Place : Piper Alpha, North Sea Date : 06.07.1988 Substance Involved : Oil, Gas Event : Explosions & Fires Loss : - Killed : 167 - Injuries :- - Financial : $ 1,860,000,000 Plant Unit Involved : compression unit, drilling platform Explosion • Condensate leaks caused the explosion in the gas compression and separation module at 10.00 PM • Deficient PTW (Permit-to-Work) System • no cross reference among all parties involved in the maintenance operations • no system for handover to the next shift • Deficient Training on the PTW System • no the PTW system training for contractors for maintenance job • no the PTW system training for all operations personnel Prolonged Oil Fire The explosion blew down the fire wall and damage the equipment at the oil separation section and started the oil fire which a thick black smoke • Deficient Hazards Analysis • at the design stage, a risk of fire was recognized • but not the explosion hazards. • Deficient Training • no inter-platform emergency communication exercise • the adjacent platform kept sending their product to alpha, because the communication system had been destroyed by the explosion Dead in Accommodation In the evening , majority of the crew were in the accommodation . The thick black oil smoke caught in the accommodation and majority of people died from carbon monoxide poisoning. Deficient Hazards Management The accommodation was design to provide some resistance for some time to fire. It was not set up to prevent the egress from the thick black oil smoke. Deficient Training The offshore installation Manager was never been trained in any simulation exercise in handling emergency People who put him on the job should be able to recognize the need for such training. Safety Auditing Deficient of Quality Audit • there was sufficient safety monitoring and auditing conducted in Piper • it was not effective because it was not on the right quality • Every single day, a full time safety operator was dedicated to watch the PTW system. There was no significant fault found in the PTW System based on that daily monitoring. There was no report saying that practices are different with what said in the paper • Each year , there was a fire insurance audit and there was no single report on the blockage of the water deluge system Gas Fire Gas lines of 2000 psi from the adjacent platforms to Alpha were caught in the oil fire and burst due to excessive heat. Deficient hazard Management • management never discussed the hazard of gas pipe line riser fails •The study disclosed that when the gas pipelines riser fails, no fire fighting would be effective and the lost of life could be enormous. • Fire Fighting At the time of disaster, the water deluge system did not work. The initial explosion destroyed the main power supply to the electric driven fire pump By design , the diesel driven back-up pump was installed in an automatic start when the electric driven pump does not work. •Deficient Quality Decision • Management decided to put the diesel driven fire pump on manual start when the drivers are in the water. • Hazards to driver is more in priority compare to number of people stay at the platform. • Deficient Safety Management • A frequent problem of blockage of the deluge systems due to corrosion and many years back management decided to replace it with non-corrosive material • Only one of the deluge systems had been replaced with non- corrosive material and it was at the drilling module which had not been in fire.