You are on page 1of 16

PROJECT NAME: SAGAR SAMRAT

Sr.
Description
No.

Rating (KW)

KVA/Phase

Voltage

Eff.

P.F.

Rated Amp

Type of Load

Demand Factor

Sea Water Lift Pump A Motor

75.0 KW

27.778 KVA

415 V

0.9

0.9

129

CONTINUOUS

100%

Helifuel Transfer Pump B

5.7 KW

2.111 KVA

415 V

0.9

0.9

10

INTERMITTENT

50%

Diesel Distribution Pump B Motor

11.0 KW

4.074 KVA

415 V

0.93

0.9

18

STAND BY

10%

Treated Water Dump Cassion Pump Motor

11.0 KW

4.583 KVA

415 V

0.85

0.8

23

INTERMITTENT

50%

Nitrogen Generation Package Compressor

132.0 KW

55.000 KVA

415 V

0.85

0.8

270

INTERMITTENT

50%

240V AC UPS

10.0 KW

3.704 KVA

415 V

0.91

0.9

17

INTERMITTENT

50%

Sea Water Pump

75.0 KW

27.778 KVA

415 V

0.91

0.9

127

CONTINUOUS

100%

Air Compressor B Motor

160.0 KW

66.667 KVA

415 V

0.85

0.8

327

STAND BY

10%

3 Winch Lube Oil Motor

8.0 KW

2.963 KVA

415 V

0.93

0.9

13

CONTINUOUS

100%

10 Leg jetting pump B

55.0 KW

20.370 KVA

415 V

0.95

0.9

89

INTERMITTENT

50%

11 24V DC UPS Supply - 2

16.0 KW

6.667 KVA

415 V

0.85

0.8

33

CONTINUOUS

100%

12 24V DC UPS For Topside F&G Supply - 2

3.0 KW

1.250 KVA

415 V

0.85

0.8

CONTINUOUS

100%

13 110V DC UPS - 2

7.0 KW

2.917 KVA

415 V

0.85

0.8

14

CONTINUOUS

100%

14 DC Drive Auxillarie No.1

30.0 KW

12.500 KVA

415 V

0.85

0.8

61

INTERMITTENT

50%

15 Oil filtration

4.0 KW

1.667 KVA

415 V

0.85

0.8

INTERMITTENT

50%

16 DC Drive Auxillarie No.2

30.0 KW

12.500 KVA

415 V

0.85

0.8

61

INTERMITTENT

50%

17 Nitrogen Generation Package Heater / Cooler

14.0 KW

5.833 KVA

415 V

0.85

0.8

29

INTERMITTENT

50%

18 Nitrogen Generation Package Air Cooler

4.0 KW

1.667 KVA

415 V

0.85

0.8

INTERMITTENT

50%

GSP-1A I/C

330.0 KW

137.500 KVA

415 V

0.9

0.8

638

CONTINUOUS

100%

Vane Pumps Motor B

95.0 KW

35.185 KVA

415 V

0.9

147

CONTINUOUS

100%

Vane Pumps Motor D

95.0 KW

35.185 KVA

415 V

0.9

147

CONTINUOUS

100%

Super Charger Pump B

110.0 KW

40.741 KVA

415 V

0.9

170

CONTINUOUS

100%

10 GSP-1B I/C

330.0 KW

137.500 KVA

415 V

0.9

0.8

638

CONTINUOUS

100%

Vane Pumps Motor A

95.0 KW

35.185 KVA

415 V

0.9

147

CONTINUOUS

100%

Vane Pumps Motor C

95.0 KW

35.185 KVA

415 V

0.9

147

CONTINUOUS

100%

Super Charger Pump A

110.0 KW

40.741 KVA

415 V

0.9

170

CONTINUOUS

100%

11 PP-1 I/C

72.6 KW

30.250 KVA

415 V

0.85

0.8

149

CONTINUOUS

100%

Grinder

1.0 KW

0.370 KVA

415 V

0.95

0.9

INTERMITTENT

50%

Heavy drill

2.6 KW

0.963 KVA

415 V

0.95

0.9

INTERMITTENT

50%

Welding #1

30.0 KW

11.111 KVA

415 V

0.95

0.9

49

INTERMITTENT

50%

Welding #2

30.0 KW

11.111 KVA

415 V

0.95

0.9

49

STAND BY

10%

12 PP-2 I/C

71.0 KW

