• NOZZLE QUANTITY MUST BE AN EVEN NUMBER • HOWEVER, NOTE THAT THE NOZZLE MUST BE
(2,4,6,8,10) SO IT IS ALWAYS BALANCED BALANCED SO THE NOZZLE QUANTITY FOR THIS
EXCEPT FOR 1 NOZZLE. ROOM WOULD BE 4 NOZZLES.
• FOR EXAMPLE: AREA FOR ROOM BELOW, IS • ENSURE THAT THE NOZZLE PLACING MUST BE
71.34m².THEREFORE, WHEN DIVIDED BY IN THE MIDDLE OF THE ROOM AND ARE OF
NOZZLE AREA COVERAGE, WILL BECOME 2.9 ~ EQUAL SIDES.
3
DETECTOR LOCATION
• ALL DETECTORS SHOULD BE IN PAIRS (HEAT & • SO, 2 PAIRS OF DETECTOR IS NEEDED FOR THIS
SMOKE = 1 PAIR) ROOM.
• FOR EXAMPLE: AREA FOR ROOM BELOW, GIVEN • ENSURE THAT THE NOZZLE PLACING MUST BE
THAT THE HEIGHT IS 3m, IS 71.34m².THEREFORE, IN THE MIDDLE OF THE ROOM AND ARE OF
WHEN DIVIDED BY HEAT DETECTOR AREA EQUAL SIDES.
COVERAGE, WILL BECOME 1.4 ~ 2
CONTINUE..
• THE LAYOUT OF THE DETECTORS SHOULD BE • IF THE QUANTITY OF NOZZLE AND DETECTORS
CRISS-CROSS TO CREATE A 2 ZONE SYSTEM. ARE THE SAME, THE DETECTORS SHOULD BE
PUSHED MORE TO THE MIDDLE OF THE ROOM AS
SHOWN.
1 2
3 4
CONTINUE..
• HOWEVER, THE PIPING SHOULD NOT BE • THE DETECTORS ARE PLACED DEPENDING ON THE
OVERLAPPING WITH THE DETECTORS, SO THE PIPING LAYOUT AND ADJUSTMENT SHOULD BE
DETECTORS WILL BE PUSHED TO THE MIDDLE OF MADE TOWARDS THE CENTRE OF THE ROOM.
THE ROOM.
PIPING LAYOUT
• THE GENERAL PIPING LAYOUT BELOW SHOW EXAMPLE FOR 2,4,6 & 8 NOZZLES
Exercise
• CO2 - EXERCISE.dwg