECONDARY NEUTRAL
PART OF GROUND FAULT CURRENT REFLECTED IN
TERTIARY AND CIRCULATES
CURRENT DIVISION BETWEEN D TERTIARY AND PRIMARY
ZERO SEQUENCE LEAKAGE REACTANCE BETWEEN
(PRIMARY to TERIARY) & ( SECONDARY to TERTIARY)
IF NO DATA AVAILABLE, ASSUME
50% OF TOTAL SECONDARY FAULT CURRENT FLOWS
IN DELTA
140
REMAINING 50% FLOWS IN THE PRIMARY NEUTRAL
POWER SYSTEM CONSULTANTS GROUP
CASE 8
SECONDARY SIDE
PHASE RELAY ON FAULTED PHASE
GROUND RELAY
PRIMARY SIDE
PHASE RELAYS ON ALL THREE PHASES
GROUND RELAY
141
POWER SYSTEM CONSULTANTS GROUP
CASE 8
FAULT LEVEL STUDIES AND RELAY COORDINATION
EXERCISE
USUAL ASSUMPTION
PU FAULT CURRENT ON = PU FAULT CURRENT ON
SECONDARY SIDE PRIMARY SIDE
CASE 9
NGR R1 = R2 = R3 = 15.88
143
POWER SYSTEM CONSULTANTS GROUP
CASE 9
144
POWER SYSTEM CONSULTANTS GROUP
CASE 9
145
POWER SYSTEM CONSULTANTS GROUP
CASE 9
CASE 9
MOST PROBABLE RELAYS TO PICK UP
GROUND RELAY ON 220 kV SIDE
PHASE RELAYS ON 11 kV SIDE
147
POWER SYSTEM CONSULTANTS GROUP
CASE 9
G
N R
Y 148
POWER SYSTEM CONSULTANTS GROUP
CASE 10
CAN FAULT CURRENT FLOW AHEAD OF THE FAULT ?
SYSTEM F Yg D Yg
Yg
GROUNDED 220kV R
11kV
149
POWER SYSTEM CONSULTANTS GROUP
CASE 10
SYSTEM F Yg D Yg
Yg
GROUNDED 220kV R
11kV
150
POWER SYSTEM CONSULTANTS GROUP
CASE 10
-j 2.7
-j 2.7
-j 298.3 -j 2.7
-j 292.9 -j 8.1 (213A)
IF = -j 301 151
POWER SYSTEM CONSULTANTS GROUP
CASE 10
NORMALLY ONE EXPECTS THE RELAY TO PICK UP ONLY
FOR FAULTS DOWN THE TRANSFORMER.
-j 2.7
-j 2.7
-j 298.3 -j 2.7
-j 292.9 -j 8.1 (213A) 152
I F = -j 301 179
POWER SYSTEM CONSULTANTS GROUP
CASE 10
REACTANCE OF HV (220 kV) to TERTIARY IS HIGH
( 36.3% IN PRESENT CASE )
THE CURRENT IS LIMITED TO 213 A
-j 2.7
-j 2.7
-j 298.3 -j 2.7
-j 292.9 -j 8.1 (213A) 153
I F = -j 301 180
POWER SYSTEM CONSULTANTS GROUP
CASE 11
SYSTEM F Yg D
Yg
220kV R
11kV
CURRENT DISTRIBUTION, FOR FAULT AT 'F' SHOWN
CASE 11
CURRENT SENSED BY GROUND FAULT RELAY AT
LOCATION 'R'
-j 7.6
CASE 12
GENERATOR F Yg D
Yg
11kV R
66kV
TRANSFORMER : 20 MVA, 8%
CASE 12
BOTH GENERATOR AND TRANSFORMER SOLIDLY GROUNDED
CURRENT THROUGH GENERATOR NEUTRAL
= 5.5 PU = 5.5 x 525 2890 AMPS
-j 2.4
-j 10.3 -j 2.4 -j 2.4
-j 5.5 -j 7.2
157
1 PU CURRENT = 525 AMPS 186
I F = -j 12.7
POWER SYSTEM CONSULTANTS GROUP
CASE 12
CASE 12
CURRENT SENSED BY GROUND FAULT RELAY AT LOCATION 'R'
GROUND FAULT RELAY CONNECTED TO RESIDUAL CIRCUIT
OR ON THE NEUTRAL OF TRANSFORMER
RELAY LOOKS FOR FAULTS AHEAD OF ITS LOCATION !!
