You are on page 1of 254

POWER ENGINEERING

TRAINING COURSE

GROUP

POWER LINKERS

Wisdom is not Virtue but Necessity 1


REV. R0, 03-03-2000
POWER SYSTEM CONSULTANTS GROUP

Power Engineering Training Course

Protection and Control Equipment Dr. K. Rajamani

and

Grounding of Electrical System Mr. H. C. Mehta

2
POWER SYSTEM CONSULTANTS GROUP

1st Day : Protection & Control Equipment

09.00 - 09.30 Hrs. Registration


09.30 - 10.00 Hrs. Inauguration
10.00 - 11.00 Hrs. 1st Session
11.00 - 11.15 Hrs. Tea Break
11.15 - 13.00 Hrs. 2nd Session
13.00 - 14.00 Hrs. Lunch Break
14.00 - 15.15 Hrs. 3rd Session
15.15 - 15.30 Hrs. Tea Break
15.30 - 17.00 Hrs. 4th Session
17.00 - 17.30 Hrs. Q-A Session 3
POWER SYSTEM CONSULTANTS GROUP

INDEX

1.0 INTRODUCTION

1.1 UNGROUNDED AND GROUNDED SYSTEM

1.2 GROUNDING AND EARTHING

2.0 UNGROUNDED SYSTEM

2.1 NEUTRAL & GROUND – DIFFERENCE

2.2 ADVANTAGES OF UNGROUNDED SYSTEM

2.3 DISADVANTAGES OF UNGROUNDED SYSTEM


4
POWER SYSTEM CONSULTANTS GROUP

2.0 UNGROUNDED SYSTEM

2.4 TRANSIENT OVER VOLTAGES IN


UNGROUNDED SYSTEM

2.5 GROUND FAULT DETECTION IN


UNGROUNDED SYSTEM

2.6 NEUTRAL INVERSION AND FERRO_RESONANCE

2.7 MITIGATING TECHNIQUES FOR


FERRO RESONANCE

2.8 UNGROUNDED SYSTEM APPLICATION 5


POWER SYSTEM CONSULTANTS GROUP

3.0 REASONS FOR GROUNDING


3.1 GROUNDING LOCATIONS

3.2 GROUNDING METHODS

3.3 MEASURE OF GROUNDING EFFECTIVENESS

3.4 EFFECTIVELY GROUNDED SYSTEM

4.0 SOLID GROUNDING


4.1 GROUNDING, ZERO SEQUENCE AND HARMONIC
CURRENTS

4.2 APPLICATIONS
6
POWER SYSTEM CONSULTANTS GROUP

5.0 RESISTANCE GROUNDING


5.1 REASONS FOR LIMITING FAULT CURRENT

5.2 HIGH RESISTANCE GROUNDING

5.3 LOW RESISTANCE GROUNDING

6.0 RESONANT GROUNDING


GROUND FAULT NEUTRALISER

7.0 GROUNDING THE BUS


7.1 ZIG – ZAG TRANSFORMER

7.2 STAR – DELTA TRANSFORMER


7
POWER SYSTEM CONSULTANTS GROUP

8.0 UNINTENTIONAL GROUNDING

9.0 SUMMARY OF COMPARISON : DIFFERENT


GROUNDING METHODS

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES

11.0 NEUTRAL GROUNDING – PHASE AND LINE


VOLTAGES

12.0 SEQUENCE VOLTAGES VS FAULT LOCATION


8
POWER SYSTEM CONSULTANTS GROUP

13.0 NEUTRAL GROUNDING - FAIRY TALES

14.0 GROUNDING – DC SYSTEM

15.0 REFERENCES

9
POWER SYSTEM CONSULTANTS GROUP

1.0 INTRODUCTION

1.1 UNGROUNDED AND GROUNDED SYSTEM

 UPTO 1940 : MOST OF THE SYSTEMS

 OPERATED UNGROUNDED

 NEUTRALS KEPT FREE ( FLOATING )

 GROUND CONNECTION NOT USEFUL FOR TRANSFER

OF THREE PHASE POWER IN THREE WIRE SYSTEM

10
POWER SYSTEM CONSULTANTS GROUP

1.1 UNGROUNDED AND GROUNDED SYSTEM

 LINE TO GROUND FAULT: MAJORITY (70%)

 NO RETURN PATH : FAULT CURRENT VERY LOW

 SERVICE NOT INTERRUPTED

 AT LEISURE, LOCATE FAULT AND RECTIFY

 RELAYING NOT ADVANCED

11
POWER SYSTEM CONSULTANTS GROUP

1.1 UNGROUNDED AND GROUNDED SYSTEM

 SOON PROBLEMS BECAME CRITICAL

 TRANSIENT OVER VOLTAGES

 ARCING GROUNDS

 INSULATION FAILURE

 GROUNDING NEUTRAL – SOLUTION ?

12
POWER SYSTEM CONSULTANTS GROUP

1.1 UNGROUNDED AND GROUNDED SYSTEM

 UNGROUNDED [ OVER VOLTAGE PROBLEM ]

GROUNDED [ OVER CURRENT PROBLEM ]

 EVEN TODAY GROUNDED VS UNGROUNDED

'THE' PREFERRED ALTERNATIVE : DOES NOT EXIST


13
POWER SYSTEM CONSULTANTS GROUP

1.2 GROUNDING AND EARTHING

• GROUNDING

 CONNECTION OF POWER SYSTEM NEUTRAL TO


GROUND (EARTH)
 NEUTRAL GROUNDING / SYSTEM GROUNDING

 CONNECTION OF CURRENT CARRYING PART TO


GROUND

 LIMIT OVER VOLTAGE OF LIVE CONDUCTOR


 INSULATION PROBLEM

14
POWER SYSTEM CONSULTANTS GROUP

• EARTHING

 ANOTHER TERM  EQUIPMENT GROUNDING

 CONNECTION OF NON CURRENT CARRYING PARTS


(LIKE ENCLOSURE) TO GROUND

 FOR HUMAN AND EQUIPMENT SAFETY

 TOUCH & STEP POTENTIAL  IN VOLTS

 THIS PRESENTATION : ONLY ABOUT NEUTRAL


GROUNDING AND NOT ABOUT EARTHING
15
POWER SYSTEM CONSULTANTS GROUP

2.0 UNGROUNDED SYSTEM

 NO INTENTIONAL CONNECTION TO GROUND FOR


EXCLUSIVE GROUNDING PURPOSE

 REALITY  NO IDEAL UNGROUNDED SYSTEM

 PHASES COUPLED TO GROUND


THROUGH CAPACITANCE

16
POWER SYSTEM CONSULTANTS GROUP

 BALANCED OPERATION • UNGROUNDED SYSTEM


• BALANCED STEADY STATE OPERATION
B

  CHARGING CURRENTS N IB
Y
= IR + IY + IB = 0 IY
R
X
IR X X
C C C
 NO RESULTANT CURRENT FIG_2
_1_A
TO EARTH
PHASOR DIAGRAM
B
VR = V Y = V B = 1.0
 NEUTRAL VOLTAGE = IR VRY= V YB= V BR=  3
G,N
R
GROUND VOLTAGE = 0 IB
IY
IR+ IY+ IB= 0


VNG= V 0 = 0
Y
FIG_2
NEUTRAL SHIFT _1_B

17
POWER SYSTEM CONSULTANTS GROUP

PHASOR DIAGRAM

• FIG 2_2_A
B I F = ( I RY+ I RB )

 SINGLE LINE TO GROUND FAULT = - (I YR+ I BR )


V
BR
=V
BG
= 3

V =V = 3
YR YG

 (PHASE) VOLTAGE TO GROUND G I  = I = I =  3 / X


N BR YR

OF HEALTHY PHASES  3
C
R

I YR+ I BR =  3 I = 3 / X
C
I BR I YR
I F = I RY + I RB

 LINE VOLTAGE TRIANGLE I YR + I BR VD = V + V


RG YG
+ V = 3.0
BG
Y

 NO CHANGE V
GN
=V
0
= 1.0
FIG_2
_2_B

 NEUTRAL VOLTAGE  GROUND VOLTAGE



NEUTRAL SHIFT  1.0 PU
 FAULT CURRENT ( IF ) : CAPACITIVE CURRENT = 3 / XC
 IF IF > 5 to 10A, ARCING GROUNDS 18
POWER SYSTEM CONSULTANTS GROUP

 FALLACY : NO HAZARD IN TOUCHING A LIVE PHASE !!

 CURRENT THROUGH BODY AND STRAY CAPACITANCE

 IF CURRENT MORE THAN A FEW MILLIAPS, INJURIOUS

IRB B
IRB
IRY Y
IRY
R
IRY + IRB XC XC
IRY
IRB
19
POWER SYSTEM CONSULTANTS GROUP

2.1 NEUTRAL & GROUND – DIFFERENCE

 NEUTRAL & GROUND  NOT ALWAYS SAME

 GROUND  ALWAYS ZERO VOLTAGE PLANE

 NEUTRAL  CAN BE AT GROUND POTENTIAL i.e. ZERO


OR
 CAN HAVE SOME NON_ZERO POTENTIAL
W.R.T GROUND

 IF NEUTRAL AT ZERO POTENTIAL  NO NEUTRAL SHIFT

 IF NEUTRAL AT NON_ZERO POTENTIAL


 NEUTRAL SHIFTED 20
POWER SYSTEM CONSULTANTS GROUP

 DEFINITION OF NEUTRAL

 CONNECT THREE IDEAL AND EQUAL RESISTORS


TO THE THREE PHASES IN STAR

 COMMON JUNCTION POINT  NEUTRAL

 VOLTAGE OF COMMON JUNCTION POINT W.R.T GROUND


 NEUTRAL VOLTAGE

21
POWER SYSTEM CONSULTANTS GROUP

• FIG 2_3
• NEUTRAL AND ZERO SEQUENCE VOLTAGE
 ZERO SEQUENCE R

VOLTAGE AT Y
B
ANY POINT IN NETWORK
V RG V YG V BG

R R R R
N
NEUTRAL SHIFT AT
THAT POINT IN THE VNG

NETWORK FIG_2_3_A

 VRG  VNG VYG  VNG VBG  VNG


--------------  -----------------  -------------- = 0
R R R
 VRG  VYG  VBG = 3 VNG

 FROM THEORY OF SYMMETRICAL COMPONENTS


VRG  VYG  VBG = 3 V0
 HENCE, VNG = V0

 ZERO SEQUENCE VOLTAGE AT ANY POINT IN NETWORK


 22
NEUTRAL SHIFT AT THAT POINT IN THE NETWORK
POWER SYSTEM CONSULTANTS GROUP

• FIG 2_4 VR = VY = VB = 1.0

 BALANCED OPERATING B VRY = V YB = V BR =  3

CONDITION VR  VRG

 VRG = 1  0 ; G ,N R VY  VYG
VYG = 1  -120 ; VB  VBG
VBG = 1  120
Y
V D = V + V + V = 3V = 0
R Y B 0
 VRG  VYG  VBG
VNG = V0 = V D / 3 = 0
= 3 VNG = 3 V0 = 0

 NEUTRAL AT GROUND POTENTIAL : NO SHIFT


23
POWER SYSTEM CONSULTANTS GROUP

 UNBALANCED OPERATING CONDITION


B

 LINE TO GROUND FAULT


ON PHASE 'R’

 VRG = 0 ; G
R
N

VYG  1  -120 ;

VBG  1  120
Y

 VRG  VYG  VBG = 3 VNG = 3 V0 = 1.0

 NEUTRAL VOLTAGE( VNG )  0.33 PU ABOVE GROUND


24
POWER SYSTEM CONSULTANTS GROUP

 NEUTRAL DISPLACEMENT  OCCURS IRRESPECTIVE OF


TYPE OF GROUNDING

 NEUTRAL DISPLACEMENT MAGNITUDE

HIGH  UNGROUNDED SYSTEM (e.g. 1 PU)


( 100% VPHASE)

LOW  SOLIDLY GROUNDED SYSTEM (e.g. 0.33 PU)


( 33% VPHASE)

25
POWER SYSTEM CONSULTANTS GROUP

 FIG_SE_CO_8

 PRESENCE OF ZERO SEQUENCE VOLTAGE V0

 DISTORTS PHASE VOLTAGES

 NEUTRAL VOLTAGE TO GROUND # 0  NEUTRAL SHIFTED

 BUT LINE to LINE VOLTAGE UNAFFECTED !

26
POWER SYSTEM CONSULTANTS GROUP

 FIG 13_4_A

 FIG 13_4_B

 NEUTRAL VOLTAGE VNG= 0  BALANCED SYSTEM ?

 NO! BOTH LINE & PHASE VOLTAGE CAN BE UNBALANCED


AND STILL THERE NEED NOT BE ANY NEUTRAL SHIFT!

 MORAL

 INDICATION OF UNBALANCE

 MEASUREMENT OF NEUTRAL VOLTAGE OR LINE to LINE


VOLTAGE  NOT POSITIVE PROOF

 MEASUREMENT OF LINE to GROUND VOLTAGE (PHASE


VOLTAGE)  POSITIVE PROOF 27
POWER SYSTEM CONSULTANTS GROUP

2.2 ADVANTAGES OF UNGROUNDED SYSTEM


 CURRENT AT THE POINT OF FAULT  VERY LOW

CORE OR IRON DAMAGE MINIMUM

 SERVICE CONTINUITY POSSIBLE EVEN WITH (L-G)


FAULT HANGING

 ZERO SEQUENCE CURRENT CIRCULATION  VERY LOW



INTERFERENCE WITH COMMUNICATION CIRCUITS 
MINIMUM
28
POWER SYSTEM CONSULTANTS GROUP

2.3 DISADVANTAGES OF UNGROUNDED SYSTEM


 MULTIPLE FAULTS TO GROUND  TRIPPING OF FEEDERS

 FEEDER A ( R to G & Y to G )  TRIP FEEDER A

 FEEDER A( R to G ) & FEEDER B( Y to G )  TRIP FEEDERS


A&B
 FEEDER A( R to G ) & FEEDER B( R to G )  NO TRIPPING

 OVERVOLAGE ON HEALTHY PHASES DURING FAULTS


 NEUTRAL  FULL INSULATION

 NOT POSSIBLE TO USE GRADED INSULATION

 LA RATING HIGHER  100% ( L to L )


29
POWER SYSTEM CONSULTANTS GROUP

2.3 DISADVANTAGES OF UNGROUNDED SYSTEM

 ARCING FAULTS, RESTRIKE  INSULATION FAILURE

 FAULT DETECTION : POSSIBLE

 FAULT LOCATION : DIFFICULT

30
POWER SYSTEM CONSULTANTS GROUP

2.4 TRANSIENT OVER VOLTAGES IN UNGROUNDED SYSTEM


 CURRENT TO BE INTERRUPTED  CAPACITIVE CURRENT
BREAKER / ARC
R,X
L

VSOURCE X
C

• FIG 2_5

 VOLTAGE & CURRENT  90 OUT OF PHASE

 INTERRUPTION AT CURRENT ZERO



 VOLTAGE MAXIMUM ( SAY 1.0 PU ) AT INTERRUPTION
31
POWER SYSTEM CONSULTANTS GROUP

2.4 TRANSIENT OVER VOLTAGES IN UNGROUNDED SYSTEM

• FIG 2_5
 RESIDUAL VOLTAGE ACROSS CAPACITIVE SYSTEM
( V RC  +1 PU ) DECAYS AS PER ITS TIME CONSTANT

 RESTRIKE OCCURS, WHEN SOURCE VOLTAGE (-VE)


