You are on page 1of 22

YGFC

Fan Coil Units

Ceiling Concealed Type

Vertical Concealed Type

Vertical Exposed Type

Ceiling Exposed Type

Size: 02 ~ 12
Air Flow: 378 ~ 2524m3/h

Content & Nomenclature

YGFC Fan Coil Units


CONTENT

Design 1
Physical Data 2
Cooling Capacity 4
Heating Capacity 12
Dimensions 13
Wiring Diagram 16

NOMENCLATURE
YGFC 04 CC 3 S

S: standard
H: high static pressure

York Fan Coil Unit

Size
02
03
04
06
08
10
12

Model
CC: ceiling concealed
CD: ceiling concealed with
down return plenum
CB: ceiling concealed with
back return plenum
VC: vertical concealed
CE: ceiling exposed
VE: vertical exposed

Coil Row
2: 2 rows cooling coil
3: 3 rows cooling coil
4: 4 rows cooling coil
A: 3 rows cooling coil & 1 row
heating coil ( for 4 pipe system)

Design

YGFC Fan Coil Units

168 models available;


Sized from 378 to 2524 m3/h;
More options to customer: 2 rows, 3 rows, 4 rows, and 3+1 rows coil.
Design and manufacturing flexibilities, more special order for customer;
Complete line accessories, and less leadtime;
Reasonable price.

Features and Benefits


Well designed and precisely manufactured;
New style and advanced structure;
High efficiency, low noise and power consumption;
Safe and reliable;
Easy installation and maintenance.
High Energy Efficiency
High efficiency AL fin cooling coil, 2 rows, 3 rows, 4 rows and 3+1 rows coil are available. Coil provides high rate of heat
transfer with large air flow and low noise fan.
Quiet Operation and Energy Conservation
Units have been optimized to ensure quiet and high efficient operation. Aluminium fan blade can avoid the aging distortion
problem of plastic made fan wheel, and rust problem of steel fan wheel. Water knockout is made of brastil with uniform water
flow and less water pressure drop.
Low Maintenance Cost
Motor uses permanent split capacitor, high precision and quality self-lube ball bearings, low noise and long life. Central axis of
motor has been thermal refined and surface anti-corrosion treated.
High Flexibility and Low Installation Cost
Ceiling concealed (horizontal concealed) coil's fan mounting plate can interchange with flange of the opening. Client can
change the direction of duct connection in field, resulting in quick and simple installation.
Vertical concealed fan coil unit can be mounted under window, client can renovate house freely, and it will be comfortable and
elegant.
Vertical exposed fan coil unit can be placed at any location of a room, beautiful shape matches with furniture, it will be
comfortable and decorative.
Ceiling exposed (horizontal exposed) fan coil unit can be mounted on ceiling directly.
Vertical and ceiling exposed unit can be mounted by removing the enclosure, it is easy to maintain and install.

Physical Data

YGFC Fan Coil Units


2 Rows Standard Type

Item

Model

02

03

04

06

08

10

12

High

378

572

767

1134

1566

1836

2214

Medium

300

470

580

820

1180

1470

1650

Low

240

350

450

630

970

1090

1230

Cooling capacity

Sensible heat (W)

1462

2113

2959

3874

5383

6280

7675

(W) (high speed)

Total heat (W)

1930

2789

3905

5114

7105

8289

10132

Heating capacity (W)

2895

4184

5858

7671

10658

12434

15197

Water flow (kg/h)

351

482

640

895

1228

1447

1754

Water pressure drop (kPa)

8.1

17.6

29

20

28

38

48

Fan

Nominal Capacity

Air Flow (m3/h)

Aluminium centrifugal forward-curved blade

Type
Number

Motor
Piping
Connection

Cooling Coil

Sound level dB(A)

Unit Net Weight (kg)

20

23

51

85

118

150

163

34

34

37

43

45

50

48

High efficiency copper tube aluminium ripple fin coil

Type
Row x stage

2x8

Max. Allowable work pressure (MPa)

1.5
3/4 tube female thread

Water inlet & outlet


Drain
CC

AC220V-1ph-50Hz

Power Supply
Power input (W)

Three speed permanent split capacitor motor

Type
Number

3/4 tube male thread


14.5

16

18.5

22

30

31

36.5

CB/CD

19

21

23

28.4

37

39

45

VE/CE

29

31

35

40

48

50

52

VC

19

21.5

24

29.4

36.5

38.5

40

Note: 1. Airflow is based on 0 Pa external static pressure.


2. Cooling capacity is specified at: 27C DB, 20C WB; 7C inlet chilled water temperature, 5C temperature rise.
3. Heating capacity is specified at: 20C DB; 60C inlet hot water temperature; same water flow and airflow as cooling.
4. Sound level dB(A) is measured in acoustical chamber according to ARI350-1986, cooling and heating capacity is measured according to ARI440-97
standard.

Physical Data (Cont.')

YGFC Fan Coil Units

2 Rows High Static Pressure Type


Item

Model

02

03

04

06

08

10

12

High

459

704

886

1296

1922

2165

2524

Medium

400

500

580

920

1420

1620

1870

Low

360

370

440

650

1100

1210

1360

Cooling capacity

Sensible heat (W)

1624

2370

3037

4016

5848

6563

7797

(W) (high speed)

Total heat (W)

2193

3202

4100

5421

7895

8860

10526

Heating capacity (W)

3289

4803

6150

8132

11842

13289

15789

Water flow (kg/h)

390

561

675

956

1386

1579

1877

Water pressure drop (kPa)

11

20

32

25

35

41

51

Fan

Nominal Capacity

Air Flow (m3/h)

Type
Number

Aluminium centrifugal forward-curved blade


1

Motor

Type
Number

Piping
Connection

Cooling Coil

Sound level dB(A)

1
AC220V-1ph-50Hz

21

47

66

100

150

185

232

38

45

42.5

45

50

53

51

Type

High efficiency copper tube aluminium ripple fin coil

Row x stage

2x8

Max. Allowable work pressure (MPa)

1.5

Water inlet & outlet

3/4 tube female thread

Drain
CC

Three speed permanent split capacitor motor

Power Supply
Power input (W)

Unit Net Weight (kg)

3/4 tube male thread


14.5

16

18.5

22

30

31

36.5

CB/CD

19

21

23

28.4

37

39

45

VE/CE

29

31

35

40

48

50

52

VC

19

21.5

24

29.4

36.5

38.5

40

Note: 1. Airflow is based on 0 Pa external static pressure.


2. Cooling capacity is specified at: 27C DB, 20C WB; 7C inlet chilled water temperature, 5C temperature rise.
3. Heating capacity is specified at: 20C DB; 60C inlet hot water temperature; same water flow and airflow as cooling.
4. Sound level dB(A) is measured in acoustical chamber according to ARI350-1986, cooling and heating capacity is measured according to ARI440-97
standard.

Physical Data (Cont.')

YGFC Fan Coil Units

3 Rows Standard Type


Item

Model

02

03

04

06

08

10

12

High

350

530

710

1050

1450

1700

2050

Medium

280

450

570

800

1150

1450

1600

Low

220

340

430

610

950

1120

1200

Cooling capacity

Sensible heat (W)

1630

2356

3298

4319

6000

7000

8556

(W) (high speed)

Total heat (W)

2200

3180

4452

5830

8100

9450

11550

Heating capacity (W)

3300

4770

6678

8745

12150

14175

17325

Water flow (kg/h)

400

550

730

1020

1400

1650

2000

Water pressure drop (kPa)

5.1

10.3

18

13.2

15.4

22

37

Fan

Nominal Capacity

Air Flow (m3/h)

Type
Number

Aluminium centrifugal forward-curved blade


1

Motor

Type
Number

Piping
Connection

Cooling Coil

Sound level dB(A)

1
AC220V-1ph-50Hz

20

23

51

85

118

150

163

33

33

37

42

44

49

47

Type

High efficiency copper tube aluminium ripple fin coil

Row x stage

3x8

Max. Allowable work pressure (MPa)

1.5

Water inlet & outlet

3/4 tube female thread

Drain
CC

Three speed permanent split capacitor motor

Power Supply
Power input (W)

Unit Net Weight (kg)

3/4 tube male thread


15.5

17

20

23.5

32

33

39

CB/CD

20

22

24.5

30

39

41

47.5

VE/CE

29.5

33

36

41

48.5

51

54

20

22

25

30

37

40

42

VC

Note: 1. Airflow is based on 0 Pa external static pressure.


2. Cooling capacity is specified at: 27C DB, 20C WB; 7C inlet chilled water temperature, 5C temperature rise.
3. Heating capacity is specified at: 20C DB; 60C inlet hot water temperature; same water flow and airflow as cooling.
4. Sound level dB(A) is measured in acoustical chamber according to ARI350-1986, cooling and heating capacity is measured according to ARI440-97
standard.

