SMAC

by Ahmed Ibrahim Al Desoky


Lube Oil pump
Manually Starts
Manually Stopped

Automatically starts
@5.45 Bar Start @17C
stop @25
SMAC Permissive

TE-110>15 C
TE-110<62 C
> 5.5 bar

BOV 100%

IGV 0%

< 0.13 Bar

VT-110 & VT-111< 12 mic.


SMAC Start up
Manually start

Override both vibration for


6 sec.

After 3 sec. open IGV 15 %


SMAC Running Mode
Operator will turn IGV
& BOV to Auto

BOV set point 5.5 Bar


IGV set point 5.25 Bar
Normal Operation
Surge controller
7

System Pressure
4

0
80 90 100 110 120 130 140

Flow/Amps
Surge curve DTS
System Pressure 3 4.46 6 bar
surge curve 89 107 127 A
DTS 99 117 137 A

If pressure increased the IGV will throttle to achieve 5.25 bar, with 60 % minimum opening

If pressure still increasing surge controller modulate the BOV

If the system pressure and motor current touches the surge curve, the compressor will unload

uBy 1st fully open the BOV then turn the IGV to manual with minimum opening (60%)
SMAC Trips
Alarm Set
No. Description Tag Trip Low Trip High
Low Alarm High Point

1
2nd Stage Inlet Temp. ('C) TE-112     55 65  

2
Discharge Temperature ('C) TE-113     55 65  

3
1st Stage Vibration (micron) VT-110     38 50  
4
2nd Stage Vibration (micron) VT-111     38 50  
5
Oil Pressure (Bar) PI-110 4.82 5.51 12.41 13.78  
6
Oil Temperature ('C) TE-110 15 21 57 62  

 7
OIL level LS-110 0
 8 Emergency Stop Signal ES-110 0
9
Stator Temperature A ('C) TE-114     140 155  
10
Stator Temperature B ('C) TE-115     140 155  

11
Stator Temperature C ('C) TE-116     140 155  

 
12
 
MAC K-111 trip K-111  