MAXIMUM (  1 PU )

 VOLTAGE AT CAPACITOR, AFTER REFLECTION, DUE TO SOURCE


V SC+ = 2 PU

 VOLTAGE ACROSS ARC / BREAKER = V SC+  V RC =  3 PU

 ARC INTERRUPTS AGAIN


32
POWER SYSTEM CONSULTANTS GROUP

2.4 TRANSIENT OVER VOLTAGES IN UNGROUNDED SYSTEM

• FIG 2_5

 RESIDUAL VOLTAGE ACROSS CAPACITOR V RC   3 PU

 RESTRIKE OCCURS AGAIN  WHEN SOURCE VOLTAGE


(+VE) MAXIMUM (  1 PU )

 VOLTAGE AT CAPACITOR, AFTER REFLECTION, DUE TO SOURCE


V SC+ =  2 PU

• VOLTAGE ACROSS ARC / BREAKER = V SC+  V RC =  5 PU

BREAKER / ARC
R,X
L

VSOURCE X
C

33
POWER SYSTEM CONSULTANTS GROUP

2.4 TRANSIENT OVER VOLTAGES IN UNGROUNDED SYSTEM

 WITH EVERY RESTRIKE  SUCCESSIVE VOLTAGE BUILD UP

 POTENTIAL FOR VERY HIGH VOLTAGES  INSULATION FAILURE

 IN ACTUAL PRACTICE, OVER VOLTAGE LESS ( 3 to 4 PU )



DUE TO PRESENCE OF FINITE RESISTANCE IN THE CIRCUIT

INCREASED SYSTEM DAMPING

34
POWER SYSTEM CONSULTANTS GROUP

2.5 GROUND FAULT DETECTION IN UNGROUNDED SYSTEM


 SENSING QUANTITY : CAN BE ONLY VOLTAGE AS CURRENT
IS LOW

 VOLTAGE  SYSTEM WIDE ATTRIBUTE


 NOT LIMITED TO INDIVIDUAL FEEDERS LIKE
CURRENT

 GROUND FAULT DETECTION POSSIBLE


GROUND FAULT LOCATION DIFFICULT

35
POWER SYSTEM CONSULTANTS GROUP

 TO LOCATE GROUND FAULT (e.g. FAULT IS ON FEEDER F3 )


FURTHER WORK REQUIRED

F1 F2 F3 R
Y
B

FAULT

36
POWER SYSTEM CONSULTANTS GROUP

2.5 GROUND FAULT DETECTION


 METHOD 1 : OPEN DELTA PT ( PREFERRED )
• FIG 2_6_A
 UNGROUNDED SYSTEM
VD = (VR + VY + VB) = 3VO = 3 VL-L = 3 * 6600 = 11,430 Volts
S1 S2
 VOLTAGE ACROSS RELAY = ---- ---- (VR + VY + VB)
T1 T2
(110 / 3) (110/3)
VD = --------------- ----------- 11430 = 63.5 Volts
(6600/ 3) 110
 IF AUXILIARY TRANSFORMER RATIO IS 110 / (110 / 3),
VD = 110 Volts
RELAY RATED FOR 63.5V AND WIRED FOR ALARM
CAN NOT BE USED IN THIS CASE 45
37
 PREFERRED RATIO FOR AUX. TRANSFORMER : 110 / (110 / 3)
POWER SYSTEM CONSULTANTS GROUP

2.5 GROUND FAULT DETECTION


 METHOD 2 : SINGLE PT ( NOT PREFERRED )
R
Y
B

U/V O/V

 FAULT ON PHASE 'R'  U / V  UNDER VOLTAGE RELAY


PICKS UP
FAULT ON PHASE 'Y' OR 'B'  O / V  OVER VOLTAGE RELAY
PICKS UP
 UNGROUNDED SYSTEM : FAULT ON PHASE 'R'
 VOLTAGES OF PHASES 'Y' AND 'B' TO GROUND
 3 x NORMAL VALUE 38
POWER SYSTEM CONSULTANTS GROUP

 METHOD 2 : SINGLE PT ( NOT PREFERRED )

 NOT RECOMMENDED FOR PRACTICAL IMPLEMENTATION

 PROBLEMS : NEUTRAL INVERSION AND FERRO_RESONANCE

39
POWER SYSTEM CONSULTANTS GROUP

2.6 NEUTRAL INVERSION AND FERRO_RESONANCE


• FIG 2_7_A
 VRG , VYG , VBG : PHASE TO GROUND IMPRESSED VOLTAGES

 VNG : NEUTRAL TO GROUND VOLTAGE

 XC : CHARGING CAPACITANCE

 XEX : TRANSFORMER EXCITING (MAGNETISING) REACTANCE

VRG  VNG VRG  VNG VYG  VNG VBG  VNG


--------------  -----------------  --------------  -------------- = 0
j XEX  j XC  j XC  j XC

 WITH VRG  VYG  VBG = 0,


VRG
VNG = ------------------- 40
1  (3 XEX / XC )
POWER SYSTEM CONSULTANTS GROUP

2.6 NEUTRAL INVERSION AND FERRO_RESONANCE


 VARIATION OF VNG FOR DIFFERENT VALUES OF XEX / XC

 VNG < 0 OR VNG > 1

 VNG  DOES NOT LIE BETWEEN 0 & 1

 VNG  , WHEN XEX / XC  1 / 3 i.e. XC / XEX  3

 DESTRUCTIVE OVER VOLTAGES STRESSING THE INSULATION

NEUTRAL VOLTAGE VARIATION


2
VN : NEUTRAL VOLTAGE

VN > 1.0
XE/XC = 1/3
1
VRG
VNG = --------------------- XE/XC ( IC/IEX ) x 0.001
0
1  (3 XEX / XC ) 10 100 1000
VN < 0.0
10000

-1

FIG_2_8
-2 41
49
POWER SYSTEM CONSULTANTS GROUP

2.6 NEUTRAL INVERSION AND FERRO_RESONANCE


 VNG > 1  NEUTRAL NOT WITH IN VOLTAGE TRIANGLE D

NEUTRAL INVERSION
B

1.0 R
G,N N'

Y 42
POWER SYSTEM CONSULTANTS GROUP

2.6 NEUTRAL INVERSION AND FERRO_RESONANCE


 SIMILAR CONCEPT : VN > VA OR VN < VB

• LET VA = 1.0 AND VB = 0 VA


-j X C
1
 VN = -----------------
VN
1– (XC/ XL)
j XL
 IF (XC / XL) < 1 ,  VN > 1 ( i.e. VN > VA )
VB
[ e.g. XC/ XL = 0.2  VN = 1.25 ]

• IF (XC/ XL) > 1 ,  VN < 0 ( i.e. VN < VB )

[ e.g. XC/ XL = 5  VN = - 0.25 ]

• VN DOES NOT LIE BETWEEN VA AND VB 43


POWER SYSTEM CONSULTANTS GROUP

2.6 NEUTRAL INVERSION AND FERRO_RESONANCE


• FIG 2_8
 XEX IC CHARGING CAPACITIVE CURRENT
------ = ----- = ---------------------------------------------------
XC IEX EXCITING CURRENT DRAWN BY PT

 IF IC >> IEX  NEUTRAL INVERSION REMOTE

 IF IEX  3 IC  FERRO_RESONANCE BETWEEN SHUNT


CAPACITANCE AND MAGNETISING
(EXCITING) REACTANCE OF PT
 SAME EFFECT IF GROUND FAULT NEUTRALISER
( PETERSON COIL) CONNECTED TO ONE PHASE RATHER
THAN TO NEUTRAL !!
44
POWER SYSTEM CONSULTANTS GROUP

2.7 MITIGATING TECHNIQUES FOR FERRO RESONANCE (FR)


 PREFER 3 SWITCHING DEVICE TO AVOID SINGLE PHASING

 DO NOT SWITCH CABLE / LINE & TRANSFORMER TOGETHER

 NO LOAD SWITCHING OF TRANSFORMER MORE SUSCEPTIBLE


TO FERRO RESONANCE THAN WITH LOAD
 CAPACITOR BANKS ON TRANSFORMER SECONDARY :
UNGROUNDED NEUTRAL MORE PRONE TO FERRO
RESONANCE THAN GROUNDED NEUTRAL

 FERRO RESONANCE – VERY UNPREDICTABLE


ANALYSIS AND CORRECTIVE ACTION

MOSTLY AFTER FIRST POSITIVE OCCURRENCE !!
45
POWER SYSTEM CONSULTANTS GROUP

2.8 UNGROUNDED SYSTEM APPLICATION


 ALL SYSTEM COMPONENTS DESIGNED FOR THIS
APPLICATION? (e.g. UE GRADE CABLE, 100% LAs, PTs WITH
HIGHER VOL_FAC, … )

 QUALITY OF ELECTRICAL MAINTENANCE


(GOOD OR SATISFACTORY?)

 FIRST GROUND FAULT  PROMPT LOCATION AND


CORRECTION

46
POWER SYSTEM CONSULTANTS GROUP

3.0 REASONS FOR GROUNDING


 PROVIDE SUFFICIENT CURRENT FOR SENSING TO ISOLATE
ONLY THE FAULTED SECTION

 LIMIT OVER VOLTAGES APPEARING ON THE SYSTEM DURING


ABNORMAL CONDITIONS LIKE FAULT

 MINIMISE THE SHIFT OF NEUTRAL FROM GROUND


POTENTIAL(0) DURING ABNORMAL CONDITIONS LIKE FAULT

47
POWER SYSTEM CONSULTANTS GROUP

3.1 GROUNDING LOCATIONS

 NEUTRAL OF STAR CONNECTED GENERATOR FIG_3_1_A

 NEUTRAL OF STAR WINDING OF TRANSFORMER FIG_3_1_B

 BUS FED FROM UNGROUNDED SOURCE


SPECIAL EQUIPMENT LIKE GROUNDING TRANSFORMER
FIG_3_1_C

48
POWER SYSTEM CONSULTANTS GROUP

3.2 GROUNDING METHODS


 SOLID GROUNDING

 RESISTANCE GROUNDING

 REACTANCE (RESONANT) GROUNDING

 ABOVE CLASSIFICATION  NATURE OF EXTERNAL CIRCUIT


FROM NEUTRAL TO GROUND

 ABOVE CLASSIFICATION  DOES NOT REFER TO DEGREE


OF GROUNDING

49
POWER SYSTEM CONSULTANTS GROUP

3.3 MEASURE OF GROUNDING EFFECTIVENESS


 EFFECTIVELY GROUNDED SYSTEM

 TRANSIENT OVER VOLTAGES MINIMUM

I1 GROUND FAULT CURRENT


 KF = ------- = -------------------------------------------------
I3 THREE PHASE FAULT CURRENT

 FOR EFFECTIVELY GROUNDED SYSTEMS, KF  0.6

• FIG 3_2

50
POWER SYSTEM CONSULTANTS GROUP

 DEFINITION
A SYSTEM OR PORTION OF THE SYSTEM CAN BE SAID TO
BE EFFECTIVELY GROUNDED WHEN FOR ALL POINTS IN THE
SYSTEM OR SPECIFIED PORTION THEROF,
( X0 / X1 ) < 3 AND ( R0 / X1 ) < 1
FOR ANY CONDITION OF OPERATION AND ANY AMOUNT
OF GENERATION CAPACITY.

SYSTEM
A B C
Y
GROUNDED
 SYSTEM MAY BE EFFECTIVELY GROUNDED FOR FAULT AT 'B'

 SAME SYSTEM MAY NOT BE EFFECTIVELY GROUNDED FOR


FAULT AT 'C' 51
POWER SYSTEM CONSULTANTS GROUP

3.4 EFFECTIVELY GROUNDED SYSTEM

 ( X0 / X1 < 3 ) AND ( R0 / X1 ) < 1

 GROUND FAULT CURRENT SUBSTANTIAL

 DURING LINE TO GROUND FAULT


VOLTAGE (LINE to GROUND) < 80% VOLTAGE (LINE to LINE)

PHASE VOLTAGE < 3 x 0.8 = 1.4 NORMAL PHASE VOLTAGE

• NEUTRAL SHIFT MINIMUM

• FIG 3_3
52
POWER SYSTEM CONSULTANTS GROUP

3.4 EFFECTIVELY GROUNDED SYSTEM

 IF SYSTEM SOLIDLY GROUNDED, SECOND RELATION


( R0 / X1 < 1 ) , USUALLY SATISFIED

 GENERATOR : X0 ( 10% ) < X1 ( 25% )

• TRANSFORMER : X0  X1

 FOR EHV LINE : X0 > X1 [ X0 / X1  4 to 5 ]


ONLY AT THE END OF LONG EHV LINE, FIRST RELATION
( X0 / X1 < 3 ) MAY NOT BE SATISFIED

53
POWER SYSTEM CONSULTANTS GROUP

3.4 EFFECTIVELY GROUNDED SYSTEM

 EFFECTIVELY GROUNDED SYSTEM NOT MANDATORY

 NON EFFECTIVELY GROUNDED SYSTEM ALSO ACCEPTABLE

 ALL SYSTEM COMPONENTS SELECTED PROPERLY

 INSULATION COORDINATION IS PROPER

54
POWER SYSTEM CONSULTANTS GROUP

4.0 SOLID GROUNDING


 DIRECT CONNECTION OF NEUTRAL TO GROUND
WITHOUT ANY EXPLICIT EXTERNAL ELEMENT LIKE
RESISTOR OR REACTOR

 GENERALLY SOLIDLY  EFFECTIVELY


GROUNDED SYSTEM GROUNDED

 SUFFICIENT GROUND CURRENT FOR RELAYING AND


COORDINATION

 IDENTIFICATION AND LOCATION OF FAULT POSSIBLE

55
POWER SYSTEM CONSULTANTS GROUP

4.0 SOLID GROUNDING


• RESIDUALLY CONNECTED CT CONNECTION ADEQUATE
• NORMAL EARTH FAULT RELAY ( RANGE 20 to 80 %)
 GROUND RELAY : RESIDUAL CONNECTION

G FIG_4_1_A
56
[ {20% to 80%} ; {10% to 40%} ]
POWER SYSTEM CONSULTANTS GROUP

4.0 SOLID GROUNDING


 PREFERABLE TO SET E / F RELAY AT 80% TO AVOID RELAY
DAMAGE

 FAULTED SECTION HAS TO BE TRIPPED

 LA  RATED FOR 80% (L to L) ACCEPTABLE

 PT  RATED FOR 150% VOLTAGE FACTOR ACCEPTABLE

57
POWER SYSTEM CONSULTANTS GROUP

4.0 SOLID GROUNDING


 SINCE GROUND FAULT CURRENT HIGH (KA)  CORE OR
IRON DAMAGE MAY NOT BE ACCEPTABLE IN COSTLY
ROTATING EQUIPMENT LIKE GENERATORS AND HT
MOTORS