Physical Data (Cont.')

YGFC Fan Coil Units

3 Rows High Static Pressure Type


Item

Model

02

03

04

06

08

10

12

High

425

652

820

1200

1780

2005

2337

Medium

400

500

580

920

1420

1620

1870

Low

360

370

440

650

1100

1210

1360

Cooling capacity

Sensible heat (W)

1852

2704

3462

4578

6667

7481

8889

(W) (high speed)

Total heat (W)

2500

3650

4674

6180

9000

10100

12000

Heating capacity (W)

3750

5475

7011

9270

13500

15150

18000

Water flow (kg/h)

445

640

770

1090

1580

1800

2140

Water pressure drop (kPa)

6.5

13

20

18

19.2

25

39

Fan

Nominal Capacity

Air Flow (m3/h)

Type
Number

Aluminium centrifugal forward-curved blade


1

Motor

Type
Number

Piping
Connection

Cooling Coil

Sound level dB(A)

1
AC220V-1ph-50Hz

21

47

66

100

150

185

232

37

45

42

45

49

52

50

Type

High efficiency copper tube aluminium ripple fin coil

Row x stage

3x8

Max. Allowable work pressure (MPa)

1.5

Water inlet & outlet

3/4 tube female thread

Drain
CC

Three speed permanent split capacitor motor

Power Supply
Power input (W)

Unit Net Weight (kg)

3/4 tube male thread


15.5

17

20

23.5

32

33

39

CB/CD

20

22

24.5

30

39

41

47.5

VE/CE

29.5

33

36

41

48.5

51

54

20

22

25

30

37

40

42

VC

Note: 1. Airflow is based on 0 Pa external static pressure.


2. Cooling capacity is specified at: 27C DB, 20C WB; 7C inlet chilled water temperature, 5C temperature rise.
3. Heating capacity is specified at: 20C DB; 60C inlet hot water temperature; same water flow and airflow as cooling.
4. Sound level dB(A) is measured in acoustical chamber according to ARI350-1986, cooling and heating capacity is measured according to ARI440-97
standard.

Physical Data (Cont.')

YGFC Fan Coil Units

4 Rows Standard Type


Item

Model

02

03

04

06

08

10

12

High

324

491

657

972

1343

1574

1898

Medium

260

430

550

780

1100

1410

1520

Low

200

310

400

580

900

1080

1130

Cooling capacity

Sensible heat (W)

1933

2816

3593

4705

6778

7956

9852

(W) (high speed)

Total heat (W)

2610

3801

4851

6352

9150

10741

13300

Heating capacity (W)

3915

5702

7277

9528

13725

16112

19950

Water flow (kg/h)

475

657

795

1111

1581

1875

2303

Water pressure drop (kPa)

4.6

16

11

13.5

19.6

34

Fan

Nominal Capacity

Air Flow (m3/h)

Type
Number

Aluminium centrifugal forward-curved blade


1

Motor

Type
Number

Piping
Connection

Cooling Coil

Sound level dB(A)

1
AC220V-1ph-50Hz

20

23

51

85

118

150

163

33

33

36

41

43

48

46

Type

High efficiency copper tube aluminium ripple fin coil

Row x stage

4x8

Max. Allowable work pressure (MPa)

1.5

Water inlet & outlet

3/4 tube female thread

Drain
CC

Three speed permanent split capacitor motor

Power Supply
Power input (W)

Unit Net Weight (kg)

3/4 tube male thread


16

17.5

20.5

24

34

35

41

CB/CD

20.5

22.5

25

30.5

41

43

49.5

VE/CE

31

34.5

38

43

51.5

54

57

21.5

24

26.5

32.5

40

42.5

45

VC

Note: 1. Airflow is based on 0 Pa external static pressure.


2. Cooling capacity is specified at: 27C DB, 20C WB; 7C inlet chilled water temperature, 5C temperature rise.
3. Heating capacity is specified at: 20C DB; 60C inlet hot water temperature; same water flow and airflow as cooling.
4. Sound level dB(A) is measured in acoustical chamber according to ARI350-1986, cooling and heating capacity is measured according to ARI440-97
standard.

Physical Data (Cont.')

YGFC Fan Coil Units

4 Rows High Static Pressure Type


Item

Model

02

03

04

06

08

10

12

High

394

604

759

1111

1648

1857

2164

Medium

380

470

540

880

1380

1540

1770

Low

340

350

420

620

1050

1120

1280

Cooling capacity

Sensible heat (W)

1967

2970

3807

5033

7333

8259

10667

(W) (high speed)

Total heat (W)

2656

4010

5140

6795

9900

11150

14400

Heating capacity (W)

3984

6015

7710

10192.5

14850

16725

21600

Water flow (kg/h)

473

703

847

1198

1738

1987

2568

10

18

16

18

22

37

Nominal Capacity

Air Flow (m3/h)

Fan

Water pressure drop (kPa)


Type
Number

Aluminium centrifugal forward-curved blade


1

Motor

Type
Number

Piping
Connection

Cooling Coil

Sound level dB(A)

1
AC220V-1ph-50Hz

21

47

66

100

150

185

232

36

43

41

43

47

50

48

Type

High efficiency copper tube aluminium ripple fin coil

Row x stage

4x8

Max. Allowable work pressure (MPa)

1.5

Water inlet & outlet

3/4 tube female thread

Drain
CC

Three speed permanent split capacitor motor

Power Supply
Power input (W)

Unit Net Weight (kg)

3/4 tube male thread


16

17.5

20.5

24

34

35

41

CB/CD

20.5

22.5

25

30.5

41

43

49.5

VE/CE

31

34.5

38

43

51.5

54

57

21.5

24

26.5

32.5

40

42.5

45

VC

Note: 1. Airflow is based on 0 Pa external static pressure.


2. Cooling capacity is specified at: 27C DB, 20C WB; 7C inlet chilled water temperature, 5C temperature rise.
3. Heating capacity is specified at: 20C DB; 60C inlet hot water temperature; same water flow and airflow as cooling.
4. Sound level dB(A) is measured in acoustical chamber according to ARI350-1986, cooling and heating capacity is measured according to ARI440-97
standard.

Cooling Capacity -2 Rows Standard Type

YGFC Fan Coil Units


(W)

Model

02

03

04

06

08

10

12

External
Static
Pressure
(Pa)
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50

Air Flow
(m3/h)
378
356
324
272
218
140
378
356
324
272
218
140
572
540
486
432
354
281
572
540
486
432
354
281
767
734
691
640
551
437
767
734
691
640
551
437
1134
1080
1021
927
806
670
1134
1080
1021
927
806
670
1566
1501
1426
1328
1220
1091
1566
1501
1426
1328
1220
1091
1836
1771
1696
1620
1528
1413
1836
1771
1696
1620
1528
1413
2214
2128
2052
1949
1836
1696
2214
2128
2052
1949
1836
1696

Inlet Water
Temp.
(C)

DB25C
WB18C
Total
Sensible
1803
1454
1744
1374
1654
1272
1501
1120
1326
961
1037
730
1669
1379
1615
1292
1532
1197
1390
1053
1228
903
960
686
2606
2101
2522
1986
2378
1829
2227
1662
1994
1445
1751
1233
2413
1994
2335
1868
2202
1720
2062
1562
1846
1357
1621
1158
3648
2942
3561
2804
3443
2648
3299
2462
3033
2198
2667
1878
3378
2791
3297
2638
3188
2490
3055
2314
2808
2065
2469
1764
4777
3852
4649
3660
4504
3465
4268
3185
3947
2860
3560
2507
4423
3655
4304
3443
4171
3258
3952
2994
3655
2688
3297
2355
6637
5352
6482
5104
6298
4845
6055
4518
5775
4185
5424
3820
6145
5079
6002
4802
5832
4556
5606
4247
5347
3932
5022
3587
7743
6244
7589
5976
7407
5698
7221
5389
6990
5065
6689
4711
7170
5925
7027
5622
6858
5358
6686
5065
6472
4759
6194
4424
9464
7632
9256
7288
9071
6978
8815
6578
8525
6178
8155
5743
8763
7242
8570
6856
8399
6562
8162
6183
7894
5804
7551
5393

Note: 1. DB= dry bulb; WB= wet bulb; sensible = sensible heat; total = total heat.
2. Water flow is per Physical Data, air flow is at high speed.
3.

Recommended selection range.