29.58 KVA

415 V

0.85

0.8

145

CONTINUOUS

100%

Winch motor

2.0 KW

0.741 KVA

415 V

0.95

0.9

CONTINUOUS

100%

Welding #3

30.0 KW

11.111 KVA

415 V

0.95

0.9

49

STAND BY

10%

Welding #4

30.0 KW

11.111 KVA

415 V

0.95

0.9

49

INTERMITTENT

50%

48.0 KW

20.000 KVA

415 V

0.85

0.8

98

CONTINUOUS

100%

40.0 KW

14.815 KVA

415 V

0.95

0.9

65

INTERMITTENT

50%

48.0 KW

20.000 KVA

415 V

0.85

0.8

98

CONTINUOUS

100%

40.0 KW

14.815 KVA

415 V

0.95

0.9

65

INTERMITTENT

50%

### LQ Switchboard I/C

212.6 KW

78.741 KVA

415 V

0.95

0.9

346

CONTINUOUS

100%

UV Sterilizer A

10.0 KW

4.167 KVA

415 V

0.9

0.8

19

INTERMITTENT

50%

Demineralised Water Maker

3.7 KW

1.542 KVA

415 V

0.9

0.8

INTERMITTENT

50%

Demineralised Water Pump A Motor

5.5 KW

1.930 KVA

415 V

0.95

0.95

INTERMITTENT

50%

Hot Water Circulation pump A

0.6 KW

0.229 KVA

415 V

0.9

0.8

INTERMITTENT

50%

Clean Diesel Pump-A

1.5 KW

0.625 KVA

415 V

0.9

0.8

INTERMITTENT

50%

Electric Water Heater B

48.0 KW

20.000 KVA

415 V

0.9

0.8

93

STAND BY

10%

Potable Water Maker A

21.5 KW

8.958 KVA

415 V

0.9

0.8

42

INTERMITTENT

50%

Potable Water Pump A Motor

3.0 KW

1.250 KVA

415 V

0.9

0.8

INTERMITTENT

50%

Sanitary pump B

3.0 KW

1.111 KVA

415 V

0.95

0.9

STAND BY

10%

10 UV Sterilizer B

10.0 KW

4.167 KVA

415 V

0.9

0.8

19

STAND BY

10%

11 Demineralised Water Pump B Motor

5.5 KW

2.292 KVA

415 V

0.85

0.8

11

STAND BY

10%

12 Hot Water Circulation pump B

0.6 KW

0.229 KVA

415 V

0.9

0.8

STAND BY

10%

13 Sanitary pump A

3.0 KW

1.111 KVA

415 V

0.95

0.9

CONTINUOUS

100%

14 Sewage treatment plant

10.0 KW

3.704 KVA

415 V

0.90

0.9

17

CONTINUOUS

100%

15 Clean Diesel Pump-B

1.5 KW

0.556 KVA

415 V

0.90

0.9

STAND BY

10%

16 Electric Water Heater A

48.0 KW

20.000 KVA

415 V

0.9

0.8

93

CONTINUOUS

100%

17 Potable Water Maker B

21.0 KW

8.750 KVA

415 V

0.91

0.8

40

STAND BY

10%

18 Potable Water Pump B Motor

3.0 KW

1.250 KVA

415 V

0.91

0.8

STAND BY

10%

### Bilge & Ballast pump B

45.0 KW

16.667 KVA

415 V

0.95

0.9

73

STAND BY

10%

### Fire Pump-B

75.0 KW

27.778 KVA

415 V

0.95

0.9

122

STAND BY

10%

### HVAC MCC Switchboard Room

200.3 KW

74.185 KVA

415 V

0.95

0.9

326

CONTINUOUS

100%

### HVAC MCC LQ

166.0 KW

61.481 KVA

415 V

0.95

0.9

270

CONTINUOUS

100%

### Galley Distribution Board

108.0 KW

40.000 KVA

415 V

0.90

0.9

185

INTERMITTENT

50%

### Laundry Distribution Board

61.0 KW

22.593 KVA

415 V

0.90

0.9

105

INTERMITTENT

50%

### Emergency Lighting Transformer

150.0 KW

55.556 KVA

415 V

0.95

0.9

244

CONTINUOUS

100%
100%

13 PP-3 I/C
1

Workshop Area Panel (Port)