 FLOW OF LARGE INTERFERENCE WITH


GROUND CURRENT  COMMUNICATION
(ZERO SEQUENCE CURRENT) CIRCUITS RUNNING IN
FROM FAULT TO SOURCE PARALLEL

58
POWER SYSTEM CONSULTANTS GROUP

4.1 GROUNDING , ZERO SEQUENCE AND PHASE ANGLE OF HARMONIC COMPONENTS

HARMONIC A B C PHASE ROTATION


HARMONIC CURRENTS FUNDAMENTAL 0 120 240 (+)VE

THIRD 0 3 x 120 3 x 240 ZERO


( 0 ) ( 0 )
FIFTH 0 5 x 120 5 x 240 ()VE
( 240 ) ( 120 )
SEVENTH 0 7 x 120 7 x 240 (+)VE
( 120 ) ( 240 )
NINTH 0 9 x 120 9 x 240 ZERO
( 0 ) ( 0 )

 (+VE) AND (-VE) SEQUENCE


ELEVENTH 0 11 x 120 11 x 240 ()VE
( 240 ) ( 120 )
THIRTEENTH 0 13 x 120 13 x 240 (+)VE
( 120 ) ( 240 )
FIFTEENTH 0 15 x 120 15 x 240 ZERO

COMPONENTS : GROUNDING SEVENTEENTH 0


( 0 )
17 x 120
(240 )
( 0 )
17 x 240
( 120 )
()VE

NO BEARING 1 0 1 0

1  120 1 0

1  240 1 0

O 3 0

 ZERO SEQUENCE [ (+VE), (-VE) ] SEQUENCE ZERO SEQUENCE

SYMMETRICAL HALF CYCLE : NO EVEN HARMONICS

COMPONENT : DEPENDS
+VE HALF
CYCLE

ON TYPE OF GROUNDING -VE HALF


CYCLE
FIG_
4_2_
B

 UNGROUNDED NEUTRAL : SUPPRESSION OF ZERO


SEQUENCE CURRENT FLOW  APPEARS AS ZERO
SEQUENCE VOLTAGE 59
POWER SYSTEM CONSULTANTS GROUP

4.1 GROUNDING , ZERO SEQUENCE AND HARMONIC CURRENTS


 EXAMPLES

 (+VE) SEQUENCE CURRENT : NORMAL LOAD CURRENT

 (-VE) SEQUENCE CURRENT : CURRENT UNDER SINGLE


PHASING

 ZERO SEQUENCE CURRENT (NEUTRAL CURRENT)

 FAULT CURRENT UNDER 1 SHORT CIRCUIT ( 50 Hz )

 EXCITING CURRENT OF TRANSFORMER


( 150 Hz, 3rd HARMONIC )
60
POWER SYSTEM CONSULTANTS GROUP

4.2 APPLICATIONS
 LV (415V)

 GENERALLY SOLIDLY GROUNDED

 IE RULES

 IF FOR ANY REASON, IF LV SYSTEM IS NOT SOLIDLY


GROUNDED, SPECIAL PERMISSION FROM ELECTRICAL
INSPECTOR REQUIRED

61
POWER SYSTEM CONSULTANTS GROUP

 LV (415V)

 FIG_4_3

 MYTH : EARTH IS GOOD EQUIPMENT GROUNDING


CONDUCTOR

 REALITY : EARTH IS THE MOST UNRELIABLE EQUIPMENT


GROUNDING CONDUCTOR
 BEST EARTH ELECTRODE RESISTANCE  1 

 ON 415 V SYSTEM, IF ONLY EARTH IS USED FOR RETURN OF


FAULT CURRENT,
MAX  (415/3) / 1
MAX  240 AMPS!

 IF FAULT CURRENT IS LIMITED TO 240 A, NEITHER O/C RELAY


NOR FUSE WILL EVER OPERATE ! 62
POWER SYSTEM CONSULTANTS GROUP

 LV (415V)

 CONCLUSIONS

 EARTH SHALL NOT BE TREATED AS SOLE EQUIPMENT


GROUNDING CONDUCTOR FOR FAULT CURRENT RETURN PATH

 MAKE AS MANY SUPPLEMENTARY CONNECTION TO EARTH


FROM EQUIPMENT AS YOU WISH

 BUT MAKE SURE THAT ALL EQUIPMENTS ARE CONNECTED TO


GROUNDING GRID (EARTH CONTINUITY) CONDUCTOR WHICH
SHALL BE CONNECTED TO SOURCE NEUTRAL

 MAJORITY OF FAULT CURRENTS SHALL BE CARRIED BY


GROUNDING GRID CONDUCTOR AND VERY LITTLE BY 'MOTHER'
EARTH
• IF EARTH CURRENT IS LESS, TOUCH POTENTIAL IS ALSO LESS
63
POWER SYSTEM CONSULTANTS GROUP

 MV ( 3.3, 6.6, 11 KV )

 SOLIDLY GROUNDED SYSTEM RARELY USED AS


HT MOTORS AND GENERATORS ARE PRESENT

 HV AND EHV (  22 KV)

 GENERALLY SOLIDLY GROUNDED

 NO ROTATING EQUIPMENT DIRECTLY CONNECTED


AT THIS LEVEL

 COST OF INSULATION VERY HIGH

 FAULTS CLEARED WITH IN 2 to 3 CYCLES 64


POWER SYSTEM CONSULTANTS GROUP

5.0 RESISTANCE GROUNDING

 RESISTOR CONNECTED BETWEEN NEUTRAL


AND GROUND

 DEPENDING ON VALUE OF LIMITING GROUND FAULT


CURRENT ( IF )
 HIGH RESISTANCE GROUNDING (HRG)
 LOW RESISTANCE GROUNDING (LRG)

65
POWER SYSTEM CONSULTANTS GROUP

5.0 RESISTANCE GROUNDING

 FOR BOTH HIGH & LOW RESISTANCE GROUNDING

 DURING LINE to GROUND FAULT

 V ( L to GROUND )  3 x NORMAL PHASE VOLTAGE

 ALMOST SAME AS FOR UNGROUNDED SYSTEM

 VOLTAGE RATING OF LA  100% (L to L)

 CABLE  UE GRADE

 TRANSIENT OVER VOLTAGE DUE TO RESTRIKE / ARCING


< 2.5 PU COMPARED TO > 3PU FOR UNGROUNDED SYSTEM
66
POWER SYSTEM CONSULTANTS GROUP

5.1 REASONS FOR LIMITING FAULT CURRENT


 REDUCE BURNING AND MELTING IN FAULTED
ELECTRICAL EQUIPMENT

 ROTATING MACHINES : WINDING DAMAGE ACCEPTABLE


CORE DAMAGE NOT ACCEPTABLE

 REDUCE MECHANICAL STRESSES ( FORCE  I2 )

 REDUCE RESTRIKE / ARCING FAULTS

 REDUCE TRANSIENT VOLTAGE RISE COMPARED TO


UNGROUNDED SYSTEM
67
POWER SYSTEM CONSULTANTS GROUP

5.2 HIGH RESISTANCE GROUNDING (HRG)


 GROUND FAULT CURRENT IF LIMITED TO LESS THAN
10 to 15 A

 FOR IF > 15 A, CORE DAMAGE, COSTLY REPAIR

 USUALLY,

CURRENT THROUGH  SYSTEM CAPACITIVE CHARGING


RESISTOR ( I R) CURRENT ( IC )

 TYPICALLY, IC  9A (3A / PHASE )

68
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT AT THE POINT OF FAULT


• FIG 5_1 I
RB
I
RB
B


I Y
UNGROUNDED SYSTEM : RY

IUG = 9 90
R I
RY
I +I
RY RB
R

I I X X
N F C C

 HRG SYSTEM : I
N
I
RY

IF = 9 90 + 9 0 = 13 45


I
N
I FIG_5
RB _1_A

B
IF I
RY
+ I
RB

IUG I
F

IN
N I
N

 RESTRIKE AND ARCING LESS R ,G

WHEN BREAKING IF THAN BR


I
YR

WHEN BREAKING IUG


+ I
YR BR
Y

69
POWER SYSTEM CONSULTANTS GROUP

5.2 HIGH RESISTANCE GROUNDING (HRG)


 IUG  POOR POWER FACTOR

AT CURRENT ZERO  VOLTAGE ACROSS GAP HIGH
 CHANCE OF RESTRIKE MORE

 IF  GOOD POWER FACTOR



AT CURRENT ZERO  VOLTAGE ACROSS GAP LOW
 CHANCE OF RESTRIKE LESS
VOLTAGE AT CURRENT ZERO

VOL
I UG
IF
PHI = 450
PHI = 90 0

70
POWER SYSTEM CONSULTANTS GROUP

5.2 HIGH RESISTANCE GROUNDING (HRG)


 EXAMPLES
 V LL = 11 kV
 CAPACITIVE CURRENT IC = 10A
 SET RESISTIVE CURRENT IR = IC = 10A
 RESISTANCE ( RG ) = (11,000 /3) / 10 = 635 
 ALTERNATE METHODS FOR INCORPORATING
RESISTANCE RG

 METHOD 1 : DIRECT GROUNDING

N
RG = 635 
71
POWER SYSTEM CONSULTANTS GROUP

5.2 HIGH RESISTANCE GROUNDING (HRG)


 METHOD 2 : DISTRIBUTION TRANSFORMER GROUNDED

N
R'G = 0.9 

11/3 kV / 240V

 USUALLY ADOPTED
 CHEAPER SOLUTION, RESISTOR : LOW , LOW VOLTAGE,
HIGH CURRENT
 TURNS RATIO = TR = VP / VS [ e.g. (11000/3) / 240V = 26.5 ]
 RG = R'G x TR2 [ 635 = 0.9 x 26.52 ]

 VOLTAGE RELAY ACROSS R'G TO SENSE GROUND FAULTS


72
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT LOW  LOCATING GROUND FAULT


DIFFICULT
 CORE BALANCE CT (CBCT)

 SENSITIVE EARTH FAULT


CURRENT RELAY G {1% to 10%}

( RANGE 1% to 10 %)
1A RELAY :
RANGE  10 MILLIAMPS to
100 MILLIAMPS

73
POWER SYSTEM CONSULTANTS GROUP

5.2 HIGH RESISTANCE GROUNDING (HRG)


 CAUTION : DO NOT EARTH NGR CUBICLE !

FROM TRANSFORMER OR
GENERATOR NEUTRAL
FIG_5_3
BUSHING

SHEET STEEL
RESISTOR ENCLOSURE
STACKS

INSULATOR
INSULATOR

TO TO
EARTH EARTH
GRID GRID

EARTH PIT EARTH


74 PIT
NGR SUPPORT FRAME SOIL LEVEL 90
POWER SYSTEM CONSULTANTS GROUP

5.3 LOW RESISTANCE GROUNDING (LRG)

 GROUND FAULT CURRENT ( IF ) LIMITED TO 400 A ( TYPICAL )

 ANOTHER CRITERIA WIDELY USED

 GROUND FAULT CURRENT ( IF ) LIMITED TO


 RATED CURRENT OF SOURCE GENERATOR
 RATED CURRENT OF SOURCE TRANSFORMER

 IF  ENOUGH TO OPERATE GROUND FAULT RELAYS

 RESIDUALLY CONNECTED CT CONNECTION ADEQUATE

 NORMAL EARTH FAULT RELAY ( RANGE 10 to 40 %)

75
POWER SYSTEM CONSULTANTS GROUP

5.3 LOW RESISTANCE GROUNDING (LRG)

 RESISTOR DIRECTLY CONNECTED BETWEEN NEUTRAL


AND GROUND

 CURRENT RELAY IN NEUTRAL CIRCUIT POSSIBLE FOR


GROUND FAULT DETECTION

 COMPARED TO HIGH RESISTANCE GROUNDING

 CORE DAMAGE AT THE POINT OF FAULT MORE


 MORE SENSITIVE AND SELECTIVE ISOLATION OF
GROUND FAULTS

76
POWER SYSTEM CONSULTANTS GROUP

6.0 RESONANT GROUNDING


 GROUND FAULT NEUTRALISER (GFN)

 GFN  REACTANCE COIL CONNECTED BETWEEN


NEUTRAL AND GROUND

IRB B
IRB

IRY Y

GFN IRY
XL IRY + IRB
R
IN F XC XC

IN IRY

IRB 77
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT AT THE POINT OF FAULT


 UNGROUNDED SYSTEM  CAPACITIVE CURRENT
[ e.g. IU = 7A  +90 ]

 HIGH RESISTANCE  CURRENT WITH GOOD PF


GROUNDED [ e.g. IH = 10A  +45 ]

 RESONANT GROUNDED  RESISTIVE CURRENT


SYSTEM [ e.g. IR = 1A  0 ]

 IR  < IU  < IH 

78
POWER SYSTEM CONSULTANTS GROUP

6.0 RESONANT GROUNDING


 CURRENT THROUGH GFN (REACTIVE CURRENT)

NEUTRALISES CAPACITIVE CURRENTS FROM HEALTHY PHASES

• FIG_6_1_A

• FIG_6_1_B

IN = IYR + IBR

1 3 1 1
-- = -----   L = -----  L = -----------
xL xC 3c 3 2 c

79
POWER SYSTEM CONSULTANTS GROUP

6.0 RESONANT GROUNDING


 TYPICAL CHARGING CURRENT = 2A / PHASE
 ASSUME VOLTAGE 11 KV
 XC = (11000 /3) / 2 = 3175 
 XL = XC / 3 = 1058 
 'K' FACTOR OF REACTOR (X / R)  20

 GROUND FAULT CURRENT MINIMUM (THEORETICALLY ZERO)



PURELY RESISTIVE, AT CURRENT ZERO  VOLTAGE ALSO
 ZERO
ARCING GROUND  SELF EXTINGUISHING /
POSSIBILITY OF RESTRIKE REMOTE
80
POWER SYSTEM CONSULTANTS GROUP

6.0 RESONANT GROUNDING


 SENSITIVITY FOR  GOOD, SUBSTANTIAL VOLTAGE (V0)
FAULT DETECTION AVAILABLE

 REACTOR  TAPS REQUIRED TO BE TUNED AT SITE


CAPACITANCE VARIES WITH CHANGING
NETWORK

 LA : 100% RATED TO BE USED

 TRANSFORMER : GRADED INSULATION CAN NOT BE USED


NEUTRAL SHALL BE FULLY INSULATED

81
POWER SYSTEM CONSULTANTS GROUP

6.0 RESONANT GROUNDING

 MAIN ARGUEMENT : FAULT CURRENT < 1 to 2 A


FOR USE CORE(IRON) DAMAGE MINIMUM

 PAST EXPERIENCE  FAULT CURRENT EVEN UPTO 10 to 15A,


CORE DAMAGE MINIMUM, ACCEPTABLE

 GFN : USED ONLY IN OLDER SYSTEM


 PRESENTLY ALMOST NOT USED

 RESISTANCE GROUNDED SYSTEM


MORE EXTENSIVELY USED

82
POWER SYSTEM CONSULTANTS GROUP

7.1 GROUNDING THE BUS


7.1 ZIG – ZAG TRANSFORMER

• FIG 7_1_A

 EACH CORE  TWO WINDINGS



CAN BE CONSIDERED AS PRIMARY & SECONDARY

 WINDINGS CONNECTED SUCH THAT

PRIMARY CARRIES CURRENT OF ONE PHASE (SAY R)


AND
SECONDARY CARRIES CURRENT OF DIFFERENT
PHASE (SAY Y)

83
POWER SYSTEM CONSULTANTS GROUP

7.1 GROUNDING THE BUS


 CAN (+VE) SEQUENCE CURRENT FLOW ?

