160KW 415V 267A 50 Hz ABB S/D Cable Sizing Detail (1+1) run Type of Cable XLPE Conductor Al Voltage Grade 1100V Current Loading on each Cable 133.5A Medium (Over Head Cable Tray) Air Ambient Temperture 50Deg C Derating Factor 0.66 Length of Cable/run 150mtr
Cable-1 3CX95Sq.mm Al Armoured XLPE Cable Current as per Catalogue After Derating Current will be Voltage Drop factor (mV/Amp/mtr) Voltage Drop for One Run (at full Load) in Volt Appr Power Loss due to Voltage Drop at Full Load (Kw/run) Hence approx Cable Loss at full load will be Cable Loss in kw in Percentage Cable-2 3CX120Sq.mm Al Armoured XLPE Cable Current as per Catalogue After Derating Current will be Voltage Drop factor (mV/Amp/mtr) Voltage Drop for One Run (at full Load) in Volt Appr Power Loss due to Voltage Drop at Full Load (Kw/run) Hence approx Cable Loss at full load will be Cable Loss in kw in Percentage Cable-3 3CX150Sq.mm Al Armoured XLPE Cable Current as per Catalogue After Derating Current will be Voltage Drop factor (mV/Amp/mtr) Voltage Drop for One Run (at full Load) in Volt Appr Power Loss due to Voltage Drop at Full Load (Kw/run) Hence approx Cable Loss at full load will be Cable Loss in kw in Percentage Cable-4 3CX150Sq.mm Al Armoured XLPE Cable Current as per Catalogue After Derating Current will be Voltage Drop factor (mV/Amp/mtr) Voltage Drop for One Run (at full Load) in Volt Appr Power Loss due to Voltage Drop at Full Load (Kw/run) Hence approx Cable Loss at full load will be
A A mV V kW kW %
A A mV V kW kW %
A A mV V kW kW %
A A mV V kW kW
1.8