14 PP-4 I/C
2

Workshop Area Panel (STBD)

Oily Water Seperator

2.0 KW

0.833 KVA

415 V

0.91

0.8

CONTINUOUS

Leg jetting pump A

55.0 KW

22.917 KVA

415 V

0.91

0.8

105

INTERMITTENT

50%

Waste Oil Discharge Pump

2.2 KW

0.917 KVA

415 V

0.91

0.8

CONTINUOUS

100%

3.0 KW

1.250 KVA

415 V

0.85

0.8

CONTINUOUS

100%

### 24V DC UPS Supply - 1

24V DC UPS For Topside F&G Supply - 1

16.0 KW

6.667 KVA

415 V

0.85

0.8

33

CONTINUOUS

100%

### Air Compressor A Motor

160.0 KW

66.667 KVA

415 V

0.85

0.8

327

INTERMITTENT

50%

11.0 KW

4.583 KVA

415 V

0.9

0.8

21

CONTINUOUS

100%

### Diesel Distribution Pump A Motor


### Helifuel Transfer Pump A

5.7 KW

2.375 KVA

415 V

0.91

0.8

11

INTERMITTENT

50%

### Sprinkler Pump

55.0 KW

20.370 KVA

415 V

0.90

0.9

94

INTERMITTENT

50%

### Life boat (PORT) Winch

22.0 KW

8.148 KVA

415 V

0.95

0.9

36

INTERMITTENT

50%

### Life boat (STBD) Winch

22.0 KW

8.148 KVA

415 V

0.95

0.9

36

INTERMITTENT

50%

### Seawater Lift Pump B Motor

35.0 KW

12.963 KVA

415 V

0.90

0.9

60

CONTINUOUS

100%

### Emergency Lighting Transformer

150.0 KW

55.556 KVA

415 V

0.95

0.9

244

CONTINUOUS

100%

### 110V DC UPS

7.0 KW

2.593 KVA

415 V

0.85

0.9

13

CONTINUOUS

100%

### 240V AC UPS

10.0 KW

3.704 KVA

415 V

0.90

0.9

17

INTERMITTENT

50%

### Bilge & Ballast pump A

45.0 KW

16.667 KVA

415 V

0.95

0.9

73

INTERMITTENT

50%

### Fire Pump-A

75.0 KW

27.778 KVA

415 V

0.95

0.9

122

CONTINUOUS

100%

Main Marine Switchboard I/C

815.0 KW

339.583 KVA

415 V

0.8

1417

CONTINUOUS

100%

Emergency Switchboard Main Deck I/C

1200.0 KW

500.000 KVA

415 V

0.8

2087

CONTINUOUS

100%

Emergency Switchboard Lower Deck I/C

835.0 KW

347.917 KVA

415 V

0.8

1452

CONTINUOUS

100%

415 V

0.8

CONTINUOUS

100%

0.000 KVA
240V Lighting DB

0.000 KVA
0.000 KVA

Normal Lighting DB 1

7.4 KW

3.083 KVA

240 V

0.8

22

CONTINUOUS

100%

Normal Lighting DB 2

7.4 KW

3.083 KVA

240 V

0.8

22

CONTINUOUS

100%

Power DB

16.5 KW

6.875 KVA

240 V

0.8

50

CONTINUOUS

100%

NLP-1

10.4 KW

4.346 KVA

240 V

0.8

31

CONTINUOUS

100%

NLP-2

9.8 KW

4.071 KVA

240 V

0.8

29

CONTINUOUS

100%

NLP-3

8.4 KW

3.508 KVA

240 V

0.8

25

CONTINUOUS

100%

NLP-4

11.5 KW

4.779 KVA

240 V

0.8

34

CONTINUOUS

100%

GDB-2

28.4 KW

11.821 KVA

240 V

0.8

85

CONTINUOUS

100%

GL-NOBLE DENTON

1 OF 16

270457193.xls

PROJECT NAME: SAGAR SAMRAT


Sr.
Description
No.
Emergency lighting DB 1

Rating (KW)

KVA/Phase

Voltage

Eff.

P.F.