 THREE LINE CURRENTS  IR = 10 ; IY = 1-120 ; IB = 1120

 PRIMARY WINDING ON CORE 1 CARRIES IR = 10


AND
SECONDARY WINDING ON CORE 1 CARRIES IY = 1-120

 BUT TRANSFORMER THEORY DEMANDS THAT


PRIMARY AND SECONDARY CURRENTS MUST BE IN
PHASE AND EQUAL (in PU)

 THIS CAN NEVER BE SATISFIED WITH THE ABOVE


CONNECTION.
 THE ZIG-ZAG CONNECTION OFFERS VERY HIGH
IMPEDANCE TO FLOW OF (+VE) SEQUENCE CURRENT 84
POWER SYSTEM CONSULTANTS GROUP

7.1 GROUNDING THE BUS

 UNDER NORMAL BALANCED SUPPLY



CURRENT DRAWN VERY LOW (ONLY EXCITING CURRENT)

 SIMILARLY THE DEVICE OFFERS VERY HIGH IMPEDANCE


TO FLOW OF (-VE) SEQUENCE CURRENT

85
POWER SYSTEM CONSULTANTS GROUP

7.1 GROUNDING THE BUS


 CAN ZERO SEQUENCE CURRENT FLOW ?
 THREE LINE CURRENTS I0 , I0 AND I0

EQUAL IN PHASE AND MAGNITUDE

 CURRENT FLOW IN PRIMARY AND SECONDARY  I0 AND I0

 TRANSFORMER THEORY PERMITS THE FLOW OF CURRENTS

 IMPEDANCE : CONVENTIONAL ZERO SEQUENCE


OFFERED LEAKAGE IMPEDANCE
 FACILITATES FLOW OF ZERO  PROVIDES GROUNDING
SEQUENCE CURRENT IN UNGROUNDED SYSTEM
(GROUND FAULT CURRENT)

 GROUND FAULT CURRENT CAN BE LIMITED BY


86
PROVIDING NGR
POWER SYSTEM CONSULTANTS GROUP

7.1 GROUNDING THE BUS


 VOLTAGE VECTOR DIAGRAM
 E : LINE to LINE VOLTAGE
 VOLTAGE ACROSS EACH WINDING = E / 3
 CURRENT CARRIED BY EACH WINDING = I0 = IF / 3
R

E/3

E/3

E/3

B Y
E 87
POWER SYSTEM CONSULTANTS GROUP

 GROUNDING TRANSFORMER
RATING (MVA) = 3 E I0 = (E/3) IF

 ZERO SEQUENCE LEAKAGE REACTANCE (X0) EXPRESSED

ON ABOVE MVA BASE


 X0  20% to 100%
 IF X0 = 20% , NGR MAY BE REQIRED TO LIMIT FAULT
CURRENT
 IF X0 = 100% , NGR MAY NOT BE REQIRED TO

LIMIT FAULT CURRENT

 NORMALLY RATED FOR 10 SEC


 COST << COMPARED TO SAME RATING OF

CONVENTIONAL TRANSFORMER ( 10% to 15% )


88
POWER SYSTEM CONSULTANTS GROUP

 TYPICAL CURRENT DISTRIBUTION


• FIG 7_2
 FAULT CURRENT = IF = 3I0 = (6600 /3) / 250 = 15.3 A

CURRENT THROUGH CURRENT THROUGH


ZIG ZAG = TWO PHASES OF DELTA = I0 = 5.1 A
MAIN TRANSFORMER TURNS RATIO = T = 6600 / (415/ 3) = 27.5
CURRENT ON SOURCE (STAR) SIDE = 5.1 x 27.5 = 141 A
 LINE TO GROUND  LINE TO LINE  IN PRESENCE OF
FAULT DELTA FAULT ON GROUNDING XR
SIDE STAR SIDE
 GROUNDING OF SOURCE OR PRIMARY NEUTRAL  IMMATERIAL
 AS REFLECTED FAULT CURRENT  LINE to LINE

 CONVERSE  FIG_13_4_A
89
POWER SYSTEM CONSULTANTS GROUP

 GROUNDING TRANSFORMER SIZING : TYPICAL CALCULATIONS


• FIG 7_3_A
 BASE MVA : 10  IB = BASE CURRENT = 10 / (3 x 11) = 0.5249 KA
 GENERATOR
 X(+VE) = X1 = X'd = 0.25 x (10 / 4) = 0.625 PU
 X(-VE) = X2 = X1 = 0.625 PU
 TRANSFORMER
 X(+VE) = X1 = 0.08 x (10 / 5.5) = 0.1455 PU
 X(-VE) = X2 = X1 = 0.1455 PU
 GROUNDING TRANSFORMER ( ZIG ZAG )
X(+VE) = X(-VE) = 
Z0 = R0 + j X0
 ZPOS = ZNEG = j(0.625 + 0.1455) = j0.7705
 ZZER = R0 + j X0 90
POWER SYSTEM CONSULTANTS GROUP

 GROUNDING TRANSFORMER SIZING : TYPICAL CALCULATIONS


 ASSUME NO EXTERNAL RESISTANCE CONNECTED BETWEEN
GROUNDING TRANSFORMER NEUTRAL AND GROUND
i.e. R0 = 0
 FOR EFFECTIVE GROUNDING
X0 R0
---- < 3 & ----- < 1
X1 X1
 R0 = 0  SECOND EXPRESSION ALWAYS SATISFIED
 CHOOSE X0 = 3 X1 = 3 x 0.7705 = j 2.3115
(ON CHOSEN 10 MVA BASE)
1
 I0 = -------------------------------------- = -j 0.2596 PU
j( 0.7705 + 0.7705 + 2.3115 )
 FAULT CURRENT IF =3 I0= 0.7788 PU = 0.7788 x 524.9  408.8
91 A
108
POWER SYSTEM CONSULTANTS GROUP

 GROUNDING TRANSFORMER SPECIFICATION

 SIZE = VL- N x IF = (11 / 3 ) x 0.4088 = 2.5962 MVA

 IMPEDANCE = X0 = 2.3115 x (2.5962 / 10) = 0.6001

 SUMMARY
TYPE : ZIG ZAG GROUNDING TRANSFORMER
VOLTAGE : 11 KV (L to L)
MVA RATING : 2.6
TIME RATING : 10 SEC
ZERO SEQUENCE REACTANCE : 60%

 TIME RATING = 10 SEC  EARTH FAULT CLEARED


WITH IN 10 SEC 92
POWER SYSTEM CONSULTANTS GROUP

7.2 STAR – DELTA TRANSFORMER

 NORMALLY USED WHEN SPARE


STAR – D TRANSFORMER
AVAILABLE

 COSTLIER THAN ZIG ZAG


TRANSFORMER I0
I0 I0 I0

I0
I0
R
IF = 3I 0

93
POWER SYSTEM CONSULTANTS GROUP

7.2 STAR – DELTA TRANSFORMER

 UNDER NORMAL OPERATING


CONDITIONS

 D SIDE  UNLOADED, 0
0 0 0
NOT SERVING
ANY LOAD
0
R 0
 CURRENT DRAWN  IF =0
ONLY EXCITING CURRENT
 VERY LOW
 FOR (+VE) AND (-VE) SEQUENCE QUANTITIES

IMPEDANCE OFFERED IS EXCITING IMPEDANCE
VERY HIGH
94
POWER SYSTEM CONSULTANTS GROUP

 UNDER 1 GROUND FAULT CONDITIONS


 FAULT CURRENT 
ZERO SEQUENCE CURRENT

I0
I0 I0 I0
 PATH AVAILABLE FOR FLOW
OF ZERO SEQUENCE I0
R I0
CURRENT FLOW
IF =3I0
 I0 FLOWS IN THREE PHASES OF STAR
 EQUIVALENT I0 CAN FLOW IN CLOSED DELTA
 IMPEDANCE OFFERED  Z L CONVENTIONAL LEAKAGE
REACTANCE
 Z(+ve) = Z(-ve) =  ; Z(zero) = Z L
 GROUND FAULT CURRENT  LIMITED BY PROVIDING NGR
95
POWER SYSTEM CONSULTANTS GROUP

 RESISTOR PROVIDED ON STAR NEUTRAL

 BUS VOLTAGE : 6.6 KV (L to L)


 NGR : 250 

• FIG_7_4_A

 NEUTRAL IMPEDANCE IN PU = ZACT / ZBASE


ZACT : ACTUAL IMPEDANCE IN 
ZBASE = kV2 / MVA3
kV : LINE to LINE VOLTAGE OF STAR CIRCUIT
MVA3 = SYSTEM BASE MVA ( 3 )

 VOLTAGE RATING OF STAR WINDING : (L to G) : 6.6 /3 kV


 IF = 3I0 = (6600 /3) / 250 = 15.3 A
 I0 = 5.1 A 96
POWER SYSTEM CONSULTANTS GROUP

 RESISTOR PROVIDED ON DELTA

 VOLTAGE RATIO 6600V / 415 V

 I0 ON STAR SIDE = 5.1 A

 TURNS RATIO = I0 I0 I0 I0
I0

(6600 / 3) / 415 = 9.18 3V 0 R

 I0 ON DELTA SIDE
I0
= 5.1 x 9.18
IF = 3I 0
= 46.8 A

 RESISTANCE ON D SIDE = ( 3 x 415 ) / 46.8 = 26.6 

 VOLTAGE RATING OF STAR WINDING : (L to L) : 6.6 KV 97


POWER SYSTEM CONSULTANTS GROUP

 RESISTOR PROVIDED ON DELTA


 FIG_7_4_B
 NEUTRAL IMPEDANCE IN PU = ZACT / ZBASE
ZACT : ACTUAL IMPEDANCE IN 
ZBASE = KV2 / MVA1
KV : LINE to LINE VOLTAGE OF D CIRCUIT

MVA1 = SYSTEM BASE MVA PER PHASE


 IN GENERAL, RD = 27 x TV2 x RS
RD = RESISTOR VALUE ON DELTA SIDE IN 
RS = RESISTOR VALUE ON STAR NEUTRAL IN 

TV = VOLTAGE RATIO = VDL-L / VSL-L [ e.g. 415 / 6600 ]


 EVEN THOUGH PRIMARY NEUTRAL SOLIDLY GROUNDED
 BEHAVES LIKE RESISTANCE GROUNDED SYSTEM !
98
POWER SYSTEM CONSULTANTS GROUP

8.0 UNINTENTIONAL GROUNDING


• FIG 8_1

 BUS FED FROM UNGROUNDED SOURCE

 FEEDER#1 : TIE FEEDER

 FEEDER#2 : TRANSFORMER FEEDER (STAR – DELTA)


DELTA : FEEDING LOADS

99
POWER SYSTEM CONSULTANTS GROUP

8.0 UNINTENTIONAL GROUNDING


• FIG_8_1

 DISTRIBUTION TRANSFORMER ON FEEDER#2 ALSO


PROVIDES GROUNDING FOR UNGROUNDED BUS

 TRANSFORMER  MAY NOT HAVE BEEN INTENDED FOR


GROUNDING AT DESIGN STAGE !!

 CONCEPT  SAME AS GROUNDING THROUGH STAR - D


TRANSFORMER DISCUSSED PREVIOUSLY

100
POWER SYSTEM CONSULTANTS GROUP

9.0 SUMMARY OF COMPARISON : DIFFERENT


GROUNDING METHODS

 TABLE 9_1

101
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


EHV BUS
 CASE 1

 ADVANTAGES T1 T2

G1 G2
 GROUND FAULT CURRENT
N1 N2
SUPPLIED BY THE
STATION LIMITED BY NGR

THE COMMON RESISTOR


 ALMOST SAME VALUE OF GROUND FAULT CURRENT
IRRESPECTIVE OF NUMBER OF GENERATORS

 LEADS TO SIMPLIFIED GROUND RELAYING


( USE OF DMT RELAYS )
102
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


 CASE 1 EHV BUS

T1 T2

G1 G2
N1 N2

NGR

 DISADVANTAGE

 SINCE NEUTRALS OF MACHINES INTERCONNECTED


WITH LOW /ZERO IMPEDANCE, HIGH ZERO SEQUENCE
CURRENT CIRCULATION BETWEEN MACHINES POSSIBLE

103
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


 CASE 2
 IN MAJORITY OF POWER STATIONS THIS GROUNDING
SCHEME USED
 ALL RESISTORS ARE NORMALLY IN SERVICE AND
NEUTRALS CLOSED
 ZERO SEQUENCE CURRENT CIRCULATION VERY LOW
 LIMITED BY RESISTORS IN THE NEUTRAL CIRCUIT

EHV BUS OF MACHINES

GT1 GT2

G1 G2
N1 N2

NGR NGR
104
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


 CASE 3
 IN SOME STATIONS, THE NEUTRALS KEPT FLOATING,
BUT BUS GROUNDED THROUGH COMMON GROUNDING
TRANSFORMER USUALLY ZIG ZAG CONNECTED
TERMINAL BUS

G1 G2

N1 N2 NGR

ZIG ZAG
GROUNDING
TRANSFORMER 105
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


 CASE 4
 LT GENERATORS – 'GENERALLY' SOLIDLY GROUNDED
 CIRCULATING HARMONIC CURRENTS ( 5th, 7th, 11th …)
BETWEEN MACHINES FLOW IRRESPECTIVE OF
NEUTRALS INTERCONNECTED OR NOT

 FORTUNATELY MAGNITUDE OF THESE VERY LESS


TERMINAL BUS 415 VOLTS

G1 G2
N1 N2

ISOLATING DEVICE
106
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


 CASE 4
 CIRCULATING HARMONIC CURRENTS
( 3rd & MULTIPLES OF 3rd ) BETWEEN MACHINES
FLOW ONLY WHEN MORE THAN ONE NEUTRAL
GROUNDED
 3rd HARMONIC CURRENT  ZERO SEQUENCE CURRENT
 IF ALL NEUTRALS GROUNDED, ZERO SEQUENCE
CURRENT CIRCULATION HIGH
TERMINAL BUS 415 VOLTS

