DESIGN PROJECT

DESIGN AND CONSTRUCTION SURVEY OF A


WATER TANK FOR 15000 INHABITANTS

SUPERVISOR PRESENTED BY

 MR KENOU WILLY  SONKENG KENGNE MARVELLOUS


YVIC CESAR
 MR NKEMOFA ELVES
TABLE OF CONTENT

 INTRODUCTION

 PRE-DIMENSIONING

 STRUCTURAL DESIGN

 RESULTS

 CONCLUSION
INTRODUCTION

THE PROJECT IS BASED AT DOUALA PRECISELY AT LUNDI IN THE LITTORAL


REGION
PRE-DIMENSIONING
Data
-Capacity of tank: 2220m³
-Height of supporting tower: 12m
Number of columns: 4
Depth of foundation: 3.5 m below ground level
Permissible stresses
For calculation relating to resistance to cracking as per (IS 3370-1968)
-M30 grade concrete
-Fe 415 grade HYSD steel
Direct tensile stress in concrete бcb =2N/mm²
Direct tensile stress in steel бst=150N/mm³
D(inside diameter at te tank)
Assuming average depth=0.75D
 
STRUCTURAL DESIGN

 Design of top dome

-Thickness of dome slab: t=16cm=160mm


-Live load of dome: 1.5KN/m²
-Self weight at dome =4KN/m²
-Finishing load: 0.10KN/m²
-Wind pressure: 0.50 KN/m²
If, R: radius of the dome
D: diameter of base =10m
 Hoop tension

₁=
 
Design of top ring beam AN :₁ =(30.84
=120.276
F₁=120.276 KN
Assume 260mm by 260mm
Area of cross section
8/70 top ring beam of ring beam
Let b=150mm and
d=230mm

 
AN :
 
Design of cylindrical tank wall

Maximum hoop tension at base of wall


F₁=
Where g: acceleration due to gravity
H: depth of water
Hoop tension at base of wall
F₁=
F₁ =350KN/m
A top of wall
F₁=
F₁ =90KN/m
 
Design of cylindrical tank wall
Maximum hoop tension at base of wall
F₁=
Where g: acceleration due to gravity
H: depth of water
Hoop tension at base of wall
F₁=
F₁ =350KN/m
A top of wall
F₁=
F₁ =90KN/m
 
Design of bottom spherical dome
Thickness at dome assume as 300mm
Diameter at base: D=10m
Central rise: r=1.67m
Self weight of dome slab:
Volume of water above the dome is
AN

Weight of water =
Total load on dome =
 
Design of column
Size=
Let the roof slab is supported by columns spaced 4m a part in both
direction.
Lt the size of column be assumed as
Total axial load on column=
SBC of sol=200KN/mm²
Material :M30 and Fe415
 
Design of a footing
Shear failure could arise:
a) At the face of the column
b) At a distance face of one column
c) Punching failure of the slab

Face shear
Total axial load on column: 7153 KN
Factored load on footing due to column is:  729.5KN
RESULTS
STRUTURAL ELEMENT LIMIT STATE DESIGN OBSERVATIONS
3-1-RESULTS
METHOD
TOP
TOP DOME
DOME
  
.   
  Area
Area of
of steel
steel required
required (mm²)
(mm²) 150mm²
150mm² -Provide
-Provide 8mm
8mm Ø(diameter
Ø(diameter
Thickness required (mm) 160mm rods)centered
rods)centered at 200mm
at 200mm both
both
  circumferentially and meridionally
Thickness
Thickness required
required (mm)
(mm) 160mm
160mm circumferentially and meridionally
TOP RING BEAM
Area of cross
Thickness section
required (mm) 34 500mm²
160mm -Provide 4bars of 16mm diameter
as main reinforcement and 8mm
TOP RING BEAM
diameter stirrups at 200mm
centers.
Area of cross section 34 500mm² -Check for crack width is ok since
ꝭcrit
CYLINDRICAL TANK WALL

Base level thickness 350mm -At base of wall provide 20 Ørods


at 150mm centered
-At 1.75m from base of wall
Steel at base 1455mm²
provide 16 Ø rods at 125mm
centered
Top level thickness 200mm -At 3.50m from base of wall
provide 12Ø rods at 100mm
centered
Steel at top 375mm² -At top of wall provide 10Ø rods at
100mm centered

BOTTOM RING BEAM

Area of cross section 480 000mm² -Provide a bars of 25mm Ø rods as


main reinforcement (4420mm²)and
6mm Ø stirrups at 100mm centers
-check for crack width is ok ,since
ꝭcrit
-Provide a ring beam at 800mm
wide by 600mm deep
BOTTOM SPHERICAL DOME

Thickness 300mm -Provide 12mmØ bars at 125mm


centers (905mm²)*2
Area steel required 670mm² circumferentially and meridionally

COLUMN

Area of cross section 90 000mmm² -Provide 6bars of 32mmØ for


main reinforcement
-Provide 4bars at 20mmØstirups
for min reinforcement
Area of steel for main 4035mm²
-Provide 6mm Østirrups at 250mm
reinforcement
centers
-Column are spaced 4m apart in
both directions and 300mm deep
Area steel for min reinforcement 720mm²
and 300mm wide
FOOTINGS

Area of cross section of footing 9 000 000mm² -Provide 20mm Østirups centered


at 200mm in both direction (Asu
and Asy)
Depth of footing 1000mmm
-No shear reinforcement required
since
Area of steel required 1260mm² -Punching shear stress is ok ,
-N o crack at the column ,since
CONCUSIONS
Aiming for a solution to the needs of the population in terms of drinking water
supply ,the council qt Lundi (Douala) has opted for the construction of a water tank,
which with help meet in needs at the population consumption at one area .To this
end, the population of Lundi has launched d a tender for the accomplishment at this
project.
This is the transwork or this work, the main objective of which is the design of
reinforced concrete water tank which will be located at Lundi. Given the water tank
retention capacity, which is very important; the dimensioning was carried out
manually and the structural strength were checked according to the constraints
acting .
The dimensioning has been done so that each element is calculated in isolation,
therefore depending on the type of stress which is specific to it, which is why we
got the following results listed in the table earlier.
At the end of this study, let us remember that the water tank is an important
part of the transport of water from the source to the dwellings .Indeed ,even if it
is only a piece of this network ,it represents the most important organ because it
is this that ,the water will be stored while waiting to be routed to the dwellings.
This dimensioning of its various elements must strictly comply with the pre-
established calculation in order to avoid premature deterioration of its structure
or even its collapse. endangering the lives of residents.
WORK PLAN
The work will be organized as follows:

GENERAL INTRODUCTION

 Chapter 1: LITERATURE REVIEW

 Chapter 2: MATERIALS AND METHODS

 Chapter 3: RESULTS AND DISCUSSION

 Chapter 4: CONCLUSIONS