What will happen to the generator when the field excitation fails? 7 days ago
Close viewer Like Comment Follow Flag o Flag as Promotion o Flag as Job o Flag as Inappropriate More o Reply Privately
4 comments
ANEESH KUMARUnfollow Follow ANEESH KUMAR ANEESH KUMAR SHANDILYA The Generator will will work as an induction generator if it is synchronized with another generator of grid, in case it does not trip on failure of excitation protection. It will draw reactive current from the system. The rotor will become hot and may get damaged. 6 days ago Unlike Like
Santanu Kumar Behera Thank you sir... Then the generator will rotate in which direction? Either direction of prime mover or opposite to it? 6 days ago Unlike Like
Ing. OleUnfollow Follow Ing. Ole Ing. Ole Knudsen It will rotate in the same direction as the prime mover if the shaft is not broken! 6 days ago Unlike Like
EmmanuelUnfollow Follow Emmanuel Emmanuel Britto ANEESH KUMAR SHANDILYA made an excelent and short description of the phenomena. Congratulations. 5 days ago