Installation Guidelines
Installation
Guidelines
X4i Kit
• One X4i Controller and mounting hardware
• Four IR-PCBs and mounting hardware
• One 0-16 bar (0-232 psi) Pressure Transducer
• 100 meters (330 feet) of 0.75 mm2 (18 gauge) wire and tie wraps
X4i Specifications
Dimensions 241mm x 291mm x 152mm
9.45” x 11.45” x 6.0”
Power Supply 50 VA
188mm 236mm
230 VAC, +/- 10% (50 Hz)
115 VAC, +/- 10% (60 Hz)
8mm Ø
Control Power 24 Vdc
Humidity 0 to 95 % RH
non-condensing
X4i
X8i Specifications
Dimensions 340mm x 241mm x 152mm
13.4” x 9.45” x 6.0”
Humidity 0 to 95 % RH
non-condensing
Power Supplies
• 115 or 230 VAC
° Terminal X04 must be configured
83
89
6
12 mm
6
4 x 4.5mm
BLUE BLACK
BROWN ORANGE
RED WHITE
GREEN VIOLET
10 32
1 2 3 4
X04 1 2 3 4
230V
T3.15A
T1.0A
T1.6A
T1.6A
115V
115V +-10%
IEC T1.0A FH1
5x20mm
1 2 3 4
X03 X02
2 1 2
X01 12 mm
141 N E
L E
147
24Vac/2 24Vac/1
T1 S1 earthed isolated L N E
Xi Controller Specifications
• 16 Bit Processor
• 1MB Flash EPROM
• 12 Bit A to D Converter
• 128 x 64 Backlit Monochrome LCD Display
• 24 VDC Powered
• 8 Digital Inputs, 6 Relay Outputs, 3 Analog Inputs
Connections In Operator’s
Manuals
• X01 thru X04
° IR-PCB of each compressor
• X05
° Pressure Transducer
• X06 (X8i only)
° RS485 Network
Connection for Xe-M, S3, IR-485
and IRv-485 gateways.
NOTE: 27 and 29 are L1
28 and 30 are L2
Picture to right is incorrect
Not for third party devices
• X01 on XPM-LED
° RS485-2 Network
° Connection for EXP
Expansion Box only!
° Not for third party devices
RS-485 Wiring
• 2 conductor shielded cable
° Belden 9841 or equivalent
° Preferably ran in grounded conduit away from high voltage
° Daisy-chain configuration
Avoid Star Configurations 5
1 P
1
P P
1
P
2 2 2
1 2 3
• Wiring:
° 4-20 mA
100 m (330 ft.) maximum
Shield grounded on Panel side only
X05
-
26
25
+ +
4-20mA