Professional Documents
Culture Documents
Use of Plastic Waste in Construction of Bituminous Roads
Use of Plastic Waste in Construction of Bituminous Roads
Submitted in partial fulfillment of the requirements for the award of the degree of
Bachelor of Technology
In
CIVIL ENGINEERING
By
11741A0168
S. SANJEEV KUMAR
11741A0176
B. RANGANATH
12745A0112
N. RAVI TEJA
12745A0113
CH. SUDHEER
12745A0117
B. VIJAY
12745A0122
ABSTRACT
properties were evaluated. Now, the concrete with recycled wastes are prepared and these are
also tested for their properties, likewise all the seven mixes were prepared. For every mix 18
specimens (6 cubes, 6 cylinders, 6 impact specimens) were casted and thus totally 126
2
specimens were prepared. Specimens of every mix were tested for compressive strength at 7
and 28 days after curing.
With constant percentage replacement of plastic waste in place of sand and
varying percentage replacement of coarse aggregate with demolished aggregate, it is found
that the density of concrete can be varied from 2500 to 2100 kg/m3. The workability of fresh
concrete was decreased with increase in addition of recycled aggregate. From the results it is
found that by replacing the natural sand and coarse aggregate by plastic waste and recycled
aggregate in the normal concrete, compressive strength (fck) and split tensile strength (ft)
increases upto 10% and then decreases with increase of recycled wastes.
From the experimental investigation, it is concluded that fine aggregate
replaced with 10% of plastic waste and coarse aggregate replaced with 10% of recycled
aggregate, the properties of fresh concrete were good and also it reached the target mean
strength of conventional concrete.
CONTENTS
ABSTRACT
List of Tables
iii
List of Figures
iv
List of Plates
Nomenclature
vi
CHAPTER - 1
Introduction
CHAPTER - 2
Review of Literature
CHAPTER - 3
Objective and Scope of Investigation
CHAPTER - 4
Experimental Investigation
Tables
20
Plates
22
4
CHAPTER - 5
Discussion of Test Results
26
Table
28
Figures
31
Plates
33
CHAPTER - 6
Conclusions & Recommendations
34
Appendix
36
References
41
LIST OF TABLES
4.1
4.2
4.3
5.1.1
5.1.2
5.2.1
5.2.2
5.2.3
LIST OF FIGURES
Fig 5.1.1
Fig 5.2.1
Fig 5.2.2
Fig 2.2.3
LIST OF PLATES
Plate 4.1
Plate 4.2
Plate 4.3
Plate 4.4
Plate 4.5
Plate 4.6
Plate 4.7
Plate 4.8
Plate 4.9
Plate 4.10
Plate 4.11
Plate 4.12
Plate 4.13
Plate 5.1
NOMENCLATURE
1. Kg
Kilogram
2. Lit
Litre
3. KN
Kilo newton
4. KN/s
5. Kg/m3
6. N/mm2
7. mm
millimeter
8. fck
9. ft
10. P
11. L
12. D
13. PW
Plastic Waste
14. RCA
15. CA
Coarse Aggregate
16. FA
Fine Aggregate
17. ASTM
18. ISI
19. N
20. A
10% Plastic waste, 90% natural Sand and 100% natural coarse aggregate
concrete
21. B
22. C
23. D
24. E
25. F
10% Plastic waste, 90% natural Sand, 50% Demolished aggregate and
50% natural coarse aggregate concrete
10
CHAPTER-1
INTRODUCTION
GENERAL
Now-a-days infrastructure development across the world created demand for
construction materials. Concrete is the premier civil engineering construction material,
concrete contains ingredients like cement, aggregates, water and admixtures. At present,
huge quantities of construction materials are required in developing countries due to
continued infrastructural growth and also huge quantities of plastic wastes and demolition
wastes are generated every year in developing countries like India. The disposal of this waste
is a very serious problem because on one side it requires huge space for its disposal while on
the other side it pollutes the environment. It is also necessary to protect and preserve the
natural resources like stone, sand etc. Continuous use of natural- resources, like river sand is
another major problem and this increases the depth of river bed resulting in drafts and also
changing the climatic conditions.
