Professional Documents
Culture Documents
# 1 in Dehumidification
Date : 02-Dec-2014
By : HVB
CONDITIONED SPACE
Internal Latent Load :
489229 Grs/#
61416 BTUH
DBT
RH
66.2 F
Abs. Hum.
40 +5 %
40.8 Grs/#
SUPPLY AIR
After Coil
9462CFM
55 F
28.2 Grs/#
9462 CFM
94.5 F
28.2 Grs/#
1962 CFM
55 F
68.9 Grs/
BYPASS AIR
7500 CFM
104.8 F
17.5 Grs/#
1962 CFM
55 F
68.9 Grs/#
PROCESS OUT
REACT IN
Precool Coil
PROCESS IN
9462 CFM
FRESH AIR
83 F
154.6 Grs/
44.2 BTU/
REACT OUT
7500 CFM
55 F
68.9 Grs/#
23.9 BTU/#
55 F
68.9 Grs/#
FLB-12500 x 1
MODEL
BTUH
312660
UTILITIES REQD.
Precoil Load
After Coil
BTUH
= 823194
= 403648.9 BTUH
=
=
TOR
68.6
33.6
TOR
REACTIVATION
Electric
KW
Steam
= 0
Kgs/Hr @ 7 Kgs/cm2
HP
LEGEND
MOTOR DETAILS
Process
=
Electrical Connection
Standard Unit Dimension
HP
Reactivation
= OR
mm
OR
mm
H.B
OR
mm
F.B
HEATER BLANK
FILTER BANK
React.
REACTIVATION