Air Entering Temperature


DB26C
DB27C
WB19C
WB20C
Total
Sensible
Total
Sensible
1938
1468
2084
1489
1876
1389
2017
1410
1779
1289
1912
1301
1614
1136
1735
1149
1426
977
1534
983
1115
739
1199
745
1795
1413
1930
1429
1737
1306
1867
1336
1647
1211
1771
1265
1494
1067
1607
1116
1321
917
1420
960
1033
693
1110
716
2802
2123
3013
2152
2712
2009
2916
2039
2557
1853
2750
1871
2395
1686
2575
1705
2144
1468
2305
1478
1883
1247
2025
1258
2594
2043
2789
2066
2511
1888
2700
1931
2368
1741
2546
1819
2217
1584
2384
1656
1985
1378
2134
1442
1743
1170
1875
1209
3922
2972
4218
3013
3829
2836
4117
2879
3702
2682
3980
2708
3547
2498
3814
2526
3261
2234
3507
2248
2868
1899
3083
1915
3632
2860
3905
2893
3545
2666
3812
2727
3428
2520
3686
2633
3285
2346
3532
2453
3020
2097
3247
2194
2655
1782
2855
1842
5137
3891
5523
3945
4999
3703
5375
3759
4843
3510
5208
3543
4589
3232
4935
3268
4245
2907
4564
2926
3828
2535
4116
2557
4756
3745
5114
3788
4628
3480
4977
3560
4484
3297
4822
3444
4249
3035
4569
3173
3930
2729
4226
2855
3545
2379
3811
2459
7137
5406
7674
5481
6970
5163
7495
5241
6772
4907
7282
4954
6510
4585
7000
4636
6210
4253
6677
4280
5833
3863
6272
3895
6608
5203
7105
5263
6454
4853
6940
4964
6270
4611
6742
4816
6028
4306
6482
4501
5750
3993
6182
4177
5400
3624
5807
3746
8326
6308
8953
6395
8161
6045
8775
6136
7964
5771
8564
5826
7764
5468
8349
5529
7516
5148
8081
5180
7193
4764
7734
4804
7709
6070
8289
6140
7556
5681
8125
5812
7374
5422
7930
5664
7189
5135
7730
5368
6959
4833
7483
5056
6660
4470
7161
4620
10176
7709
10942
7816
9953
7372
10702
7484
9754
7068
10488
7135
9478
6675
10192
6750
9167
6279
9857
6318
8769
5807
9429
5856
9422
7419
10132
7505
9215
6929
9909
7088
9013
6641
9711
6936
8776
6269
9437
6553
8488
5894
9127
6167
8119
5449
8730
5632

DB28C
WB21C
Total
Sensible
2209
1534
2138
1469
2027
1361
1839
1202
1626
1035
1271
785
2084
1468
2017
1410
1912
1301
1735
1157
1534
996
1199
754
3193
2218
3091
2125
2915
1956
2729
1784
2443
1556
2146
1325
3013
2122
2916
2039
2750
1871
2575
1717
2305
1497
2025
1273
4471
3105
4364
3000
4219
2832
4043
2643
3717
2368
3268
2018
4218
2970
4117
2879
3980
2708
3814
2543
3507
2277
3083
1939
5855
4066
5697
3916
5520
3705
5231
3419
4838
3018
4363
2693
5523
3890
5375
3759
5208
3543
4935
3290
4564
2964
4116
2589
8134
5649
7945
5460
7719
5180
7421
4850
7078
4508
6648
4104
7674
5404
7495
5241
7282
4954
7000
4667
6677
4336
6272
3944
9490
6590
9301
6393
9078
6092
8850
5784
8566
5456
8198
5061
8953
6305
8775
6136
8564
5826
8349
5566
8081
5248
7734
4864
11599
8055
11344
7796
11117
7461
10803
7061
10448
6655
9994
6169
10942
7706
10702
7484
10488
7135
10192
6795
9857
6400
9429
5930

Heat transfer correction factor at different fan speed


02
03
04
06
08
Model
Medium Sensible 0.84 0.83 0.84 0.85 0.85
0.90 0.85 0.86 0.88 0.87
speed
Total
Low Sensible 0.64 0.68 0.75 0.71 0.70
0.73 0.72 0.78 0.75 0.74
speed
Total

10
0.85
0.88
0.69
0.73

12
0.87
0.89
0.69
0.73

Cooling Capacity -3 Rows Standard Type

YGFC Fan Coil Units


(W)

Model

02

03

04

06

08

10

12

External
Static
Pressure
(Pa)
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50

Air Flow
(m3/h)
350
330
300
252
202
130
350
330
300
252
202
130
530
500
450
400
328
260
530
500
450
400
328
260
710
680
640
593
510
405
710
680
640
593
510
405
1050
1000
945
858
746
620
1050
1000
945
858
746
620
1450
1390
1320
1230
1130
1010
1450
1390
1320
1230
1130
1010
1700
1640
1570
1500
1415
1308
1700
1640
1570
1500
1415
1308
2050
1970
1900
1805
1700
1570
2050
1970
1900
1805
1700
1570

Inlet Water
Temp.
(C)

DB25C
WB18C
Total
Sensible
2055
1657
1989
1566
1886
1450
1711
1277
1512
1096
1183
833
1903
1573
1841
1473
1746
1364
1584
1200
1400
1030
1095
782
2970
2395
2875
2264
2711
2086
2539
1895
2273
1647
1996
1406
2750
2273
2662
2130
2510
1961
2351
1781
2104
1547
1848
1320
4159
3354
4060
3197
3925
3019
3761
2807
3458
2505
3040
2141
3851
3182
3759
3007
3634
2839
3482
2638
3201
2354
2815
2011
5446
4392
5299
4173
5135
3950
4865
3631
4500
3261
4059
2858
5042
4167
4907
3926
4754
3714
4505
3413
4167
3064
3758
2684
7566
6102
7390
5819
7180
5523
6902
5151
6583
4771
6184
4355
7006
5790
6842
5474
6648
5194
6391
4842
6096
4482
5726
4090
8827
7119
8652
6813
8444
6495
8232
6143
7968
5774
7626
5370
8173
6755
8011
6409
7818
6108
7622
5774
7378
5425
7061
5044
10789
8701
10552
8308
10341
7955
10049
7499
9719
7042
9297
6547
9990
8256
9770
7816
9575
7480
9305
7049
8999
6617
8608
6149

Note: 1. DB= dry bulb; WB= wet bulb; sensible = sensible heat; total = total heat.
2. Water flow is per Physical Data, air flow is at high speed.
3.

Recommended selection range.

Air Entering Temperature


DB26C
DB27C
WB19C
WB20C
Total
Sensible
Total
Sensible
2210
1674
2376
1697
2138
1584
2299
1608
2028
1469
2180
1483
1840
1295
1978
1310
1626
1114
1748
1121
1272
842
1367
849
2046
1611
2200
1630
1980
1489
2129
1523
1877
1380
2019
1442
1703
1217
1832
1272
1506
1046
1619
1094
1177
790
1266
817
3194
2420
3434
2453
3092
2290
3325
2325
2915
2113
3135
2132
2730
1922
2935
1944
2444
1674
2628
1684
2147
1422
2308
1434
2957
2329
3180
2356
2863
2152
3078
2202
2699
1985
2903
2073
2528
1805
2718
1887
2263
1571
2433
1644
1988
1334
2137
1379
4472
3388
4808
3434
4365
3233
4694
3282
4220
3058
4538
3087
4044
2848
4349
2880
3718
2546
3998
2563
3269
2165
3515
2183
4140
3260
4452
3298
4042
3039
4346
3109
3907
2873
4201
3001
3745
2675
4026
2796
3442
2391
3701
2501
3027
2031
3255
2100
5856
4436
6296
4497
5698
4221
6127
4285
5521
4001
5937
4039
5232
3684
5625
3725
4839
3314
5203
3335
4364
2890
4693
2915
5422
4269
5830
4319
5276
3967
5673
4058
5112
3759
5497
3927
4844
3460
5209
3617
4480
3111
4818
3255
4041
2712
4345
2803
8136
6163
8748
6249
7964
5886
8544
5975
7720
5594
8301
5647
7422
5227
7981
5285
7079
4849
7612
4879
6649
4403
7150
4441
7533
5931
8100
6000
7357
5532
7911
5659
7148
5256
7686
5490
6872
4909
7389
5132
6555
4552
7048
4762
6157
4132
6620
4271
9492
7191
10206
7290
9303
6891
10003
6995
9079
6579
9763
6641
8851
6233
9518
6303
8568
5868
9213
5906
8200
5430
8817
5477
8789
6920
9450
7000
8614
6477
9262
6625
8407
6182
9040
6457
8196
5854
8813
6120
7933
5509
8530
5764
7593
5096
8164
5267
11601
8789
12474
8910
11346
8404
12200
8531
11119
8057
11956
8133
10805
7609
11619
7695
10450
7158
11237
7203
9996
6620
10749
6676
10742
8458
11550
8556
10506
7899
11296
8080
10296
7570
11071
7908
10005
7146
10758
7471
9676
6719
10404
7030
9256
6212
9953
6421

