Professional Documents
Culture Documents
• On all modern split bus systems, the APU can be started and operated during flight. This allows the APU
generator to provide back-up power in the event of a main generator failure. A fourth emergency
generator powered by the ram air turbine is also available if the other generators fail.
• The four AC generators are shown at the bottom of Figure with considering APU. These generators are
connected to their respective busses through the generator breakers. For example, generator 1 sends
current through GB1 to AC bus 1. AC bus 1 feeds a variety of primary electrical loads, and feeds sub-
busses that in turn power additional loads.
Split bus system
• With both generators operating and all systems normal, AC bus 1 and AC bus 2 are
kept isolated. Typically, during flight, the APB (bottom center of Figure) would be
open and the APU generator off; the emergency generator (bottom right) would
also be off and disconnected. If generator one should fail, the following happens:
• The GB 1 is opened by the GCU to disconnect the failed generator.
• The BPCU closes BTB 1 and BTB 2. This supplies AC power to AC bus 1 from
generator 2.
• The pilots start the APU and connect the APU generator. At that time, the BPCU
and GCUs move the appropriate BTBs to correctly configure the system so the APU
powers bus 1 and generator 2 powers bus 2. Once again, two AC generators
operate independently to power AC bus 1 and 2.
Split-parallel bus system
Split-parallel bus system
• The main generators are driven by the main turbine engines. Each
generator is connected to its load bus through a generator control
breaker (GCB). The generator control unit closes the GCB when the
pilot calls for generator power and all systems are operating normally.
Each load bus is connected to various electrical systems and
additional sub-busses. The BTB are controlled by the BPCU and
connect each load bus to the left and right sync bus. A split systems
breaker (SSB) is used to connect the left and right sync busses and is
closed during a normal flight. With the SSB, GCBs, and BTBs, in the
closed position the generators operate in parallel. When operating in
parallel, all generators must be in phase.