You are on page 1of 42

CSC-211 Numerical Backup Protection

Equipment
Users Manual
CAUTION
1) This manual applies only to CSC-211.
2) Please read the manual and the specification of the installation,
adjustment, testing, operation and maintenance carefully.
3) To prevent damage to equipment, dont plug-hot-plug any unit of the
equipment and touch the chips and components in printed circuit board.
4) Please use the eligible testing equipments and devices to test and detect
the CSC-211 protection equipment.
5) If any abnormity occurred in the equipment or unusual maintenance is
needed, please promptly contact with the agents or our service hotline.
6) The operation password is: 8888.
WARNING
1) During operation of electrical equipment, certain parts of this equipment
are under high voltage. Improper behavior could result in severe personal
injury or significant equipment damage.
2) Only qualified personnel should work on this equipment or in vicinity of the
equipment. These persons must be familiar with warning & service
procedure described in this manual, as well as with safety regulations.
3) Prerequisites to proper & safety operation of the equipment are proper
storage, setup, installation, operation & maintenance of the equipment.
4) In particularly cases, the general rules & safety regulations according to
relating standards (e.g. IEC, National standards or other International
standards) for work with high voltage equipment must be observed.
COPYRIGHT
All rights reserved.
Registered trademark


are registered trademark of Beijing sifang automation co., ltd.
CONTENTS
1 Introduction ........................................................................................................................ 1
2 Features .............................................................................................................................. 3
3 Construction....................................................................................................................... 4
4 Protection functions .......................................................................................................... 5
4.1 HS/LS OC protection (Both MODEL 1 and MODEL 2) ................................................ 5
4.2 HS/LS EF protection (Both MODEL 1 and MODEL 2) ................................................. 7
4.3 INV OC/EF protection (Both MODEL 1 and MODEL 2) ............................................... 9
4.4 Overload protection (Only MODEL 1)......................................................................... 12
4.5 UV&OV protection (Both MODEL 1 and MODEL 2)................................................... 12
4.6 Thermal overload protection (Only MODEL 1) .......................................................... 13
4.7 CBF protection (Only MODEL 1) ................................................................................. 14
4.8 U/F protection (Only MODEL 2)................................................................................... 15
4.9 VT supervision.............................................................................................................. 16
5 Technical Data .................................................................................................................. 18
6 Measurement and Control............................................................................................... 20
6.1 Measurement ................................................................................................................ 20
6.2 Operation method control ........................................................................................... 20
6.3 Programmable scheme logic ...................................................................................... 20
7 Fault Record and Analysis.............................................................................................. 21
7.1 Fault records................................................................................................................. 21
7.2 Disturbance records..................................................................................................... 21
7.3 Events records.............................................................................................................. 21
7.4 Operation records ........................................................................................................ 22
8 Communications.............................................................................................................. 22
9 Diagnostics....................................................................................................................... 22
10 Setting Table ................................................................................................................. 23
10.1 Setting list for MODEL 1 .............................................................................................. 23
10.2 Setting list for MODEL 2 .............................................................................................. 26
11 Selection and ordering data....................................................................................... 30
12 Terminal Diagram......................................................................................................... 31
12.1 Terminal Diagram of MODEL 1.................................................................................... 31
12.2 Terminal Diagram of MODEL 2.................................................................................... 32
13 Dimension drawings in mm......................................................................................... 33
14 The Principle Outline of Logic Module....................................................................... 34
14.1 Logic 1 Module ............................................................................................................. 34
14.2 Logic 2 Module ............................................................................................................. 35
15 Menu Frame................................................................................................................... 36
CSC-211 Numerical Backup Protection equipment Manual
-1-
1 Introduction
Fig.1 Actual photo of CSC-211 Numerical Backup Protection Equipment
The CSC-211 provides protection, control, and monitoring functions with both local and remote
humanization interfaces. It also displays the present trip/alarm conditions and records past trip,
alarm or control events, maximum demand levels, and energy consumption is also performed.
Logic scheme file and setting file can be entered with a PC running the EPPC software
provided for the CSC-211. EPPC software provides easy access to all front panel functions.
Actual values and status can be displayed, altered, stored, and printed. Settings can be
downloaded at any time to the front panel program port of the relay via a computer cable
connected to the serial port of any personal computer.
A summary of the available protection functions is shown as follow. For a complete
understanding of each features operation, refer to Section 4: Protection Functions.
High set over-current protection with direction or non-direction ( HS OC );
Low set over-current protection with direction or non-direction ( LS OC );
Inverse definite minimum time Lag of over-current protection with direction or non-
direction (INV OC );
High set earth fault protection with direction or non-direction ( HS EF );
Low set earth fault protection with direction or non-direction ( LS EF );
Inverse definite minimum time Lag of earth fault protection with direction or non-direction (
INV EF );
Overload protection ( O L);
Under voltage and over voltage protection ( UV&OV );
Thermal over load protection ( Therm OL );
Under frequency protection ( U/F );
Circuit breaker failure protection ( CBF );
Not only as a protection relay, CSC-211 also performs control and monitoring functions and
therefore helps the user in cost-effective power system management, and ensures reliable
supply of electric power to the customers.
CSC-211 Numerical Backup Protection equipment Manual
-2-
CSC-211 Numerical Backup Protection equipment Manual
-3-
2 Features
Equipped with 32 bits embedded micro-control unit (MCU) and 14 bits A/D converter, the
equipment has very strong capacity of data processing.
Relay logic and the control logic schemes can be customized by means of friendly graphic
tools.
Detailed operation information and fault records are provided for the optimization operation
and the fault analysis.
