Professional Documents
Culture Documents
Fluidics
Fluid logic control systems
Course teacher
Prof. Mahbubur Razzaque
1
Fluid logic control systems
Fluid logic control systems use logic devices that switch a fluid, usually air,
from one outlet of the device to another outlet. Hence, an output of a fluid
logic device is either ON or OFF as it is rapidly switched from one state to
the other by the application of a control signal.
Fluid logic control systems have several advantages over electrical logic
control systems. For example, fluid logic devices are not as adversely
affected by temperature extremes, vibration, and mechanical shock. In
addition fluid logic systems are ideally suited for applications where electric
arcing or sparks can cause a fire or an explosion. Also fluid logic devices do
not generate electric noise and therefore will not interfere with nearby
electric equipment.
Devices that use a fluid for control logic purposes are broadly classified as
either moving-part logic (MPL) devices or fluidic devices.
Since fluidic components have no moving parts, they virtually do not wear
out. However, component malfunction can occur due to clogging of critical
flow passageways if contaminants in the air supply are not eliminated by
proper filtration.
These two useful functions can be accomplished for both MPL control
systems and electrical control systems.
Moving-part logic circuits use four major logic control functions: AND,
OR,
NOT, and MEMORY.
4
AND Function
Figure 16-4(a) shows a circuit that provides the AND function, which
requires that two or more control signals must exist in order to obtain an
output. The circuit consists of three two-way, two-position, pilot-actuated,
spring-offset valves connected in series. If control signals exist at all three
valves (A, B, and C), then output D will exist. If any one of the pilot signals
is removed, output D will disappear.
OR Function
An OR circuit is one in which a control signal at any one valve will produce
an output. Thus, all control signals must be off in order for the output not to
exist.
5
This is accomplished in Figure 16-5(a), in which the three valves are now
hooked in parallel. If any one of the valves picks up an air pilot signal, it
will produce an output at D.
NOT Function
In a NOT function, the output is ON only when the single input control
signal A is OFF, and vice versa. This is illustrated in Figure 16-6(a), which
shows that the output will not exist if the control signal A is received.
6
MEMORY Function
Figure 16.8 shows an MPL circuit which controls the extension and
retraction strokes of two double-acting cylinders. The operation is as
follows, assuming that both cylinders are initially fully retracted: when the
START valve V1 is momentarily depressed, pilot valve V2 shifts to extend
cylinder 1.
8
At full extension, limit valve V4 is actuated to shift valve V5 and extend
cylinder 2. On full extension, limit valve V6 is actuated. This shifts valve
V2 to retract cylinder 1. On full retraction, limit valve V3 is actuated. This
shifts valve V5 to fully retract cylinder 2. Thus, the cylinder sequence is as
follows: cylinder 1 extends, cylinder 2 extends, cylinder 1 retracts, and
finally cylinder 2 retracts.