G1 G2
N1 N2

ISOLATING DEVICE
107
POWER SYSTEM CONSULTANTS GROUP

10.0 GENERATOR NEUTRAL GROUNDING PRACTICES


 CASE 4
 ONLY ONE NEUTRAL KEPT CLOSED  PROVIDES RETURN
PATH FOR GROUND FAULT CURRENT

 NEUTRAL ISOLATION DEVICE


(BREAKER / CONTACTOR / SWITCH ) FOR EACH
GENERATOR REQUIRED
TERMINAL BUS 415 VOLTS

G1 G2
N1 N2

ISOLATING DEVICE
108
POWER SYSTEM CONSULTANTS GROUP

11.0 NEUTRAL GROUNDING – PHASE AND LINE


VOLTAGES
 DEPENDING ON TYPE OF GROUNDING 
PHASE AND LINE VOLTAGES CHANGE DURING FAULTED
CONDITION

 TYPICAL POWER PLANT AUXILIARY SYSTEM

 FIG_11_1

 NGR OF UAT VARIED TO SIMULATE DIFFERENT GROUNDINGS


 FROM UNGROUNDED TO SOLIDLY GROUNDED

109
POWER SYSTEM CONSULTANTS GROUP

 ANALYSIS DONE USING SEQUENCE COMPONENTS

 UNDER BALANCED OPERATING B

CONDITION

 PHASE VOLTAGES
G
VR  = VY  = VB  = 1.0 N R

 LINE VOLTAGES
VRY  = VYB  = VBR  = 3
Y

 OPEN DELTA VOLTAGE : VD = VR + VY + VB = 0

110
POWER SYSTEM CONSULTANTS GROUP

 FAULT CONDITION : FAULT ON PHASE A


 NEUTRAL : SOLIDLY GROUNDED
B
 FAULT CURRENT = 8.5kA
 HEALTHY BUS PHASE VOLTAGES
VY AND VB  NEAR NORMAL
VY  1  -120o ; VB  1  120o G
 LINE VOLTAGES VRY  AND VBR  N R
FALLS FROM 3 to 1.0 PU.
 LINE VOLTAGE VYB  NO CHANGE,
AS FAULT IS ON PHASE A
Y
 LINE VOLTAGE TRIANGLE : ISOSCELES

 OPEN DELTA VOLTAGE : VD = 1.0 PU ( PHASE VOLTAGE)

 NEUTRAL VOLTAGE WRT GROUND = 0.33 VPHASE 111


POWER SYSTEM CONSULTANTS GROUP

 NEUTRAL : HIGH RESISTANCE GROUNDED B

 FAULT CURRENT  10 AMPS

 ALMOST UNGROUNDED SYSTEM G


N
R
 HEALTHY BUS PHASE VOLTAGES

VY  AND VB  RISE FROM 1 to 3


Y
 LINE VOLTAGES VRY , VYB AND VBR  NO CHANGE

 LINE VOLTAGE TRIANGLE : EQUILATERAL

 OPEN DELTA VOLTAGE : VD = 3.0 PU

( 3 TIMES PHASE VOLTAGE)

 NEUTRAL VOLTAGE WRT GROUND = 1.0 PU


112
POWER SYSTEM CONSULTANTS GROUP

 NEUTRAL : LOW RESISTANCE GROUNDED


 FAULT CURRENT > FOR HIGH RESISTANCE GROUNDED (10A)
< FOR SOLIDLY GROUNDED (8543A)
FAULT CURRENT = 3480A B

 CHANGES IN BOTH :
PHASE VOLTAGES VY AND VB
LINE VOLTAGES VRY AND VBR
N
 LINE VOLTAGE VYB  NO CHANGE G
R

 LINE VOLTAGE TRIANGLE :


CLOSE TO EQUILATERAL Y

 OPEN DELTA VOLTAGE : VD = 2.5 to 3.0 PU


NEARLY THE SAME AS FOR UNGROUNDED OR
113
HIGH RESISTANCE GROUNDED SYSTEM
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT VS VOLTAGE

• FIG 11_3

 VARY NGR VALUE AND CALCULATE


FAULT CURRENT
MINIMUM LINE VOLTAGE VLMIN

OPEN DELTA VOLTAGE VD

 VD - NEARLY 3.0 FOR THE ENTIRE RANGE FROM


UNGROUNDED to LOW RESISTANCE GROUNDED REGION.

FALLS RAPIDLY ONLY WHEN APPROACHING SOLIDLY


GROUNDED REGION
114
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT VS VOLTAGE

 VLMIN  - LINE VOLTAGE NEARLY 3 FOR THE ENTIRE RANGE


FROM UNGROUNDED to LOW RESISTANCE GROUNDED
REGION.
FALLS RAPIDLY ONLY WHEN APPROACHING SOLIDLY
GROUNDED REGION

 FAULT CURRENT FOR SOLIDLY GROUNDED NEUTAL : 8543 A

115
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT VS VOLTAGE

 ASSUME UNDER VOLTAGE RELAYS CONNECTED BETWEEN


LINES INSTEAD OF LINE TO GROUND.

 UNDER VOLTAGE RELAY SETTING : 70% ( SAY )

 RELAY WILL NOT PICK UP UNTIL FAULT CURRENT > 5000 A

 EVEN WITH SOLIDLY GROUNDED NEUTRAL, FAULT


CURRENT CAN BECOME LOWER THAN 5000A FOR
ARCING FAULTS

 ARCING FAULT WITH SOLIDLY GROUNDED NEUTRAL 


RESISTANCE GROUNDED NEUTRAL AND SOLID FAULT

116
POWER SYSTEM CONSULTANTS GROUP

 FAULT CURRENT VS VOLTAGE


MORAL !!!
 UNGROUNDED, HIGH / LOW RESISTANCE GROUNDED
SYSTEM
 ABSURD TO CONNECT UNDERVOLTAGE RELAYS
BETWEEN LINES
 CONNECT THE RELAYS ONLY BETWEEN LINE AND
GROUND
 SOLIDLY GROUNDED SYSTEM
 PREFERABLE TO CONNECT THE RELAYS
BETWEEN LINE AND GROUND FOR POSITIVE
PICK UP EVEN FOR FAULTS WITH RESISTANCE

CONNECT UNDER VOLTAGE RELAYS ONLY BETWEEN LINE AND GROUND


117

138
POWER SYSTEM CONSULTANTS GROUP

12.0 SEQUENCE VOLTAGES VS FAULT LOCATION


 (+VE) SEQUENCE VOLTAGE
HIGH  AT SOURCE (e.g. 1.0 PU)
SOURCES (SYNCHRONOUS MACHINES)
PRODUCE ONLY (+VE) SEQUENCE VOLTAGE.
LOW  AT POINT OF DISTURBANCE (e.g. 0 PU)
FOR EXAMPLE, AT FAULT POINT,

(+VE) SEQUENCE VOLTAGE IS ZERO.

S NETWORK
F

(+VE)

S F 118
POWER SYSTEM CONSULTANTS GROUP

12.0 SEQUENCE VOLTAGES VS FAULT LOCATION


 ZERO SEQUENCE VOLTAGE
HIGH  AT POINT OF DISTURBANCE
LOW  AT SOURCE ; SOURCES(SYNCHRONOUS MACHINES)
DO NOT PRODUCE ZERO SEQUENCE VOLTAGE
 (-VE) SEQUENCE VOLTAGE
 SAME AS ZERO SEQUENCE VOLTAGE

 FOR FAULT AT 'F', ZERO SEQUENCE VOLTAGE RELAY


AT 'P' , AWAY FROM FAULT, MAY NOT PICK UP
S NETWORK
F
(ZERO)

(-VE)

119
S P F
POWER SYSTEM CONSULTANTS GROUP

13.0 NEUTRAL GROUNDING – FAIRY TALES


FAULT CURRENT RETURNS TO ANY TRANSFORMER NEUTRAL ?

120
POWER SYSTEM CONSULTANTS GROUP

13.0 NEUTRAL GROUNDING – FAIRY TALES


 FUNDAMENTAL PRINCIPLE OF TRANSFORMER OPERATION
 AMPERE TURNS BALANCE

 IPRI x TPRI  ISEC x TSEC

 IF THIS RELATIONSHIP CAN NOT BE SATISFIED DUE TO


PHYSICAL CONNECTIONS, NO CURRENT WILL FLOW

Ia TA IA
IN TC
Ta
Ib Tb
Tc IC
TB
I IB
c

IF 121
POWER SYSTEM CONSULTANTS GROUP

13.0 NEUTRAL GROUNDING – FAIRY TALES


 FUNDAMENTAL PRINCIPLE OF TRANSFORMER OPERATION

 AMPERE TURNS BALANCE :


IA TA  Ia Ta ; IB T B  I b T b ; IC TC  Ic Tc

 KCL HAS TO BE SATISFIED


IA + IB + IC = IN FAULT CURRENT RETURNING TO NEUTRAL

Ia TA IA
IN TC
Ta
Ib Tb
Tc IC
TB
Ic IB

IF 122
POWER SYSTEM CONSULTANTS GROUP

 CASE 1
 ABSENCE OF PRIMARY NEUTRAL GROUNDING
 NO CURRENT CAN FLOW ON SECONDARY SIDE
 FAULT CURRENT IS ZERO EVEN WHEN NEUTRAL IS GROUNDED !!
 BEHAVES LIKE  UNGROUNDED SYSTEM

SOURCE TRANSFORMER

123
POWER SYSTEM CONSULTANTS GROUP

 CASE 2

 BOTH PRIMARY AND SECONDARY NEUTRALS GROUNDED

 FOR FAULT CURRENT RETURNING THROUGH SECONDARY


NEUTRAL, EQUIVALENT CURRENT THROUGH PRIMARY
NEUTRAL CAN FLOW

 BUT CAN THIS CURRENT ACTUALLY FLOW ?


SOURCE TRANSFORMER

F 124
POWER SYSTEM CONSULTANTS GROUP

 CASE 2

 NO ! : PRIMARY NEUTRAL CURRENT DOES NOT HAVE


RETURN PATH AS SOURCE IS UNGROUNDED

 FAULT CURRENT IS ZERO EVEN WHEN BOTH NEUTRALS


GROUNDED !!

 AGAIN BEHAVES LIKE  UNGROUNDED SYSTEM


SOURCE TRANSFORMER

F 125
POWER SYSTEM CONSULTANTS GROUP

 CASE 3
 BOTH PRIMARY AND SECONDARY NEUTRALS GROUNDED
AND SOURCE ALSO GROUNDED
 CURRENTS CAN FLOW IN BOTH THE SECONDARY AND
PRIMARY SIDES OF TRANSFORMER AND SATISFY :
AMPERE TURNS BALANCE AND KCL
 BEHAVES LIKE  TRULY GROUNDED SYSTEM

SOURCE TRANSFORMER
0 0

0 0

Ia IA

126
149
IF
POWER SYSTEM CONSULTANTS GROUP

 CASE 4
 TRANSFORMER SECONDARY NEUTRAL GROUNDED
THROUGH RESISTANCE
 TRANSFORMER PRIMARY NEUTRAL AND SOURCE SOLIDLY
GROUNDED
 CURRENTS CAN FLOW IN BOTH THE SECONDARY AND
PRIMARY SIDES OF TRANSFORMER
SOURCE TRANSFORMER
0 0

0 0

Ia R IA

127
F 150
POWER SYSTEM CONSULTANTS GROUP

 CASE 4

 GROUND FAULT CURRENT ON SECONDARY SIDE LIMITED


BY NGR VALUE
 ONLY THE EQUIVALNT REFLECTED CURRENT OF
REDUCED SECONDARY CURRENT FLOWS ON THE PRIMARY
SIDE, EVEN THOUGH PRIMARY NEUTRAL AND SOURCE
NEUTRAL ARE SOLIDLY GROUNDED
SOURCE TRANSFORMER
0 0

0 0

Ia R IA

128
F 151
POWER SYSTEM CONSULTANTS GROUP

 CASE 4
 EXAMPLE : TRANSFORMER 11 KV / 6.6 KV, NGR = 38
GROUND FAULT CURRENT
ON SECONDARY SIDE = (6600 /3) / 38 = 100 A
EQUIVALENT CURRENT
ON PRIMARY SIDE = 100 * 6.6 / 11 = 60A

SOURCE TRANSFORMER
0 0

0 0

Ia R IA

129
60 A 100 A IF 152
POWER SYSTEM CONSULTANTS GROUP

 CASE 5

 TRANSFORMER SECONDARY NEUTRAL AND SOURCE


GROUNDED THROUGH RESISTANCE
 TRANSFORMER PRIMARY NEUTRAL SOLIDLY GROUNDED
 CURRENTS CAN FLOW IN BOTH THE SECONDARY
AND PRIMARY SIDES OF TRANSFORMER

SOURCE TRANSFORMER
0 0

0 0

Ia R IA

I F130
155
POWER SYSTEM CONSULTANTS GROUP

 CASE 5
 GROUND FAULT CURRENT ON SECONDARY SIDE LIMITED
BY NGR VALUE
 THE EQUIVALNT REFLECTED CURRENT ON THE PRIMARY
SIDE ENCOUNTERS ANOTHER NGR ON SOURCE SIDE
 OVERALL EFFECT : FAULT CURRENT REDUCES
SUBSTANTIALLY
SOURCE TRANSFORMER
0 0

0 0

Ia R IA

I 131
F 156
POWER SYSTEM CONSULTANTS GROUP

 CASE 5

 EXAMPLE : TRANSFORMER 11 KV / 6.6 KV, NGR = 38


SOURCE NGR = 64 
 GROUND FAULT CURRENT ON SOURCE SIDE = 100 A
 GROUND FAULT CURRENT ON SECONDARY SIDE = 62 A

EQUIVALENT CURRENT ON PRIMARY SIDE = 37A


SOURCE TRANSFORMER
0 0

0 0

Ia R IA

100 A
37 A 62 A I132
F
157
POWER SYSTEM CONSULTANTS GROUP

 CASE 6
 TRANSFORMER  D - STAR GROUNDED

 LINE TO GROUND FAULT ON STAR SIDE


 LINE TO LINE FAULT ON D SIDE

Ia 0 0
IN 0
0
IA

IF
133
POWER SYSTEM CONSULTANTS GROUP

 CASE 6
 RELAYS RESPONDING TO FAULT
 STAR SIDE
 PHASE RELAY ON FAULTED PHASE
 GROUND RELAY
 DELTA SIDE
 PHASE RELAYS ON TWO PHASES
[ GROUND RELAY DOES NOT PICK UP ! ]

Ia 0 0
IN 0
0
IA

134
IF 159
POWER SYSTEM CONSULTANTS GROUP

 CASE 6
 VOLTAGE VECTORS

 STAR SIDE  NEUTRAL SHIFT ( VNG  0)

 DELTA SIDE  NO NEUTRAL SHIFT ( VNG = 0)

NO NEUTRAL SHIFT  DOES NOT NECESSARILY MEAN


VOLTAGES ARE BALANCED!
DELTA STAR
R
B
VR = 1.0 VR = 0
VY = 0.51 VY = 0.88
N G
VB = 0.51 R VB = 0.88
VNG = 0 G VNG = 0.11
N 135
B Y Y
POWER SYSTEM CONSULTANTS GROUP