Independent high precision measurement system is designed to meet the demands of the
remote monitoring and metering.
All of important hardware and software components are supervised continuously, and
irregularities in hardware and program sequence can be detected and alarmed, which
improve the security and availability of the protection system significantly.
Friendly user interface provided 11 specified LEDs and graphical crystal display, which can
clearly indicate the operation information and implement easy maintenance.
High precision real-time clock is embedded in the equipment, and the networks
synchronization and the GPS pulse synchronization are provided for fault record and
analysis, which require precise time sequence.
High-standard performance of EMC (Electro Magnetic Compatibility), ensures that the
equipment can work in rigorous electrical environment and atmospheric environment.
CSC-211 Numerical Backup Protection equipment Manual
-4-
3 Construction
The enclosure for equipment is 19/2 inches in width and 4U in height according to
IEC 60297-3.
The equipment is flush mounted with panel cutout.
The equipment for cabinet mounting has rear connection terminals.
The front panel of the equipment is unclosed from the top of the equipment. LCD,
LEDs and keys are mounted on the panel. There is a serial interface on the panel.
Draw-out modules for serviceability are fixed by lock component.
The modules can be combined through the bus on the rear board. Both the
equipment and the other system can be combined through the rear interfaces
Fig 1 shows the Flush-mounted enclosure of CSC-211 with panel cutout.
CSC-211 Numerical Backup Protection equipment Manual
-5-
4 Protection functions
4.1 HS/LS OC protection (Both MODEL 1 and MODEL 2)
Both HS and LS OC protections can be selected as instantaneous or definite time
delayed protection according to the time delay setting. If the time setting is zero, it will be
worked as instantaneous over current protection. Otherwise will be definite time delay
over current protection.
These two protections can be configured as forward directional, reverse directional or
non-directional. And the non-directional element will block the forward and the reverse
elements. Characteristic angle of directional element is selectable, 30 or 45. These two
over current protections are all blocked by VT fail.
Direction element adopts 90
o
connection (shown as Tab.1), and it takes effect to A, B, C
phase respectively. The direction arrangement of U/I is shown as Fig.2. To avoid dead
zone when voltage is too low to determine direction, direction element takes the voltage
memory.
Tab.1 Voltage and current of direction element
Phase Current Voltage
A Ia Ubc
B Ib Uca
C Ic Uab
FWD.
ZONE
RVD.
ZONE
Characteristic
Angle (C.A.)
C.A.+90
C.A.-90
C.A.+87.5
C.A.-87.5
Fig 2. Forward and reverse zone of direction element
CSC-211 Numerical Backup Protection equipment Manual
-6-
FWD
Ia>I
Phase A at FWD
AND
FWD
Ib>I
Phase B at FWD
AND
FWD
Ic>I
Phase C at FWD
AND
FWD element
ON
OFF
OR
RVD
Ia>I
Phase A at RVD
AND
RVD
Ib>I
Phase B at RVD
AND
RVD
Ic>I
Phase C at RVD
AND
RVD element
ON
OFF
OR
NOD
Ia>I
NOD
Ib>I
NOD
Ic>I
NOD element
ON
OFF
OR
AND
AND
AND
T
0
FWD
T
0
RVD
T
0
NOD
Relay Trip
Relay Trip
Relay Trip
Function
ON
OFF
VT Fail
Fig 3. Logic of HS/LS OC protection
The settings for HS OC protection is showed in Tab.2 and Tab.3.
Tab.2 Settings list for HS OC protection
No. Caption Scope Unit Memo
5
HS OC FWD I 0.05~100 A
High set of current for over current at forward
direction
6
HS OC RVD I 0.05~100 A
High set of current for over current at reverse
direction
7 HS OC NOD I 0.05~100 A High set of current for over current at non-direction
8 HS OC FWD T 0.00~60.0 s High set of time for over current at forward direction
9 HS OC RVD T 0.00~60.0 s High set of time for over current at reverse direction
10 HS OC NOD T 0.00~60.0 s High set of time for over current at non-direction
Tab.3 Function element ON/OFF for HS OC protection
CSC-211 Numerical Backup Protection equipment Manual
-7-
Bit Set to 0 Set to 1
Func Dir F/R Bit 2 HS OC FWD OFF HS OC FWD ON
Func Dir F/R Bit 3 HS OC RVD OFF HS OC RVD ON
Func Non Dir Bit 1 HS OC NOD OFF HS OC NOD ON
Func Bit Bit 1 HS OC FUNC OFF HS OC FUNC ON
Func Setting Bit 13 C.A. of OC 30 C.A. of OC 45
The settings for LS OC protection is showed in Tab.4 and Tab.5.
Tab.4 Settings list for LS OC protection
No. Caption Scope Unit Remark
11
LS OC FWD I 0.05~100 A
Low set of current for over current at forward
direction
12
LS OC RVD I 0.05~100 A
Low set of current for over current at reverse
direction
13 LS OC NOD I 0.05~100 A Low set of current for over current at non-direction
14 LS OC FWD T 0.00~300 s Low set of time for over current at forward direction
15 LS OC RVD T 0.00~300 s Low set of time for over current at reverse direction
16 LS OC NOD T 0.00~300 s Low set of time for over current at non-direction
Tab.5 Function element ON/OFF for LS OC protection
Bit Set to 0 Set to 1
Func Dir F/R Bit 4 LS OC FWD OFF LS OC FWD ON
Func Dir F/R Bit 5 LS OC RVD OFF LS OC RVD ON
Func Non Dir Bit 2 LS OC NOD OFF LS OC NOD ON
Func Bit Bit 2 LS OC FUNC OFF LS OC FUNC ON
Func Setting Bit 13 C.A. of OC 30 C.A. of OC 45
4.2 HS/LS EF protection (Both MODEL 1 and MODEL 2)
Both HS and LS EF protection can be selected as instantaneous or definite time delayed
protection according to the time delay setting. If the time setting is zero, it will be worked
as instantaneous earth fault protection. Otherwise will be definite time delay earth fault
protection.
These two protections can be configured as forward directional, reverse directional or
non-directional. And the non-directional element will block the forward and the reverse
elements. Characteristic angle of directional element is selectable, -45 or -60. These
two earth fault protections are all blocked by VT fail.
The direction arrangement of U/I is shown as Fig.2. The U is calculated by three phase
Voltage, and the current I comes from analog input IN.
UC UB UA U + + =
The logic of HS/LS EF is showed as Fig4.
CSC-211 Numerical Backup Protection equipment Manual
-8-
FWD
IN>I
IN at FWD
AND
FWD element
ON
OFF
RVD
IN>I
IN at RVD
AND
RVD element
ON
OFF
NOD
IN>I
NOD element
ON
OFF
AND
AND
AND
T
0
FWD
T
0
RVD
T
0
NOD
Relay Trip
Relay Trip
Relay Trip
Function
ON
OFF
VT Fail
Fig 4. Logic of HS/LS EF protection
The settings for HS EF protection is showed in Tab.6 and Tab.7.
Tab.6 Settings list for HS EF protection
No. Caption Scope Unit Memo
17 HS EF FWD I 0.05~100 A High set of current for earth fault at forward direction
18 HS EF RVD I 0.05~100 A High set of current for earth fault at reverse direction
19 HS EF NOD I 0.05~100 A High set of current for earth fault at non-direction
20 HS EF FWD T 0.00~60.0 s High set of time for earth fault at forward direction
21 HS EF RVD T 0.00~60.0 s High set of time for earth fault at reverse direction
22 HS EF NOD T 0.00~60.0 s High set of time for earth fault at non-direction
Tab.7 Function element ON/OFF for HS EF protection
Bit Set to 0 Set to 1
Func Dir F/R Bit 8 HS EF FWD OFF HS EF FWD ON
Func Dir F/R Bit 9 HS EF RVD OFF HS EF RVD ON
Func Non Dir Bit 4 HS EF NOD OFF HS EF NOD ON
Func Bit Bit 4 HS EF FUNC OFF HS EF FUNC ON
Func Setting Bit 14 C.A. of EF -45 C.A. of EF -60
The settings for LS EF protection is showed in Tab.8 and Tab.9.
Tab.8 Settings list for LS EF protection
No. Caption Scope Unit Remark
23 LS EF FWD I 0.05~100 A Low set of current for earth fault at forward direction
24 LS EF RVD I 0.05~100 A Low set of current for earth fault at reverse direction
25 LS EF NOD I 0.05~100 A Low set of current for earth fault at non-direction
CSC-211 Numerical Backup Protection equipment Manual
-9-
26 LS EF FWD T 0.00~300 s Low set of time for earth fault at forward direction
27 LS EF RVD T 0.00~300 s Low set of time for earth fault at reverse direction
28 LS EF NOD T 0.00~300 s Low set of time for earth fault at non-direction
Tab.9 Function element ON/OFF for LS EF protection
Bit Set to 0 Set to 1
Func Dir F/R Bit 10 LS EF FWD OFF LS EF FWD ON
Func Dir F/R Bit 11 LS EF RVD OFF LS EF RVD ON
Func Non Dir Bit 5 LS EF NOD OFF LS EF NOD ON
Func Bit Bit 5 LS EF FUNC OFF LS EF FUNC ON
Func Setting Bit 14 C.A. of EF -45 C.A. of EF -60
4.3 INV OC/EF protection (Both MODEL 1 and MODEL 2)
The operating time of the INV OC/EF function reduces when the fault current increases
and it can therefore achieve shorter operating time for fault location closer to the source.
Four different characteristics are provided and described as follow:
Curve 1 (Normal/Standard inverse):
( )
p
p
t
I I
t

=
1
14 . 0
02 . 0
refer relay setting menu
Curve 2 (Very inverse):
( )
p
p
t
I I
t