Rated Amp

Type of Load

Demand Factor

5.4 KW

2.250 KVA

240 V

0.8

16

CONTINUOUS

100%

Emergency lighting DB 2

5.0 KW

2.083 KVA

240 V

0.8

15

CONTINUOUS

100%

LQ Emergency lighting DB

2.8 KW

1.179 KVA

240 V

0.8

CONTINUOUS

100%

LQ PAGA

5.2 KW

2.167 KVA

240 V

0.8

16

CONTINUOUS

100%

LQ F & G

1.0 KW

0.417 KVA

240 V

0.8

CONTINUOUS

100%

LQ LAN System

1.0 KW

0.417 KVA

240 V

0.8

CONTINUOUS

100%

LQ Entertainment system

1.0 KW

0.417 KVA

240 V

0.8

CONTINUOUS

100%

Space heater DB

4.0 KW

1.667 KVA

240 V

0.8

12

CONTINUOUS

100%

NLP-5

5.7 KW

2.354 KVA

240 V

0.8

17

CONTINUOUS

100%

Jacking Control panel

6.0 KW

2.500 KVA

240 V

0.8

18

CONTINUOUS

100%

Sprinkler Pump

4.0 KW

1.667 KVA

240 V

0.8

12

CONTINUOUS

100%

GL-NOBLE DENTON

2 OF 16

270457193.xls

HARBOR MODE

FROM
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel

Main Marine Panel


GSP - 1A
GSP - 1A
GSP - 1A
Main Marine Panel
GSP - 1B
GSP - 1B
GSP - 1B
###
Main Marine Panel
PP - 1
PP - 1
PP - 1
PP - 1
###
Main Marine Panel
PP - 2
PP - 2
PP - 2
###
Main Marine Panel
PP - 3
Main Marine Panel
PP - 4
Emergency Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
###
###
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
###
###
###
###

Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
GL-NOBLE DENTON

3 OF 16

270457193.xls

HARBOR MODE

FROM
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB

GL-NOBLE DENTON

4 OF 16

270457193.xls

PROJECT :
PROJECT NO.

Load Details
Sr.No.

Description

DOC NO. : SSCP-1381-GLND-EL-DWG-020


REVISION : 2

APPENDIX - B - CABLE SIZING CHART (AC LOADS)

OCD042

Breaker Setting Details

Rating (KW)

KVA/Phase

Voltage

Efficiency

P.F.

Rated
Amp

Type of Load

Demand
Factor

FROM

TYPE
MAX Thermal
DOL/VFD/FEED
Overload
ER
Rating

Overload Range
(103%) for Gen &
Xmer 110%

Cable Sizing Calculation

Nearest AT ( 3%
Overload & 10% Amper Trip Amper Frame
Gen Trans)

Starting
Power
Factor

Starting Current

Length
Mtr

Cable Size

No of
Core

Cables
Runs/
Phase

Diversified
cable rating

Resistance
/km

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

MAIN MARINE SWITCHBOARD CABLE SIZING


Sea Water Lift Pump A Motor
Helifuel Transfer Pump B
Diesel Distribution Pump B Motor
Treated Water Dump Cassion Pump Motor
Nitrogen Generation Package Compressor
240V AC UPS
Sea Water Pump
Air Compressor B Motor
3 Winch Lube Oil Motor
Leg jetting pump B
24V DC UPS Supply - 2
24V DC UPS For Topside F&G Supply - 2
110V DC UPS - 2
DC Drive Auxillarie No.1
Oil filtration
DC Drive Auxillarie No.2
Nitrogen Generation Package Heater / Cooler

75.0 KW
5.7 KW
11.0 KW
11.0 KW
132.0 KW
10.0 KW
75.0 KW
160.0 KW
8.0 KW
55.0 KW
16.0 KW
3.0 KW
7.0 KW
30.0 KW
4.0 KW
30.0 KW
14.0 KW

27.78
2.11
4.07
4.58
55.00
3.70
27.78
66.67
2.96
20.37
6.67
1.25
2.92
12.50
1.67
12.50
5.83

415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V

0.9
0.9
0.93
0.85
0.85
0.91
0.91
0.85
0.93
0.95
0.85
0.85
0.85
0.85
0.85
0.85
0.85

