Professional Documents
Culture Documents
392133.bojcic Mestrovic 2009
392133.bojcic Mestrovic 2009
SUMMARY
In distribution area of Elektra ibenik, self-feeding protection relays WIC1-2-P-E, produced by
ABB, are mainly used at medium voltage blocks with switches, protecting thus distribution transformers
and distribution medium voltage power grid. These relays belog to the newer generation of protection
devices that use digital technology based on microprocessors for collecting and processing data related
to protection.
WIC1 relays of series 2-P-E, the same ones as those installed in the transformer station TS
10(20)/ 0.4 kV Tribunj 2, are used as protection from overload, short circuit and grounded circuit.
This report will present the selection of work mode, functional values and settings of the selffeeding relays WIC1-2-PE, with respect to the equipment configuration and associated distribution
network, in the transformer station TS 10(20) / 0.4kV Tribunj 2.
Key words: self-feeding relays, selection of work pattern, selection of functional values, settings,
protection,
1.
UVOD
esti ispadi el. energetskog sustava, te viesatno otklanjanje uzroka tih ispada kao i nepostojanje
zatite u transformatorskoj stanici TS 10(20)/0,4 kV Tribunj 2 kao vornoj toci preko koje su napojene
transformatorske stanice 10(20)/0,4 kV na otocima ibenskog arhipelaga Kaprije, irje, Obonjan, Zlarin,
zahtjevali su da se pristupi rekonstrukciji zranih SN 10 kV vodova, ali isto tako i revitalizaciji postojeeg
SN rasklopnog postrojenja u TS 10(20)/0,4 kV Tribunj 2, njegova uvoenja putem UHF radio signala iz
HEP-ODS-ova dispeerskog centra u ibeniku u sustav daljinskog voenja distribucijskog podruja
Elektre ibenik kao i ve spomenutog uvoenja i podeenja relejne zatite. Pri realizaciji ovog projekta
davala se je prednost izvedbi sekundarnog sustava koji zahtijeva najmanji obim radova na montai i
oienju u samom postrojenju a kako je revitalizacija transformatorske stanice na 10 kV naponskoj razini
ukljuivala i zamjenu SN opreme vodilo se rauna i o kompatibilnosti zatitnih ureaja i SN opreme.
S obzirom na snagu transformatora i iz nje rezultirajuu struju u trafo polju su ugraeni strujni
mjerni transformatori WIC1-W2, a s obzirom na struju optereenja izlaza Kaprije i nazivnu vrijednost
struje kabela strujni mjerni transformatori tip WIC1-W4 u vodnom polju V5 (Kaprije).
2.
Napajanje releja se vri pomou strujnih transformatora. Energija strujnih transformatora koristi
se takoer za ispravan rad i okidanje strujnog prekidaa (energija okidanje je osigurana preko
kapacitivnog spremnika u zatitnom releju) te prua strujni signal za obradu.
2
Relej ima tri analogna mjerna ulaza (3x fazna struja) a koji su posebno podeeni prema strujnim
transformatorima koji se koriste u WIC1 sustavu a koji su uvjetovani nazivnom strujom distributivnog
transformatora odnosno strujom optereenja tienog izlaza i nazivnom vrijednosti struje kabela/voda.
Samonapajajui strujni krug, kroz strujne transformatore, aktivira zatitne i mjerne funkcije, ak i
kad nema pomonog napajanja, poinjui od minimalne vrijednosti primarne struje od 0,2 x In. Jedinica
se moe uskladiti sa pomonim napajanjem sa 24 V d.c nominalnog napona (takvo rjeenje je
primjenjeno u TS 10(20)/0,4 kV Tribunj 2. Po potrebi je isitavajui pohranjene podatake u integriranu
memorijsku jedinicu mogue saznati koji je zatitni element izazvao isklop odnosno da li je isklop
uzrokovan vanjskim signalom.
4.
Ulazni parametri za izbor zatite svakako su uzemljenje neutralne toke (u sluaju TS 35/10 (20)
kV Vodice radi se o izoliranoj neutralnoj toki uz mogunost njenog uzemljavanja preko zajednikog
maloomskog otpornika), te konfiguracija mree, kao i provjere termikog naprezanja vodova. U novije
vrijeme svi potrebni prorauni izvode se pomou odgovarajueg raunalnog programa koji nam daje sve
potrebne podatke potrebne za podeenje zatite. U DP Elektra ibenik koriste programski paket
PowerCAD (prije TOKSwin).
Podeenje releja ostvaruje se preko DIP preklopki smjetenih s prednje strane releja
4.1.
4.1.1.