=
1
5 . 13
refer relay setting menu
Curve 3 (Extremely inverse):
( )
p
p
t
I I
t

=
1
80
2
refer relay setting menu
Curve 4 (Long time inverse):
( )
p
p
t
I I
t

=
1
120
refer relay setting menu
INV OC/EF protection can be set as directional and is also affected by VT fail similar with
HS/LS OC/EF protection as above.
The directional unit has been showed in Fig.2
The logic of INV OC is showed as Fig5.
CSC-211 Numerical Backup Protection equipment Manual
-10-
FWD
Ia>I
Phase A at FWD
AND
FWD
Ib>I
Phase B at FWD
AND
FWD
Ic>I
Phase C at FWD
AND
FWD element
ON
OFF
RVD
Ia>I
Phase A at RVD
AND
RVD
Ib>I
Phase B at RVD
AND
RVD
Ic>I
Phase C at RVD
AND
RVD element
ON
OFF
NOD
Ia>I
NOD
Ib>I
NOD
Ic>I
NOD element
ON
OFF
t FWD
Relay Trip
Relay Trip
Function
ON
OFF
VT Fail
AND
AND
AND
EXP
FWD
t
FWD
EXP
FWD
t
FWD
EXP
FWD
OR
AND
AND
AND
t RVD
Relay Trip
EXP
RVD
t RVD
EXP
RVD
t
RVD
EXP
RVD
OR
OR AND
t NOD
EXP
NOD
Fig 5. Logic of INV OC protection
The settings for the INV OC protections are showed in Tab.10 and Tab.11.
Tab.10 Setting list for INV OC protection
No Caption Scope Unit Remark
29 INV OC FWD I 0.05~100 A Current set for INV over current at forward direction
30 INV OC FWD T 0.005~5 s Time set for INV over current at forward direction
31 CRV SEL OF FOC 1~4 -
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
32 INV OC RVD I 0.05~100 A Current set for INV over current at reverse direction
33 INV OC RVD T 0.005~5 s Time set for INV over current at reverse direction
34 CRV SEL OF ROC 1~4 -
I IEC SI or NI
2 IEC VI
CSC-211 Numerical Backup Protection equipment Manual
-11-
3 IEC EI
4 ANSI LTI
35 INV OC NOD I 0.05~100 A Current set for INV over current at non-direction
36 INV OC NOD T 0.005~5 s Time set for INV over current at non-direction
37 CRV SEL OF NOC 1~4 -
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
Tab.11 Function element ON/OFF for INV OC protection
Bit Set to 0 Set to 1
Func Dir F/R Bit 12 INV OC FWD OFF INV OC FWD ON
Func Dir F/R Bit 13 INV OC RVD OFF INV OC RVD ON
Func Non Dir Bit 6 INV OC NOD OFF INV OC NOD ON
Func Bit Bit 6 INV OC FUNC OFF INV OC FUNC ON
Func Setting Bit 13 C.A. of EF 30 C.A. of EF 45
The logic of INV EF is showed as Fig6.
FWD
IN>I
IN at FWD
AND
FWD element
ON
OFF
RVD IN>I
IN at RVD
AND
RVD element
ON
OFF
NOD
IN>I
NOD element
ON
OFF
t FWD
Relay Trip
Relay Trip
Function
ON
OFF
VT Fail
AND
EXP
FWD
AND
t
RVD
Relay Trip
EXP
RVD
AND
t NOD
EXP
NOD
Fig 6. Logic of INV EF protection
The settings for INV EF protections are showed in Tab.12 and Tab.13.
Tab.12 Setting list for INV EF protection
CSC-211 Numerical Backup Protection equipment Manual
-12-
No Caption Scope Unit Remark
38 INV EF FWD I 0.05~100 A Current set for INV earth fault at forward direction
39 INV EF FWD T 0.005~250 s Time set for INV earth fault at forward direction
40 CRV SEL OF FEF 1~4 -
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
41 INV EF RVD I 0.05~100 A Current set for INV earth fault at reverse direction
42 INV EF RVD T 0.005~5 s Time set for INV earth fault at reverse direction
43 CRV SEL OF REF 1~4 -
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
44 INV EF NOD I 0.05~100 A Current set for INV earth fault at non-direction
45 INV EF NOD T 0.005~5 s Time set for INV earth fault at non-direction
46 CRV SEL OF NEF 1~4 -
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
Tab.13 Function element ON/OFF for INV EF protection
Bit Set to 0 Set to 1
Func Dir F/R Bit 14 INV EF FWD OFF INV EF FWD ON
Func Dir F/R Bit 15 INV EF RVD OFF INV EF RVD ON
Func Non Dir Bit 7 INV EF NOD OFF INV EF NOD ON
Func Bit Bit 7 INV EF FUNC OFF INV EF FUNC ON
Func Setting Bit 14 C.A. of EF -45 C.A. of EF -60
4.4 Overload protection (Only MODEL 1)
This protection is just a definite time-delayed (time can be set very long) over-current
element.
The settings for overload protection are showed in Tab.14 and Tab.15.
Tab.14 Setting list for overload protection
No Caption Scope Unit Remark
50 Overload I 0.2~10 A Current set for overload protection
51 Overload T 0.1~1000 s Time set for overload protection
Tab.15 Function element ON/OFF for overload protection
Bit Set to 0 Set to 1
Func Bit Bit 10 OL FUNC OFF OL FUNC ON
4.5 UV&OV protection (Both MODEL 1 and MODEL 2)
When any phase-to-phase voltage in normal state turns to be less than or more than
predetermined value, it will result in tripping after predetermined time.
This protection includes two stages. Either stage can be chose either over voltage
protection or under voltage protection, and they have the same time setting delay. It is
CSC-211 Numerical Backup Protection equipment Manual
-13-
showed as Fig7.
Max Uphase-phase > UOV
AND
AND
OR
AND
T
0
DO-UV&OV
Function
VT Fail
1
UV&OV is OV
UV&OV is UV
Min Uphase-phase < UUV
ON
OFF
DI input (CB closed) AND
Fig 7. Logic of UV&OV protection
The settings for the UV&OV protection is showed in Tab.16 and Tab.17
Tab.16 Setting list for UV&OV protection
No Caption Scope Unit Remark
52 for model 1
47 for model 2
UV stg1 V 66~110 V Voltage set of under voltage for UV&OV at stage1
53 for model 1
48 for model 2
OV stg1 V 110~154 V Voltage set of over voltage for UV&OV at stage1
54 for model 1
49 for model 2
UV&OV stg1 T 0.1~10 s Time set for UV&OV at stage1
55 for model 1
50 for model 2
UV stg2 V 66~110 V Voltage set of under voltage for UV&OV at stage2
56 for model 1
51 for model 2
OV stg2 V 110~154 V Voltage set of over voltage for UV&OV at stage2
57 for model 1
52 for model 2
UV&OV stg2 T 0.1~10 s Time set for UV&OV at stage2
Tab.17 Function element ON/OFF for UV&OV protection
Bit Set to 0 Set to 1
Func Setting Bit 11 UV&OV stg1 UV UV&OV stg1 OV
Func Setting Bit 12 UV&OV stg2 UV UV&OV stg2 OV
Func Bit Bit 8 UV&OV FUNC OFF UV&OV FUNC ON
4.6 Thermal overload protection (Only MODEL 1)
Transformer design has changed over the years, with less and less metal being used per
MVA of transformer power. This has reduced the withstand time which a transformer can
be allowed to be run in an over loaded state. This equipment provides thermal overload
protection to cut down the transformer.
IEC curve:
CSC-211 Numerical Backup Protection equipment Manual
-14-
t thermal trip time
eq
I equivalent thermal current
thermal time constant

I rms thermal current setting


C H / hot spot weighting factor
p
I prior current takes into account cyclic loading
Here, , C H / 1 and

I are all settings, and


3
IC IB IA
I
eq
+ +
= ,
p
I equals to the
equivalent current before overload.
The settings for the thermal overload protection is showed in Tab.18 and Tab.19
Tab.18 Setting list for the thermal overload protection
No Caption Scope Unit Remark
47 Thermal I 0.2~10 A Current set for thermal overload protection
48
Thermal T 6~7200 s
Time set thermal for overload protection (thermal time
constant)
48 Thermal H/C 0~1 - hot spot weighting factor
Tab.19 Function element ON/OFF for thermal overload protection
Bit Set to 0 Set to 1
Func Bit Bit 9 THERM FUNC OFF THERM FUNC ON
4.7 CBF protection (Only MODEL 1)
Both single phase CBF and 3 phases CBF are provided in the CSC-211 equipment
model 1.
( )


