Substation Automation Products

Introduction to the Relion® 670 series


Hardware

© SA-T Training
1MRG004718
Section 03

Contents

 Hardware - General
 Hardware configuration
 Modules
 Hardware overview
 Local HMI
 Summary
 Hardware modules
 Communication
 Time synchronization

© SA-T Training
1MRG004718
Slide 2
Section 03

Relion® 670 series – Hardware general

 Platform based
 Closed casings of common look
 HMI unit with Ethernet PC port
 Small or medium size
graphical display
 Common modules
 Easy future hardware addition
possibilities
 Dimension
 1/2, 3/4 or 1/1 of 19” wide and 6U
high
 Mounting flexibility
 Flush-, semi-flush, wall- and rack
mounting
 Side by side
 Compression type or ring lug
cable termination

© SA-T Training
1MRG004718
Slide 3
Section 03

Relion 670 series – Hardware general

 I/O flexibility
 0 - 12 - 24 analog inputs with
different input combinations
 1A or 5A on the CT inputs
 Up to 220V on the VT inputs
 3 to 14 slot positions to be used for
binary inputs/outputs and transducer
inputs
 Max 224 binary inputs
 Max 96 binary outputs
 Max 24 mA inputs
 Binary input voltage 24-250 Vdc
 LDCM (per LDCM and in each
direction)
 4 currents and 8 binary signals
or
 192 binary signals

© SA-T Training
1MRG004718
Slide 4
Section 03

Relion 670 series – Hardware general

 Time synchronization
 TCP/IP, Ethernet
 IEC 61850, DNP 3.0
 LON, SPA
 IRIG-B
 GPS
 Binary input
 Communication
 IEC 61850-8-1, DNP 3.0
 LON, SPA
 LDCM (C37.94, G.703 or X21)

© SA-T Training
1MRG004718
Slide 5
Section 03

Relion 670 series – Hardware general

1/1 19” case, 6U high  Transformer Input Module TRM1


and TRM2 (none, one or two)
 Analog Digital Conversion module
ADM1 and ADM2 (corresponds to
TRMx)
 Central Processing Unit NUM
(always included)
 Input / Output modules BIM, BOM,
SOM, IOM and MIM
 Power supply module PSM (always
included)

ADM
Power
Supply
In- / NUM TRM
Outputs

© SA-T Training
1MRG004718
Slide 6
Section 03

Hardware configuration – Backplane modules

1/1 19” rack UBM  Universal Backplane Module


(UBM)
 1/1 19” case (from right to left)
 TRM1 and TRM2, Slot 40, 41
 ADM1 and ADM2, Slot 31, 32

CBM  NUM, Slot P30 (always)

 1/2 19” case


 TRM1, Slot P40
Slot no: P1, P3 … P30 - P40,
P13 P32  ADM1, Slot P31
P41
 NUM, Slot P30 (always)

 Combined Backplane Module


UBM (CBM)
1/2 19” rack
 1/1 19” case (from left to right)
 PSM, Slot 1 (always)
 11 CAN-bus slots, Slot 3-13

 1/2 19” case


CBM  PSM, Slot 1 (always)
 3 CAN-bus slots, Slot 3-5
Slot no: P1, P3 … P30, P31 P40
P5
© SA-T Training
1MRG004718
Slide 7
Section 03

Hardware configuration – 1/1 19” case


3 cPCI positions

ADM

PSM
NUM
TRM
CAN-bus

PMC 1 1
PC-MIP 2 2
CAN-master
I/O modules like BIM, BOM, SOM,
CBM IOM and MIM connected to the
UBM CAN-bus
11*CAN-bus
ADM

NUM
TRM

PSM
ADM
TRM

CAN-bus

PMC 1 1
PC-MIP 2 2
View from the front side
© SA-T Training
1MRG004718
Slide 8
Section 03

Hardware configuration – 1/1 19” case

2 cPCI positions

ADM

PSM
NUM
TRM
CAN-bus

1
PMC 1 1
PC-MIP 2 2
CAN-master
I/O modules like BIM, BOM,
CBM SOM, IOM and MIM connected to
UBM the CAN-bus
14*CAN-bus

View from the front side


© SA-T Training
1MRG004718
Slide 9
Section 03

Transformer input module (TRM)

