Professional Documents
Culture Documents
59
V.T
59N
V/F
46
32
51 C.T
I.C.T.
87G
26
G
~
64F
40
26
SHAFT
CURRENT
46
C.T
21
32
59N
POWER SYSTEM
• INTERACTION
OFCOMPONENTS,GENERATORS,TRANSMISSION AND
LOAD.
• THREE PHASE BALANCED SYSTEM,ENERGISED AT
DIFFERENT VOLTAGE LEVELS.
• OBJECTIVES; MINIMUM LOSSES,SAFETY AND
AVAILABILITY.
• FRQUENCY;INDICATOR OF ACTIVE POWER.
• VOLTAGE;INDICATOR OF REACTIVE POW
MECHANISM OF FAULT CURRENT FLOW
• DURING EARTH FAULT CURRENT FLOW S VIA GROUND
TOWARDS SOURCE,REALISING ELECTRICAL ISOLATION AND
SHRING OF CURRENT BASED ON IMPEDANCES.
• GENERATOR PRODUCE ONLY POSITIVE SEQUENCE;NEGATIVE
AND ZERO AT FAULT POINT.
• PH-PH FAULTS,POS.AND NEG.SEQUENCE PRESENT.
• PH-G FAULTS; POS. NEG. AND ZERO SEQUENCE PRESENT.
• CONVERSION OF FAULT CURRENT IN DELTA-STAR WINDING.
Generator Current During Fault
Sequence Components
Sequence Components During Fault
COMPONENTS OF A PROTECTIVE SYSTEM
Impedance
Loss of relay trip
field zone
locus
Differential Protection, 87
CT STATOR
P1 P2 P1 P2
S1 S2
S1 S2
OPERATING
COIL
RESTRAING
COIL
GENERATOR GROUND FAULT PROTECTION
A
B
Stator
C
CT
51
NGR
OVER VOLTAGE,59 & UNDER VOLTAGE ,27
(3rd Harmonic)
• Used with secondary winding of earthing Transformer, in
generator neutral.
• Impedance of earthing transformer is equal to winding
capacitance impedance.
• 3rd Harmonics are produced due to winding capacitance.
• Usually impedance of earthing transformer limit the fault
current from 5A to 15A.
• 59, is set to operate at 5% of maximum neutral voltage.
Protect only 95% winding.
• 27, sense the 3rd harmonic voltage.27 & 59 bring 100% stator
earth fault. Inject 15 to 20 Hz into neutral via secondary of
earthing Transformer and measure current.
LOSS OF EXCITATION, 40
• BY UNINTENTIONAL OPENING OF FIELD BREAKER.
• OPEN OR SHORT CIRCUIT OF MAIN FIELD WINDING.
• FAULT IN THE ‘AVR’.
• GENERATOR GOES OUT OF SYNCHRONISM.
• STAOR CURRENT INCREASES.
• OPERATES AS INDUCTION GENERATOR.
• STILL DELIVERING ‘MW’.
• SPEED HIGHER THAN THE SYSTEM.
• ABSORB ‘VARS’ FROM SYSTEM FOR EXCITATION AND
VOLOTAGE DROPS IN THE SYSTEM
• EMF BECOMES LESS THAN TERMINAL VOLTAGE.
40-cont…..
• STATOR END REGIONS AND ROTOR OVERHEATED.
• SALIENT POLE MACHINES ARE LESS SENSITIVE THAN
WOUND ROTOR.
• MEASURE CURRENT IN EXCITATION CIRCUIT,USING
UNDER CURRENT RELAY.
• USE DIRECTIONAL REACTIVE POWER MEASURING
RELAY.
• USE IMPEDANCE RELAY TO DETECT IMPEDANCE
LOCUS IN 4TH QUADRENT.
ROTOR EARTH FAULT,64
• FIELD WINDING IS ELECRICALLY ISOLATED FROM GROUND.
• INSULATION FAILS DUE TO VIBRATIO,EXCESSIVE FIELD
CURRENT AND FAULTY COOLING.
• FIRST GROUND-NO HARM BUT INCREASED STRESSES TO
GROUND AT OTHER POINTS ESPECIALLY BY STATOR
TRANSIENTS.
• TWO OR MORE GROUNDS CAUSE MAGNETIC AND THERMAL
UNBALANCES.
• PESENCE OF FIRST GROUND FAULT MAKES DETECTION OF
SECOND FAULT DIFFICULT.
• BYPASSED WINDING DUE TO DOUBLE GROUND WILL
UNBALANCE THE AIR GAP FLUXES.
64 cont….
• Increased field current unbalance the magnetic
forces on opposite side of rotor.
• Create vibration, spring the shaft and may rotor grind
against the stator.
• Conventional scheme using high impedance ground
of field DC.
• AC injection, 40V from 110V VTs is connected to
excitation circuit via a capacitive voltage divider and
measure AC leakage current.
• Inject 50V DC supply and measure leakage current.
AC Injection Method
VT
40V
SUPPLY
CURRENT
TRIGGER
ROTOR
CAPACITIVE VOLTAGE
DEVIDER
Conventional Ground Protection
EXCITER BEARING
FIELD WINDING
SLIP
RINGS
GROUNDIN
G BRUSH
LEAKAGE
RELAY
NEGATIVE PHASE SEQUENCE CURREN
PROTECTION,46.
• NEGATIVE SEQUENCE CURRENTS(I2)ARE GENERATED DUE TO
UNBALANCE LOAD.
• SINGLE AND TWO PHASE SHORT CIRCUIT’
• NON TRANSPOSED LINES HAVING UNBALANCED
CAPACITANCE.
• WITH BALANCED LOAD AMPERE-TURN WAVE PRODUCED BY
STATOR CURRENT ROTAES SYNCHRONOUSLY WITH ROTOR.
• NEGATIVE SEQUENCE CURRNT HAS OPPOSITE PHASE
ROTATION AND PRODUCE ADDITIONAL AMPERE-TURN
WAVE,WHICH ROTATES IN OPPOSITE DIRECTION.THUS FLUX
WAVES ROTATE RELATIVELY AT TWICE THE SYNCHRONOUS
SPEED
46 cont…..
• DOUBLE FREQUENCY CURRENT INCREASE EDDY-
LOSSES WHICH CAUSE EXCESSIVE OVER-HEATING.
• ABOVE CONTINUOUS ‘I2’ LIMIT, I2²t FACTOR IS
ESTABLISHED FOR TEMPRATURE RISE.
• CTs BASED I2 FILTERS OR FOURIOR-ANALYSIS OF
CURRENT WAVE-FORM,THEN USE OF OVER
CURRENT RELAY.
Negative Sequence Relay
NEGATIVE SEQUENCE RELAY 46
ALARM
STAGE TIMER
I2 ALARM
TRIP STAGE
THERMAL REPLICA
&
70
TIME 60
50
40
30
20
10
UNIT TRANSFORMER
GENERATOR
WINDING CAPACITANCE
100%
95%
59 27
- +
Relaying with Earthing Transformer
GEN
180 HZ
LOADING
EARTHING RESISTOR
59 27
TRANSFORMER
50
Over voltage 59
59
VT
GEN Z