=
2 2
2 2
/ 1
ln

I I
I C H I
t
eq
P eq
CSC-211 Numerical Backup Protection equipment Manual
-15-
CBF Ia>I
DI-START A_ph
AND
CBF
Ib>I
DI-START B_ph
CBF
Ic>I
DI-START C_ph
OR
Internal trip
OR
T
0
CBF
DO-START
B_ph
Function
ON
OFF
AND
AND
DI-START 3_ph
OR
AND
AND
AND
AND
T
0
CBF
T
0
CBF
T
0
CBF
DO-START
C_ph
DO-START
3_ph
DO-START
A_ph
Fig 8. Logic of CBF protection
The settings for the CBF protection is showed in Tab.20 and Tab.21
Tab.20 Setting list for the CBF protection
No Caption Scope Unit Remark
58 CBF OC I 0.05~100 A Current set for CBF protection
59 CBF OC T 0~32.00 s Time set for CBF protection
Tab.21 Function element ON/OFF for CBF protection
Bit Set to 0 Set to 1
Func Bit Bit 11 CBF FUNC OFF CBF FUNC ON
4.8 U/F protection (Only MODEL 2)
When network frequency in normal state is less than predetermined value, this protection
will result in tripping after predetermined time. It has 4 stages .And Df/Dt is another
operate element only for stage 1 and 2 to trip after the same time. The relative of two
elements U/F and Df/Dt can be chosen as OR or AND. The U/F and the Df/Dt are all
calculated by software from voltage of phase A to B. There are two elements to block this
protection: VT failure and the minimum of voltage of phase to phase is less than 70V. The
U/F logic of stage 1 is showed at Fig 9, so is stage 2.
CSC-211 Numerical Backup Protection equipment Manual
-16-
Df/Dt >
AND
AND
OR
T
0
DO-UF
Function
VT Fail
Df/Dt AND
Df/Dt >
ON
OFF
Min.Uphase-phase < 70V
AND
Df/Dt OR
F <
AND
OR
Df/Dt element
ON
OFF
AND
Fig 9. Logic of U/F protection
The settings for the U/F protection is showed in Tab.22 and Tab.23
Tab.22 Setting list for UF protection
No Caption Scope Unit Remark
53 U/F stg1 F 45.0 50.0 Hz Current set for under frequency protection at stage 1
54 U/F stg1 T 0.3 5.0 s Time set for under frequency protection at stage 1
55 U/F stg12 F 45.0 50.0 Hz Current set for under frequency protection at stage 2
56 U/F stg2 T 0.3 5.0 s Time set for under frequency protection at stage 2
57 U/F stg3 F 45.0 50.0 Hz Current set for under frequency protection at stage 3
58 U/F stg3 T 0.3 5.0 s Time set for under frequency protection at stage 3
59 U/F stg4 F 45.0 50.0 Hz Current set for under frequency protection at stage 4
60 U/F stg4 T 0.3 5.0 s Time set for under frequency protection at stage 4
61 Df/Dt stg1 0.2 1.0 Hz/s Df/Dt set for under frequency protection at stage 1
62 Df/Dt stg2 0.2 1.0 Hz/s Df/Dt set for under frequency protection at stage 2
Tab.23 Function element ON/OFF for UF protection
Bit Set to 0 Set to 1
Func Bit bit 11 U/F stg1 OFF U/F stg1 ON
Func Bit bit 12 U/F stg2 OFF U/F stg2 ON
Func Bit bit 13 U/F stg3 OFF U/F stg3 ON
Func Bit bit 14 U/F stg4 OFF U/F stg4 ON
Func Setting Bit 4 Df/Dt stg1 OFF Df/Dt stg1 ON
Func Setting Bit 5 Df/Dt stg2 OFF Df/Dt stg2 ON
Func Setting Bit 9 Df/Dt stg1 AND Df/Dt stg1 OR
Func Setting Bit 10 Df/Dt stg2 AND Df/Dt stg2 OR
4.9 VT supervision
Voltage transformer supervision can supervise bus voltage and report single-phase
broken, two-phase broken and three-phase broken. Any of the following conditions
satisfy and last 9 seconds, CSC-211 will report the alarm of TV broken or no-voltage.
Self-generated zero sequence voltage and three-phase voltage are all less than 8V,
CSC-211 Numerical Backup Protection equipment Manual
-17-
and any phase current is more than 0.125A (considered as no-voltage);
Self-generated zero sequence voltage is more than 8V, and minimum phase-to-
phase voltage is less than 16V (considered as two-phase broken);
Self-generated zero sequence voltage is more than 8V, and the difference between
maximum phase-to-phase voltage and minimum phase-to-phase voltage is more
than 16V (considered as single-phase broken).
For the directional protection, the perfect bus-voltage is significant to their operation.
Therefore, VT fail will block the protection with directional elements, under voltage, and
under frequency.
CSC-211 Numerical Backup Protection equipment Manual
-18-
5 Technical Data
Rated inputs
DC Voltage:220V/110V
AC Voltage: 3 / 100 V i.e 63.5 V Ph-N
AC Current: 1A/5A
Frequency: 50Hz
Burdens
DC circuit: < 5W standby + 0.5 per energized relay
AC Voltage/phase < 0.15VA
AC Current/phase < 0.25VA
Thermal
withstand
AC Current
1s @ 40In
10s @ 20In
continuous @ 4In
AC Voltage
10s @ 1.4Un
continuous @ 1.2Un
Contacts Make/Break: 1A; 220Vdc
Accuracy
Protection thresholds : 3%
Time delay : 3% with a minimum of 20ms
Measurements:
typical 0.2 % at I,U
typical 0.5 % at P,Q, kW, kVA
Working range
Voltage : 0.4V-120V
Current: 0.04In -30In
Frequency: 40-55Hz/50
Report accuracy
Distinguishability of event record: 1ms
Precision of GPS: 1ms
Communications
RS485: Screened twisted pair,19200bps max
Electrical Ethernet: UTP5, RJ45 connection
Fiber Ethernet: optical fiber,820nm ST connection
High voltage
withstand
Insulation resistance:
IEC 60255-5 > 1000 MV
Dielectric withstand:
IEC 60255-5
2kV common mode
1kV differential mode
Impulse voltage:
IEC 60255-5
5kV common mode
1kV differential mode
EMC
Fast transient disturbance:
IEC 61000-4-4
4kV auxiliary voltage, class 4
Electrostatic discharge:
IEC 61000-4-2
8kV, class 4
Radio Frequency:
ANSI C37.90.2
35V/m
Impulse:
IEC 61000-4-3
10V/m
High frequency disturbance:
IEC 61000-4-1
2.5kV common mode, class 3
1kV differential mode, class 3
Mechanical
performance
Vibrations:
IEC 60255-21-1
Response and endurance, class 1
CSC-211 Numerical Backup Protection equipment Manual
-19-
Shock:
IEC 60255-21-2
Response and withstand, class 1
Bump:
IEC 60255-21-2
Response and withstand, class 1
Atmospheric
environment
Temperature:
IEC 60255-6
Storage 25C to +70C
Operation 25C to + 55C
Humidity:
IEC 60068-2-3
56 days at 93%
RH and 40C
Fault recording
Instantaneous values of all analog quantities fed to the relay.
Record capacity: 6*1second
CSC-211 Numerical Backup Protection equipment Manual
-20-
6 Measurement and Control
6.1 Measurement
The CSC-211 equipment monitors permanently all the current and voltage inputs,
calculates the frequency, the phase to phase voltage, P, and Q, shows the values on the
LCD display and stores the measurements in memory. The measured values are
measured by the independent high precision module, which can ensure the true RMS
with 0.2% accuracy (nominal conditions).
Instantaneous measurements
Phase current: Ia, Ib, Ic;
Phase voltage: Ua, Ub, Uc;
Three phase active power P, reactive power Q, power factor;
Frequency;
Forward/reverse active power, forward/reverse reactive power;
Mean, maximum, minimum value of the current and voltage during some time;
Sequence currents and voltages;
Thermal status.
6.2 Operation method control
The settings are divided into two categories: protection settings, and control and support
settings. 32 setting groups are provided for different operating conditions and adaptive
relaying. The soft function pressboards are provided for activation or inhibition of the
protection element. All settings and the states of the soft function pressboards are stored
in E2PROM.
6.3 Programmable scheme logic
The programmable scheme logic feature of support software EPPC allows user to