DB28C
WB21C
Total
Sensible
2519
1749
2437
1675
2311
1551
2097
1370
1853
1180
1449
895
2376
1673
2299
1608
2180
1483
1978
1319
1748
1135
1367
860
3640
2528
3524
2422
3323
2230
3111
2034
2785
1774
2447
1510
3434
2419
3325
2325
3135
2132
2935
1957
2628
1706
2308
1452
5097
3539
4975
3419
4810
3228
4609
3013
4237
2699
3726
2300
4808
3386
4694
3282
4538
3087
4349
2899
3998
2596
3515
2211
6674
4635
6495
4464
6293
4224
5963
3897
5515
3513
4974
3071
6296
4434
6127
4285
5937
4039
5625
3750
5203
3379
4693
2951
9273
6440
9057
6225
8799
5906
8459
5529
8068
5139
7578
4678
8748
6161
8544
5975
8301
5647
7981
5320
7612
4943
7150
4497
10818
7513
10604
7288
10349
6945
10089
6594
9765
6220
9346
5769
10206
7187
10003
6995
9763
6641
9518
6345
9213
5982
8817
5545
13222
9182
12932
8888
12674
8506
12316
8050
11911
7587
11394
7033
12474
8785
12200
8531
11956
8133
11619
7746
11237
7297
10749
6760

Heat transfer correction factor at different fan speed


02
03
04
06
08
Model
Medium Sensible 0.84 0.83 0.84 0.85 0.85
speed
Total
0.90 0.85 0.86 0.88 0.87
Low Sensible 0.64 0.68 0.75 0.71 0.70
speed Total
0.73 0.72 0.78 0.75 0.74

10
0.85
0.88
0.69
0.73

12
0.87
0.89
0.69
0.73

Cooling Capacity -4 Rows Standard Type

YGFC Fan Coil Units


(W)

Model

02

03

04

06

08

10

12

External
Static
Pressure
(Pa)
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50

Air Flow
(m3/h)
324
306
278
233
187
120
324
306
278
233
187
120
491
463
417
370
304
241
491
463
417
370
304
241
657
630
593
549
472
375
657
630
593
549
472
375
972
926
875
795
691
574
972
926
875
795
691
574
1343
1287
1222
1139
1046
935
1343
1287
1222
1139
1046
935
1574
1519
1454
1389
1310
1211
1574
1519
1454
1389
1310
1211
1898
1824
1759
1671
1574
1454
1898
1824
1759
1671
1574
1454

Inlet Water
Temp.
(C)

DB25C
WB18C
Total
Sensible
2438
1966
2359
1858
2237
1721
2030
1515
1794
1300
1403
988
2257
1866
2184
1748
2071
1618
1879
1424
1661
1221
1299
928
3550
2863
3437
2706
3241
2493
3035
2265
2716
1968
2386
1680
3287
2717
3182
2546
3001
2344
2810
2129
2515
1849
2209
1578
4531
3654
4423
3483
4276
3289
4098
3058
3767
2730
3313
2333
4196
3467
4096
3277
3960
3093
3795
2875
3488
2565
3067
2191
5933
4785
5774
4546
5595
4304
5301
3956
4903
3553
4422
3114
5494
4540
5346
4277
5180
4047
4908
3718
4540
3338
4095
2925
8547
6893
8348
6573
8111
6239
7797
5819
7437
5389
6985
4919
7914
6540
7729
6184
7510
5867
7220
5469
6886
5063
6468
4620
10033
8091
9834
7743
9597
7383
9356
6982
9057
6563
8668
6104
9290
7678
9105
7284
8887
6943
8663
6563
8386
6166
8026
5733
12423
10019
12151
9567
11908
9160
11572
8636
11191
8109
10705
7539
11503
9507
11250
9000
11026
8614
10715
8117
10362
7619
9912
7080

Note: 1. DB= dry bulb; WB= wet bulb; sensible = sensible heat; total = total heat.
2. Water flow is per Physical Data, air flow is at high speed.
3.

Recommended selection range.

Air Entering Temperature


DB26C
DB27C
WB19C
WB20C
Total
Sensible
Total
Sensible
2621
1986
2819
2013
2537
1879
2728
1908
2405
1743
2586
1760
2182
1537
2347
1554
1929
1321
2074
1330
1508
999
1622
1007
2427
1911
2610
1933
2349
1766
2526
1807
2227
1638
2395
1711
2021
1443
2173
1509
1786
1240
1921
1298
1397
937
1502
969
3818
2892
4105
2932
3696
2737
3974
2779
3485
2525
3747
2549
3263
2298
3509
2324
2921
2001
3141
2013
2566
1699
2759
1714
3535
2783
3801
2816
3422
2573
3679
2632
3226
2372
3469
2478
3021
2158
3249
2256
2705
1878
2908
1965
2376
1594
2555
1648
4872
3691
5239
3742
4756
3523
5114
3576
4598
3332
4944
3363
4407
3103
4738
3138
4051
2775
4356
2792
3562
2359
3830
2379
4511
3552
4851
3593
4404
3311
4736
3387
4258
3131
4578
3270
4080
2914
4387
3047
3751
2605
4033
2725
3298
2214
3546
2288
6380
4833
6860
4900
6209
4599
6676
4668
6016
4359
6468
4400
5700
4014
6129
4059
5272
3611
5669
3634
4755
3149
5113
3176
5907
4651
6352
4705
5749
4322
6181
4422
5570
4096
5989
4278
5278
3770
5675
3941
4882
3390
5249
3547
4403
2955
4734
3054
9190
6962
9882
7059
8976
6649
9652
6749
8721
6320
9377
6379
8384
5904
9015
5970
7997
5477
8598
5512
7511
4974
8076
5016
8510
6700
9150
6778
8311
6249
8937
6393
8075
5937
8683
6202
7763
5545
8347
5797
7404
5142
7962
5379
6955
4668
7478
4825
10788
8173
11600
8286
10574
7833
11370
7951
10320
7478
11097
7549
10061
7085
10818
7164
9738
6670
10471
6712
9320
6172
10022
6225
9989
7865
10741
7956
9791
7362
10528
7531
9555
7026
10275
7339
9315
6654
10016
6956
9017
6262
9696
6551
8630
5792
9279
5987
13359
10120
14364
10260
13065
9678
14048
9824
12804
9278
13768
9366
12443
8762
13379
8860
12033
8242
12939
8294
11511
7623
12377
7688
12369
9739
13300
9852
12097
9096
13008
9305
11856
8717
12748
9106
11521
8229
12388
8603
11142
7738
11981
8095
10658
7153
11461
7394

DB28C
WB21C
Total
Sensible
2988
2075
2891
1987
2742
1840
2487
1626
2199
1400
1719
1061
2819
1985
2728
1908
2586
1760
2347
1564
2074
1347
1622
1020
4351
3022
4212
2895
3972
2666
3719
2431
3329
2121
2924
1805
4105
2891
3974
2779
3747
2549
3509
2339
3141
2039
2759
1735
5553
3857
5421
3726
5241
3517
5023
3283
4617
2941
4060
2506
5239
3689
5114
3576
4944
3363
4738
3159
4356
2829
3830
2409
7272
5050
7076
4864
6857
4602
6497
4246
6009
3827
5420
3345
6860
4831
6676
4668
6468
4400
6129
4086
5669
3681
5113
3216
10475
7274
10231
7031
9940
6671
9556
6246
9114
5805
8561
5284
9882
6959
9652
6749
9377
6379
9015
6010
8598
5583
8076
5079
12296
8539
12052
8283
11762
7894
11467
7495
11100
7070
10623
6557
11600
8169
11370
7951
11097
7549
10818
7212
10471
6800
10022
6303
15226
10574
14891
10235
14594
9794
14182
9269
13716
8736
13120
8099
14364
10115
14048
9824
13768
9366
13379
8919
12939
8402
12377
7785

Heat transfer correction factor at different fan speed


02
03
04
06
08
Model
Medium Sensible 0.84 0.83 0.84 0.85 0.85
speed
0.90 0.85 0.86 0.88 0.87
Total
Low Sensible 0.64 0.68 0.75 0.71 0.70
0.73 0.72 0.78 0.75 0.74
speed
Total

10
0.85
0.88
0.69
0.73

12
0.87
0.89
0.69
0.73

10

Cooling Capacity -2 Rows High Static Pressure Type

YGFC Fan Coil Units


(W)