So, the sustainable concept was introduced in construction industry due to growing
concern about the future of our planet, because it is a huge consumer of natural resources as
well as waste producer. This has created what we call the biggest problem of the world,
demolished waste and plastic waste accumulation. Hence there is a need to recycle these
waste into something more useful and environment friendly. To achieve this, major emphasis
must be laid on the use of waste from various industries. The use of aggregates from
construction and demolition waste in pavement beds is the most usual way of reusing this
material. Even though considered as a valid re-use technique, it is not the best economic
valorization of this resource and it is considered by many researchers to be a down-cycling
process that depreciates the capacities of the material. But the production of structural
concrete with recycled aggregates, however, offers great potential and recycles the materials
11
viably and effectively. Research into new and innovative use of waste materials being
undertaken world-wide and innovative ideas that are expressed are worthy of this important
subject.
12
CHAPTER-2
REVIEW OF LITERATURE
In this chapter a brief literature survey conducted on utilization of plastic waste and
demolished waste in making concrete has been presented.
Recycled aggregate is becoming an increasingly popular way to utilize aggregate left
behind when structures or roadways are demolished and also the waste plastics which are
produced from industries and households. In the past, these two wastes were disposed of in
low lying areas, but with more attention being paid to environmental concerns, concrete
recycling allows reuse of the plastic waste and demolished waste while also keeping
construction costs down. When structures made of concrete are demolished or renovated and
also when the plastics are thrown away after getting used, concrete recycling is an
increasingly common method of utilizing the rubble and plastic waste individually or
combined. Concrete and Plastic waste was once routinely trucked to landfills for disposal,
but recycling has a number of benefits that have made it a more attractive option in this age
of greater environmental awareness, more environmental laws and the desire to keep
construction costs down.
Tomas U. Ganiron Jr. [1] has reported that Plastic as a substitute to fine aggregate to
concrete mixture has shown unusual characteristic upon accumulation of water in the mixture
for the material had floated on the surface of the water, nevertheless, upon the completion of
mixing the material has suitably bonded to the mixture. In the analysis of its grain particle, in
comparison to sand, which is one of the major components of concrete mixture, plastic,
implies significant lightness in terms of its mass evaluation. Overall, the effect of the plastic
on the properties of the specimen was acceptable.
13
Shodolapo Oluyemi Franklin, Mmasetlhomo Tommy Gumede, [2] stated that it is obvious
that structural compressive strengths may be developed in concretes incorporating up to
100% recycled aggregates based on standard mix design procedures. They also noted that the
compressive, split tensile and flexural strengths, as well as the modulus of elasticity of
recycled aggregate concretes, are generally lower than that of conventional concretes made
entirely from natural aggregates.
Ganesh Tapkire1, Satish parihar, et al.,[3] reported that by using the plastic in concrete mix
reduces to the weight of cube upto 15% and it is possible to use the plastic in concrete and
bonding admixture in concrete and also increase the percentage of plastic in concrete.
Shiva Kumar. M, Nithin K, B.M Gangadharappa, [4] reported that aggregate ratio of 1:8 with
50 % of CA and 50% of Building Demolished Waste (BDW) is recommended for low
traffic volume. Similarly mix design with w/c ratio of 0.40 and 0.45 with 50% of CA and
50% of BDW is suitable for intended use.
Youcef Ghernouti, Bahia Rabehi, et al.,[5] stated that the bulk density has decreased
considerably for all concretes with the content of replacement of sand by plastic waste that
also becomes lighter than conventional concrete with 40% of plastic waste. Being given that
the concrete must have good workability, fluidity is significantly improved by the presence
of this waste.
Ashraf M. Wagih, et al., [6] stated that concrete rubble could be transformed into useful
recycled aggregate used in concrete production with properties suitable for most structural
concrete applications.
14
Mohd. Monish et al., [7] stated recycled aggregate concrete may be an alternative to the
conventional concrete and water required producing the same workability increases with the
increase in the percentage of demolished waste.
Nitish Puri, Brijesh Kumar, Himanshu Tyagi, [8] stated that there is a considerable increase
in the compressive strength as well as flexural strength of concrete when the aggregates are
fully or partially replaced with construction debris. However maximum strength was shown
by concrete mix having 25% recycled debris aggregates and 75% natural aggregates.
Mohan Reddy, Bhavani and Ajitha [9] reported that the present study reveals that concrete
can be successfully produced using Recycled Coarse Aggregate (RCA) that have been
produced from demolition and construction waste. Concrete produced by RCA does not
perform as well as concretes produced by CA in terms of strength. However, the concrete
still has a strength that would make it suitable for some applications.