customize the protection and control functions. It is also used to program the functionality
of the optically isolated inputs, relay outputs and LED indications. The trigger conditions
and the record length could easy set by this function.
CSC-211 Numerical Backup Protection equipment Manual
-21-
7 Fault Record and Analysis
The CSC-211 equipment can supervise the operation information of the devices and
correlative circuit, which include fault records, events records, disturbance records and
operation records. The internal real-time clock provides the time time-tag for all type
records, the time distinguish ability is 1ms. The networks synchronization and the GPS
pulse (adaptive second or minute pulse) synchronization are supported by the real-time
clock system. A lithium battery provides a backup for the real time clock and all records in
the event of supply failure. This battery is supervised and easily replaced from the front of
the relay.
7.1 Fault records
Records of the last 40 faults are stored in battery backed memory. Some important data
during the fault or manual operation are record. The information provided in the fault
record includes:
Fault time tag: date and time
Operation event table: operation protection, operation time
Operation data: current, voltage, frequency, phase angle
Active setting groups
States of the soft function pressboards
7.2 Disturbance records
Disturbance records are used to capture the analog and digital data of certain length
before or after some event, it can reappearance the operation states of the devices
during the fault period, any logic element and digital input could trigger the disturbance
records. The internal disturbance recorder has 12 analogue channels, 32 digital channels
(digital inputs, digital outputs, element states) and time tag. Data is sampled 20 times a
cycle and typically 2 disturbance records, each of up to 5 seconds duration are stored in
battery backed memory. Disturbance records can be extracted from the relay via the
remote communications and saved in the COMTRADE format. These records may be
examined using support software EPPC.
7.3 Events records
Up to 1000 time-tagged event records are stored in battery backed memory, and can be
extracted using the communication ports or showed on the front panel display. The event
CSC-211 Numerical Backup Protection equipment Manual
-22-
records include: operation events, alarm events, changing of digital input state or digital
output state, time tag and the current status of the protection.
7.4 Operation records
The latest 40 time-tagged operation records are stored in the battery backed memory, it
includes: the modification or switch of the setting groups, close or open control of the
circuit breaker. These data could provide information for the detailed fault analysis.
8 Communications
All models of CSC-211 series equipments provide the following communications ports
and protocols for the user:
Double or single 10M Ethernet port of cable or fiber.
One RS485 communication port
One RS232 debug port
IEC60870-5-103
CSC-211 equipment can transmit real-time data to the local monitoring system, or
remotely to the SCADA, these data include settings, measurements and alarms, as well
as fault, event and disturbance records. The communication settings (relay address, data
rate, parity, etc.) can be programmed using the relay front port. Software allows easy
setting of any CSC-211 model, in addition to uploading of event, fault and disturbance
records, settings and measurements.
The detailed protocols are provided in the products manual.
9 Diagnostics
Automatic tests including power-on diagnostics and continuous self-monitoring, ensure a
high degree of reliability. When any abnormal status is detected, the alarm indicators and
related relay are driven, and the dependent events could be record immediately. For
some fatal faults, the relay could be blocked to avoid the unwanted operation. The results
of the self-test functions are stored in non-volatile memory.
The virtual test function is provided for the automatic tests of the substation automation
system. The function contains automatic counter point of digital input, automatic
triggering of SOE.
Test features available on the user interface provide examination of input quantities,
states of the digital inputs and relay outputs. A local monitor port provides digital outputs,
selected from a prescribed list of signals, including the status of protection element, and
may be used in conjunction with test equipment. These test signals can also be viewed
using the communications ports, and the front panel user interface.
CSC-211 Numerical Backup Protection equipment Manual
-23-
10 Setting Table
10.1 Setting list for MODEL 1
Setting List and Description
No. Caption Scope Unit Memo Function
1 Func Dir F/R 0000 - FFFF
For forward and reverse directional
element
2 Func Setting 1 0000 - FFFF For UV/OV, C.A. and rated current
3 Func Bit 0000 - FFFF Function selective
4 Func Non Dir 0000 - FFFF For non-directional element
5 HS OC FWD I 0.05 - 100 A
6 HS OC RVD I 0.05 - 100 A
7 HS OC NOD I 0.05 - 100 A
8 HS OC FWD T 0.0 - 60.00 s
9 HS OC RVD T 0.0 - 60.00 s
10 HS OC NOD T 0.0 - 60.00 s
11 LS OC FWD I 0.05 - 100 A
12 LS OC RVD I 0.05 - 100 A
13 LS OC NOD I 0.05 - 100 A
14 LS OC FWD T 0.0 - 300.0 s
15 LS OC RVD T 0.0 - 300.0 s
16 LS OC NOD T 0.0 - 300.0 s
OC
17 HS EF FWD I 0.05 - 100 A
18 HS EF RVD I 0.05 - 100 A
19 HS EF NOD I 0.05 - 100 A
20 HS EF FWD T 0.0 - 60.00 s
21 HS EF RVD T 0.0 - 60.00 s
22 HS EF NOD T 0.0 - 60.00 s
23 LS EF FWD I 0.05 - 100 A
24 LS EF RVD I 0.05 - 100 A
25 LS EF NOD I 0.05 - 100 A
26 LS EF FWD T 0.0 - 300.0 s
27 LS EF RVD T 0.0 - 300.0 s
28 LS EF NOD T 0.0 - 300.0 s
EF
29 INV OC FWD I 0.05 - 100 A
30 INV OC FWD T 0.005 - 5 s
31 CRV SEL OF FOC 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
32 INV OC RVD I 0.05 - 100 A
33 INV OC RVD T 0.005 - 5 s
34 CRV SEL OF ROC 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
35 INV OC NOD I 0.05 - 100 A
36 INV OC NOD T 0.005 - 5 s
INV OC
CSC-211 Numerical Backup Protection equipment Manual
-24-
No. Caption Scope Unit Memo Function
37 CRV SEL OF NOC 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
38 INV EF FWD I 0.05 - 100 A
39 INV EF FWD T 0.005 - 5 s
40 CRV SEL OF FEF 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
41 INV EF RVD I 0.05 - 100 A
42 INV EF RVD T 0.005 - 5 s
43 CRV SEL OF REF 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
44 INV EF NOD I 0.05 - 100 A
45 INV EF NOD T 0.005 - 5 s
46 CRV SEL OF NEF 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
INV EF
47 Thermal I 0.2 - 10.0 A
48 Thermal T 6 - 7200 s
49 Thermal H/C 0.0 - 1
50 Overload I 0.2 - 10.0 A
51 Overload T 0.1 - 6000 s
OL
52 UV stg1 V 66.0 - 110.0V V Phase-to-Phase
53 OV stg1 V 110.0 - 154.0 V Phase-to-Phase
54 UV&OV stg1 T 0.1 - 10.0 s
55 UV stg2 V 66.0 - 110.0V V Phase-to-Phase
56 OV stg2 V 110.0 - 154.0 V Phase-to-Phase
57 UV&OV stg2 T 0.1 - 10.0 s
UV&OV
58 CBF OC I 0.05 A - 100 A
59 CBF OC T 0.1 - 32.00 s
CBF
60 Mea CT Ratio 0.001 - 10.0 kA/A Primary Mea CT /1000
61 Mea VT Ratio 0.01 - 10.0 kV/V Primary PT/1000