TRANSFORMER
GENERATOR R P S
0.25
0.25
0.25
0.25
16 16
1.25 0.25 0.25
0.75 0.75 159
I F = 1.5 188
POWER SYSTEM CONSULTANTS GROUP
CASE 13
TRANSFORMER NEUTRAL SOLIDLY GROUNDED
FIG 13_10
AUTO_TRANSFORMER : NEUTRAL SOLIDLY GROUNDED
CASE 14
CAN GROUND CURRENT (ZERO SEQUENCE) FLOW WITOUT
GROUND FAULT ?
OF COURSE YES!
161
POWER SYSTEM CONSULTANTS GROUP
CASE 14
EXAMPLE
TRANSFORMER
SOURCE 33 KV 11 KV
500 0
500 120
O O
162
POWER SYSTEM CONSULTANTS GROUP
CASE 14
R PHASE OPEN ( e.g. CONDUCTOR SNAPS )
633 93
650 -40 650 -40 163
192
POWER SYSTEM CONSULTANTS GROUP
CASE 14
IF CT RATIO 500/1 AND (PS)PLUG SETTING 0.5
650
PSM (PLUG SETTING MULTIPLIER) = ---------- = 2.6 > 2
500 x 0.5
EARTH FAULT RELAYS (51N) WILL PICK UP
TRANSFORMER
SOURCE 33 kV 11 kV
633 93
650 -40 650 -40 164
193
POWER SYSTEM CONSULTANTS GROUP
CASE 14
CONCEPT SAME
165
POWER SYSTEM CONSULTANTS GROUP
BATTERIES : 110 V, 55 V, 24 V
VDC
R
(-VE) 110
166
POWER SYSTEM CONSULTANTS GROUP
VDC
R
(-VE) 110
167
POWER SYSTEM CONSULTANTS GROUP
15.0 REFERENCES
ANSI / IEEE STD 142 : IEEE RECOMMENDED PRACTICE
FOR GROUNDING OF INDUSTRIAL AND COMMERCIAL
POWER SYSTEMS [ GREEN BOOK ]
• UNGROUNDED SYSTEM
N IB
Y
IY
R
IR X X X
C C C
FIG_2_1_A
169
POWER SYSTEM CONSULTANTS GROUP
PHASOR DIAGRAM
B
V = VY = VB = 1.0
R
IR VRY = VYB = V BR = 3
G,N
R
IY
IB IR + IY + IB = 0
VNG = V0 = 0
Y
FIG_2_1_B
170
POWER SYSTEM CONSULTANTS GROUP
UNGROUNDED SYSTEM
IRB B
IRB
IRY Y
IRY
R
IRY + IRB IF XC XC
IRY
FIG_2_2_A
IRB
171
POWER SYSTEM CONSULTANTS GROUP
PHASOR DIAGRAM
B I F = ( I RY + I RB )
= - ( I YR + I BR )
VBR = VBG = 3
VYR = VYG = 3
G I BR = I YR = I = 3 / X
N C
R
I YR + I BR = 3 I = 3 / X
C
I BR I YR
I F = I RY + I RB
I YR + I BR V D = V RG + V YG + V BG = 3.0
Y
VGN = V0 = 1.0 FIG_2_2_B
172
POWER SYSTEM CONSULTANTS GROUP
Y
B
V RG V YG V BG
R R R
N
VNG
FIG_2_3_A
173
POWER SYSTEM CONSULTANTS GROUP
B VR = VY = VB = 1.0
VRY = V YB = V BR = 3
VR VRG
G VY VYG
N R
VB VBG
V D = V + V + V = 3V = 0
R Y B 0
V= V = V D /3 =0
NG 0
Y
FIG_2_4_A
174
POWER SYSTEM CONSULTANTS GROUP
SOLIDLY GROUNDED
IF = 8543 AMPS