K. Ramadevi, R. Manju [10] was observed that the split tensile strength increased up to 2%
replacement of the fine aggregate with PET bottle fibers and it gradually decreased for 4%
and 6% replacements. Hence, the replacement of the fine aggregate with 2% replacement
will be reasonable with high split tensile strength compared to the other specimens casted
and tested.
R. Kumutha and K. Vijai [11] reported that from the obtained results, it is clear that there is a
possibility to use crushed coarse aggregate in making concrete since the target mean strength
is achieved. As there is considerable reduction in flexural strength with recycled aggregates,
further research is needed to explore about the usage of recycled aggregates in combination
of different fibrous materials.
15
Prabir Das, R. Lakshmi, S. Nagan, et al., [12] has reported that the use of waste plastics in
concrete is relatively a new development in the world of concrete technology and lot of
research must be done to use this material is actively used in concrete construction. The use
of plastics in concrete lowered the strength of resultant concrete, therefore. The research
must be oriented towards systems that help in overcoming this drawback of use of plastics in
concrete.
Al-Manaseer AA, Dalal TR, et al., [13] stated that a reduction in the mechanical resistance
according to the increase in percentage of plastic waste, which remains always close to the
reference concrete, when they recorded a fall of compressive strength at 28 days about 10
and 24 % or the concretes containing 10 and 20 % of waste respectively.
Keeping the above literature survey in view, in the present investigation, an attempt has been
made to study the behavior of concrete which comprises of both waste plastic and
demolished waste in various percentage replacement to fine aggregate and coarse aggregate
respectively.
16
CHAPTER-3
3.2 OBJECTIVES
The specific objectives of the present investigation are as listed below.
To conduct the feasibility study of producing concrete with plastic waste and
demolished aggregate.
18
CHAPTER-4
EXPERIMENTAL INVESTIGATION
To start with mix design has been conducted for M25 concrete making use of ISI
method of mix design using normal constituents of concrete. In the course of investigation,
natural sand has been replaced by 10% (constant for all the mixes) of plastic waste and also
coarse aggregate has been replaced by 0%, 10%, 20%, 30%, 40% and 50% of demolished
aggregate. For the study of various properties different specimens has been cast and tested.
Here a constant water-cement ratio of 0.45 has been adopted. The experimental part of the
investigation has been planned in the following three stages.
Stage I:
Stage II:
Stage III:
Testing of specimens
STAGE I:
Main constituents of concrete viz., fine aggregate, coarse aggregate, cement, water,
plastic waste and demolished aggregate have been procured from various places. Fine
aggregate has been procured from local river, coarse aggregate (20mm) has been procured
from plant. Potable water is used for mixing and curing of concrete. Plastic waste (1-4mm
sizes pieces) which is produced from households, factories, commercial places etc., has been
procured from Estate (Bellary Bypass) and the demolished aggregate is obtained from
demolished buildings, tested concrete specimens from laboratory are procured and made into
pieces and they are sieved to 20mm size.
19
Cement :
Locally available Nagarjuna Ordinary Portland Cement (OPC) of 53 grade of cement
brand conforming to ISI standards has been procured and various tests have been carried out
according to IS8112-1989 from them it is found that
a) Specific gravity of cement is 3.15
b) Initial and Final setting times of cement are 32 minutes and 580 minutes
respectively
c) Fineness of cement is 4%
Fine aggregate:
Locally available river sand is procured and is found to be conformed to Zone-I of table 4 of
IS:383-1970. Various tests have been carried out as per the procedure given in IS: 383-1970.
From them it is found that
a) Specific Gravity of fine aggregate is 2.60
b) Bulk Density
Loose: 1400 kg/m3
Compacted: 1557 kg/m3
c) Fineness modulus of fine aggregate is 2.90
The sieve analysis results are presented in Table 4.1 and the set of sieves is shown in
Plate 4.3
Plastic Waste:
The waste plastics are collected from dump sites and from various factories, the collected
plastic is cleaned and made into pieces of varying size from 1-4 mm. Various tests have been
conducted on plastic waste and following results are found out.
a) Specific gravity of plastic waste is 0.46
b) Density of plastic waste is 72 kg/m3
c) Fineness Modulus of plastic waste is 4.7
20
Coarse Aggregate:
Machine crushed aggregate conforming to IS: 383-1970 consisting of 20mm maximum size
of aggregates has been obtained from the local quarry. The test result of coarse aggregate as
below.