Definition of Func Dir F/R
BIT 0 1
15 INV EF FWD OFF INV EF FWD ON
14 INV EF FWD OFF INV EF FWD ON
13 INV OC RVD OFF INV OC RVD ON
12 INV OC FWD OFF INV OC FWD ON
11 LS EF RVD OFF LS EF RVD ON
10 LS EF FWD OFF LS EF FWD ON
9 HS EF RVD OFF HS EF RVD ON
8 HS EF FWD OFF HS EF FWD ON
CSC-211 Numerical Backup Protection equipment Manual
-25-
7 Not used Not used
6 Not used Not used
5 LS OC RVD OFF LS OC RVD ON
4 LS OC FWD OFF LS OC FWD ON
3 HS OC RVD OFF HS OC RVD ON
2 HS OC FWD OFF HS OC FWD ON
1 Not used Not used
0 Not used Not used
Definition of Func Setting 1
BIT 0 1
15 Not used Not used
14 C.A. of EF -45 C.A.of EF -60
13 C.A.of OC 30 C.A.of OC 45
12 UV&OV stg2 UV UV&OV stg2 OV
11 UV&OV stg1 UV UV&OV stg1 OV
10 Not used Not used
9 Not used Not used
8 Neu CT Rated 5A Neu CT Rated 1A
7 Pha CT Rated 5A Pha CT Rated 1A
4~6 Not used Not used
0~3 Not used Not used
Definition of Func Bit
BIT 0 1
15 Not used Not used
14 Not used Not used
13 Not used Not used
12 Not used Not used
11 CBF FUNC OFF CBF FUNC ON
10 OL FUNC OFF OL FUNC ON
9 THERM FUNC OFF THERM FUNC ON
8 UV&OV FUNC OFF UV&OV FUNC ON
7 INV EF FUNC OFF INV EF FUNC ON
6 INV OC FUNC OFF INV OC FUNC ON
5 LS EF FUNC OFF LS EF FUNC ON
4 HS EF FUNC OFF HS EF FUNC ON
3 Not used Not used
2 LS OC FUNC OFF LS OC FUNC ON
1 HS OC FUNC OFF HS OC FUNC ON
0 Not used Not used
Definition of Func Non Dir
BIT 0 1
8~15 Not used Not used
CSC-211 Numerical Backup Protection equipment Manual
-26-
7 INV EF NOD OFF INV EF NOD ON
6 INV OC NOD OFF INVOC NOD ON
5 LS EF NOD OFF LS EF NOD ON
4 HS EF NOD OFF HS EF NOD ON
3 Not used Not used
2 LS OC NOD OFF LS OC NOD ON
1 HS OC NOD OFF HS OC NOD ON
0 Not used Not used
10.2 Setting list for MODEL 2
Setting List and Description
No. Caption Scope Unit Memo Function
1 Func Dir F/R 0000 - FFFF
For forward and reverse directional
element
2 Func Setting 0000 - FFFF
For UV/OV, U/F , C.A. and rated
current
3 Func BIT 0000 - FFFF Function selective ON oor OFF
4 Func Non Dir 0000 - FFFF For non-directional element
5 HS OC FWD I 0.05 - 100 A
6 HS OC RVD I 0.05 - 100 A
7 HS OC NOD I 0.05 - 100 A
8 HS OC FWD T 0.0 - 60.00 s
9 HS OC RVD T 0.0 - 60.00 s
10 HS OC NOD T 0.0 - 60.00 s
11 LS OC FWD I 0.05 - 100 A
12 LS OC RVD I 0.05 - 100 A
13 LS OC NOD I 0.05 - 100 A
14 LS OC FWD T 0.0 - 300.0 s
15 LS OC RVD T 0.0 - 300.0 s
16 LS OC NOD T 0.0 - 300.0 s
OC
17 HS EF FWD I 0.05 - 100 A
18 HS EF RVD I 0.05 - 100 A
19 HS EF NOD I 0.05 - 100 A
20 HS EF FWD T 0.0 - 60.00 s
21 HS EF RVD T 0.0 - 60.00 s
22 HS EF NOD T 0.0 - 60.00 s
23 LS EF FWD I 0.05 - 100 A
24 LS EF RVD I 0.05 - 100 A
25 LS EF NOD I 0.05 - 100 A
26 LS EF FWD T 0.0 - 300.0 s
27 LS EF RVD T 0.0 - 300.0 s
28 LS EF NOD T 0.0 - 300.0 s
EF
29 INV OC FWD I 0.05 - 100 A
30 INV OC FWD T 0.005 - 5 s
INV OC
CSC-211 Numerical Backup Protection equipment Manual
-27-
No. Caption Scope Unit Memo Function
31 CRV SEL OF FOC 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
32 INV OC RVD I 0.05 - 100 A
33 INV OC RVD T 0.005 - 5 s
34 CRV SEL OF ROC 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
35 INV OC NOD I 0.05 - 100 A
36 INV OC NOD T 0.005 - 5 s
37 CRV SEL OF NOC 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
38 INV EF FWD I 0.05 - 100 A
39 INV EF FWD T 0.005 - 5 s
40 CRV SEL OF FEF 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
41 INV EF RVD I 0.05 - 100 A
42 INV EF RVD T 0.005 - 5 s
43 CRV SEL OF REF 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
44 INV EF NOD I 0.05 - 100 A
45 INV EF NOD T 0.005 - 5 s
46 CRV SEL OF NEF 1~4 -----
I IEC SI or NI
2 IEC VI
3 IEC EI
4 ANSI LTI
INV EF
47 UV stg1 V 66.0 - 110.0V V Phase-to-Phase
48 OV stg1 V 110.0 - 154.0 V Phase-to-Phase
49 UV&OV stg1 T 0.1 - 10.0 s
50 UV stg2 V 66.0 - 110.0V V Phase-to-Phase
51 OV stg2 V 110.0 - 154.0 V Phase-to-Phase
52 UV&OV stg2 T 0.1 - 10.0 s
UV&OV
53 U/F stg1 F 45.00 - 50.00 Hz
54 U/F stg1 T 0.40 - 5.00 s
55 U/F stg2 F 45.00 - 50.00 Hz
56 U/F stg2 T 0.40 - 5.00 s
57 U/F stg3 F 45.00 - 50.00 Hz
58 U/F stg3 T 0.40 - 5.00 s
59 U/F stg4 F 45.00 - 50.00 Hz
60 U/F stg4 T 0.40 - 5.00 s
61 U/F dF/dt 1.0 - 10.0 Hz/s
U/F
62 Mea CT Ratio 0.001 - 10.0 kA/A Primary Mea CT /1000
CSC-211 Numerical Backup Protection equipment Manual
-28-
No. Caption Scope Unit Memo Function
63 Mea PT Ratio 0.01 - 10.0 kV/V Primary PT/1000
Definition of Func Dir F/R
BIT 0 1
15 INV EF FWD OFF INV EF FWD ON
14 INV EF FWD OFF INV EF FWD ON
13 INV OC RVD OFF INV OC RVD ON
12 INV OC FWD OFF INV OC FWD ON
11 LS EF RVD OFF LS EF RVD ON
10 LS EF FWD OFF LS EF FWD ON
9 HS EF RVD OFF HS EF RVD ON
8 HS EF FWD OFF HS EF FWD ON
7 Not used Not used
6 Not used Not used
5 LS OC RVD OFF LS OC RVD ON
4 LS OC FWD OFF LS OC FWD ON
3 HS OC RVD OFF HS OC RVD ON
2 HS OC FWD OFF HS OC FWD ON
1 Not used Not used
0 Not used Not used
Definition of Func Setting 1
BIT 0 1
15 Not used Not used
14 C.A. of EF -45 C.A.of EF -60
13 C.A.of OC 30 C.A.of OC 45
12 UV&OV stg2 UV UV&OV stg2 OV
11 UV&OV stg1 UV UV&OV stg1 OV
10 Df/Dt stg2 AND Df/Dt stg2 OR
9 Df/Dt stg1 AND Df/Dt stg1 OR
8 Neu CT Rated 5A Neu CT Rated 1A
7 Pha CT Rated 5A Pha CT Rated 1A
6 Not used Not used
5 Df/Dt stg2 OFF Df/Dt stg2 ON
4 Df/Dt stg1 OFF Df/Dt stg1 ON
0~3 Not used Not used
Definition of Func Bit
BIT 0 1
15 Not used Not used
14 U/F stg4 OFF U/F stg4 ON
13 U/F stg3 OFF U/F stg3 ON
12 "U/F stg2 OFF U/F stg2 ON
CSC-211 Numerical Backup Protection equipment Manual
-29-
11 U/F stg1 OFF U/F stg1 ON
10 Not used Not used
9 Not used Not used
8 UV&OV FUNC OFF UV&OV FUNC ON
7 INV EF FUNC OFF INV EF FUNC ON
6 INV OC FUNC OFF INV OC FUNC ON
5 LS EF FUNC OFF LS EF FUNC ON
4 HS EF FUNC OFF HS EF FUNC ON
3 Not used Not used
2 LS OC FUNC OFF LS OC FUNC ON
1 HS OC FUNC OFF HS OC FUNC ON
0 Not used Not used
Definition of Func Non Dir
BIT 0 1
8~15 Not used Not used
7 INV EF NOD OFF INV EF NOD ON
6 INV OC NOD OFF INVOC NOD ON
5 LS EF NOD OFF LS EF NOD ON
4 HS EF NOD OFF HS EF NOD ON
3 Not used Not used
2 LS OC NOD OFF LS OC NOD ON
1 HS OC NOD OFF HS OC NOD ON
0 Not used Not used
CSC-211 Numerical Backup Protection equipment Manual
-30-
11 Selection and ordering data
Position
Ordering
Codes
1 2 3 4 5 6 7 8 9
CSC 211-
10
/
2 Phases Mea TA(Ia,Ic) 5NSF.081.009(blank) 0
3 Phases Mea TA 6NSF.001.002H H
1. AC1 Module
2. AC2 Module
Phase rated current 1A and neutral 1A 6NSF.001.003G G
3. COM Module
Communication Port Configuration : 6NSF.001.003G 6
4. CPU Module
Enhanced Configuration (double Ethernet ): 6NSF.004.002A 2
5. LOGIC1 Module
Configuration : F6SF.006.006 5
6. LOGIC2 Module
Configuration : F6SF.06.005 7
7. POWER Module
DC110V 6SF.009.031.1 1
DC220V 6SF.009.031.2 2
8. MMI Module
Standard Configuration (LCD resolution 160X80 ) 6NSF.005.002A 1
9. Structural Style
Switch cabinet mounting K
Pack screen (cabinet) mounting (default configuration ) D
10. Software Version
Standard Configuration
DC110V CSC 211-HG625711D1
DC220V CSC 211-HG625721D1
CSC-211 0
Numerical Backup Protection Equipment
6 2 5 7 1
Phase rated current 1A and neutral 5A 6NSF.001.003Q Q
Phase rated current 5A and neutral 5A 6NSF.001.003L L
Phase rated current 5A and neutral 1A 6NSF.001.003B B
Mode 1 (CBF) 1
Mode 2 (UF) 2
C
S
C
-
2
1
1