B VR = 0, FAULTED PHASE
VY = 0.992
VB = 0.996
VRY = VY = 0.992
VYB = 3
G
N VBR = VB = 0.996
R
VD = 0.977
V NG = V0 = V D / 3 = 0.326
FIG_2_4_B
Y 175
POWER SYSTEM CONSULTANTS GROUP
+5
No restrike
+1
Current interruption
Source
voltage -3 FIG_2_5
176
216
POWER SYSTEM CONSULTANTS GROUP
T1
6600/3
--------
110 / 3
S1
T2
110
--------
110 / 3
S2
VD = 3VO = VR + VY + VB FIG_2_6_A
R 177
POWER SYSTEM CONSULTANTS GROUP
UNGROUNDED SYSTEM
S1 S2
VOLTAGE ACROSS RELAY = ---- ---- (VR + VY + VB)
T1 T2
FIG_2_6_B
178
POWER SYSTEM CONSULTANTS GROUP
FIG_2_6_C
179
POWER SYSTEM CONSULTANTS GROUP
Y
B
N
VNG
FIG_2_7_A
180
POWER SYSTEM CONSULTANTS GROUP
XC : CHARGING CAPACITANCE
VN > 1.0
VN : NEUTRAL VOLTAGE
XE/XC = 1/3
1
-1
FIG_2_8
-2 182
222
POWER SYSTEM CONSULTANTS GROUP
• NEUTRAL INVERSION
B
1.0 R
G,N N'
Y FIG_2_9_A
183
POWER SYSTEM CONSULTANTS GROUP
• GROUNDING LOCATIONS
FIG 3_1_A
185
POWER SYSTEM CONSULTANTS GROUP
FIG 3_1_B
186
POWER SYSTEM CONSULTANTS GROUP
3 X2T
I 1 = 3 I 0 = ------------------------- I2
Z +VE + Z -VE + Z 0
3 X0G
= ------- = 3.5714 PU Z0
0.84 X0T
3.5714
K F = ----------- > 1 I FIG 3_2
0
2.6316
188
• SINGLE PHASE FAULT CURRENT > THREE PHASE FAULT CURRENT
POWER SYSTEM CONSULTANTS GROUP
VOLTAGE VARIATION
2
1.75
1.5
VOLTAGE PU
0.8 * V(L_L)
1.25
MAX_PHASE_VOLTAGE
1
0.75
0.5
V_NEUTRAL
0.25
FIG_3_3
RO / X1
0
0.01 0.1 1 189
10
229
POWER SYSTEM CONSULTANTS GROUP
G
FIG_4_1_A
[ {20% to 80%} ; {10% to 40%} ]
190
POWER SYSTEM CONSULTANTS GROUP
G {1% to 10%}
FIG_4_1_B
191
POWER SYSTEM CONSULTANTS GROUP
1 0 1 0
1 120 1 0
1 240 1 0
O 3 0
+VE HALF
CYCLE
FIG_4_2_B
-VE HALF
CYCLE 193
POWER SYSTEM CONSULTANTS GROUP
IRB B
IRB
IRY Y
R IRY
IRY + IRB
R
IN IF XC XC
IN IRY
IN
FIG_5_1_A
IRB 194
POWER SYSTEM CONSULTANTS GROUP
PHASOR DIAGRAM
B
IRY + IRB
IF
N IN
R,G
IBR IYR
VOL
I UG
IF
0
PHI = 45
PHI = 90 0
FIG_5_2
196
236
POWER SYSTEM CONSULTANTS GROUP
IRB B
IRB
IRY Y
GFN IRY
XL IRY + IRB
R
IN F XC XC
IN IRY
FIG_6_1_A
IRB
197
POWER SYSTEM CONSULTANTS GROUP
B
IRY + IRB VNG = 1.0
VBR = VBG = 3
VYR = VYG = 3
N G
R
IBR = IYR= I = 3 / XC
IR