0.9
0.9
0.9
0.8
0.8
0.9
0.9
0.8
0.9
0.9
0.8
0.8
0.8
0.8
0.8
0.8
0.8

129
10
18
23
270
17
127
327
13
89
33
6
14
61
8
61
29

CONTINUOUS
INTERMITTENT
STAND BY
INTERMITTENT
INTERMITTENT
INTERMITTENT
CONTINUOUS
STAND BY
CONTINUOUS
INTERMITTENT
CONTINUOUS
CONTINUOUS
CONTINUOUS
INTERMITTENT
INTERMITTENT
INTERMITTENT
INTERMITTENT

100%
50%
10%
50%
50%
50%
100%
10%
100%
50%
100%
100%
100%
50%
50%
50%
50%

Main Marine Panel


Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel
Main Marine Panel

DOL
DOL
DOL
DOL
DOL
FEEDER
DOL
DOL
DOL
DOL
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER

141.9
11
19.8
25.3
297
NA
139.7
359.7
14.3
97.9
NA
NA
NA
NA
NA
NA
NA

148.35
11.5
20.7
26.45
310.5
18.7
146.05
376.05
14.95
102.35
36.3
6.6
15.4
67.1
8.8
67.1
31.9

148
12
21
26
311
20
146
376
15
102
40
7
17
74
10
74
35

150 AT
16 AT
25 AT
32 AT
325 AT
25 AT
150 AT
400 AT
16 AT
125 AT
50 AT
10 AT
20 AT
80 AT
16 AT
80 AT
40 AT

160 AF
100 AF
100 AF
100 AF
400 AF
100 AF
160 AF
400 AF
100 AF
160 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF

0.3
0.3
0.3
0.3
0.3
0.9
0.3
0.3
0.3
0.3
0.8
0.8
0.8
0.8
0.8
0.8
0.8

838.5
65
117
149.5
1755
NA
825.5
2125.5
84.5
578.5
NA
NA
NA
NA
NA
NA
NA

100
35
35
70
50
35
70
60
35
71
35
100
35
66
67
68
50

3C x 95 mm2+E
3C x 2.5 mm2+E
3C x 6 mm2+E
3C x 10 mm2+E
3R x 3C x 70 mm2+E
3C x 6 mm2+E
3C x 95 mm2+E
3R x 3C x 95 mm2+E
3C x 2.5 mm2+E
3C x 70 mm2+E
3C x 16 mm2+E
3C x 4 mm2+E
3C x 4 mm2+E
3C x 35 mm2+E
3C x 2.5 mm2+E
3C x 35 mm2+E
3C x 16 mm2+E

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1
1
1
1
3
1
1
3
1
1
1
1
1
1
1
1
1

160.769
16.66
28.322
39.151
399.84
28.322
160.769
482.307
16.66
133.28
53.312
22.491
22.491
86.632
16.66
86.632
53.312

0.24
9.45
3.89
2.30
0.34
3.89
0.24
0.24
9.45
0.34
1.45
5.87
5.87
0.66
9.45
0.66
1.45