 CASE 7
 TRANSFORMER
 STAR GROUNDED [P]  D [T]  STAR GROUNDED [S]
D - TERTIARY WINDING, USUALLY DESIGNED TO CARRY ONLY
ZERO SEQUENCE CURRENTS UNDER NORMAL
CONDITIONS – UNLOADED – NO CURRENT
 SOURCE UNGROUNDED OR PRIMARY NEUTRAL UNGROUNDED
 RESULTS SAME
TRANSFORMER
SOURCE P T S
0 0

0
136
POWER SYSTEM CONSULTANTS GROUP

 CASE 7

 TYPICAL CURRENT(PU) DISTRIBUTION SHOWN FOR


FAULT ON SECONDARY SIDE

 AMPERE  TURNS BALANCE AND KCL SATISFIED

 NO CURRENT THROUGH PRIMARY NEUTRAL 

SOURCE UNGROUNDED

TRANSFORMER
SOURCE P T S
2 2 1 1
0 0
0 3
1 1 3
1 1
1
IF137
=3
162
POWER SYSTEM CONSULTANTS GROUP

 CASE 7
 RELAYS RESPONDING TO FAULT
 SECONDARY SIDE
 PHASE RELAY ON FAULTED PHASE
 GROUND RELAY
 PRIMARY SIDE
 PHASE RELAYS ON ALL THREE PHASES
[ GROUND RELAY DOES NOT PICK UP ]
TRANSFORMER
SOURCE P T S
2 2 1 1
0 0
0 3
1 1 3
1 1
1 138
IF = 3 163
POWER SYSTEM CONSULTANTS GROUP

 CASE 8

 FIG13_5_B

 TRANSFORMER
 STAR GROUNDED [P]  D [T]  STAR GROUNDED [S]

 SOURCE ALSO GROUNDED

 TYPICAL CURRENT(PU) DISTRIBUTION SHOWN FOR FAULT


ON SECONDARY SIDE

 AMPERE  TURNS BALANCE AND KCL SATISFIED

139
POWER SYSTEM CONSULTANTS GROUP

 CASE 8
 BECAUSE OF PRESENCE OF D TERTIARY
CURRENT(PU) THROUGH PRIMARY NEUTRAL
LESS THAN
CURRENT(PU) THROUGH SECONDARY NEUTRAL
 PART OF GROUND FAULT CURRENT REFLECTED IN
TERTIARY AND CIRCULATES
 CURRENT DIVISION BETWEEN D TERTIARY AND PRIMARY
 ZERO SEQUENCE LEAKAGE REACTANCE BETWEEN
(PRIMARY to TERIARY) & ( SECONDARY to TERTIARY)
 IF NO DATA AVAILABLE, ASSUME
 50% OF TOTAL SECONDARY FAULT CURRENT FLOWS
IN DELTA
140
 REMAINING 50% FLOWS IN THE PRIMARY NEUTRAL
POWER SYSTEM CONSULTANTS GROUP

 CASE 8

 RELAYS RESPONDING TO FAULT

 SECONDARY SIDE
 PHASE RELAY ON FAULTED PHASE
 GROUND RELAY

 PRIMARY SIDE
 PHASE RELAYS ON ALL THREE PHASES
 GROUND RELAY

141
POWER SYSTEM CONSULTANTS GROUP

 CASE 8
 FAULT LEVEL STUDIES AND RELAY COORDINATION
EXERCISE

 USUAL ASSUMPTION
PU FAULT CURRENT ON = PU FAULT CURRENT ON
SECONDARY SIDE PRIMARY SIDE

• ABOVE CAN BE GROSSLY WRONG IN PRESENCE OF


DTERTIARY

• FOR FAULT ON SECONDARY SIDE, GROUND FAULT


RELAY ON PRIMARY SIDE SENSES MUCH LOWER
CURRENT THAN SET FOR.

• FOR FINE TUNING RELAY COORDINATION STUDIES,


THIS SHALL BE TAKEN CARE OFF
142
POWER SYSTEM CONSULTANTS GROUP

 CASE 9

 SYSTEM CONSIDERED FOR SIMULATION


 FIG 13_6_A

 G1 : 30.625 MVA, X'd = 13.6%

 G2 : 13.125 MVA, X'd = 25%

 NGR R1 = R2 = R3 = 15.88 

 GROUND FAULT CURRENT LIMITED TO


[ (11000 /3) / 15.88 = 400 A ]

143
POWER SYSTEM CONSULTANTS GROUP

 CASE 9

 TRANSFORMER : 220 / 11 / 3.3 kV [ H – L – T ]

REACTANCE ON 30 MVA BASE


H – L : 12.1 %
L – T : 21.2 %
H – T : 36.3 %

 220 KV O/H LINE : IMPEDANCE ON 10 MVA BASE


Z (+VE) = 0.00008 + j 0.00045
Z(zero) = 0.00033 + j 0.00115

 SYSTEM FAULT LEVEL : F(3) = F(1) = 2983 MVA

144
POWER SYSTEM CONSULTANTS GROUP

 CASE 9

 GENERATING SOURCE AT ONE END & SYSTEM AT


OTHER END

 LV SIDE (11 kV) OF TRANSFORMER


 RESISTANCE GROUNDED : IFAULT < 400 A

 FOR 1 to GROUND FAULT ON 220 kV SIDE,

 CONTRIBUTION FROM SOURCE SIDE :


 400 x 11 / 220 = 20 A ?
 ABOVE NOT CORRECT 
BECAUSE OF PRESENCE OF D TERTIARY

145
POWER SYSTEM CONSULTANTS GROUP

 CASE 9

 RESULTS OF ANALYSIS USING SEQUENCE COMPONENTS


• FIG 13_7

 TOTAL FAULT CURRENT IF = 310 x 26.25 = 8.1 kA

 ZERO SEQUENCE CURRENT CONTRIBUTION

 FROM SYSTEM SIDE (220 kV) = 8.3 x 26.25 = 218 A


THIS CURRENT >> 20A ANTICIPATED EARLIER
NOTE : THIS CURRENT IS ALMOST REACTIVE!

 FROM SOURCE SIDE (11 kV) = 0.1 x 525 = 53 A


NOTE : THIS CURRENT IS RESISTIVE! 146
POWER SYSTEM CONSULTANTS GROUP

 CASE 9
 MOST PROBABLE RELAYS TO PICK UP
GROUND RELAY ON 220 kV SIDE
PHASE RELAYS ON 11 kV SIDE

 FOR 220 kV FAULTS, IN SPITE OF NGR ON 11 kV SIDE


BEHAVIOUR  SOLIDLY GROUNDED SYSTEM
 CAUSE
PRESENCE OF D TERTIARY!

147
POWER SYSTEM CONSULTANTS GROUP

 CASE 9

 VOLTAGE ON 220 kV SIDE (SOLIDLY GROUNDED)

| VY | = | VB | = | VRY | = | VBR | = V D  1.0


B

G
N R

Y 148
POWER SYSTEM CONSULTANTS GROUP

 CASE 10
 CAN FAULT CURRENT FLOW AHEAD OF THE FAULT ?

SYSTEM F Yg D Yg
Yg
GROUNDED 220kV R
11kV

 EVEN WITHOUT SOURCE ON 11 kV SIDE,


FOR FAULT AT 'F', CAN RELAY AT LOCATION
'R' PICK UP ?

149
POWER SYSTEM CONSULTANTS GROUP

 CASE 10

 COMMON PERCEPTION  RELAY CAN NOT SENSE ?

 NO! RELAY CAN SENSE IF TRANSFORMER HAS

STAR GROUNDED D SECONDARY OR TERTIARY


PRIMARY + FOR ZERO SEQ CURRENT
CIRCULATION

SYSTEM F Yg D Yg
Yg
GROUNDED 220kV R
11kV

150
POWER SYSTEM CONSULTANTS GROUP

 CASE 10

 CURRENT SENSED BY GROUND FAULT RELAY AT


LOCATION 'R'

3I0 = 8.1 PU = 8.1 x 26.25 = 213 A


TRANSFORMER

SYSTEM R P(220) T S(11)

-j 2.7 -j 2.7 -j 2.7

-j 2.7
-j 2.7

-j 298.3 -j 2.7
-j 292.9 -j 8.1 (213A)
IF = -j 301 151
POWER SYSTEM CONSULTANTS GROUP

 CASE 10
 NORMALLY ONE EXPECTS THE RELAY TO PICK UP ONLY
FOR FAULTS DOWN THE TRANSFORMER.

 IF THE SETTING IS LOW, IT CAN PICK UP FOR EVEN FOR


FAULTS AHEAD OF TRANSFORMER

 AGAIN THE CAUSE  PRESENCE OF D TERTIARY


TRANSFORMER

SYSTEM R P(220) T S(11)

-j 2.7 -j 2.7 -j 2.7

-j 2.7
-j 2.7

-j 298.3 -j 2.7
-j 292.9 -j 8.1 (213A) 152
I F = -j 301 179
POWER SYSTEM CONSULTANTS GROUP

 CASE 10
 REACTANCE OF HV (220 kV) to TERTIARY IS HIGH
( 36.3% IN PRESENT CASE )
 THE CURRENT IS LIMITED TO 213 A

 IF THE REACTANCE IS LOW, CURRENT CAN BE STILL HIGHER


 NEXT EXAMPLE : CASE 11

 RELAY HAS TO SENSE ONLY DOWNSTREAM FAULTS?


 DIRECTIONAL ELEMENT TO BE ADDED
67 TRANSFORMER
SYSTEM R P(220) T S(11)
-j 2.7 -j 2.7 -j 2.7

-j 2.7
-j 2.7
-j 298.3 -j 2.7
-j 292.9 -j 8.1 (213A) 153
I F = -j 301 180
POWER SYSTEM CONSULTANTS GROUP

 CASE 11

 SYSTEM SIMILAR TO CASE 10 , EXCEPT TRANSFORMER

 CONVENTIONAL TWO WINDING STAR – DELTA


TRANSFORMER

 REACTANCE STAR – DELTA : 12.1%


( 36.3% IN CASE10 )
 NO SOURCE ON 11 kV SIDE,

SYSTEM F Yg D
Yg
220kV R
11kV
 CURRENT DISTRIBUTION, FOR FAULT AT 'F' SHOWN

IN NEXT SLIDE 154


POWER SYSTEM CONSULTANTS GROUP

 CASE 11
 CURRENT SENSED BY GROUND FAULT RELAY AT
LOCATION 'R'

3I0 = 22.8 PU = 22.8 x 26.25 = 599A


[ IN CASE 10, 3I0 = 213A ]
 MORE CHANCE FOR GROUND FAULT RELAY TO PICK UP
IN THIS CASE
TRANSFORMER
SYSTEM R P S
-j 7.6
-j 7.6
-j7.6

-j 7.6

-j 298.4 -j 7.6 -j 7.6


-j 283.2 -j 22.8 155
I F = -j 306 182
POWER SYSTEM CONSULTANTS GROUP

 CASE 12

 VERY SIMILAR TO CASE 11 ,


EXCEPT SYSTEM  GENERATOR

GENERATOR F Yg D
Yg
11kV R
66kV

 CONVENTIONAL TWO WINDING STAR – DELTA


TRANSFORMER

 GENERATOR : 18.75 MVA, X'd = 20%, Xo = 10%

 TRANSFORMER : 20 MVA, 8%

 NO SOURCE ON 66 kV SIDE 156


POWER SYSTEM CONSULTANTS GROUP

 CASE 12
 BOTH GENERATOR AND TRANSFORMER SOLIDLY GROUNDED
 CURRENT THROUGH GENERATOR NEUTRAL
= 5.5 PU = 5.5 x 525  2890 AMPS

 CURRENT THROUGH TRANSFORMER NEUTRAL


= 7.2 PU = 7.2 x 525  3780 AMPS
TRANSFORMER
GENERATOR R P S
-j 2.4
-j 2.4
-j 2.4

-j 2.4
-j 10.3 -j 2.4 -j 2.4
-j 5.5 -j 7.2
157
1 PU CURRENT = 525 AMPS 186
I F = -j 12.7
POWER SYSTEM CONSULTANTS GROUP

 CASE 12

 BOTH GENERATOR AND TRANSFORMER RESISTANCE


GROUNDED [(11000/3) / 16 = 400 AMPS ]
 CURRENT THROUGH GENERATOR NEUTRAL
= 0.75 PU  400 AMPS
 CURRENT THROUGH TRANSFORMER NEUTRAL

= 0.75 PU  400 AMPS


TRANSFORMER
GENERATOR R P S
0.25
0.25
0.25
0.25
16  16 
1.25 0.25 0.25
0.75 0.75
I F = 1.5 1 PU CURRENT = 525 AMPS
158
POWER SYSTEM CONSULTANTS GROUP

 CASE 12
 CURRENT SENSED BY GROUND FAULT RELAY AT LOCATION 'R'
 GROUND FAULT RELAY CONNECTED TO RESIDUAL CIRCUIT
OR ON THE NEUTRAL OF TRANSFORMER
 RELAY LOOKS FOR FAULTS AHEAD OF ITS LOCATION !!

 STAR (GROUNDED) – DELTA : PECULIAR CONFIGURATION FOR


GROUND FAULT CURRENT FLOW

TRANSFORMER
GENERATOR R P S
0.25
0.25
0.25
0.25
16  16 
1.25 0.25 0.25
0.75 0.75 159
I F = 1.5 188
POWER SYSTEM CONSULTANTS GROUP

 CASE 13
 TRANSFORMER NEUTRAL SOLIDLY GROUNDED

 FOR GROUND FAULT  NEUTRAL CARRIES LARGE GROUND


FAULT CURRENT ?
 NOT ALWAYS!

 FIG 13_10
 AUTO_TRANSFORMER : NEUTRAL SOLIDLY GROUNDED

 FAULT ON 220 KV SIDE

 CURRENT THROUGH TRANSFORMER NEUTRAL  MINIMUM

 STANDBY EARTH FAULT RELAYS (51SN) ON NEUTRAL MAY

NOT PICK UP EVEN THOUGH NEUTRAL SOLIDLY GROUNDED!


160
POWER SYSTEM CONSULTANTS GROUP

 CASE 14
 CAN GROUND CURRENT (ZERO SEQUENCE) FLOW WITOUT
GROUND FAULT ?
 OF COURSE YES!

