SELECT WATER PUMP HP

CO O LINGTO W E R

W ater O utlet

W ATE R -CO O LE D PACKAG E D UNIT

W ATE RPUMP

W ater Inlet

Unit model: AWX610 Pipe length: 210 ft (2 way) Water flow: 150 usgpm Pressure Drop 1. Pipe length 210 ft. Add 50% for fitting = 315 ft 315 x 8 100 = 25.2 ft 2. Unbalanced head at base of cooling tower = 10 ft Unit (5.5 psig x 2) x 2.31 = 25.41 ft. Note: 1 psig = 2.31 ft Water Flow (USGPM) x Head 3960 (150) x 67 = Brake HP 3960 2.59 = Brake HP Brake HP = 2.59 HP = 2.59 = 3.2 HP 0.8 Pump motor Hp = 4 Hp or 3 Kw = Brake HP Total item 1 to 3 25.2 ft + 10 ft + 25.41 ft = 60.61 ft 61 ft Add 10% = 67 ft (Head) Find the water pump (HP)