a) Specific Gravity of coarse aggregate is 2.64
b) Water absorption of coarse aggregate is 1.02%
c) Bulk Density
Loose: 1481 kg/m3
Compacted: 1651kg/m3
d) Fineness modulus of Coarse aggregate is 6.75
The sieve analysis results are presented in Table 4.2 and the set of sieves is shown in Plate4.4
Demolished Aggregate:
Demolished aggregate is procured from demolished structures and the concrete specimens
from laboratory. After collecting, they are broken down into pieces and also various tests are
conducted on it.
a) Specific Gravity of Demolished aggregate is 2.45
b) Water absorption of demolished aggregate is 0.31%
The demolished aggregate is shown in Plate 4.2 and its sieve analysis results are presented in
Table 4.3
Water:
Potable water which is available in the laboratory has been used in this experimental program
for mixing and curing.
21
MIX DESIGN:
Mix design can be defined as the process of selecting suitable ingredients of concrete
and determining their relative proportions with the objective of producing concrete of certain
minimum strength and durability as economically as possible. The design of concrete mix is
not a simple task on account of widely varying properties of the constituent materials, the
condition that prevail at the work and the condition that are present.
Design of concrete mix requires complete knowledge of various properties of the
constituent materials, the complications, in case of changes on these conditions at the site.
The design of concrete mix needs not only the knowledge of material properties of concrete
in plastic condition, but also needs wider knowledge and experience of concreting. Even
then, the proportion of the materials of the concrete found out at the laboratory requires
modifications and readjustments to suit the field conditions.
In the present investigation M25 grade of concrete is considered. The mix of concrete
is designed as per the guidelines given in IS 10262, and the mix proportion is 1:1.36:2.66
with a water/cement ratio of 0.45. Subsequently mixes were prepared with replacement of
fine aggregate by plastic waste at a constant percentage of 10% and replacing the coarse
aggregate by demolished aggregate at percentages of 0, 10, 20, 30, 40 and 50. For every
weight replacement cubes, cylinders and impact specimens are cast and tested to find various
test results.
Mixing of Concrete:
Initially the ingredients such as cement and sand are mixed, to which plastic waste is
added and thoroughly mixed. After some time coarse aggregate and demolished aggregate
are added and thoroughly mixed. Water is measured exactly, then it is added to the dry mix
and it is thoroughly mixed until a mixture of uniform colour and consistency are achieved
which is then ready for casting. Prior to casting of specimens, workability is measured in
accordance with the code IS: 1199-1959 and determined by slump and compaction factor
tests.
22
STAGE II:
Casting of Specimens:
After the completion of workability tests, the concrete has been placed in the standard
metallic moulds in three layers and has been compacted each time by tamping rod. Before
placing the concrete inside faces of the mould are coated with the machine oil for easy
removal after wards. The concrete in the moulds have been vibrated for 30 seconds using the
table vibrator and the surfaces of the specimens have been finished smoothly. The cast
specimens are shown in Plate 4.8.
This distance will be the slump of the concrete. The apparatus of slump cone and slump is
show in Plate 4.5. When practicable, duplicate slump test should be made and the average of
the two slumps reported. The concrete temperature at time of testing should also be reported.
The entire operation from the start of filling to the removal of the mould should be carried
out without interruption and be completed within an elapsed time of 1.5 minutes.
Density of concrete:
The density of concrete varies, depending on the density of the aggregate used to mix
the concrete and the amount of air within it. Floors, bridges and other structural components
use high-density concrete, while low-density concrete works in areas with harsh weather and
in some roads. Density is defined as mass divided by volume. Kilogram per cubic metre is
the typical unit for measuring concrete density. The unit weight is determined by the formula
below.
D = (McMm)/Vm
Where,
D = Density of the concrete in N/m3
Mc = Weight of the measure holding the concrete in N
Mm =Weight of the empty concrete measure in N
Vm = Volume of the measure in m3
Fresh concrete in the Mould is shown in Plate 4.7
Curing Procedure:
After the casting of cubes, cylinders and impact specimens, the moulds are kept for
air curing for one day and the specimens are removed from the moulds after 24 hours of
casting of concrete specimens. Marking has been done on the specimens to identify the
percentage of plastic waste and percentage of Demolished aggregate. Then they are placed in
24
water tank for curing. All the specimens have been cured for desired age. Specimens in
curing tank are shown in Plate 4.9
The identification of the specimens is as follows:
1. N-100% Natural aggregate concrete or Conventional concrete
2. A -10 % Plastic waste, 90% Natural Sand and 100% Natural coarse aggregate
concrete
3. B - 10% Plastic waste, 90% Natural Sand, 10% Demolished aggregate and 90%
Natural coarse aggregate concrete
4. C-10% Plastic waste, 90% Natural Sand, 20% Demolished aggregate and 80%
Natural coarse aggregate concrete
5. D-10% Plastic waste, 90% Natural Sand, 30% Demolished aggregate and 70%
Natural coarse aggregate concrete
6. E-10% Plastic waste, 90% Natural Sand, 40% Demolished aggregate and 60%
Natural coarse aggregate concrete
7. F-10% Plastic waste, 90% Natural Sand, 50% Demolished aggregate and 50%
Natural coarse aggregate concrete
25
For each percentage of plastic waste and demolished aggregate, 6 cube specimens
have been cast. In all 42 cubes of size 150mm x 150mm x 150mm have been cast.