Model

02

03

04

06

08

10

12

External
Static
Pressure
(Pa)
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50

Air Flow
(m3/h)
459
432
410
378
264
173
459
432
410
378
264
173
704
664
619
572
435
346
704
664
619
572
435
346
886
853
814
767
605
486
886
853
814
767
605
486
1296
1231
1177
1134
918
767
1296
1231
1177
1134
918
767
1922
1847
1755
1566
1501
1341
1922
1847
1755
1566
1501
1341
2165
2071
1960
1836
1706
1553
2165
2071
1960
1836
1706
1553
2524
2426
2339
2214
2093
1933
2524
2426
2339
2214
2093
1933

Inlet Water
Temp.
(C)

DB25C
WB18C
Total
Sensible
2048
1652
1980
1559
1924
1480
1838
1372
1503
1089
1188
836
1897
1568
1834
1467
1782
1392
1702
1289
1392
1023
1100
785
2991
2412
2895
2279
2783
2141
2664
1988
2287
1657
2010
1416
2769
2289
2680
2144
2577
2013
2467
1869
2117
1557
1862
1330
3830
3089
3751
2954
3655
2811
3534
2637
3096
2243
2740
1930
3546
2931
3473
2778
3384
2644
3272
2479
2866
2108
2537
1812
5064
4084
4921
3875
4799
3692
4700
3508
4177
3027
3778
2661
4689
3875
4556
3645
4444
3472
4352
3297
3868
2844
3498
2499
7374
5947
7211
5678
7009
5391
6577
4908
6424
4655
6033
4248
6828
5643
6677
5342
6490
5070
6090
4614
5948
4374
5586
3990
8276
6674
8073
6357
7829
6022
7548
5633
7246
5250
6875
4841
7663
6333
7475
5980
7249
5663
6989
5294
6709
4933
6365
4547
9833
7929
9617
7572
9424
7250
9139
6820
8857
6418
8473
5967
9104
7524
8905
7124
8726
6817
8462
6411
8201
6030
7846
5604

Note: 1. DB= dry bulb; WB= wet bulb; sensible = sensible heat; total = total heat.
2. Water flow is per Physical Data, air flow is at high speed.
3.

11

Recommended selection range.

Air Entering Temperature


DB26C
DB27C
WB19C
WB20C
Total
Sensible
Total
Sensible
2203
1669
2368
1692
2129
1577
2290
1601
2069
1499
2225
1514
1976
1392
2125
1407
1616
1107
1738
1114
1277
846
1373
853
2039
1606
2193
1624
1972
1482
2120
1516
1916
1409
2060
1472
1830
1307
1968
1367
1496
1039
1609
1087
1182
794
1271
820
3216
2436
3458
2470
3113
2306
3347
2341
2992
2168
3217
2189
2865
2017
3080
2040
2459
1684
2644
1695
2162
1432
2325
1444
2978
2345
3202
2372
2882
2167
3099
2217
2771
2037
2979
2128
2653
1895
2852
1981
2277
1581
2448
1654
2002
1343
2152
1389
4118
3120
4428
3163
4033
2988
4337
3033
3930
2848
4225
2874
3800
2676
4086
2706
3329
2280
3579
2294
2946
1951
3168
1968
3813
3002
4100
3037
3735
2808
4016
2872
3639
2675
3912
2795
3519
2513
3783
2627
3082
2140
3314
2239
2728
1831
2933
1893
5445
4125
5855
4182
5291
3919
5690
3979
5160
3739
5549
3775
5054
3559
5434
3599
4492
3077
4830
3096
4063
2690
4368
2713
5042
3970
5421
4016
4899
3684
5268
3768
4778
3513
5138
3670
4680
3343
5032
3494
4159
2888
4472
3022
3762
2525
4045
2610
7929
6007
8526
6090
7754
5744
8338
5830
7536
5461
8104
5513
7072
4980
7604
5036
6907
4731
7427
4761
6487
4296
6975
4332
7342
5781
7895
5848
7180
5398
7720
5522
6978
5131
7503
5360
6548
4677
7041
4890
6396
4441
6877
4647
6006
4031
6458
4167
8899
6741
9568
6835
8681
6430
9334
6528
8418
6100
9051
6157
8116
5715
8727
5779
7791
5336
8377
5370
7392
4895
7949
4937
8239
6488
8860
6563
8038
6044
8643
6182
7794
5731
8381
5986
7515
5368
8080
5611
7214
5010
7757
5241
6845
4594
7360
4748
10573
8010
11368
8120
10341
7660
11119
7776
10134
7343
10896
7413
9827
6921
10567
6998
9524
6523
10241
6565
9111
6034
9797
6085
9789
7708
10526
7797
9575
7199
10296
7365
9383
6899
10089
7207
9099
6499
9784
6795
8818
6124
9482
6407
8436
5662
9071
5852

DB28C
WB21C
Total
Sensible
2511
1743
2427
1668
2359
1583
2253
1472
1842
1173
1456
898
2368
1668
2290
1601
2225
1514
2125
1417
1738
1128
1373
864
3665
2545
3548
2438
3410
2289
3265
2134
2802
1785
2464
1521
3458
2435
3347
2341
3217
2189
3080
2054
2644
1717
2325
1462
4694
3260
4597
3159
4479
3006
4331
2831
3794
2417
3358
2073
4428
3118
4337
3033
4225
2874
4086
2724
3579
2324
3168
1992
6206
4310
6031
4145
5882
3948
5760
3765
5120
3261
4631
2858
5855
4123
5690
3979
5549
3775
5434
3623
4830
3136
4368
2747
9038
6276
8838
6074
8590
5765
8061
5268
7873
5015
7394
4564
8526
6004
8338
5830
8104
5513
7604
5070
7427
4823
6975
4387
10143
7043
9895
6800
9594
6439
9250
6046
8880
5656
8426
5201
9568
6738
9334
6528
9051
6157
8727
5818
8377
5440
7949
4999
12051
8368
11786
8101
11550
7752
11201
7321
10855
6914
10385
6410
11368
8006
11119
7776
10896
7413
10567
7045
10241
6650
9797
6161

Heat transfer correction factor at different fan speed


02
03
04
06
08
Model
Medium Sensible 0.84 0.83 0.84 0.85 0.85
0.90 0.85 0.86 0.88 0.87
speed
Total
Low Sensible 0.64 0.68 0.75 0.71 0.70
0.73 0.72 0.78 0.75 0.74
speed
Total

10
0.85
0.88
0.69
0.73

12
0.87
0.89
0.69
0.73

Cooling Capacity -3 Rows High Static Pressure Type

YGFC Fan Coil Units


(W)

Model

02

03

04

06

08

10

12

External
Static
Pressure
(Pa)
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50

Air Flow
(m3/h)
425
400
380
350
244
160
425
400
380
350
244
160
652
615
573
530
403
320
652
615
573
530
403
320
820
790
754
710
560
450
820
790
754
710
560
450
1200
1140
1090
1050
850
710
1200
1140
1090
1050
850
710
1780
1710
1625
1450
1390
1242
1780
1710
1625
1450
1390
1242
2005
1918
1815
1700
1580
1438
2005
1918
1815
1700
1580
1438
2337
2246
2166
2050
1938
1790
2337
2246
2166
2050
1938
1790

Inlet Water
Temp.
(C)

DB25C
WB18C
Total
Sensible
2335
1883
2258
1778
2194
1688
2095
1564
1713
1242
1354
953
2162
1787
2090
1672
2031
1587
1940
1470
1586
1167
1254
895
3409
2750
3300
2598
3172
2440
3037
2267
2607
1889
2292
1614
3157
2609
3056
2445
2937
2295
2812
2130
2414
1775
2122
1516
4366
3521
4276
3367
4166
3205
4029
3007
3529
2557
3124
2200
4043
3341
3959
3167
3858
3014
3730
2826
3268
2403
2892
2066
5773
4655
5610
4417
5471
4209
5358
3999
4762
3451
4307
3033
5345
4417
5194
4155
5066
3958
4961
3759
4409
3242
3988
2849
8407
6780
8221
6473
7990
6146
7498
5595
7323
5307
6877
4843
7784
6433
7612
6089
7398
5780
6943
5259
6781
4986
6368
4548
9434
7608
9204
7247
8925
6865
8604
6421
8260
5986
7837
5519
8735
7219
8522
6818
8263
6456
7967
6036
7648
5624
7257
5183
11209
9040
10963
8633
10744
8264
10419
7775
10097
7317
9659
6802
10379
8578
10151
8121
9948
7772
9647
7308
9349
6874
8944
3689

Note: 1. DB= dry bulb; WB= wet bulb; sensible = sensible heat; total = total heat.
2. Water flow is per Physical Data, air flow is at high speed.
3.

