You are on page 1of 4

MENGEMUKAKAN PELAN PINDAAN AS BUILT BAGI BLOK F, KOMPLEKS

JABATAN KERJA RAYA MALAYSIA ( JKR ), DI ATAS LOT NO 75, SEKSYEN


60 JALAN SULTAN SALAHUDDIN, BANDAR KUALA LUMPUR, 50480
WILAYAH PERSEKUTUAN KUALA LUMPUR UNTUK :
TETUAN JABATAN KERJA RAYA MALAYSIA

Hose Reel System

1) Determination of water storage capacity (according to UBBL)

Minimum storage required for the first hose reel = 2,275 Litre
For each additional hose reel = 1,137.5 Litre up to a maximum of 9,100 Litre.
Therefore :-
Storage capacity = 2,275 + (1,137.5)(33)
= 39,796 Litre
According to UBBL 1984 , the maximum storage for hose reel tank up to 9,100 Litre @
9.1 m3.

Existing fire tank at site has combined the capacity for Sprinkler + Wet Riser + Hose
Reel system.
Min. Sprinkler tank capacity = 80 m3 (OH 1 - 45m)
Min. Wet riser tank capacity = 45.3 m3
Min. Hose reel tank capacity = 9.1 m3
Total Tank Capacity = 134.6m3

Existing Fire Tank Size : 4.88m x 7.32m x 3.66m (H) + 2.44m x 3.66m x 3.66m (H)
Existing Fire Tank Effective Capacity = 141.1 m3

Hence, existing sprinkler/wet riser/hose reel tank capacity is sufficient.

HR/1
HOSE REEL
2) Determination of pump capacity

i) Pump Flow Rate


Hose Reel System
Each hose reel required pumps flow rate of 30 Ltr/min i.e 6.6 Igpm, So consider 4
hose reel will activate simultaneously during fire mode.
 4 x 6.6 = 26.4 Igpm

ii) Pump Head :

Consider the highest point


Pump Head, H = static head + pressure required at outlet + pressure drop due
to friction in the piping
Where
static head = vertical distance between the furthest point and pump
discharge level
static head = 56.2 m
= 184.34 ft
pressure required
at outlet = 70 ft
pressure drop due
to friction = calculated as follows

HR/2
HOSE REEL
Water Pipe Description No. of Equal Eff. 10% Head
Flow Size Item Length Length Safety Consume
(Igpm) (in) (ft) (ft) Factor (ft)
30 6 Static pipe - 250 337.6 371.4 0.0736
Tee 1 28.2
Elbow 9 6.6
30 2 Static pipe - 6.6 6.6 7.3 0.2976
6 1 Rubber - - 100 0.065 6.5
hose
TOTAL 6.87

P=( 6.05 x 10 5 )( L)(Q1.85)


(C1.85) (D4.87)

For 6 in pipe :
Where Q = 30 igpm=136.36 Ltr/min
L = 371.4 ft = 113.2 m
C = 120
D = 150 mm
Hence, P = 0.0022 bar
= 0.0224 m
= 0.0736 ft

For 2 in pipe :
Where Q = 30 igpm=136.36 Ltr/min
L = 7.3 ft = 2.2 m
C = 120
D = 50 mm
Hence, P = 0.0089 bar
= 0.0907 m
= 0.2976 ft

HR/3
HOSE REEL
Pump Head, H = 184.34 + 70 + 6.87
= 261.21 ft
Add 10 % ≈ 261 ft

Hose reel pump capacity required = 24 Igpm @ 261 ft head


Since the hose reel flow rate/ pressure required is less than specified for jockey pump,
hence the selected capacity for jockey pump is satisfied.

Hose Reel Jockey


24 Igpm @ 261 ft head < 30 Igpm @ 410 ft head

HR/4
HOSE REEL

You might also like