Solved Problem
Gesmundo, Shenlhee D.
ME-4D
ME ELECTIVE 1
Problem:
An air conditioned theater is to be maintained at 80 degrees
Fahrenheit dry bulb temperature and 50% relative humidity.
The calculated total sensible heat load in the theater is
620,000 BTU/hr., and the latent heat load is 210,000 BTU per
hour. The air mixture at 84 degrees F dry bulb and 72
degrees F wet bulb temperature by chilled water-cooling coils
and delivered as supply to the theater. Calculate tons of
refrigeration required. Solve in English and Metric.
Solution:
Given:
pt 1. @ 84 deg F DBT, 72 deg F WBT or
pt 2. @ 63 deg F DBT, 59 deg F WBT
pt 3. @ 80 deg F DBT, 50% RH
Qs = 620,000 BTU/hr
Required:
• Cooling Load in TOR (English)
1.) Working Equation Qa = 2522.17 lb/min*(35.8 – 25.8)BTU/lb
Qs = ma*Cpa*(T3 – T2)
ma = 151,330.2416 lb/hr/60
ma = 2,522.17 lb/min
Solution:
Given:
Pt 1. @ 28.9 deg C DBT, 22.2 deg C WBT or
Pt 2. @ 17.22 deg C DBT, 15 deg C WBT
Pt 3. @ 26.67 deg C DBT, 50% RH
Qs = 181.7 kW
Qlatent = 61.54 kW
Required:
Qs = ma*Cpa*(T3 – T2)
ma = 19.22 kg/s