Recommended selection range.

Air Entering Temperature


DB26C
DB27C
WB19C
WB20C
Total
Sensible
Total
Sensible
2511
1902
2700
1929
2427
1798
2610
1825
2359
1709
2537
1726
2253
1587
2423
1604
1842
1262
1981
1270
1456
964
1565
972
2325
1831
2500
1852
2248
1690
2417
1729
2184
1606
2349
1678
2086
1490
2243
1558
1706
1185
1834
1239
1348
905
1449
935
3666
2777
3942
2816
3548
2628
3816
2668
3411
2472
3668
2495
3266
2300
3512
2326
2803
1920
3014
1932
2464
1632
2650
1646
3395
2673
3650
2704
3286
2470
3533
2527
3158
2322
3396
2426
3024
2160
3252
2258
2595
1802
2791
1886
2282
1531
2454
1583
4695
3556
5048
3606
4598
3406
4944
3457
4480
3246
4817
3277
4332
3051
4658
3085
3795
2599
4080
2616
3359
2224
3612
2243
4347
3423
4674
3462
4257
3201
4578
3275
4148
3050
4460
3186
4011
2865
4313
2995
3514
2440
3778
2553
3110
2087
3344
2157
6207
4702
6674
4767
6032
4468
6486
4536
5883
4263
6326
4303
5762
4057
6195
4103
5121
3507
5506
3530
4631
3067
4980
3093
5747
4526
6180
4578
5585
4199
6006
4296
5447
4005
5857
4184
5335
3811
5736
3984
4741
3293
5098
3445
4288
2878
4611
2975
9040
6848
9720
6943
8839
6548
9505
6647
8592
6226
9238
6285
8062
5678
8669
5741
7874
5393
8467
5428
7395
4897
7952
4939
8370
6591
9000
6667
8185
6154
8801
6295
7955
5849
8554
6110
7465
5332
8027
5574
7291
5063
7840
5297
6847
4595
7363
4750
0144
7685
10908
7791
9896
7331
10641
7441
9596
6954
10319
7019
9252
6516
9948
6588
8882
6083
9550
6122
8427
5581
9061
5628
9393
7396
10100
7481
9163
6890
9853
7048
8885
6533
9554
6824
8567
6119
9212
6397
8224
5711
8843
5975
7803
5237
8390
5413
12053
9131
12960
9257
11789
8732
12676
8864
11552
8371
12422
8450
11203
7889
12046
7978
10857
7436
11674
7484
10386
6878
11168
6937
11160
8787
12000
8889
10915
8207
11737
8396
10697
7865
11502
8216
10373
7409
11154
7746
10053
6981
10810
7304
9617
6454
10341
6672

DB28C
WB21C
Total
Sensible
2862
1988
2767
1902
2689
1805
2568
1679
2100
1337
1659
1024
2700
1901
2610
1825
2537
1726
2423
1615
1981
1286
1565
985
4179
2902
4044
2780
3888
2609
3722
2433
3195
2035
2809
1734
3942
2776
3816
2668
3668
2495
3512
2341
3014
1957
2650
1667
5351
3716
5241
3602
5106
3427
4938
3227
4325
2755
3828
2363
5048
3555
4944
3457
4817
3277
4658
3105
4080
2650
3612
2271
7075
4913
6875
4725
6705
4500
6567
4292
5836
3718
5279
3259
6674
4700
6486
4536
6326
4303
6195
4130
5506
3575
4980
3132
10303
7155
10075
6924
9793
6572
9189
6006
8975
5717
8429
5203
9720
6845
9505
6647
9238
6285
8669
5779
8467
5498
7952
5001
11562
8030
11280
7752
10938
7341
10545
6892
10123
6448
9605
5929
10908
7682
10641
7441
10319
7019
9948
6632
9550
6201
9061
5699
13738
9540
13436
9235
13167
8837
12769
8346
12375
7882
11838
7308
12960
9127
12676
8864
12422
8450
12046
8031
11674
7581
11168
7024

Heat transfer correction factor at different fan speed


02
03
04
06
08
Model
Medium Sensible 0.84 0.83 0.84 0.85 0.85
0.90 0.85 0.86 0.88 0.87
speed
Total
Low Sensible 0.64 0.68 0.75 0.71 0.70
0.73 0.72 0.78 0.75 0.74
speed
Total

10
0.85
0.88
0.69
0.73

12
0.87
0.89
0.69
0.73

12

Cooling Capacity -4 Rows High Static Pressure Type

YGFC Fan Coil Units


(W)

Model

02

03

04

06

08

10

12

External
Static
Pressure
(Pa)
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50
0
10
20
30
40
50

Air Flow
(m3/h)
394
370
352
324
226
148
394
370
352
324
226
148
604
569
531
491
373
296
604
569
531
491
373
296
759
732
698
657
519
417
759
732
698
657
519
417
1111
1056
1009
972
787
657
1111
1056
1009
972
787
657
1648
1583
1505
1343
1287
1150
1648
1583
1505
1343
1287
1150
1857
1776
1681
1574
1463
1332
1857
1776
1681
1574
1463
1332
2164
2080
2006
1898
1795
1658
2164
2080
2006
1898
1795
1658

Inlet Water
Temp.
(C)

DB25C
WB18C
Total
Sensible
2481
2001
2398
1889
2331
1793
2226
1661
1820
1319
1438
1013
2297
1898
2221
1777
2158
1686
2061
1562
1685
1239
1332
951
3746
3021
3626
2855
3485
2681
3337
2490
2864
2075
2518
1773
3468
2866
3357
2686
3227
2521
3090
2341
2652
1950
2331
1665
4801
3872
4702
3703
4582
3524
4430
3306
3881
2812
3435
2419
4446
3674
4354
3483
4242
3314
4102
3108
3593
2642
3181
2272
6347
5119
6168
4857
6016
4627
5891
4397
5236
3794
4736
3335
5877
4857
5711
4569
5570
4352
5455
4133
4848
3565
4385
3132
9248
7458
9043
7120
8789
6761
8248
6155
8056
5837
7565
5327
8563
7076
8373
6698
8138
6358
7637
5785
7459
5484
7005
5003
10415
8399
10160
8000
9852
7579
9499
7089
9119
6608
8652
6093
9644
7970
9408
7526
9123
7127
8795
6663
8443
6208
8011
5722
13451
10848
13156
10359
12893
9917
12503
9330
12117
8780
11591
8163
12455
10293
12182
9745
11938
9326
11576
8770
11219
8249
10733
7666

Note: 1. DB= dry bulb; WB= wet bulb; sensible = sensible heat; total = total heat.
2. Water flow is per Physical Data, air flow is at high speed.
3.

13

Recommended selection range.

Air Entering Temperature


DB26C
DB27C
WB19C
WB20C
Total
Sensible
Total
Sensible
2668
2021
2868
2049
2579
1910
2773
1939
2506
1816
2695
1833
2394
1686
2574
1705
1957
1341
2105
1349
1547
1024
1663
1033
2470
1945
2656
1967
2388
1795
2568
1837
2321
1706
2495
1782
2216
1583
2383
1655
1812
1259
1949
1317
1432
961
1540
993
4028
3051
4331
3093
3898
2888
4192
2931
3748
2716
4030
2741
3588
2527
3858
2555
3079
2109
3311
2123
2708
1793
2911
1808
3729
2936
4010
2970
3610
2714
3881
2776
3470
2551
3731
2665
3322
2373
3572
2481
2851
1980
3066
2072
2507
1683
2696
1739
5163
3911
5551
3695
5056
3745
5437
3802
4926
3570
5297
3604
4764
3355
5122
3392
4173
2858
4487
2876
3694
2446
3972
2467
4780
3764
5140
3807
4682
3520
5034
3601
4562
3354
4905
3503
4411
3151
4743
3294
3864
2683
4155
2807
3420
2295
3677
2373
6825
5170
7339
5242
6632
4913
7132
4987
6468
4687
6955
4731
6335
4461
6812
4511
5630
3856
6054
3881
5092
3372
5476
3401
6319
4976
6795
5033
6141
4617
6603
4723
5989
4404
6440
4600
5866
4190
6307
4380
5213
3620
5606
3788
4715
3165
5070
3271
9944
7533
10692
7637
9723
7203
10455
7311
9451
6848
10162
6913
8869
6245
9536
6315
8662
5933
9314
5970
8134
5387
8747
5433
9207
7250
9900
7333
9003
6769
9681
6925
8751
6434
9409
6721
8212
5865
8830
6132
8020
5570
8624
5827
7532
5055
8099
5225
11199
8484
12042
8601
10925
8093
11748
8215
10594
7677
11391
7749
10214
7193
10983
7273
9805
6716
10543
6758
9303
6161
10003
6213
10370
8165
11150
8259
10116
7606
10877
7781
9809
7213
10547
7534
9457
6755
10169
7062
9079
6305
9762
6596
8614
5781
9262
5976
14463
10957
15552
11109
14146
10479
15211
10637
13863
10046
14906
10140
13444
9467
14456
9573
13029
8924
14009
8980
12464
8254
13402
8324
13392
10545
14400
10667
13098
9848
14084
10075
12836
9438
13802
9859
12448
8891
13385
9295
12064
8378
12972
8765
11541
7745
12409
8006