 Isolation barrier preventing


disturbances to enter into
670 series
 Adapt measured values to static
circuitry
 Up to 12 analog inputs can be
connected (settable 50 or 60 Hz)
 0 - 6 U, 110-220V rated range
 6 -12 I, 1A and/or 5A rated current
 Connectors (same type for all I/O-
modules)
 Screw compression or
 Ring lug

© SA-T Training
1MRG004718
Slide 10
Section 03

Transformer input module (TRM1 or 2)

1A 1A 5A 5A 110-220 V
metering metering

9I+3U 9 3 All except REB670


9 3 All except REB670
5 4 3 RET670 RED670
7I+5U 7 5 All except REB670
7 5 All except REB670
1 6 5 Customized
4 3 5 Customized
4 3 5 Customized
4 3 5 Customized
6I+6U 6 6 All except REB670
6 6 All except REB670
3 3 6 REL670

© SA-T Training
1MRG004718
Slide 11
Section 03

Transformer input module (TRM1 or 2)

1A 1A 5A 5A 110-220 V
metering metering

12I 12 All except REL670


and REC670
12 All except REL670
and REC670
6I 6 All except REB670
6 All except REB670

© SA-T Training
1MRG004718
Slide 12
Section 03

Analog to digital conversion module (ADM1)

Analog inputs (from TRM1)


P31

Mounting position for OEM


module (only on ADM1)
P31:1

cPCIbus

Possible mounting position for


P31:2 LDCM, GTM or RS485 module
Possible mounting position
for LDCM or GTM module
P31:3
Front
© SA-T Training
1MRG004718
Slide 13
Section 03

Analog to digital conversion module (ADM2)

Analog inputs (from TRM2)


P32

cPCIbus

Possible mounting position for


P32:2 LDCM or GTM modules

P32:3
Front
© SA-T Training
1MRG004718
Slide 14
Section 03

Numerical module (NUM)


P30

UBM interface
P30:1
Mounting position
for SLM module

P30:2 Possible mounting position


for IRIG-B or LDCM modules

P30:3 Possible mounting position for


LDCM module

cPCIbus

Front
© SA-T Training
1MRG004718
Slide 15
Section 03

Optical Ethernet module (OEM)

 Communication
 Ethernet (100 Mbit/s)
 IEC 61850-8-1
 IEC 61850-9-2LE
 DNP 3.0

 One or two channels


P31:1  Connectors
 Glass fiber, type ST
 Max 1 module per IED
 Mounted on ADM1

© SA-T Training
1MRG004718
Slide 16
Section 03

Serial communication module (SLM)


Rear

 Communication
 LON
 SPA or
 IEC 60870-5-103
 Connectors
 Glass fiber, type ST
P30:1  Plastic fiber, type HFBR
snap-in
 Combination of glass &
plastic fiber
 Max 1 module per IED
 Mounted on NUM

© SA-T Training
1MRG004718
Slide 17
Section 03

Line data communication module (LDCM)

 Up to 4 modules per IED (option)


Rear  Application example
 Line differential protection
 Need to exchange large number of binary
information
 Communication:
 multiplexed, route switched or dedicated
fibre using C37.94
 external modems for G.703 and G.703E1
 Different ranges
 Short range (SR), Multi-mode, ≈ 3 km
 Medium range (MR), Single-mode, ≈ 80 km
 Long range (LR), Single-mode, ≈ 120-150
km
 Connectors
 SR: Type ST; MR and LR: Type FC
 Module mounted on ADM and/or on NUM
(depending if IRIG-B and RS485 are included
and the number of LDCMs)

© SA-T Training
1MRG004718
Slide 18
Section 03

Galvanic LDCM (X21-LDCM)

 The optical ports in LDCM (C37.94) may be replaced with galvanic


X21-port (option)
 Up to 4 modules per IED (same as optical LDCM)
 Connectors
 Electrical 15-pole female mini D-sub
 Module mounted on ADM and/or on NUM (depending if IRIG-B and RS485
are included and number of LDCMs)

© SA-T Training
1MRG004718
Slide 19
Section 03

GPS time synchronization module (GTM)