For each percentage of plastic waste and demolished aggregate, 6 impact specimens
have been cast. In all 42 impact specimens of size 150mm diameter and 75mm height
have been cast.
STAGE III :
26
Compressive strength =
Load
Area
in N/mm2
Where,
P= Compressive load on the cylinder
L= Length of the cylinder
D= Diameter of the cylinder
The results have been tabulated and graphical variations have been studied
27
The impact resistance of the specimen was determined by using drop weight method
of Impact test recommended by ACI Committee 544 procedure. The size of the specimen
considered is 150mm diameter and 75mm thickness and the weight of hammer (m) is 4.54
Kg with a drop of 457mm (h). The specimens are placed on the base plate with the finished
face up and positioned within four lugs of the impact testing equipment. The bracket with the
cylindrical sleeve is fixed in place and the hardened steel ball is placed on the top of the
specimen within the bracket. The drop hammer is then placed with is base upon the steel ball
and held vertically. The hammer is dropped repeatedly; the number of blows required for the
first visible crack to form at the top surface of the specimen is recorded and also for ultimate
failure is recorded.
The first crack was based on visual observation (N1). White washing the surface of
the test specimen facilitated the identification of this crack. Ultimate failure is defined in
terms of the number of blows required to open the cracks in the specimens (N2) sufficiently
to enable fractured pieces to touch three of the four positioning lugs on the base plate. The
stages of ultimate failure are clearly recognized by the fractured specimen butting against the
lugs on the base plate. A view of showing the impact energy test is shown in Plate 4.12.
The impact resistance of the specimen was determined at 28 days. The first visible
crack (N1) and then cause ultimate failure (N2) were noted for all the specimens. The impact
energy delivered to the specimen is calculated from equation given below.
EI = N x m x g x h
Where,
EI is Impact Energy (N m),
N is the number of blows,
m is mass of the drop hammer (kg),
g is gravity acceleration (m/sec2) and
h is height of drop hammer (m).
The results have been tabulated and graphical variations have been studied.
28
IS
Sieve
No.
Weight Retained
in (Grams)
Cumulative Weight
Retained in (Grams)
Cumulative
Percentage Weight
Retained (X)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
4.75
2.36
2.00
1.18
0.6
0.425
0.3
0.125
0.09
Pan
0
97
45.8
223.7
350
58.7
120.7
94.1
7.8
2.2
0
97
142.8
366.5
716.5
775.2
895.9
990
997.8
1000
0
9.7
14.28
36.65
71.65
77.52
89.59
99.00
99.78
100
Cumulative
Percentage
Weight Passing
N=100-X
100
90.30
85.72
63.35
28.35
22.48
10.41
1.0
0.22
0
IS
Sieve
No.
Weight Retained
in (Grams)
1.
2.
3.
4.
5.
6.
7.
25
20
12.5
10
6.3
4.75
Pan
0
1660
2080
1035
145
40
40
0
Cumulative Weight
Cumulative
Retained in
Percentage Weight
(Grams)
Retained (X)
0
1660
3740
4775
4920
4960
5000
5000
0
33.2
74.8
95.5
98.4
99.2
100
100
Cumulative
Percentage Weight
Passing
N = 100-X
100
66.8
26.2
4.5
1.6
0.8
0
0
IS
Sieve
No.
Weight Retained
in (Grams)
1.
2.
3.
4.
5.
6.
7.