B IYR
IYR + IBR = 3 I = 3 / XC
IN = 1 / XL
Y IYR + IBR
( IN ) IN = - (IRY + IRB)
FIG_6_1_B
198
POWER SYSTEM CONSULTANTS GROUP
E/3 P
E/ 3
FIG_7_1_A
3I0 NGR 199
POWER SYSTEM CONSULTANTS GROUP
E/3
E/3
E/3
B Y
E FIG_7_1_B
200
POWER SYSTEM CONSULTANTS GROUP
I0(5.1)
2I0 (10.2)
IF =3I 0
I0 (5.1) I0 (15.3)
(5.1)
I0
(5.1)
250
FIG_7_2
3I0
(15.3) 201
POWER SYSTEM CONSULTANTS GROUP
GENERATOR E = 1.0
4 MVA
X'd : 0.25
ZPOS
415 V
TRANSFORMER
5.5 MVA
X : 0.08 D ZNEG
11 KV
FAULT
Z ZER
ZIG ZAG GROUNDING
TRANSFORMER FIG 7_3_A
NGR
I0
IF = 3I 0 202
POWER SYSTEM CONSULTANTS GROUP
GENERATOR
X(-VE) = X2 = X1 = 0.625 PU
TRANSFORMER
X(-VE) = X2 = X1 = 0.1455 PU
X(+VE) = X(-VE) =
FIG 7_3_B
Z0 = R0 + j X0 203
POWER SYSTEM CONSULTANTS GROUP
ZERO SEQUENCE
EQUIVALENT CIRCUIT
I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0
I0
R I0
FIG 7_4_A
I F = 3I 0
204
POWER SYSTEM CONSULTANTS GROUP
ZERO SEQUENCE
EQUIVALENT CIRCUIT
I0
I0 I0 I0 I0 t
V0 Z 0= z 0 + R/3
3V 0 R
I0
I0
FIG 7_4_B
I F = 3I 0
205
POWER SYSTEM CONSULTANTS GROUP
I0 2I 0
I0
I0
I0 I0 I0 3I0
I F = 3I 0
FEEDER #1
I0 I0
FIG_8_1
I0
206
FEEDER #2
POWER SYSTEM CONSULTANTS GROUP
T1 T2
G1 G2
N1 N2
NGR
FIG_10_1_A
208
POWER SYSTEM CONSULTANTS GROUP
CASE 2
EHV BUS
GT1 GT2
G1 G2
N1 N2
NGR NGR
FIG_10_1_B
209
POWER SYSTEM CONSULTANTS GROUP
G1 G2
N1 N2 NGR
ZIG ZAG
GROUNDING
TRANSFORMER FIG_10_2_A
210
POWER SYSTEM CONSULTANTS GROUP
• CASE 4
G1 G2
N1 N2
ISOLATING DEVICE
FIG_10_2_B
211
POWER SYSTEM CONSULTANTS GROUP
R = 1 K GT
250 MVA
235 MVA G 10%
X'd 30%
16 KV
UAT
10 MVA
10%
6.6 KV
B
IF = 3480 AMPS
VR = 0, FAULTED PHASE
VY = 1.419
VB = 1.822
VRY = VY = 1.419
N VYB = 3
G VBR = VB = 1.822
R
VD = 2.769
VGN = V0 = 0.923
FIG_11_2_A
Y
213
POWER SYSTEM CONSULTANTS GROUP
B
IF = 10 AMPS
VR = 0, FAULTED PHASE
VY = 3
VB = 3
N G VRY = VY = 3
R VYB = 3
VBR = VB = 3
VD = 3.0
VGN = V0 = 1.0
Y FIG_11_2_B
214
POWER SYSTEM CONSULTANTS GROUP
2
VL_MIN
1.5 70%
VL_RAT
0.5
FIG_11_3
0
10 100 1000 10000215
CURRENT IN AMPS 255
POWER SYSTEM CONSULTANTS GROUP
FAIRY TALES
FAULT CURRENT RETURNS TO ANY TRANSFORMER NEUTRAL ?