161
POWER SYSTEM CONSULTANTS GROUP

 CASE 14

 EXAMPLE

 NORMAL LOAD CURRENT ON 33 KV SIDE : 500A

TRANSFORMER

SOURCE 33 KV 11 KV

500  0

500  -120  LOAD

500 120
O O

162
POWER SYSTEM CONSULTANTS GROUP

 CASE 14
 R PHASE OPEN ( e.g. CONDUCTOR SNAPS )

 GROUND CURRENT (ZERO SEQ CURRENT) : 650A

 APPEARS AS IF R PHASE CURRENT NOW TRIES TO FLOW


THROUGH GROUND !
TRANSFORMER
SOURCE 33 kV 11 kV

513 -155  LOAD

633  93 
650  -40  650 -40  163
192
POWER SYSTEM CONSULTANTS GROUP

 CASE 14
 IF CT RATIO  500/1 AND (PS)PLUG SETTING  0.5
650
 PSM (PLUG SETTING MULTIPLIER) = ---------- = 2.6 > 2
500 x 0.5
 EARTH FAULT RELAYS (51N) WILL PICK UP
TRANSFORMER
SOURCE 33 kV 11 kV

513 -155  LOAD

633  93 
650  -40  650 -40  164
193
POWER SYSTEM CONSULTANTS GROUP

 CASE 14

 POLE DISCREPENCY DEDUCTION

 CONCEPT SAME

 TWO POLES CLOSED AND ONE POLE OPEN

 EARTH FAULT RELAY (51N) USED AS BACK UP


TO DETECT THIS SITUATION

165
POWER SYSTEM CONSULTANTS GROUP

14.0 GROUNDING – DC SYSTEM


 PLANT EMERGENCY SYSTEM : NORMALLY FED BY
DC SYSTEM

 DC SYSTEM : BATTERY, CHARGER, DC SWITCHGEAR

 BATTERIES :  110 V,  55 V,  24 V

 CENTRE POINT GROUNDED THROUGH HIGH RESISTANCE

CZA (+VE) 110

VDC
R
(-VE) 110

166
POWER SYSTEM CONSULTANTS GROUP

14.0 GROUNDING – DC SYSTEM


 POLE (+VE OR –VE) TO GROUND FAULTS DO NOT CAUSE
DISRUPTION. THIS CURRENT (VERY SMALL) DETECTED
BY CZA (CENTRE ZERO AMMETER).

 POLE TO POLE FAULTS RESULT IN


SHORT CIRCUIT CURRENT : VERY RARE

CZA (+VE) 110

VDC
R
(-VE) 110

167
POWER SYSTEM CONSULTANTS GROUP

15.0 REFERENCES
 ANSI / IEEE STD 142 : IEEE RECOMMENDED PRACTICE
FOR GROUNDING OF INDUSTRIAL AND COMMERCIAL
POWER SYSTEMS [ GREEN BOOK ]

 ELECTRICAL TRANSMISSION AND DISTRIBUTION REFERENCE


BOOK : WESTINGHOUSE ELECTRIC CORPORATION

 J & P TRANSFORMER BOOK

 PROTECTIVE RELAYING : J LEWIS BLACKBURN,

PUBLISHER : MARCEL DEKKER INC

 ELECTRICAL EARTHING AND ACCIDENT PREVENTION :

EDITED BY M. G. SAY 168


POWER SYSTEM CONSULTANTS GROUP

• UNGROUNDED SYSTEM

• BALANCED STEADY STATE OPERATION


B

N IB
Y

IY
R

IR X X X
C C C

FIG_2_1_A
169
POWER SYSTEM CONSULTANTS GROUP

PHASOR DIAGRAM
B
V = VY = VB = 1.0
R
IR VRY = VYB = V BR =  3

G,N
R
IY
IB IR + IY + IB = 0

VNG = V0 = 0

Y
FIG_2_1_B
170
POWER SYSTEM CONSULTANTS GROUP

 UNGROUNDED SYSTEM

 SINGLE LINE TO GROUND FAULT

IRB B
IRB

IRY Y

IRY

R
IRY + IRB IF XC XC

IRY
FIG_2_2_A
IRB
171
POWER SYSTEM CONSULTANTS GROUP

PHASOR DIAGRAM

B I F = ( I RY + I RB )
= - ( I YR + I BR )
VBR = VBG = 3

VYR = VYG = 3

G I BR  = I YR = I =  3 / X
N C
R
I YR + I BR =  3 I = 3 / X
C
I BR I YR
I F = I RY + I RB

I YR + I BR V D = V RG + V YG + V BG = 3.0
Y
VGN = V0 = 1.0 FIG_2_2_B
172
POWER SYSTEM CONSULTANTS GROUP

 NEUTRAL AND ZERO SEQUENCE VOLTAGE

Y
B

V RG V YG V BG

R R R
N

VNG

FIG_2_3_A
173
POWER SYSTEM CONSULTANTS GROUP

• BALANCED STEADY STATE CONDITIONS

B VR = VY = VB = 1.0

VRY = V YB = V BR =  3

VR  VRG

G VY  VYG
N R
VB  VBG

V D = V + V + V = 3V = 0
R Y B 0

V= V = V D /3 =0
NG 0
Y
FIG_2_4_A
174
POWER SYSTEM CONSULTANTS GROUP

SOLIDLY GROUNDED
IF = 8543 AMPS

B VR = 0, FAULTED PHASE
VY = 0.992
VB = 0.996

VRY = VY = 0.992
VYB = 3
G
N VBR = VB = 0.996
R
VD = 0.977
V NG = V0 = V D / 3 = 0.326

FIG_2_4_B
Y 175
POWER SYSTEM CONSULTANTS GROUP

TRANSIENT OVER VOLTAGE

+5

No restrike

+1

Current interruption

Source
voltage -3 FIG_2_5
176
216
POWER SYSTEM CONSULTANTS GROUP

 OPEN DELTA PT CONNECTION

T1
6600/3
--------
110 /  3
S1

T2
110
--------
110 / 3
S2
VD = 3VO = VR + VY + VB FIG_2_6_A
R 177
POWER SYSTEM CONSULTANTS GROUP

 UNGROUNDED SYSTEM

VD = (VR + VY + VB) = 3VO = 3 VL-L = 3 * 6600 = 11,430 Volts

S1 S2
 VOLTAGE ACROSS RELAY = ---- ---- (VR + VY + VB)
T1 T2

(110 / 3) (110/3)


VD = --------------- ----------- 11430 = 63.5 Volts
(6600/ 3) 110

FIG_2_6_B
178
POWER SYSTEM CONSULTANTS GROUP

 IF AUXILIARY TRANSFORMER RATIO IS 110 / (110 / 3),


VD = 110 Volts

RELAY RATED FOR 63.5V AND WIRED FOR ALARM


CAN NOT BE USED IN THIS CASE

 PREFERRED RATIO FOR AUX. TRANSFORMER : 110 / (110 / 3)

FIG_2_6_C
179
POWER SYSTEM CONSULTANTS GROUP

 NEUTRAL INVERSION AND FERRO_RESONANCE

Y
B

VRG VYG VBG XC XC XC


== == ==
XEX

N
VNG

FIG_2_7_A
180
POWER SYSTEM CONSULTANTS GROUP

 VRG , VYG , VBG : PHASE TO GROUND IMPRESSED VOLTAGES

 VNG : NEUTRAL TO GROUND VOLTAGE

 XC : CHARGING CAPACITANCE

 XEX : TRANSFORMER EXCITING (MAGNETISING) REACTANCE

VRG  VNG VRG  VNG VYG  VNG VBG  VNG


--------------  -----------------  --------------  -------------- = 0
j XEX  j XC  j XC  j XC

WITH VRG  VYG  VBG = 0,


VRG
VNG = -------------------
FIG_2_7_B
1  (3 XEX / XC )
181
POWER SYSTEM CONSULTANTS GROUP

NEUTRAL VOLTAGE VARIATION


2

VN > 1.0
VN : NEUTRAL VOLTAGE

XE/XC = 1/3
1

XE/XC ( IC/IEX ) x 0.001


0
10 100 1000 10000
VN < 0.0

-1

FIG_2_8
-2 182
222
POWER SYSTEM CONSULTANTS GROUP

• NEUTRAL INVERSION
B

1.0 R
G,N N'

Y FIG_2_9_A
183
POWER SYSTEM CONSULTANTS GROUP

 SIMILAR CONCEPT : VN > VA OR VN < VB

• LET VA = 1.0 AND VB = 0 VA


-j X C
1
 VN = -----------------
VN
– (XC/ XL)
j XL
 IF (XC / XL) < 1 ,  VN > 1 ( i.e. VN > VA )
VB
[ e.g. XC/ XL = 0.2  VN = 1.25 ]

 IF (XC/ XL) > 1 ,  VN < 0 ( i.e. VN < VB )

[ e.g. XC/ XL = 5  VN = - 0.25 ]


FIG_2_9_B
184
• VN DOES NOT LIE BETWEEN VA AND VB
POWER SYSTEM CONSULTANTS GROUP

• GROUNDING LOCATIONS

FIG 3_1_A
185
POWER SYSTEM CONSULTANTS GROUP

FIG 3_1_B
186
POWER SYSTEM CONSULTANTS GROUP

GROUNDING EQUIPMENT FIG 3_1_C


187
POWER SYSTEM CONSULTANTS GROUP

• 3 FAULT AND 1 TO GROUND FAULT


X’d = 0.3 X t = 0.08 F
Yg G
D  X 1G Z +VE
X1G = X2G = 0.3 X1T = X2T = 0.08 X T
1
X0G = 0.1 X0T = 0.08
I1
• 3  FAULT
1 1
I 3  = ------- = ------- = 2.6316 PU X G
2
Z +VE 0.38 Z - VE

3 X2T
I 1 = 3 I 0 = ------------------------- I2
Z +VE + Z -VE + Z 0

3 X0G
= ------- = 3.5714 PU Z0
0.84 X0T
3.5714
K F = ----------- > 1 I FIG 3_2
0
2.6316
188
• SINGLE PHASE FAULT CURRENT > THREE PHASE FAULT CURRENT
POWER SYSTEM CONSULTANTS GROUP

VOLTAGE VARIATION
2

1.75

1.5
VOLTAGE PU

0.8 * V(L_L)
1.25
MAX_PHASE_VOLTAGE
1

0.75

0.5
V_NEUTRAL

0.25
FIG_3_3
RO / X1
0
0.01 0.1 1 189
10
229
POWER SYSTEM CONSULTANTS GROUP

 GROUND RELAY : RESIDUAL CONNECTION

G
FIG_4_1_A
[ {20% to 80%} ; {10% to 40%} ]
190
POWER SYSTEM CONSULTANTS GROUP

G {1% to 10%}

FIG_4_1_B

191
POWER SYSTEM CONSULTANTS GROUP

PHASE ANGLE OF HARMONIC COMPONENTS

HARMONIC A B C PHASE ROTATION

FUNDAMENTAL 0 120 240 (+)VE

THIRD 0 3 x 120 3 x 240 ZERO


( 0 ) ( 0 )
FIFTH 0 5 x 120 5 x 240 ()VE
( 240 ) ( 120 )
SEVENTH 0 7 x 120 7 x 240 (+)VE
( 120 ) ( 240 )
NINTH 0 9 x 120 9 x 240 ZERO
( 0 ) ( 0 )
ELEVENTH 0 11 x 120 11 x 240 ()VE
( 240 ) ( 120 )
THIRTEENTH 0 13 x 120 13 x 240 (+)VE
( 120 ) ( 240 )
FIFTEENTH 0 15 x 120 15 x 240 ZERO
( 0 ) ( 0 ) FIG_4_2_A
SEVENTEENTH 0 17 x 120 17 x 240 ()VE
192
(240 ) ( 120 )
POWER SYSTEM CONSULTANTS GROUP

1 0 1 0

1  120 1 0

1 240 1 0

O 3 0

[ (+VE), (-VE) ] SEQUENCE ZERO SEQUENCE

SYMMETRICAL HALF CYCLE : NO EVEN HARMONICS

+VE HALF
CYCLE
FIG_4_2_B
-VE HALF
CYCLE 193
POWER SYSTEM CONSULTANTS GROUP

• RESISTANCE GROUNDED SYSTEM

• SINGLE LINE TO GROUND FAULT

IRB B
IRB

IRY Y

R IRY
IRY + IRB
R
IN IF XC XC

IN IRY
IN
FIG_5_1_A
IRB 194
POWER SYSTEM CONSULTANTS GROUP

PHASOR DIAGRAM

B
IRY + IRB
IF

N IN
R,G

IBR IYR

IYR + IBR FIG_5_1_B


Y
195
POWER SYSTEM CONSULTANTS GROUP

VOLTAGE AT CURRENT ZERO

VOL

I UG

IF
0
PHI = 45
PHI = 90 0

FIG_5_2
196
236
POWER SYSTEM CONSULTANTS GROUP

• GROUND FAULT NEUTRALISER (PETERSON COIL)

IRB B
IRB

IRY Y

GFN IRY
XL IRY + IRB
R
IN F XC XC

IN IRY
FIG_6_1_A
IRB
197
POWER SYSTEM CONSULTANTS GROUP

B
IRY + IRB VNG = 1.0

VBR = VBG =  3

VYR = VYG =  3

N G
R
IBR = IYR= I =  3 / XC
IR
B IYR
IYR + IBR =  3 I = 3 / XC

IN = 1 / XL
Y IYR + IBR
( IN ) IN = - (IRY + IRB)
FIG_6_1_B
198
POWER SYSTEM CONSULTANTS GROUP

• ZIG – ZAG GROUNDING TRANSFORMER


R Y B
E E
I0 IR = 1 0 I0 IY = 1 -120 I0 IB =1 120

E/3 P

E/ 3

FIG_7_1_A
3I0 NGR 199
POWER SYSTEM CONSULTANTS GROUP

• VOLTAGE TRIANGLE FOR ZIG-ZAG CONNECTION

E/3

E/3

E/3

B Y
E FIG_7_1_B
200
POWER SYSTEM CONSULTANTS GROUP

• TYPICAL CURRENT DISTRIBUTION (GROUNDING TRANSFORMER)


 3I 0 (141) 415V / 6600V
(5.1)
I0
 3I 0 (141) 0

I0(5.1)
2I0 (10.2)
IF =3I 0
I0 (5.1) I0 (15.3)
(5.1)

I0
(5.1)
250 
FIG_7_2
3I0
(15.3) 201
POWER SYSTEM CONSULTANTS GROUP

GROUNDING TRANSFORMER SIZING : TYPICAL CALCULATIONS

GENERATOR E = 1.0
4 MVA
X'd : 0.25
ZPOS
415 V

TRANSFORMER
5.5 MVA
X : 0.08 D ZNEG
11 KV

FAULT
Z ZER
ZIG ZAG GROUNDING
TRANSFORMER FIG 7_3_A
NGR
I0
IF = 3I 0 202
POWER SYSTEM CONSULTANTS GROUP

 BASE MVA : 10  IB = BASE CURRENT = 10 / (3 x 11) = 0.5249 KA

 GENERATOR

 X(+VE) = X1 = X'd = 0.25 x (10 / 4) = 0.625 PU

 X(-VE) = X2 = X1 = 0.625 PU

 TRANSFORMER

 X(+VE) = X1 = 0.08 x (10 / 5.5) = 0.1455 PU

 X(-VE) = X2 = X1 = 0.1455 PU

 GROUNDING TRANSFORMER ( ZIG ZAG )