3 OFF
4 ON
Za relej odabrati emo tip isklopne krivulje (H/V fuse) pa DIP sklopke 5-8 u grupi 1 moraju biti
postavljene u slijedee poloaje:
5 OFF
6 ON
7 ON
8 OFF
5 ON
6 ON
7 OFF
8 ON
5
4.1.2.
S obzirom na nazivnu struju podmorskog kabela od 155 A, tip strujnih mjernih transformatora u
vodnom polju, zahtjev da se postigne to vea osjetljivost zemljospojne zatite te odabranu karakteristiku
prorade za nazivnu struju postavljamo na IS = 72 A pa poloaj DIP sklopki grupe 1 mora biti slijedei:
1 ON
2 OFF
3 OFF
4 OFF
5 OFF
6 OFF
7 OFF
8 OFF
Vrijeme prorade za ovaj relej uzeti emo prema karakteristici s postavljenim vremenski o struji
neovisnim vremenom prorade (DEFT).
5 OFF
6 OFF
7 OFF
8 ON
Kratkospojna zatita
Kratkospojna zatita podeava se DIP sklopkama grupe 3 i to:
-
4.2.1.
5 OFF
6 ON
7 OFF
8 OFF
IK3 = 504 A
U sluaju napajanja preko nadzemnog voda (VP Mrzanci) u TS 30/10 kV VODICE dobiveni su
slijedei rezultati:
IK2 = 406 A
IK3 = 469 A
tI>> = 0,4 s
tI>> = 0,1 s
Da bi se postavile navedene vrijednosti DIP sklopke grupe 3 moraju biti u slijedeim poloajima:
1 OFF
2 OFF
3 ON
4 OFF
4.3
5 OFF
6 ON
7 OFF
8 OFF
Zemljospojna zatita
Zemljospojna zatita podeava se DIP sklopkama grupe 4 i to:
-
podeenje proradne struje zemljospojne zatite s obzirom na nazivnu struju (x IS) sklopke
1-4
vrijeme prorade zemljospojne zatite sklopke 5-8
Da bi se postigla selektivnost i osigurala prorada kod malih struja (zemni spoj preko velikog
prelaznog otpora) podeenja DIP prekidaa moraju biti slijedee:
1 OFF
2 OFF
3 OFF
4 OFF
4.3.2.
5 OFF
6 OFF
7 OFF
8 OFF
IE> = 7,2 A
tIe> = 0,1
Poto se radi o neusmjerenoj zemljospojnoj zatiti u obzir prilikom podeenja moramo uzeti i
doprinos vodova koji se nalaze iza releja prilikom nastanka zemnog spoja (27 A) pa vrijednoti na koje
emo izvriti podeenje iznose:
IE> = 28,8 A
tIe> = 0,1 s
5 OFF
6 OFF
7 OFF
8 OFF
ISPITIVANJE ZATITE
5.
ispravnost oienja
podeene vrijednosti zatitnog releja
Ispravnost oienja
Ispitivanje zatite provodi se sklopom prikazanim na slici:
U slijedeoj tablici prikazane su struje koje treba narinuti da bi se ispitala zatita releja u trafo i
vodnom polju:
Trafo polje
zatita
nadstrujna
kratkospojna
zemljospojna
6.
ZAKLJUAK
Nove generacije numerikih releja u kojima su najee integrirane funkcije zatite, upravljanja,
nadzora, signalizacije i mjerenja sve su vie dio integriranog sustava zatite i voenja u distributivnoj
mrei. Mogunost pohranjivanja raznih podataka koji se mogu koristiti u analizama pogonskih dogaanja i
za potrebe voenja sustava kao i mogunost njihova koritenja za daljinsku komunikaciju na krugove
isklopa/uklopa omoguuje naim dispeerskim centrima kvalitetniji nadzor nad postrojenjioma i efikasnije
otklanjanje kvarova u sustavu.
S druge strane sve ubrzaniji razvoj novih releja, popratne opreme, sve sloenija struktura releja
stavlja pred problem nas korisnike zbog pomanjkanja dokumentacije. Naime, u dostupnim prirunicima
najvei dio sadraja se odnosi na konfiguraciju gdje se osnovna zatitna funkcija izjednaava i izgubi u
masi dodatnih funkcija koje relej nudi.
Ipak, pouzdan i siguran rad relejne zatite svakako su razlog da se krene u postupnu
revitalizaciju seundarnog sustava relejne zatite uvoenjem novih tehnologija i koncepcijskih rjeenja, a
sve s ciljem kvalitetnog napajanja potroaa.
LITERATURA
[1] ABB: Upute za koritenje releja serije WIC1-2-P-E, 2003.
[2] http://library.abb.com/
[3] DP Elektra ibenik: Elaborat rekonstrukcije SN bloka u TS 10(20)/0,4 kV Tribunj 2
10