Professional Documents
Culture Documents
B023 Gas Pipes Calculations - Rev A
B023 Gas Pipes Calculations - Rev A
CONTRACT NO.
DOCUMENT NO.
DOCUMENT TITLE
GREENWICH SQUARE
VC-50339
B023
GAS PIPE SIZING CALC
DESCRIPTION
DATE
ENGINEER
Based on Indicative P&ID 01/02/2013 NH
Gas Booster for Con. Blr
27/02/2013 NH
CHECKED BY
NH
NH
DRAWING NO.
D-339-C-02
D-339-C-02
Rev
O
O
18.5 mbar
Assumptions
10.973 kWh/m3
9.8757 kWh/m3
Unit
Output
kW
1860
2500
2500
800
Boiler 1
Boiler 2
Boiler 3
CHP (kWe)
39.5 MJ/m3
35.6 MJ/m3
Fuel consumption
kW
2067
2941
2941
2091
Efficiency
%
Pressure Min
mbar
90%
85%
85%
Fuel Consumption
188
268
268
210
18
63
63
80
10040 kW
36144 MJ
934.0 m3/h
BLR 2
BL3
CHP
BLR 1
Gas Booster (GB)1
D
10 mbar
6m
18 mbarg after the meter
SSV
Inlet Node
O
DN200
18 mbar
B
DN150
15mbar
63mbar
GB3
H
15 mbar
63mbar
GB2
F
15mbar
GB4
3m
3m
DN100
DN100
1m
A DN200 C
31m
DN200
12.5m
DN100
G
15 mbar
18 mbar
19 mbar before Gas Meter
4m
TBC
Confirmed
Confirmed
Sensitivity Analysis
CHP1 Gas
Boiler1 Gas
Boiler 2 Gas
Boiler3 Gas
100.0%
100.0%
100.0%
0.0%
Route
Inlet
Slamshut V/v
O-A
A-B
A-C
C-D
C-E
E-F
E-G
G-H
Length (m)
31
8
1
2.5
12.5
3
4
3
24.99730471
15.10847982
6.820737195
4.136811106
5.142099526
6.383479559
0
0
55.99730471
23.10847982
7.820737195
6.636811106
17.64209953
9.383479559
4
3
666
666
666
188
478
210
268
268
0
0
dP (mbar)
1.3
0.523
0.086
0.039
0.241
0.031
0.541
0.000
0.000
Pressure Size NB
18
16.7
16.177
16.091
16.052
15.850
15.820
15.309
15.309
15.309
200
150
200
100
200
100
200
100