26.5
20
12.5
10
6.3
4.75
Pan
180
2760
1920
110
20
10
0
Cumulative
Cumulative
Weight Retained in Percentage Weight
(Grams)
Retained (X)
180
2940
4860
4970
4990
5000
5000
3.6
58.6
97.2
99.4
99.8
100
100
30
Cumulative
Percentage Weight
Passing
N= 100-X
96.4
41.4
2.8
0.6
0.2
0
0
Plate 4.1
Plate 4.2
31
PLATE 4.3
32
THE MOULD
SPECIMENS IN MOULDS
33
PLATE 4.10
A VIEW OF COMPRESSION
TESTING OF CUBE
CHAPTER-5
Compressive Strength:
The Cube compressive strength results with constant percentage replacement of fine
aggregate by plastic waste and varying percentage replacement of coarse aggregate by
demolished aggregate are presented in Table 5.2.1. The graphical variation of compressive
36
strength versus percentage replacement of fine aggregate by plastic waste and varying
percentage replacement of coarse aggregate by demolished aggregate are presented in Fig
5.2.1. From the above Table and Figure it may be observed that there is a decrease in
compressive strength with 10% Plastic waste and 0% to 50% replacement of demolished
waste in place of natural sand and coarse aggregate.
37
WORKABILITY OF CONCRETE
Table 5.1.1
Mix Name
% of Plastic
Waste
Slump in mm
Compaction
Factor in %
% of
Demolished
Waste
0
80
85.00
10
100
89.00
10
10
90
82.50
10
20
75
89.20
10
30
50
83.40
10
40
30
82.10
10
50
20
84.30
Mix Name
% of Plastic
Waste
% of
Demolished
Waste
Density in kg/m3
2373
10
2135
10
10
2270
10
20
2174
10
30
2188
10
40
2165
10
50
2130
38
Mix Name
3
4
5
6
7
21.60
14.07
24.40
8.15
30.96
10.74
27.50
11.11
25.75
8.15
22.30
Mix Name
3
4
5
6
7
39
2.23
2.04
2.39
1.75
2.32
1.70
1.94
1.68
1.86
1.67
1.72
Mix
Code
Mix Name
Conventional Concrete
Initial Crack
Impact Energy
(Nm) at 28
Days
9661.20
6492.80
5617.60
7408.70
6954.14
6085.72
5102.00
40
2400
FA and CA
replaced with
PW and RCA
2350
2300
2250
2200
2150
2100
2050
2000
Type Of Mix
Fig 5.1.1 Density of Concrete Vs. Percentage Replacement of Plastic waste and Demolished
Aggregate
35
30
7 Days
25
28 Days
20
15
10
5
0
Type Of Mix
Fig 5.2.1 Cube Compressive strength Vs. Percentage Replacement of Plastic waste and
Demolished Aggregate
41
8
7
7 Days
28 Days
5
4
3
2
1
0
Type Of Mix
Fig 5.2.2 Split Tensile Strength Vs. Percentage Replacement of Plastic waste and
Demolished Aggregate
Impact Energy Of Specimen at 28
days in Nm
12000
Impact
Energy
At First
Crack
10000
8000
6000
4000
2000
0
Type Of Mix
Fig 5.2.3 Impact Energy of Concrete Vs. Percentage Replacement of Plastic waste and
Demolished Aggregate
42
43
CHAPTER-6
4. However maximum strength was shown by concrete mix having 10% plastic
waste aggregates and 20% demolished aggregates. Hence this is supposed to be
the best combination with respect to compressive strength. On overall basis, it is
observed that compressive strength increases with increase in demolished
aggregate content and reaches an optimum value of 20% (and 10% plastic waste)
and afterwards it gets decreased for various contents of demolished aggregate.
5. The Split tensile strength of Plastic waste and recycled aggregate concrete is seen
to decrease with increase in percentage of demolished aggregate (and also plastic
waste) content and reaches an optimum value at 20% (and 10% plastic waste) and
afterwards gets decreased with increase in content of demolished aggregate.
6. Use of these waste materials not only cuts down the cost of construction, but also
contributes in safe disposal of waste materials.
7. The production cost decreased remarkably.
44
RECOMMENDATIONS
The following recommendations are done from the investigation :
1. This type of concrete can be effectively used in construction of simple,
unimportant and non-load bearing structures.
2. This type of concrete can be used in making of lightweight concrete.
3. This type of concrete can be used in laying roads in rural areas and also for
construction of footpaths.
4. In future, work should be done in such a way that the percentage of plastic waste
is also to be varied in different percentages along with the demolished waste to
know its characteristics and performance.