Rear  Time Synchronizing (option)


 Number of channels
 GPS: 1
 PPS: 1
 Connectors
 Antenna 50 Ohm: SMA
 Optical PPS: Type ST
 Module mounted on ADM (1p2)

© SA-T Training
1MRG004718
Slide 20
Section 03

Time synchronizing module (IRIG-B)

Rear
 Time Synchronizing using
a station clock (option)
 Number of channels
 IRIG-B: 1
 PPS: 1
 Connectors
P30:2
 Electrical IRIG-B:
BNC
 Optical PPS:
Type ST
 Module mounted on NUM

© SA-T Training
1MRG004718
Slide 21
Section 03

Galvanic RS485 communication module (DNP 3.0)

Rear  Station Bus


Communication (option)
 DNP 3.0
 Serial communication,
alternative for Ethernet
communication
 2400 – 19200 Bits/s
 Connectors
 RS 485 6-pole
 Soft ground 2-pole
connector
 Max 1 module per IED
 Mounted on ADM1

© SA-T Training
1MRG004718
Slide 22
Section 03

Power supply module (PSM)

 DC/DC Converter providing full


isolation between IED and
P1 external battery system
 Input range: 24-60 V DC or
 Input range: 90-250 V DC
 Internal fail relay output
 Connectors (same type for all
I/O-modules)
 Screw compression or
 Ring lug

Front

© SA-T Training
1MRG004718
Slide 23
Section 03

Binary input module (BIM)

 16 Independent Binary Inputs


 Debounce filter, T = 5 ms
 Oscillation suppression detection within
1 s; > 0 - 40 Hz
 Pulse counting at all inputs (option)
 Auxiliary voltage
 24/40 V DC (±20%)
 48/60 V DC (±20%)
 110/125 V DC (±20%)
 220/250 V DC (±20%)
 Connectors (same type for all I/O-
modules)
 Screw compression or
 Ring lug

© SA-T Training
1MRG004718
Slide 24
Section 03

Binary output module (BOM)

 24 Single Output Relays or


 12 Double pole Command
Output Relays
 Connectors (same type for
all I/O-modules)
 Screw compression or
 Ring lug

© SA-T Training
1MRG004718
Slide 25
Section 03

Static binary output module (SOM)

 6 Fast Static Outputs


 48-60 VDC or
 110-250 VDC
 Operating time < 1ms
 6 Change over Output Relays
 Connectors (same type for all
I/O-modules)
 Screw compression or
 Ring lug

© SA-T Training
1MRG004718
Slide 26
Section 03

Binary input/output module (IOM)

 8 independent Binary Inputs and 12


Binary Output Relays (10 trip and
signal relays, 2 fast signal relays)
 Fix filter time 5 ms
 Auxiliary voltage
 24/40 V DC (±20%)
 48/60 V DC (±20%)
 110/125 V DC (±20%)
 220/250 V DC (±20%)
 Connectors (same type for all I/O-
modules)
 Screw compression or
 Ring lug

© SA-T Training
1MRG004718
Slide 27
Section 03

mA input module (MIM)

 6 independent input channels


 Software selected input ranges
 0-5, 0-10, 0-20, 4-20 mA
 ± 5, ± 10, ± 20 mA
 Resolution: 16 bit
 Accuracy: 0,1%
 Connectors (same type for all
I/O-modules)
 Screw compression or
 Ring lug

© SA-T Training
1MRG004718
Slide 28
Section 03
Hardware overview, 1/1 – 19” case

11*CAN 3*PCI

SLM

OEM

PSM

LDCM
(≤4 pieces)
GTM

IRIG-B TRM1 TRM2


NUM
I/O RS485 ADM1 ADM2
© SA-T Training
1MRG004718
Slide 29
Section 03

Hardware overview – I/O modules, 1/1 case


MIM *)
(max 4)

IOM
(max 6)

SOM *)
(max 4) 6 Transducer inputs,
BOM *) setting range + 20 mA
1/1 Case (max 4)
12 binary outputs
Option 1:
BIM and 8 binary inputs
• 1 TRM (max 11/14)
• ≤ 14 I/O modules
6 static and 6 change
Option 2: over binary outputs
• 2 TRM
24 binary outputs
• ≤ 11I/O modules

