MicroTron Auto-Monitoring & Dosing System

for Cooling Tower Water Treatment

taking a zero tolerance


approach to bacteria control,
delivers piece of mind
We know that open cooling tower systems offer perfect conditions for proliferation
and dissemination of bacteria such as Legionella.
While it is not possible to completely remove this risk without removal of the system,
it is possible to manage the risk. Taking a Zero Tolerance approach to bacteria
control is particularly important for management in high profile, high risk sites. At the
heart of any cooling water risk management plan is the chemical dosage system.
Inter-Chemicals offer full range of dosing control equipment that can be tailored to
suit all applications. Our equipment packages are classified as below:

Key Components:
1.0 MicroTron Controller (Model: LCFB-2AD)
 Microprocessor control for Cooling Tower conductivity monitoring.
 Standard electrodes in SCH 80 PVC female slip tees.
 Standard Tower Conductivity Probes: TE-4A: 150psi (10.3 bar)/ 140F (58C)
Max
 Conductivity Control: 0-5000 S/cm scale
 Accuracy: +/- 1%
 Feed Timers (Selectable)

Pulse: 0-99 min, 59sec run time, 1-99 counts


% of time: 0-99 min, 59sec run time, 1-99% time
Feed with Bleed: Limit timer 0-99 min, 59 sec
Post Feed Bleed: Limit timer 0-99 min, 59 sec cycle, 1-99% of bleed cycle
Tower Biocide Timer: 28 day programmable with pre-bleed and bleed lockout
functions

 Enclosure: Heavy duty NEMA 4X type high impact thermoplastic with


padlockable gasketed Lexan viewing door.

2.0 Peristaltic Pump (Model: MP2-R) : 3 units







Adjustable speed
IP 65 rating enclosure
Maximum Capacity: 1 litre/hour.
Maximum pressure: 3 bar (43.5psi)

Liquid Ends Material


Component
Roller Tube
Fittings
Foot Filter
Injection Valve
Discharge Tube
Suction Tube

Standard
EDPM
PP
AISI 316
AISI 316 - Viton
PE 4 x 6 mm (0.15 x 0.23)
Clear PVC 4 x 6 mm (0.15 x 0.23)

3.0 Flow Assembly with Injection Points









Burkert 2/2-way Solenoid Valve type 5281.


Chemical Injection socket
Sensor holder socket
PVC check valve
Isolation ball valve
Sampling Ball Valve

4.0 PP Board with pipe bracket


 Dimensions: W 400mm x H 800 mm
 Fully assemble system and fixed to the board

5.0 Applications





Re-circulating water systems.


Cooling Tower water treatment system
Auto bleed-off with conductivity control
Fully automated chemical feed and biocide control

Recommended for High Risk/High Profile sites such as Hotels,


hospitals, shopping centres, high-rise CBD buildings as well as
remote locations. Recognised as industry best practice.