216
FIG 13_1_A
POWER SYSTEM CONSULTANTS GROUP
Ia TA IA
IN TC
Ta
Ib Tb
Tc I C
TB
IB
Ic
IF
217
FIG 13_1_B
POWER SYSTEM CONSULTANTS GROUP
FAIRY TALES
• CASE 1 :
SOURCE TRANSFORMER
FIG 13_2_A
218
POWER SYSTEM CONSULTANTS GROUP
• CASE 2 :
SOURCE TRANSFORMER
FIG 13_2_B
219
POWER SYSTEM CONSULTANTS GROUP
• CASE 3 :
SOURCE TRANSFORMER
0 0
0 0
Ia IA
IF
FIG 13_2_C
220
POWER SYSTEM CONSULTANTS GROUP
CASE 4 :
SOURCE TRANSFORMER
0 0
0 0
Ia R IA
60 A 100 A IF
FIG 13_3_A
221
POWER SYSTEM CONSULTANTS GROUP
CASE 5 :
SOURCE TRANSFORMER
0 0
0 0
Ia R IA
100 A
37 A 62 A IF
FIG 13_3_B
222
POWER SYSTEM CONSULTANTS GROUP
CASE 6
Ia 0 0
IN 0
0
IA
IF
FIG 13_4_A
223
POWER SYSTEM CONSULTANTS GROUP
• VOLTAGE VECTORS
DELTA STAR
R
B
VR = 1.0 VR = 0
VY = 0.51 N G VY = 0.88
VB = 0.51 R VB = 0.88
• CASE 7
TRANSFORMER
SOURCE P T S
2 2 1 1
0
0 3 0
1 1 3
1 1
1
IF = 3
FIG 13_5_A
225
POWER SYSTEM CONSULTANTS GROUP
• CASE 8
TRANSFORMER
SOURCE P T S
4 4 1 1
0
2 5 0
1 1 5
1 1
2
1
IF = 5
FIG 13_5_B
226
POWER SYSTEM CONSULTANTS GROUP
SYSTEM
220 KV
R R O/H LINE
G1 G2
SOURCE T
11 KV R 400A
FIG 13_6_A
227
POWER SYSTEM CONSULTANTS GROUP
H – L : 12.1 %
L – T : 21.2 %
FIG 13_6_B
H – T : 36.3 %
228
POWER SYSTEM CONSULTANTS GROUP
FIG 13_6_C
229
POWER SYSTEM CONSULTANTS GROUP
• CASE 9
TRANSFORMER STAR GROUNDED [P] D [T] STAR GROUNDED [S]
TRANSFORMER
-j 2.76
-j 2.76
SOURCE
SYSTEM
11 KV 220 KV
-j 2.76 0.25 - j1.54
- 0.6 + j 8.6
0.25 - j1.54
- 0.25 + j 4.3
0.6 - j11.36 - j 298.3
- 0.25 + j 4.3
• CASE 10
TRANSFORMER
-j 2.7
-j 2.7
-j 298.3 -j 2.7
-j 292.9 -j 8.1
IF = -j 301
FIG 13_8_A
231
POWER SYSTEM CONSULTANTS GROUP
CASE11
TRANSFORMER
SYSTEM R P S
-j 7.6
-j 7.6
-j7.6
-j 7.6
FIG 13_8_B
232
POWER SYSTEM CONSULTANTS GROUP
• CASE 12
SOLIDLY GROUNDED
TRANSFORMER
GENERATOR R P S
-j 2.4
-j 2.4
-j 2.4
-j 2.4
IF = -j 12.7
FIG 13_9_A
1 PU CURRENT = 525 AMPS 233
POWER SYSTEM CONSULTANTS GROUP
GENERATOR R P S
0.25
0.25
0.25
0.25
16 16
• CASE 13
AUTOTRANSFORMER NEUTRAL GROUNDED D [TERTIARY ]
XHM = 9.5%; XML = 47.4%; XHL = 31% ON 37.5 MVA BASE
SOURCE LOAD
132 KV 220 KV
588 408
655
180 11 KV
90 90
0
90
90 0
FIG 13_10
235
408 0 408
POWER SYSTEM CONSULTANTS GROUP