5. Sand and Coarse aggregate can be replaced successfully in concrete.
6. Work can be carried out on other wastes such as E-waste, PVC waste etc., for its
replacement in place of fine aggregate.
45
APPENDIX1
25 N/mm2
20mm
0.90
medium
e) Type of exposure
mild
3.15
i) Coarse aggregate
2.64
2.60
0.87
i) Coarse aggregate
Nil
Nil
c) Specific gravity
d) Specific gravity
i) Waste plastic
e) Water absorption
46
Nil
Nil
i) Coarse aggregate
9.09
3.20
Where,
ck = target average compressive strength at 28 days.
fck =characteristic compressive strength at 28 days.
S=Standard deviation.
t =Assumed as per IS 456-2000=1.65
47
Water-Cement Ratio:
Adopt water cement ratio as 0.45
48
Change in condition
0%
-2.4%
+3%
0%
0%
+1.5%
+3%
-0.9%
49
For the specified maximum size of aggregate of 20mm, the amount of entrapped air in the
wet concrete is 2%
V= [W+C/SC+(1/P)*Fa/Sfa]*1/1000
0.98=(191.6 +
426
3.15
1
0.341
2.64
1
1000
V= [W+C/SC+(1/P)*Ca/Sca]*1/1000
0.98=(191.6 +
426
3.15
1
10.341
2.64
1
1000
WATER
CEMENT
F.A
C.A
192
426
579
1136
0.45
1.36
2.66
This mix is 0.45: 1: 1.36: 2.66 (by mass). For 50 kg of cement, the quantities of materials are
worked out as below:
Cement =50 kg
Water content = 22.5 litres
Fine aggregate = 68 kg
Coarse aggregate = 133 kg
50
REFERENCES
[1] Tomas U. Ganiron Jr. (2014) Effect of Thermoplastic as Fine Aggregate to Concrete
Mixture International Journal of advanced science and technology, volume 16.
[2] Shodolapo Oluyemi Franklin1, Mmasetlhomo Tommy Gumede, (2014)Studies on
Strength and Related Properties of Concrete Incorporating Aggregates from Demolished
Wastes Open Journal of Civil Engineering, 311-317,.
[3] Ganesh Tapkire1, Satish parihar, et al., (2014) Recycled plastic used in concrete paver
block, IJRET Volume: 03 Special Issue: 09.
[4] Shiva Kumar. M, Nithin K, B.M Gangadharappa, (2014) Use of building demolished
waste as coarse aggregate in concrete, IJRET, vol. (3).
[5] Youcef Ghernouti, Bahia Rabehi, Brahim Safi and Rabah Chaid, (2013) Use of Plastic
Bag Waste in the Concrete JIS Publications, vol.(8).
[6] Ashraf M. Wagih, Hossam Z. El-Karmoty, Magda Ebid, Samir H. Okba,
(2013)Recycled construction and demolition concrete waste as aggregate for structural
concrete HBRC Journal 9, 193-200.
[7] Mohd Monish, Vikas Srivastava1, V.C. Agarwal1, P.K. Mehta and Rakesh Kumar,
(2013) Demolished Waste as coarse aggregate in concrete J. Acad. Indus. Res. Vol. 1(9).
[8] Nitish Puri, Brijesh Kumar, Himanshu Tyagi, (2013) Utilization of Pulverized plastic in
cement concrete as fine aggregate International Journal of Innovative Technology and
Exploring Engineering (IJITEE) Volume-2, Issue-2.
[9] Mohan Reddy, Bhavani and Ajitha, (2012) Local Construction And Demolition Waste
Used As Coarse Aggregates In Concrete IJERA Vol. 2, Issue 5, October.
[10] Ms. K.Ramadevi, Ms. R. Manju, (2012) Experimental Investigation on the Properties
of Concrete With Plastic Bottle Fibers as Fine Aggregates, IJETAE, Vol. 2, Issue 6.
[11] R. Kumutha and K. Vijai, (2010) Strength of Concrete incorporating aggregates
recycled from Demolition Waste ARPN Journal, Vol. 5.
51
[12] Prabir Das, (2004) Engineering Plastics: New Generation Products for Building and
Construction, CE & CR.
[13] Al-Manaseer AA, Dalal TR, (1997) Concrete containing plastic aggregates, Concrete
International, vol. 19, no. 8, pp. 4752.
[14] MirjanaMaleev, Vlastimir Radonjanin and Sneana Marinkovi,(2010) Recycled
Concrete as Aggregate for Structural Concrete Production.
