T.V.D.

CALCULATION
Customer Name : DMRC
DG Rating Detail : 2 x 1010KVA
Total Generation Capacity *
Generation Voltage
Base Load

2020 KVA
:
0.415
KV
:
1 KW
:
1.25 KVA
:
Motor Load
355 KW
:
443.75 KVA
:
Startup FLC
2.5 times
:
Transient Load
1109.38 KVA
:
P.f. (Base Load)
0.8
:
P.f. (Transient)
0.2
:
X'd
0.164
:
X"d
0.131
:
* Cumulative kVA of all the alternators connected to feed the load.

T.V.D. %

7.363 %

Loading Step :

(To be Filled)

T.V.D. CALCULATION
DG Rating
DG Voltage
Base Load
Motor Load
Startup FLC
Transient Load
P.f. (Base Load)
P.f. (Transient)
X'd
X"d

:
:
:
:
:
:
:
:
:
:
:
:

2020
0.415
1
1.25
355
443.75
2.5
1109.38
0.8
0.2
0.164
0.131

KVA
KV
KW
KVA
KW
KVA
times
KVA

(To be Inserted)

P.f.*P.f
P.f.*P.f

=
=

0.64
0.04

1-P.f.*P.f.
1-P.f.*P.f.

Base Load

0.00062 p.u.

Transient Load

0.5492 p.u.

1 =

1
. . ( )

1292.8

1 =

1
(1 . . 2 )

969.6

2 =

1
. . ( )

0.36417

2 =

1
(1 . . 2 )

1.78406

0.1475

0.415
6.6
11

YES
NO

+ "
2

1 2 2 + 2 2 + 2 1 2 + 1 2
(1 + 2 )2 + (1 + 2 )2

0.36519

1 2 2 + 2 2 + 2 1 2 + 1 2
(1 + 2 )2 + (1 + 2 )2

1.78228

0.92637

7.363 %

1 2 + (1 + )2

2 + 2

2 + ( + )2

1 2 + 1 2

. . . % = 1 100

T.V.D. %