N
u
m
e
r
i
c
a
l

B
a
c
k
u
p

P
r
o
t
e
c
t
i
o
n

e
q
u
i
p
m
e
n
t
























M
a
n
u
a
l
-
3
1
-
1
2


T
e
r
m
i
n
a
l

D
i
a
g
r
a
m
1
2
.
1

T
e
r
m
i
n
a
l

D
i
a
g
r
a
m

o
f

M
O
D
E
L

1
O
u
t
p
u
t
14
19
GND 20
16
18
17
15 NOT USED
4
9
COM
POWER OFF
DC- I NPUT
11
10
12
13
5
7
6
8
1
3
2
X8
POWER COM LOGI C2
X7
LOGI C1
X6
4
24V COM
NOT USED
9
11
10
12
6
7
5
8
CPU
2
3
1
X5
I
n
p
u
t
s
X4
AC2
4
4
6
5
9
10
12
11
5
6
7
8
AC2
2
3
1
X3
1
3
2
X2
4
9
10
12
11
5
6
7
8
AC1
1
3
2
X1
P
o
w
e
r

I
n
p
u
t
REMACCESS BLK
RELAY TEST
NOT USED
B
u
s
/
L
i
n
e
P
r
o
t
e
c
t
i
o
n

c
u
r
r
e
n
t
M
e
a
s
u
r
e
m
e
n
t
D
i
g
i
t
a
l

I
n
p
u
t
s
CB CLOSED
START CBF_Aph
2
4
V
+24V
24V
E
t
h
e
r
n
e
t
E
t
h
e
r
n
e
t
14
19
20
16
18
17
15
4
9
10
11
12
13
5
7
6
8
1
3
2
NOT USED
ALARM
START C- PH
OPERATI ON
14
19
20
16
18
17
15
RELAY TRI P1
4
9
10
11
12
13
5
7
6
8
1
3
2
RELAY TRI P2
OVERLOAD
CBF ALARM
UV&OV STG1
UV&OV STG2
NOT USED
NOT USED
NOT USED
NOT USED
RELAY TRI P1
RELAY TRI P2
UV&OV STG2
UV&OV STG2
ALARM
V
o
l
t
a
g
e
NOT USED
NOT USED
NOT USED
NOT SUED
START CBF_Bph
START CBF_Cph
CBF- 1
START 3- PH
CBF- 1
START A- PH
CBF- 1
START A- PH
CBF- 2
START A- PH
CBF- 3
START B- PH
CBF- 1
START B- PH
CBF- 2
RESET
M
e
a
s
u
r
e
m
e
n
t
START CBF_3ph
C
S
C
-
2
1
1

N
u
m
e
r
i
c
a
l

B
a
c
k
u
p

P
r
o
t
e
c
t
i
o
n

e
q
u
i
p
m
e
n
t
























M
a
n
u
a
l
-
3
2
-
1
2
.
2

T
e
r
m
i
n
a
l

D
i
a
g
r
a
m

o
f

M
O
D
E
L

2
O
u
t
p
u
t
14
19 NOT USED
GND 20
16
18
17 NOT USED
15 NOT USED
4
9
COM
POWER OFF
DC- I NPUT
11
10
12
13
5
7
6
8
1
3
2
X8
POWER COM
14
19
20
16
18
17
15
LOGI C2
RELAY TRI P1
4
9
10
11
12
13
5
7
6
8
X7
LOGI C1
1
3
2
X6
4
24V COM
9
11
10
12
6
7
5
8
CPU
RESET 2
3
1
X5
I
n
p
u
t
s
X4
AC2
4
4
6
5
9
10
12
11
5
6
7
8
AC2
2
3
1
X3
1
3
2
X2
4
9
10
12
11
5
6
7
8
AC1
1
3
2
X1
P
o
w
e
r

I
n
p
u
t
RELAY TRI P2
REMACCESS BLK
RELAY TEST
NOT USED
E
t
h
e
r
n
e
t
B
u
s
/
L
i
n
e
P
r
o
t
e
c
t
i
o
n