16 binary inputs *) Total number of MIM, SOM and BOM must be ≤ 4

© SA-T Training
1MRG004718
Slide 30
Section 03

Hardware overview – I/O modules, 3/4 case


MIM *)
(max 1)

IOM
(max 5/6)

SOM *)
(max 4) 6 Transducer inputs,
BOM *) setting range + 20 mA
3/4 Case
(max 4)

Option 1: 12 binary outputs


BIM and 8 binary inputs
• 1 TRM
(max 5/8)
• ≤ 8 I/O modules
6 static and 6 change
Option 2: over binary outputs
• 2 TRM
24 binary outputs
• ≤ 5 I/O modules

16 binary inputs *) Total number of MIM, SOM and BOM must be ≤ 4

© SA-T Training
1MRG004718
Slide 31
Section 03

Hardware overview – I/O modules, 1/2 case


MIM
(n.a.)

IOM
(max 3)

SOM
(max 3) 6 Transducer inputs,
BOM setting range + 20 mA
1/2 Case
(max 3)
• 1TRM 12 binary outputs
BIM and 8 binary inputs
• ≤ 3 I/O modules
(max 3)

6 static and 6 change


over binary outputs
24 binary outputs

16 binary inputs

© SA-T Training
1MRG004718
Slide 32
Section 03

Hardware overview – I/O modules, Ring lugs

1/1 Case 3/4 Case

Option 1: Option 1:
• 1 TRM • 1 TRM 1/2 Case
• ≤ 7 I/O modules • ≤ 4 I/O modules
• 1TRM
Option 2: Option 2: • ≤ 1 I/O modules
• 2 TRM • 2 TRM
• ≤ 5 I/O modules • ≤ 2 I/O modules

© SA-T Training
1MRG004718
Slide 33
Section 03

Local HMI

 Small or medium size screen


 Graphical LCD display (80 x 240 or
320 x 240 pixels)
 3 status indication LEDs indicate the
status of the IED
 Ready, Start and Trip
 15 indication LEDs
 12 push buttons for navigation,
control etc.
 Ethernet front port connection, RJ45

© SA-T Training
1MRG004718
Slide 34
Section 03

Summary – Basic hardware modules

 Universal Backplane Module (UBM)


 Combined Backplane Module (CBM)
 Main Processing Module (NUM)
 Power Supply Module (PSM)

© SA-T Training
1MRG004718
Slide 35
Section 03

Summary – Specific hardware modules

 Binary Input Module (BIM)


 Binary Output Modules
 Relay outputs (BOM)
 Static and relay outputs (SOM)
 Binary I/O Module (IOM)
 mA input Module (MIM)
 Analog Input Module (TRM)
 Analog to Digital conversion Module (ADM)
 Data communication Module (LDCM)
 Optical (C37.94) or galvanic (X21)
 Serial communication Modules
 LON, SPA or IEC 60870-5-103 (SLM)
 DNP 3.0 galvanic (RS485)
 Optical Ethernet Module (OEM)
 Time Synchronization Modules
 GPS (GTM)
 IRIG-B

© SA-T Training
1MRG004718
Slide 36
Section 03

Summary – Communication

 OEM (TCP/IP, Ethernet, SA-system)


 IEC 61850-8-1
 IEC 61850-9-2LE
 DNP 3.0
 SLM (Serial Communication Module)
 LON (SA-system)
 SPA or IEC 60870-5-103 (SMS-
system)
 RS485 (SA-system)
 DNP 3.0
 LDCM (communication between IEDs)
 IEEE/ANSI C37.94
 G.703/G.703E1 optical to galvanic
conversion
 X21-modem connection

© SA-T Training
1MRG004718
Slide 37
Section 03

Summary – Time synchronization

 OEM (TCP/IP, Ethernet)


 IEC 61850-8-1
 DNP 3.0
 SLM (Serial Communication Module)
 LON
 SPA
 RS485
 DNP 3.0
 GSM (GPS – module)
 IRIG-B
 Electrical IRIG-B
 Optical PPS
 Binary input

© SA-T Training
1MRG004718
Slide 38
Section 03

© SA-T Training
1MRG004718
Slide 39