DB28C
WB21C
Total
Sensible
3041
2112
2939
2020
2857
1917
2728
1783
2231
1421
1763
1088
2868
2020
2773
1939
2695
1833
2574
1716
2105
1367
1663
1046
4591
3188
4443
3054
4271
2867
4089
2673
3510
2236
3086
1905
4331
3050
4192
2931
4030
2741
3858
2572
3311
2150
2911
1831
5884
4086
5763
3961
5615
3769
5430
3549
4756
3030
4210
2599
5551
3909
5437
3802
5297
3604
5122
3415
4487
2914
3972
2498
7779
5402
7559
5195
7373
4948
7220
4719
6417
4087
5804
3583
7339
5168
7132
4987
6955
4731
6812
4541
6054
3931
5476
3444
11334
7871
11083
7617
10772
7229
10108
6607
9873
6288
9272
5723
10692
7530
10455
7311
10162
6913
9536
6357
9314
6048
8747
5501
12765
8864
12452
8558
12075
8104
11642
7609
11176
7118
10604
6545
12042
8480
11748
8215
11391
7749
10983
7322
10543
6846
10003
6291
16485
11448
16124
11082
15801
10605
15323
10015
14850
9459
14206
8769
15552
10952
15211
10673
14906
10140
14456
9637
14009
9097
13402
8429

Heat transfer correction factor at different fan speed


02
03
04
06
08
Model
Medium Sensible 0.84 0.83 0.84 0.85 0.85
0.90 0.85 0.86 0.88 0.87
speed
Total
Low Sensible 0.64 0.68 0.75 0.71 0.70
0.73 0.72 0.78 0.75 0.74
speed Total

10
0.85
0.88
0.69
0.73

12
0.87
0.89
0.69
0.73

Heating Capacity

YGFC Fan Coil Units

2 Rows Heating Capacity (2 pipes system)


External Inlet
static
Water
Pressure Temp.
(Pa)
(C)
0
10
20
40
30
40
50
0
10
20
50
30
40
50
0
10
20
60
30
40
50

(W)

Air Entering Temperature 20C

02S
1434
1387
1316
1194
1054
825
2159
2090
1982
1798
1588
1243
2895
2801
2657
2410
2129
1666

02H
1629
1577
1495
1357
1198
937
2454
2375
2252
2043
1805
1412
3289
3183
3019
2739
2419
1893

03S
2072
2005
1902
1726
1524
1192
3121
3021
2865
2599
2295
1796
4184
2789
3840
3484
3077
2408

03H
2379
2302
2183
1981
1749
1369
3583
3467
3288
2983
2635
2062
4803
4648
4407
3999
3532
2763

04S
2901
2808
2663
2416
2134
1669
4370
4229
4010
3639
3214
2514
5858
5669
5376
4878
4308
3371

04H
3046
2948
2795
2536
2240
1753
4588
4440
4210
3820
3374
2640
6150
5951
5644
5121
4523
3539

06S
3799
3677
3487
3164
2794
2186
5723
5538
5252
4765
4208
3293
7671
7423
7040
6388
5641
4414

06H
4028
3897
3696
3354
2962
2317
6066
5870
5567
5051
4461
3490
8132
7869
7462
6771
5980
4679

08S
5279
5108
4844
4396
3882
3037
7951
7694
7296
6621
5847
4575
10658
10314
9781
8875
7838
6133

08H
5865
5676
5383
4884
4313
3375
8834
8549
8107
7356
6497
5083
11842
11460
10868
9861
8709
6814

10S
6159
5960
5652
5128
4529
3544
9276
8976
8513
7724
6822
5337
12434
12033
11411
10354
9144
7155

10H
6582
6370
6041
5481
4841
3787
9914
9594
9098
8255
7291
5704
13289
12860
12196
11066
9773
7647

12S
7527
7284
6908
6268
5536
4331
11337
10971
10404
9441
8337
6523
15197
14706
13947
12655
11176
8745

12H
7821
7568
7177
6512
5751
4500
11779
11398
10810
9808
8662
6778
15789
15279
14490
13148
11612
9085

Note: Water flow and airflow are per Physical Data.

3 Rows Heating Capacity (2 pipes system)


External Inlet
static
Water
Pressure Temp.
(Pa)
(C)
0
10
20
40
30
40
50
0
10
20
50
30
40
50
0
10
20
60
30
40
50

(W)

Air Entering Temperature 20C


02S
1634
1582
1500
1361
1202
940
2462
2382
2259
2050
1810
1417
3300
3193
3082
2748
2427
1899

02H
1857
1797
1705
1547
1366
1069
2798
2707
2567
2329
2057
1610
3750
3629
3441
3123
2758
2158

03S
2363
2286
2168
1967
1737
1359
3558
3443
3266
2963
2617
2048
4770
4616
4377
3972
3508
2745

03H
2712
2624
2489
2258
1994
1560
4084
3952
3748
3401
3004
2350
5475
5298
5024
4559
4026
3150

04S
3308
3201
3035
2754
2432
1903
4982
4821
4572
4148
3664
2867
6678
6462
6128
5561
4911
3843

04H
3473
3360
3187
2892
2554
1998
5230
5061
4800
4355
3846
3009
7011
6785
6434
5838
5156
4034

06S
4331
4191
3975
3607
3185
2492
6524
6313
5987
5432
4798
3754
8745
8463
8025
7282
6431
5032

06H
4591
4443
4214
3823
3377
2642
6915
6692
6346
5758
5086
3979
9270
8971
8507
7719
6817
5334

08S
6018
5824
5523
5011
4426
3463
9064
8771
8318
7548
6666
5215
12150
11758
11150
10117
8935
6991

08H
6687
6471
6136
5568
4917
3847
10071
9746
9242
8386
7406
5795
13500
13064
12389
11241
9928
7768

10S
7021
6794
6443
5846
5163
4040
10575
10233
9704
8805
7777
6085
14175
13717
13008
11804
10424
8156

10H
7504
7261
6886
6248
5518
4318
11302
10937
10372
9411
8311
6503
15150
14661
13903
12615
11141
8717

12S
8581
8304
7875
7145
6311
4938
12924
12507
11861
10762
9505
7437
17325
16765
15899
14427
12741
9969

12H
8915
8627
8182
7424
6556
5130
13428
12994
12323
11181
9875
7726
18000
17419
16519
14989
13237
10357

Note: Water flow and airflow are per Physical Data.

14

Heating Capacity (Cont.')

YGFC Fan Coil Units

4 Rows Heating Capacity (2 pipes system)


External Inlet
static
Water
Pressure Temp.
02S
02H
03S
03H
(Pa)
(C)
1939
1973
2824
2979
0
1876
1910
2733
2883
10
1780
1811
2592
2734
20
40
1615
1643
2352
2481
30
1426
1451
2077
2191
40
1116
1135
1625
1714
50
2921
2972
4253
4487
0
2826
2876
4116
4342
10
2680
2727
3903
4418
20
50
2432
2475
3542
3736
30
2148
2186
3128
3300
40
1681
1710
2447
2582
50
3915
3984
5702
6015
0
3789
3855
5517
5821
10
3593
3656
5232
5520
20
60
3260
3317
4748
5009
30
2879
2930
4193
4423
40
2253
2292
3281
3461
50
Note: Water flow and airflow are per Physical Data.