[15] Al-Manaseer AA, Dalal TR, (1997), Concrete containing plastic aggregates, Concrete
International, vol. 19, no. 8, pp. 4752.
[16] P.M. Subramanian, Plastic recycling and waste Management in the US Resources,
Conservation and recycling vol. (28) pp 253263.
[17] S R Yadav, S R Pathak, (2009) Use Of Recycled Concrete Aggregate In Making
Concrete- An Overview 34th Conference on OUR WORLD IN CONCRETE &
STRUCTURES: 16 18 August 2009, Singapore.
[18] Hassani, A, Ganjidoust, H, & Maghanaki, AA, (2005), Use of plastic waste (polyethylene terephthalate) in asphalt concrete mixture as aggregate replacement. Waste
Management & Research, vol. 23, pp. 322327.
[19] Mehta, P.K.,(2001) Reducing the environmental impact of concrete, Concrete. Int.,
23(10), 61-66.
[20] Yong, P.C and Teo, D.C.L. (2009), Utilization of Recycled Aggregate as Coarse
Aggregate in Concrete, UNIMAS E-Journal of Civil Engineering, Vol.1(1), pp.1-6.
[21] Raghatate Atul M Use Of Plastic In A Concrete To Improve Its Properties of A.S.
Polytechnic, India in International Journal of Advanced Engineering Research and Studies.
[22] Ryu, J.S. (2002), An experimental study on the effect of recycled aggregate on concrete
properties Res. 54(1): 7-12
[23] Baboo R, Tabin-Rushad S, Bhavesh KR, Duggal SK, (2012), Study of waste plastic
mix concrete with plasticizer, International Scholarly Research Network, ISRN Civ Eng.,
pp. 15.
[24] Hansen, T.C. (1992) Recycling of demolished concrete RIELM Report No. 6, E and
FN Spon, UK.
[25] Collins, R.J. (1994) The use of recycled aggregates in Concrete BRE Report, Building
Research Establishment, U.K.
52
[26] IS: 456-2000, Plain and Reinforced Concrete Code of Practice, Bureau of Indian
Standards.
[27] IS: 8112 -1989, Specifications for 53-Grade Portland Cement, Bureau of Indian
Standards.
[28] IS: 10262 -1982, Recommended Guidelines for Concrete Mix Design, Bureau of
Indian Standards.
[29] Dhir,R.K Hewlett, P.C. and Chan, Y.N.Near (1991) Surface characteristics of concrete
: Abrasion resistance, Materials and Structures, vol.24, pp,122-128
[30] Limbachiya, M.C. Leelawat and Dhir (2000), Use of Recycled concrete aggregate in
high-strength concrete vol.33, pp 574-580
[31] Fraaiji, A.L., pietersen, H.S. & Vries (2002) Performance of concrete with Recycled
Aggregates. Proceedings of International conference on Sustainable concrete construction.
University of Dundee, Scotland, pp.187-198.
[32] Kenai, Debieb & AzzouZ (2002). Mechanical properties and Durability of concrete
Made with coarse and Recycled Aggregate. Proceedings of International conference on
sustainable concrete construction, University of Dundee, Scotland, UK, pp. 383-392.
[33] Poon, C.S., shui, Z.H. & Lam, L. (2004). Effect of Microstructure of ITZ on
compressive strength of concrete prepared with Recycled Aggregates. Construction and
Building Materials, 18, pp. 461-468.
[34] Toutanji, H., Delatte, Aggoun, Duval.R & Damson, A. (2004). Effect of supplementary
cementitious Materials on The compressive strength and Durability of short- Term Cured
concrete. Cement and concrete Research, 34 (2), pp. 311-319.
[35] Kong. D., T., Zheng, J., Ma, C., Jiang, J & Jiang, J. (2010). Effect and Mechanism of
surface- coating pozzolanics Materials around Aggregate concrete. Construction and
Building Materials, 24, pp. 701-708.
[36] S.Mindess, J.F. Young, concrete, prentice-Hall, New Jersey, (1981)D.Back, Recycle
concrete as a source of aggregate, ACI Mater. J.74 (22) (1977)212-219.
[37] ACPA, concrete paving Technology, Recycling concrete pavement, American concrete
pavement Association, Skokie, IL, 1993.
53
PROJECT ASSOCIATES
Ranganath Ballast
N. Ravteja
54
S.Sanjeev Kumar
B.Vijay
CH.Sudheer
55