X(+VE) = X(-VE) = 
FIG 7_3_B

Z0 = R0 + j X0 203
POWER SYSTEM CONSULTANTS GROUP

ZERO SEQUENCE
EQUIVALENT CIRCUIT

I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0

I0
R I0
FIG 7_4_A
I F = 3I 0
204
POWER SYSTEM CONSULTANTS GROUP

ZERO SEQUENCE
EQUIVALENT CIRCUIT

I0
I0 I0 I0 I0 t
V0 Z 0= z 0 + R/3
3V 0 R
I0

I0
FIG 7_4_B
I F = 3I 0
205
POWER SYSTEM CONSULTANTS GROUP

UNINTENTIONAL GROUNDING TRANSFORMER


I0
0

I0 2I 0
I0

I0

I0 I0 I0 3I0

I F = 3I 0
FEEDER #1
I0 I0

FIG_8_1
I0
206
FEEDER #2
POWER SYSTEM CONSULTANTS GROUP

COMPARISON OF DIFFERENT GROUNDING METHODS


HIGH LOW SOLIDLY
UNGROUNDED RESISTANCE RESISTANCE GROUNDED
GROUNDED GROUNDED
I1-  / I3-  < 0.5% < 1% 5% to 20% > 60%

TRANSIENT OVERVOLTAGE 3 to 6 PU NOT MORE THAN 1.5 to 2.5 PU

ARRESTOR RATING 100% 80%

PT VOLTAGE FACTOR 190% FOR 3 SEC 150% FOR


3 SEC
FAULT LOCATION NO PERHAPS YES
IMMEDIATE DISCONNECTION
AFTER GROUND FAULT NO OPTIONAL YES

EXPECTED REPAIR NEW WINDING INSULATION


(WINDING) AFTER GROUND
FAULT
EXPECTED REPAIR PERHAPS CORE
NIL CORE
(CORE) AFTER GROUND STACKING
FAULT STACKING Table_9_1
MULTIPLE FAULTS OFTEN SELDOM 207
POWER SYSTEM CONSULTANTS GROUP

 GROUNDING GENERATOR NEUTRAL


CASE 1
EHV BUS

T1 T2

G1 G2

N1 N2

NGR
FIG_10_1_A
208
POWER SYSTEM CONSULTANTS GROUP

CASE 2
EHV BUS

GT1 GT2

G1 G2

N1 N2

NGR NGR

FIG_10_1_B
209
POWER SYSTEM CONSULTANTS GROUP

• GROUNDING GENERATOR NEUTRAL


• CASE 3
TERMINAL BUS

G1 G2

N1 N2 NGR

ZIG ZAG
GROUNDING
TRANSFORMER FIG_10_2_A
210
POWER SYSTEM CONSULTANTS GROUP

• CASE 4

TERMINAL BUS 415 VOLTS

G1 G2

N1 N2

ISOLATING DEVICE
FIG_10_2_B
211
POWER SYSTEM CONSULTANTS GROUP

• TYPICAL POWER PLANT DISTRIBUTION


S

220 KV FL : 10,000 MVA

R = 1 K GT
250 MVA
235 MVA G 10%
X'd 30%
16 KV

UAT
10 MVA
10%

6.6 KV

6.6 KV : THREE PHASE FAULT LEVEL : 8450 A


FIG_11_1
SINGLE PHASE FAULT LEVEL
FOR SOLID GROUNDING : 8543 A 212
POWER SYSTEM CONSULTANTS GROUP

• LOW RESISTANCE GROUNDED

B
IF = 3480 AMPS

VR = 0, FAULTED PHASE
VY = 1.419
VB = 1.822

VRY = VY = 1.419
N VYB = 3
G VBR = VB = 1.822
R
VD = 2.769
VGN = V0 = 0.923

FIG_11_2_A
Y
213
POWER SYSTEM CONSULTANTS GROUP

• HIGH RESISTANCE GROUNDED

B
IF = 10 AMPS

VR = 0, FAULTED PHASE
VY = 3
VB = 3

N G VRY = VY = 3
R VYB = 3
VBR = VB = 3

VD = 3.0
VGN = V0 = 1.0

Y FIG_11_2_B
214
POWER SYSTEM CONSULTANTS GROUP

VOLTAGE - CURRENT CURVES


3
V_DELTA
2.5
VOLTAGE IN PU

2
VL_MIN

1.5 70%
VL_RAT

0.5
FIG_11_3

0
10 100 1000 10000215
CURRENT IN AMPS 255
POWER SYSTEM CONSULTANTS GROUP

FAIRY TALES
FAULT CURRENT RETURNS TO ANY TRANSFORMER NEUTRAL ?

216
FIG 13_1_A
POWER SYSTEM CONSULTANTS GROUP

• AMPERE TURNS BALANCE

Ia TA IA

IN TC
Ta
Ib Tb
Tc I C
TB
IB
Ic

IF
217
FIG 13_1_B
POWER SYSTEM CONSULTANTS GROUP

FAIRY TALES
• CASE 1 :

SOURCE TRANSFORMER

FIG 13_2_A
218
POWER SYSTEM CONSULTANTS GROUP

• CASE 2 :

SOURCE TRANSFORMER

FIG 13_2_B
219
POWER SYSTEM CONSULTANTS GROUP

• CASE 3 :

SOURCE TRANSFORMER
0 0

0 0

Ia IA

IF

FIG 13_2_C
220
POWER SYSTEM CONSULTANTS GROUP

CASE 4 :

SOURCE TRANSFORMER
0 0

0 0

Ia R IA

60 A 100 A IF

FIG 13_3_A
221
POWER SYSTEM CONSULTANTS GROUP

CASE 5 :

SOURCE TRANSFORMER
0 0

0 0

Ia R IA

100 A
37 A 62 A IF

FIG 13_3_B
222
POWER SYSTEM CONSULTANTS GROUP

CASE 6

Ia 0 0
IN 0
0
IA

IF

FIG 13_4_A
223
POWER SYSTEM CONSULTANTS GROUP

• VOLTAGE VECTORS

DELTA STAR

R
B

VR = 1.0 VR = 0
VY = 0.51 N G VY = 0.88
VB = 0.51 R VB = 0.88

VNG = 0 VNG = 0.11


G
N
B Y Y
FIG 13_4_B
224
POWER SYSTEM CONSULTANTS GROUP

• CASE 7
TRANSFORMER

SOURCE P T S

2 2 1 1
0
0 3 0

1 1 3
1 1

1
IF = 3

FIG 13_5_A
225
POWER SYSTEM CONSULTANTS GROUP

• CASE 8

TRANSFORMER

SOURCE P T S

4 4 1 1
0
2 5 0

1 1 5
1 1
2
1
IF = 5

FIG 13_5_B
226
POWER SYSTEM CONSULTANTS GROUP

• SYSTEM FOR SIMULATION

SYSTEM

220 KV
R R O/H LINE

G1 G2

SOURCE T

11 KV R 400A
FIG 13_6_A
227
POWER SYSTEM CONSULTANTS GROUP

G1 : 30.625 MVA, X'd = 13.6%

G2 : 13.125 MVA, X'd = 25%

NGR R1 = R2 = R3 = 15.88  [ 11000 / 3 x 15.88 = 400 A ]

TRANSFORMER : 220 / 11 / 3.3 KV [ H – L – T ]

REACTANCE ON 30 MVA BASE

H – L : 12.1 %

L – T : 21.2 %
FIG 13_6_B
H – T : 36.3 %
228
POWER SYSTEM CONSULTANTS GROUP

220 KV O/H LINE : IMPEDANCE ON 10 MVA BASE

Z (+VE) = 0.00008 + j 0.00045

Z(zero) = 0.00033 + j 0.00115

SYSTEM FAULT LEVEL : F(3) = F(1) = 2983 MVA

FIG 13_6_C
229
POWER SYSTEM CONSULTANTS GROUP

• CASE 9
TRANSFORMER  STAR GROUNDED [P]  D [T]  STAR GROUNDED [S]
TRANSFORMER

-j 2.76
-j 2.76
SOURCE
SYSTEM
11 KV 220 KV
-j 2.76 0.25 - j1.54

- 0.6 + j 8.6
0.25 - j1.54

- 0.25 + j 4.3
0.6 - j11.36 - j 298.3

- 0.25 + j 4.3

0.1 0.1 I = 0.6 – j 309.66


F
ALL CURRENTS IN PU 0.1 – j 8.28 0.5 – j 301.38
1 PU CURRENT ON 11 KV SIDE = 525 A
230
1 PU CURRENT ON 220 KV SIDE = 26.25 A FIG 13_7
POWER SYSTEM CONSULTANTS GROUP

• CASE 10
TRANSFORMER

SYSTEM R P(220) T S(11)

-j 2.7 -j 2.7 -j 2.7

-j 2.7
-j 2.7

-j 298.3 -j 2.7
-j 292.9 -j 8.1
IF = -j 301

FIG 13_8_A
231
POWER SYSTEM CONSULTANTS GROUP

CASE11
TRANSFORMER

SYSTEM R P S

-j 7.6
-j 7.6
-j7.6

-j 7.6

-j 298.4 -j 7.6 -j 7.6


-j 283.2 -j 22.8
I F = -j 306

FIG 13_8_B
232
POWER SYSTEM CONSULTANTS GROUP

• CASE 12

SOLIDLY GROUNDED
TRANSFORMER

GENERATOR R P S

-j 2.4
-j 2.4
-j 2.4

-j 2.4

-j 10.3 -j 2.4 -j 2.4


-j 5.5 -j 7.2

IF = -j 12.7
FIG 13_9_A
1 PU CURRENT = 525 AMPS 233
POWER SYSTEM CONSULTANTS GROUP

RESISTANCE GROUNDED : 11000 / (3 * 16) = 400 AMPS


TRANSFORMER

GENERATOR R P S

0.25
0.25
0.25

0.25
16 16 

1.25 0.25 0.25


0.75 0.75
I F = 1.5

1 PU CURRENT = 525 AMPS


FIG 13_9_B
234
POWER SYSTEM CONSULTANTS GROUP

• CASE 13
AUTOTRANSFORMER  NEUTRAL GROUNDED  D [TERTIARY ]
XHM = 9.5%; XML = 47.4%; XHL = 31%  ON 37.5 MVA BASE
SOURCE LOAD
132 KV 220 KV

588 408
655

180 11 KV
90 90
0

90

90 0

FIG 13_10
235
408 0 408
POWER SYSTEM CONSULTANTS GROUP

TRANSFORMER

SOURCE 33 KV 11 KV

500  0

500  -120 LOAD


500 120
O O

FIG 13_11_A
236
POWER SYSTEM CONSULTANTS GROUP

TRANSFORMER

SOURCE 33KV 11 KV

LOAD
513 -155 

650  -40  633  93  650 -40 

FIG 13_11_B
237
POWER SYSTEM CONSULTANTS GROUP

SOLIDLY GROUNDED NEUTRAL

ACCIDENTAL CONTACT

SITCHGEAR

N V TOUCH

GRID
RE =
1 

E

238
FIG_4_3
POWER SYSTEM CONSULTANTS GROUP

• BALANCED STEADY STATE CONDITIONS

B VR = VY = VB = 1.0

VRY = V YB = V BR =  3

VR  VRG

G VY  VYG
N R
VB  VBG

V D = V + V + V = 3V = 0
R Y B 0

V NG = V0 = VD / 3 = 0
Y
FIG_2_4_A
239
POWER SYSTEM CONSULTANTS GROUP

SOLIDLY GROUNDED
IF = 8543 AMPS

B VR = 0, FAULTED PHASE
VY = 0.992
VB = 0.996

VRY = VY = 0.992
VYB = 3
G
N VBR = VB = 0.996
R
VD = 0.977
V NG = V0 = V D / 3 = 0.326

FIG_2_4_B
Y 240
POWER SYSTEM CONSULTANTS GROUP

NEUTRAL VOLTAGE VARIATION


2

VN > 1.0
VN : NEUTRAL VOLTAGE

XE/XC = 1/3
1

XE/XC ( IC/IEX ) x 0.001


0
10 100 1000 10000
VN < 0.0

-1

FIG_2_7_A
FIG_2_8
-2 241
282
POWER SYSTEM CONSULTANTS GROUP

ZERO SEQUENCE
EQUIVALENT CIRCUIT

I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0

I0
R I0
FIG 7_4_A
I F = 3I 0
242
POWER SYSTEM CONSULTANTS GROUP

ZERO SEQUENCE
EQUIVALENT CIRCUIT

I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0

I0
R I0
FIG 7_4_A
I F = 3I 0
243
POWER SYSTEM CONSULTANTS GROUP

 GROUNDING GENERATOR NEUTRAL


CASE 1
EHV BUS

T1 T2

G1 G2

N1 N2

NGR
FIG_10_1_A
244
POWER SYSTEM CONSULTANTS GROUP

• CASE 4

TERMINAL BUS 415 VOLTS

G1 G2

N1 N2

ISOLATING DEVICE
FIG_10_2_B
245
POWER SYSTEM CONSULTANTS GROUP

TERMINAL BUS 415 VOLTS

G1 G2

N1 N2

ISOLATING DEVICE

FIG_10_2_B
246
POWER SYSTEM CONSULTANTS GROUP

TRANSIENT OVER VOLTAGE

+5

No restrike

+1

Current interruption

Source
voltage -3 FIG_2_5
247
288
POWER SYSTEM CONSULTANTS GROUP

TRANSIENT OVER VOLTAGE

+5

No restrike

+1

Current interruption

Source
voltage -3 FIG_2_5
248
289
POWER SYSTEM CONSULTANTS GROUP

• GROUND FAULT NEUTRALISER (PETERSON COIL)

IRB B
IRB

IRY Y

GFN IRY
XL IRY + IRB
R
IN F XC XC

IN IRY
FIG_6_1_A
IRB
249
POWER SYSTEM CONSULTANTS GROUP

UNINTENTIONAL GROUNDING TRANSFORMER


I0
0

I0 2I 0
I0

I0

I0 I0 I0 3I0

I F = 3I 0
FEEDER #1
I0 I0

FIG_8_1
I0
250
FEEDER #2
POWER SYSTEM CONSULTANTS GROUP

 ZERO_SEQUENCE VOLTGAE DISTORTS PHASE VOLTAGE


 ZERO_SEQUENCE VOLTGAE  NO DISTORTION OF LINE TO
LINE VOLTAGE
 NEUTRAL SHIFTED
R

VR

VBR VRY
V0 N,G
N'
VY
VB
FIG_SE_CO_8

B VYB Y 251
POWER SYSTEM CONSULTANTS GROUP

ZERO SEQUENCE
EQUIVALENT CIRCUIT

I0 t
I0 I0 I0 V0 Z 0= z 0 + 3R
I0

I0
R I0
FIG 7_4_A
I F = 3I 0
252
POWER SYSTEM CONSULTANTS GROUP

ZERO SEQUENCE
EQUIVALENT CIRCUIT

I0
I0 I0 I0 I0 t
V0 Z 0= z 0 + R/3
3V 0 R
I0

I0
FIG 7_4_B
I F = 3I 0
253
POWER SYSTEM CONSULTANTS GROUP

Ia 0 0
IN 0
0
IA

IF

FIG 13_4_A

254

You might also like