c
u
r
r
e
n
t
M
e
a
s
u
r
e
m
e
n
t
D
i
g
i
t
a
l

I
n
p
u
t
s
2
4
V
+24V
24V
NOT USED
NOT USED
UV&OV STG2
14
19
20
16
18
17
15
U/ F 1
4
9
10
11
12
13
5
7
6
8
1
3
2
NOT USED
ALARM
U/ F 2
U/ F 3
U/ F 4
OPERATI ON
CB CLOSED
NOT USED
NOT USED
NOT USED
E
t
h
e
r
n
e
t
RELAY TRI P1
RELAY TRI P2
U/ F 1
U/ F 1
U/ F 2
ALARM
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
V
o
l
t
a
g
e
UV&OV STG2
UV&OV STG2
UV&OV STG1
M
e
a
s
u
r
e
m
e
n
t
NOT USED
CSC-211 Numerical Backup Protection equipment Manual
-33-
13 Dimension drawings in mm
Dimension drawings for CSC-211 used 19/2 inch (4U) enclosure for panel flush-mounting
and cabinet mounting.
Fig.10 Flush-mounted enclosure of CSC-211 with panel cutout
CSC-211 Numerical Backup Protection equipment Manual
-34-
14 The Principle Outline of Logic Module
14.1 Logic 1 Module
V3
V4
V1
V6
V17
V18
V9
TOBLOCKDIGITALOUTPUTS
V19
+24V
24VCOM
24VCOM
V16
+24B
V20
9 12
QDJD
8 5
QDJC
DO4
DO2
DO3
DO5
DO2
DO12
DO11
+
1
-
16
CKJ5A
DSP1A-24V
+
1
-
16
CKJ4A
DSP1A-24V
V8
DO13
+
1
-
16
FGJA
DSP1A1B-24V
V7
+
1
-
16
QDJA
DSP2A-24V
DO1
V2
+
1
-
16
GJA
DSP1A1B-24V
5 8
GJB
+
1
-
16
U1
GJXA
DSP2A-L2-24V
5 8
FGJB
9 12
FGJC
12 9 GJE
+
2
-
15
U2
GJXB
DSP2A-L2-24V
+
1
-
16
U1
BHXHA
DSP2A-L2-24V
+
2
-
15
U2
BHXHB
DSP2A-L2-24V
+
1
-
16
CKJ1A
DSP2A-24V
+
1
-
16
CKJ3A
DSP2A-24V
START 3- PH CBF/ UF 4
START C- PH CBF/ UF 3
START A- PH CBF/ UF 1
START B- PH CBF/ UF 2
SI GNAL RESET
STARTUP
HARDWARE ALARM
ALARM
+
1
-
16
BHXH1A
DSP1A-24V
12 9
CKJ1B
X1
X2
START A-PH CBF-1/UF 1
5 8
CKJ1E
X3
X4
START A-PH CBF-2/UF 1
5 8
CKJ2B
X5
X6
START A-PH CBF-3/UF 1
12 9
CKJ3B
X7
X8
STARTB-PH CBF-1/UF 2
5 8
CKJ3E
X9
X10
START B-PH CBF-2/UF 2
5 8
CKJ5B
X13
X14
START3-PHCBF-1/UF 4
5 8
CKJ4B
X11
X12
STARTC-PH CBF-1/UF 3
5 8
BHXH1B
X15
X16
OPERATIONALARM
5 8
BHXHD
5 8
GJXD
X17
X18
OPERATIONALARM(LATCHED)
X19
ALARM
X20
X19
X18
X17
X16
X15
X14
X13
X12
X11
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
1
2
4
5
6
7
8
9
10
3
11
12
13
14
15
16
17
18
19
20
J2
+
1
-
16
CKJ2A
DSP1A-24V
DI14
TOCPUASADIGITALINPUT
V32
V33
V34
V35
V36
V37
DO3
DO4
DO5
DO6
DO7
X20
V38
V39
V40
DO8
DO9
DO10
CSC-211 Numerical Backup Protection equipment Manual
-35-
14.2 Logic 2 Module
1
2
4
5
6
7
8
9
10
3
11
12
13
14
15
16
17
18
19
20
J2
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
X14
X15
X16
X17
X18
X19
X20
V1
24VCOM
DO7
+
1
-
16
CKJ1A
DSP2A-24V
RELAY TRI P
+
1
-
16
CKJ2A
DSP2A-24V
12 9
QDJB
5 8
QDJE
5 8
CKJ4E
X13
X14 UV&OVSTG2
X15
X16 UV&OVSTG2
5 8
CKJ6B
X17
X18
OVERLOAD/NOT USED
X19
X20
12 9
CKJ7E
5 8
CKJ7B
1
3
2
LX1
5 8
CKJ2E
X7
X8 RELAY TRIP 2
5 8
CKJ3B
X9
X10 UV&OVSTG1
12 9
CKJ4B
X11
X12
12 9
CKJ1B
X1
X2 RELAY TRIP 1
5 8
CKJ1E
X3
X4 RELAY TRIP 2
12 9
CKJ2B
X5
X6 RELAY TRIP 1
5 8
CKJ5B
UV&OVSTG2
DO6
V6
+
1
-
16
CKJ3A
DSP1A-24V
UV&OV STG 1
V3
V4
DO9
DO8
DO10
+
1
-
16
CKJ7A
DSP1A1B-24V
+
1
-
16
CKJ6A
DSP1A-24V
V2
+
1
-
16
CKJ4A
DSP2A-24V
CBF ALARM/ NOT USED
OVERLOAD/ NOT USED
UV&OV STG 2
V5
+
1
-
16
QDJA
DSP2A-24V
DO1
STARTUP
+
1
-
16
CKJ5A
DSP1A-24V
CBFALARM/NOT USED
CSC-211 Numerical Backup Protection equipment Manual
-36-
15 Menu Frame
Tab.24
Abbr.
(LCD Display)
Meaning Remarks
OpStatus Operating Status
Analog Analog Input
Inspecting the analog input of the
equipment.
Measure Measurement analog input
Inspecting the measurement analog input of
the equipment.
DI Status of digital inputs Inspecting the status of digital inputs.
OpConfig
SetGr Settings Group Switching setting group
Time Configuring time
Settings Settings operation
Read Read settings
Write Write settings
Switch Switch settings group
Delete Delete settings
Report Query and manage report
Event Query the event report
Listing the time of the event reports which is
searched by time sect, selecting the report
with and key, inspecting the content
with SET key.
Alarm Query the alarm report
Listing the time of the alarm reports which is
searched by time sect, selecting the report
with and key, inspecting the content
with SET key.
Wave Query the report with wave
Listing the time of the reports with wave
which is searched by time sect, selecting the
report with and key, inspecting the
content with SET key.
Operate Query the operate report
Listing the time of the operate reports which
is searched by time sect, selecting the report
with and key, inspecting the content
with SET key.
Erase Erase report
Erase event Erase the event reports Erase all the event reports
Erase Alarm Erase the alarm reports Erase all the alarm reports
Erase Wave Erase the reports with wave Erase all the reports with wave
ComConf Communication Configure
Ether 1# Ethernet port 1 Set Ethernet port 1 in CPU module
Ether 2# Ethernet port 2 Set Ethernet port 2 in CPU module
Serial Set serial port
Type Communication type
select COM for 61850, select RS232 for
EPPC, and select RS485 for IEC103
BaudRate Baud rate select 9600
Parity Parity verify
Label Set the address Hex
Dev Addr Equipment address
STA name Name of station ASCII
Bay name ASCII
Testing
CSC-211 Numerical Backup Protection equipment Manual
-37-
DO Test the digital output
DI Test the digital input
Pilot Test the LED
Accuracy Test the accuracy of AI
zero Test the zero drift of AI Show the zero drift of protection AI
remote Remote test
Event Function operation
Alarm
Include hardware alarm, VT fail and trip
failure
Signal Digital input
Metering Measurement analog input
exper Experiment status
Setup
Module Select the network module
Network Setup the network module Only for the network in CPU module
DIO Set
If configure the DIO module. For 61850
protocal, it is OFF
Remote Remote setup Only used for 2000 protocal, not for 61850
Return Return mode
Manual return or automatic return of
information.
Analog
Protection AI or
measurement AI
Active deliver AI of IEC 103 (measurement
AI or measurement and protection AI)
Status Real time or extend
Parameter Time parameter
Setting Settings inside equipment Threshold of non-current
Measure Measurement analog timing
Zero Zero drift Adjust zero drift of measurement AI again
Scale Adjust AI Scale Adjust scale of measurement AI
Save Save the adjustment Save the adjustment for zero drift and scale
Clear Clear the energy Clear the pulse energy calculate
Printer Printer setup
DevInfo Device information
version Version of software
OpInfo Operation information
ETH1# Ethernet port 1 In CPU module
ETH2# Ethernet port 2 In CPU module
MMI Man machine interface
CSC-211 Numerical Backup Protection equipment Manual
-38-

You might also like