TRANSFORMER
SOURCE 33 KV 11 KV
500 0
500 120
O O
FIG 13_11_A
236
POWER SYSTEM CONSULTANTS GROUP
TRANSFORMER
SOURCE 33KV 11 KV
LOAD
513 -155
FIG 13_11_B
237
POWER SYSTEM CONSULTANTS GROUP
ACCIDENTAL CONTACT
SITCHGEAR
N V TOUCH
GRID
RE =
1
E
238
FIG_4_3
POWER SYSTEM CONSULTANTS GROUP
B VR = VY = VB = 1.0
VRY = V YB = V BR = 3
VR VRG
G VY VYG
N R
VB VBG
V D = V + V + V = 3V = 0
R Y B 0
V NG = V0 = VD / 3 = 0
Y
FIG_2_4_A
239
POWER SYSTEM CONSULTANTS GROUP
SOLIDLY GROUNDED
IF = 8543 AMPS
B VR = 0, FAULTED PHASE
VY = 0.992
VB = 0.996
VRY = VY = 0.992
VYB = 3
G
N VBR = VB = 0.996
R
VD = 0.977
V NG = V0 = V D / 3 = 0.326
FIG_2_4_B
Y 240
POWER SYSTEM CONSULTANTS GROUP
VN > 1.0
VN : NEUTRAL VOLTAGE
XE/XC = 1/3
1
-1
FIG_2_7_A
FIG_2_8
-2 241
282
POWER SYSTEM CONSULTANTS GROUP
ZERO SEQUENCE
EQUIVALENT CIRCUIT
I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0
I0
R I0
FIG 7_4_A
I F = 3I 0
242
POWER SYSTEM CONSULTANTS GROUP
ZERO SEQUENCE
EQUIVALENT CIRCUIT
I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0
I0
R I0
FIG 7_4_A
I F = 3I 0
243
POWER SYSTEM CONSULTANTS GROUP
T1 T2
G1 G2
N1 N2
NGR
FIG_10_1_A
244
POWER SYSTEM CONSULTANTS GROUP
• CASE 4
G1 G2
N1 N2
ISOLATING DEVICE
FIG_10_2_B
245
POWER SYSTEM CONSULTANTS GROUP
G1 G2
N1 N2
ISOLATING DEVICE
FIG_10_2_B
246
POWER SYSTEM CONSULTANTS GROUP
+5
No restrike
+1
Current interruption
Source
voltage -3 FIG_2_5
247
288
POWER SYSTEM CONSULTANTS GROUP
+5
No restrike
+1
Current interruption
Source
voltage -3 FIG_2_5
248
289
POWER SYSTEM CONSULTANTS GROUP
IRB B
IRB
IRY Y
GFN IRY
XL IRY + IRB
R
IN F XC XC
IN IRY
FIG_6_1_A
IRB
249
POWER SYSTEM CONSULTANTS GROUP
I0 2I 0
I0
I0
I0 I0 I0 3I0
I F = 3I 0
FEEDER #1
I0 I0
FIG_8_1
I0
250
FEEDER #2
POWER SYSTEM CONSULTANTS GROUP
VR
VBR VRY
V0 N,G
N'
VY
VB
FIG_SE_CO_8
B VYB Y 251
POWER SYSTEM CONSULTANTS GROUP
ZERO SEQUENCE
EQUIVALENT CIRCUIT
I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0
I0
R I0
FIG 7_4_A
I F = 3I 0
252
POWER SYSTEM CONSULTANTS GROUP
ZERO SEQUENCE
EQUIVALENT CIRCUIT
I0
I0 I0 I0 I0 t
V0 Z 0= z 0 + R/3
3V 0 R
I0
I0
FIG 7_4_B
I F = 3I 0
253
POWER SYSTEM CONSULTANTS GROUP
Ia 0 0
IN 0
0
IA
IF
FIG 13_4_A
254