(W)

Air Entering Temperature 20C


04S
3604
3488
3307
3001
2650
2074
5428
5253
4982
4520
3992
3123
7277
7041
6678
6059
5351
4187

04H
3819
3695
3504
3180
2808
2197
5752
5566
5278
4789
4230
3310
7710
7461
7075
6420
5670
4436

06S
4719
4567
4331
3930
3471
2715
7108
6878
6523
5919
5227
4090
9528
9220
8744
7934
7007
5482

06H
5048
4885
4633
4204
3713
2905
7604
7358
6978
6332
5592
4375
10193
9863
9354
8487
7496
5865

80S
6789
6578
6239
5661
4999
3912
10239
9908
9396
8526
7530
5891
13725
13282
12595
11429
10093
7897

80H
7355
7118
6750
6125
5409
4232
11078
10720
10166
9225
8147
6374
14850
14370
13628
12366
10921
8545

10S
7980
7722
7323
6645
5869
4592
12019
11631
11030
10008
8839
6916
16112
15591
14786
13416
11848
9271

10H
8284
8016
7602
6898
6092
4767
12477
12074
11450
10389
9175
7179
16725
16185
15349
13927
12300
9624

12S
9881
9562
9068
8228
7267
5686
14883
14402
13658
12393
10945
8564
19950
19306
18308
16612
14671
11479

1 Row Heating Capacity (4 pipes system)


External Inlet
static
Water
Pressure Temp.
02S
02H
03S
03H
(Pa)
(C)
926
1053
1339
1537
0
896
1019
1296
1487
10
850
966
1229
1410
20
40
771
876
1115
1280
30
681
774
985
1130
40
533
606
770
884
50
1395
1585
2016
2314
0
1350
1534
1951
2240
10
1280
1455
1850
2124
20
50
1162
1320
1679
1927
30
1026
1166
1483
1702
40
803
912
1160
1332
50
1870
2125
2703
3103
0
1810
2056
2616
3002
10
1716
1950
2481
2847
20
60
1557
1769
2251
2583
30
1375
1563
1988
2282
40
1076
1223
1555
1785
50
Note: Water flow and airflow are per Physical Data.

12H
10698
10353
9818
8909
7868
6156
16114
15593
14787
13418
11850
9272
21600
20902
19822
17986
15885
12429

(W)

Air Entering Temperature 20C


04S
1874
1814
1720
1561
1378
1078
2823
2732
2591
2351
2076
1624
3784
3662
3473
3151
2783
2177

04H
1968
1904
1806
1639
1447
1132
2964
2868
2720
2468
2180
1705
3973
3845
3646
3308
2922
2286

06S
2454
2375
2252
2044
1805
1412
3697
3577
3393
3078
2719
2127
4956
4795
4548
4126
3644
2851

06H
2602
2518
2388
2167
1913
1497
3919
3792
3596
3263
2882
2255
5253
5083
4821
4374
3863
3023

08S
3410
3300
3129
2840
2508
1962
5136
4970
4713
4277
3777
2955
6885
6663
6318
5733
5063
3962

08H
3789
3667
3477
3155
2786
2180
5707
5523
5237
4752
4197
3284
7650
7403
7020
6370
5656
4402

10S
3978
3850
3651
3313
2926
2289
5592
5799
5499
4990
4407
3448
8033
7773
7371
6689
5907
4622

10H
4252
4115
3902
3541
3127
2447
6404
6198
5877
5333
4710
3685
8585
8308
7878
7149
6313
4940

12S
4863
4706
4462
4049
3576
2798
7324
7087
6721
6099
5386
4214
9818
9500
9010
8175
7220
5649

12H
5052
4889
4636
4207
3715
2907
7609
7363
6983
6336
5596
4378
10200
9871
9361
8494
7501
5869

Heat Transfer Correction Factor of Different Fan Speed


Model

02S

02H

03S

03H

04S

04H

06S

06H

08S

08H

10S

10H

12S

12H

Medium speed

0.90

0.94

0.85

0.85

0.86

0.87

0.88

0.88

0.87

0.86

0.87

0.88

0.88

0.89

Low speed

0.72

0.85

0.73

0.76

0.76

0.76

0.75

0.76

0.72

0.74

0.72

0.74

0.72

0.74

15

Dimensions

YGFC Fan Coil Units

Ceiling Concealed Type

Water outlet G3/4


Water Inlet G3/4
Drain Connection
R3/4
Model

C*

YGFC-02-CC-2(3,4)-S(H)

520

590

730

830

YGFC-03-CC-2(3,4)-S(H)

620

690

830

930

YGFC-04-CC-2(3,4)-S(H)

720

790

930

1030

YGFC-06-CC-2(3,4)-S(H)

940

1010

1150

1250

YGFC-08-CC-2(3,4)-S(H)

1240

1310

1450

1550

YGFC-10-CC-2(3,4)-S(H)

1340

1410

1550

1650

YGFC-12-CC-2(3,4)-S(H)

1540

1610

1750

1850

Note:1. Right hand unit shown, left hand unit opposite.


2. The plenum connection (down plenum or back plenum) can be changed in according to field installation.
3. C* is the dimension for extended drain pan. (option)

Ceiling Concealed Type with Down Return Plenum

Water outlet G3/4


Water Inlet G3/4
Drain Connection
R3/4
Model

C*

YGFC-02-CD-2(3,4)-S(H)

520

590

730

830

508

YGFC-03-CD-2(3,4)-S(H)

620

690

830

930

608

YGFC-04-CD-2(3,4)-S(H)

720

790

930

1030

708

YGFC-06-CD-2(3,4)-S(H)

940

1010

1150

1250

928

YGFC-08-CD-2(3,4)-S(H)

1240

1310

1450

1550

1228

YGFC-10-CD-2(3,4)-S(H)

1340

1410

1550

1650

1328

YGFC-12-CD-2(3,4)-S(H)

1540

1610

1750

1850

1528

Note:1. Right hand unit shown, left hand unit opposite.


2. The plenum connection (down plenum or back plenum) can be changed in according to field installation.
3. C* is the dimension for extended drain pan. (Option)
4. The dimension in () refer to plenum with filter.

16

Dimensions (Cont.')

YGFC Fan Coil Units

Ceiling Concealed with Back Return Plenum

Water outlet G3/4


Water Inlet G3/4
Drain Connection
R3/4
Model

C*

YGFC-02-CB-2(3,4)-S(H)

520

590

730

830

508

YGFC-03-CB-2(3,4)-S(H)

620

690

830

930

608

YGFC-04-CB-2(3,4)-S(H)

720

790

930

1030

708

YGFC-06-CB-2(3,4)-S(H)

940

1010

1150

1250

928

YGFC-08-CB-2(3,4)-S(H)

1240

1310

1450

1550

1228

YGFC-10-CB-2(3,4)-S(H)

1340

1410

1550

1650

1328

1850

1528

YGFC-12-CB-2(3,4)-S(H)
1540
1610
1750
Note:1. Right hand unit shown, left hand unit opposite.
2. The plenum connection (down plenum or back plenum) can be changed in according to field installation.
3. C* is the dimension for extended drain pan. (Option)
4. The dimension in () refers to plenum with filter.

Ceiling, Vertical Exposed Type


Water outlet G3/4

Water
Inlet G3/4

17

Drain Connection R3/4

Model

YGFC-02-VE(CE)-2(3, 4)

905

727

624

847

YGFC-03-VE(CE)-2(3, 4)

1026

848

724

968

YGFC-04-VE(CE)-2(3, 4)

1147

969

824

1089

YGFC-06-VE(CE)-2(3, 4)

1388

1210

1044

1330

YGFC-08-VE(CE)-2(3, 4)

1631

1451

1344

1571

YGFC-10-VE(CE)-2(3, 4)

1752

1572

1444

1692

YGFC-12-VE(CE)-2(3, 4)

1993

1815

1644

1935

Dimensions (Cont.')

YGFC Fan Coil Units

Vertical Concealed Type


Water outlet G3/4
Water Inlet G3/4

Drain Connection R3/4

Model

YGFC-02-VC-2(3, 4)

594

655

YGFC-03-VC-2(3, 4)

694

755

YGFC-04-VC-2(3, 4)

794

855

YGFC-06-VC-2(3, 4)

1014

1075

YGFC-08-VC-2(3, 4)

1314

1375

YGFC-10-VC-2(3, 4)

1414

1475

YGFC-12-VC-2(3, 4)

1614

1675

18

Wiring Diagram

YGFC Fan Coil Units


CC/CB/CD/CE/VE/VC Wiring

Install Connection

Unit junction Box

3 Speed Switch
High Speed

Red

Medium Speed

Blue

Low Speed

Black

MOTOR

Yellow
Power
Line

Neutnal
Line

Red
Blue

MOTOR

Black

Ground
Yellow

Warning: Connect lines correctly, otherwise, it will cause motor damage.


Note: 1. Multiple fan coil units can not be controlled by one switch.
2. Power line and neutral line cant be connected wrong.

19

*Subject to change without notice.

YORK INTERNATIONAL
York International (Northern Asia) Ltd.

Unit 1008, 10/F., Tower  , World Trade Square, 123 Hoi Bun Road, Kwun Tong, Kowloon, Hong Kong.

FORM NO.: C120.YGFC(GZF)(1200)


Tel: (852)23319286

Fax: (852)23319840

You might also like