Application
Field of application in acc. with EN 1854.
For gas, air and fumes.
Switching ranges from 0.4 to 500 mbar, see
table specifications.
The pressure switches DG can also be used
as special-design pressure switches as defined
Solenoid Valve Make UNI with EVA series Main Burner Valve
Pilot Burner Solenoid Valve Make VMR
Pressure Regulator Valve on Pilot Gas Line
BURNER MANAGEMENT SYSTEM FOR SINTER PLANT 4.5 MTPA
FBB Make Standard Burner With only one electrode for ignition as well as ionization.
Two types of main burners located in centre and side have different capacity in volume/hr.
All 36 burners are top fired with pilot control and without flame sensor.
Normally burner has four modes with the Type of Gas Selection-
1. HEATUP MODE
2. FLOW CONTROL MODE
3. PRESSURE CONTROL MODE
4. LOW FIRE MODE
Before Start Up the pressure of Mixed Gas/Coke Oven Gas
Working Pressure-105 mBar
Maximum Pressure(Trip Limit)-150 mBar
Minimum Pressure(Become unhealthy)-40 mbar
FOLLOWING STEPS AFTER CHECKING START INTERLOCKHAS TO BE FOLLOWED
Execute start push button after checking start interlock (500ms ) and u will find following steps getting
executed in SFC