Professional Documents
Culture Documents
Minimum storage required for the first hose reel = 2,275 Litre
For each additional hose reel = 1,137.5 Litre up to a maximum of 9,100 Litre.
Therefore :-
Storage capacity = 2,275 + (1,137.5)(33)
= 39,796 Litre
According to UBBL 1984 , the maximum storage for hose reel tank up to 9,100 Litre @
9.1 m3.
Existing fire tank at site has combined the capacity for Sprinkler + Wet Riser + Hose
Reel system.
Min. Sprinkler tank capacity = 80 m3 (OH 1 - 45m)
Min. Wet riser tank capacity = 45.3 m3
Min. Hose reel tank capacity = 9.1 m3
Total Tank Capacity = 134.6m3
Existing Fire Tank Size : 4.88m x 7.32m x 3.66m (H) + 2.44m x 3.66m x 3.66m (H)
Existing Fire Tank Effective Capacity = 141.1 m3
HR/1
HOSE REEL
2) Determination of pump capacity
HR/2
HOSE REEL
Water Pipe Description No. of Equal Eff. 10% Head
Flow Size Item Length Length Safety Consume
(Igpm) (in) (ft) (ft) Factor (ft)
30 6 Static pipe - 250 337.6 371.4 0.0736
Tee 1 28.2
Elbow 9 6.6
30 2 Static pipe - 6.6 6.6 7.3 0.2976
6 1 Rubber - - 100 0.065 6.5
hose
TOTAL 6.87
For 6 in pipe :
Where Q = 30 igpm=136.36 Ltr/min
L = 371.4 ft = 113.2 m
C = 120
D = 150 mm
Hence, P = 0.0022 bar
= 0.0224 m
= 0.0736 ft
For 2 in pipe :
Where Q = 30 igpm=136.36 Ltr/min
L = 7.3 ft = 2.2 m
C = 120
D = 50 mm
Hence, P = 0.0089 bar
= 0.0907 m
= 0.2976 ft
HR/3
HOSE REEL
Pump Head, H = 184.34 + 70 + 6.87
= 261.21 ft
Add 10 % ≈ 261 ft
HR/4