Professional Documents
Culture Documents
CALCULATION
Customer Name : DMRC
DG Rating Detail : 2 x 1010KVA
Total Generation Capacity *
Generation Voltage
Base Load
2020 KVA
:
0.415
KV
:
1 KW
:
1.25 KVA
:
Motor Load
355 KW
:
443.75 KVA
:
Startup FLC
2.5 times
:
Transient Load
1109.38 KVA
:
P.f. (Base Load)
0.8
:
P.f. (Transient)
0.2
:
X'd
0.164
:
X"d
0.131
:
* Cumulative kVA of all the alternators connected to feed the load.
T.V.D. %
7.363 %
Loading Step :
(To be Filled)
T.V.D. CALCULATION
DG Rating
DG Voltage
Base Load
Motor Load
Startup FLC
Transient Load
P.f. (Base Load)
P.f. (Transient)
X'd
X"d
:
:
:
:
:
:
:
:
:
:
:
:
2020
0.415
1
1.25
355
443.75
2.5
1109.38
0.8
0.2
0.164
0.131
KVA
KV
KW
KVA
KW
KVA
times
KVA
(To be Inserted)
P.f.*P.f
P.f.*P.f
=
=
0.64
0.04
1-P.f.*P.f.
1-P.f.*P.f.
Base Load
0.00062 p.u.
Transient Load
0.5492 p.u.
1 =
1
. . ( )
1292.8
1 =
1
(1 . . 2 )
969.6
2 =
1
. . ( )
0.36417
2 =
1
(1 . . 2 )
1.78406
0.1475
0.415
6.6
11
YES
NO
+ "
2
1 2 2 + 2 2 + 2 1 2 + 1 2
(1 + 2 )2 + (1 + 2 )2
0.36519
1 2 2 + 2 2 + 2 1 2 + 1 2
(1 + 2 )2 + (1 + 2 )2
1.78228
0.92637
7.363 %
1 2 + (1 + )2
2 + 2
2 + ( + )2
1 2 + 1 2
. . . % = 1 100
T.V.D. %