1
2
3
4

GROUP STARTER PANEL - 1A CABLE SIZING


GSP-1A I/C
Vane Pumps Motor B
Vane Pumps Motor D
Super Charger Pump B

330.0 KW
95.0 KW
95.0 KW
110.0 KW

137.50
35.19
35.19
40.74

415 V
415 V
415 V
415 V

0.9
1
1
1

0.8
0.9
0.9
0.9

638
147
147
170

CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS

100%
100%
100%
100%

Main Marine Panel


GSP - 1A
GSP - 1A
GSP - 1A

FEEDER
DOL
DOL
DOL

NA
161.7
161.7
187

701.8
169.05
169.05
195.5

769
169
169
196

630 AT
180 AT
180 AT
200 AT

800 AF
250 AF
250 AF
250 AF

0.8
0.3
0.3
0.3

NA
955.5
955.5
1105

50
35
35
35

3R x 3(1C x 120) mm2


2R x 3C x 50 mm2+E
2R x 3C x 50 mm2+E
2R x 3C x 50 mm2+E

1
3
3
3

3
2
2
2

797.181
214.914
214.914
214.914

0.19
0.49
0.49
0.49

1
2
3
4

GROUP STARTER PANEL - 1B CABLE SIZING


GSP-1B I/C
Vane Pumps Motor A
Vane Pumps Motor C
Super Charger Pump A

330.0 KW
95.0 KW
95.0 KW
110.0 KW

137.50
35.19
35.19
40.74

415 V
415 V
415 V
415 V

0.9
1
1
1

0.8
0.9
0.9
0.9

638
147
147
170

CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS

100%
100%
100%
100%

Main Marine Panel


GSP - 1B
GSP - 1B
GSP - 1B

FEEDER
DOL
DOL
DOL

NA
161.7
161.7
187

701.8
169.05
169.05
195.5

769
169
169
196

630 AT
180 AT
180 AT
200 AT

800 AF
250 AF
250 AF
250 AF

0.8
0.3
0.3
0.3

NA
955.5
955.5
1105

50
35
35
35

3R x 3(1C x 120) mm2


2R x 3C x 50 mm2+E
2R x 3C x 50 mm2+E
2R x 3C x 50 mm2+E

1
3
3
3

3
2
2
2

797.181
214.914
214.914
214.914

0.19
0.49
0.49
0.49

1
2
3
4
5

POWER PANEL - 1 CABLE SIZING


PP-1 I/C
Grinder
Heavy drill
Welding #1
Welding #2

72.6 KW
1.0 KW
2.6 KW
30.0 KW
30.0 KW

30.25
0.37
0.96
11.11
11.11

415 V
415 V
415 V
415 V
415 V

0.85
0.95
0.95
0.95
0.95

0.8
0.9
0.9
0.9
0.9

149
2
4
49
49

CONTINUOUS
INTERMITTENT
INTERMITTENT
INTERMITTENT
STAND BY

100%
50%
50%
50%
10%

Main Marine Panel


PP - 1
PP - 1
PP - 1
PP - 1

FEEDER
FEEDER
FEEDER
FEEDER
FEEDER

NA
NA
NA
NA
NA

163.9
2.2
4.4
53.9
53.9

180
2
5
59
59

200 AT
10 AT
10 AT
63 AT
63 AT

250 AF
100 AF
100 AF
100 AF
100 AF

0.8
0.9
0.9
0.9
0.9

NA
NA
NA
NA
NA

20
35
35
35
35

2R x 3C x 50 mm2+E
3C x 4 mm2+E
3C x 4 mm2+E
3C x 25 mm2+E
3C x 25 mm2+E

3
3
3
3
3

2
1
1
1
1

214.914
22.491
22.491
69.972
69.972

0.49
5.87
5.87
0.92
0.92

1
2
3
4

POWER PANEL - 2 CABLE SIZING


PP-2 I/C
Winch motor
Welding #3
Welding #4

71.0 KW
2.0 KW
30.0 KW
30.0 KW

29.58
0.74
11.11
11.11

415 V
415 V
415 V
415 V

0.85
0.95
0.95
0.95

0.8
0.9
0.9
0.9

145
3
49
49

CONTINUOUS
CONTINUOUS
STAND BY
INTERMITTENT

100%
100%
10%
50%

Main Marine Panel


PP - 2
PP - 2
PP - 2

FEEDER
DOL
FEEDER
FEEDER

NA
3.3
NA
NA

159.5
3.45
53.9
53.9

175
3
59
59

180 AT
10 AT
63 AT
63 AT

250 AF
100 AF
100 AF
100 AF

0.8
0.3
0.9
0.9

NA
19.5
NA
NA

20
35
35
35

2R x 3C x 50 mm2+E
3C x 4 mm2+E
3C x 25 mm2+E
3C x 25 mm2+E

3
3
3
3

2
1
1
1

214.914
22.491
69.972
69.972

0.49
5.87
0.92
0.92

1
2

POWER PANEL - 3 CABLE SIZING


PP-3 I/C
Workshop Area Panel (Port)

48.0 KW
40.0 KW

20.00
14.81

415 V
415 V

0.85
0.95

0.8
0.9

98
65

CONTINUOUS
INTERMITTENT

100%
50%

Main Marine Panel


PP - 3

FEEDER
FEEDER

NA
NA

107.8
71.5

118
78

125 AT
80 AT

160 AF
100 AF

0.8
0.9

NA
NA

35
35

3C x 70 mm2+E
3C x 35 mm2+E

3
3

1
1

133.28
86.632

0.34
0.66

1
2

POWER PANEL - 4 CABLE SIZING


PP-4 I/C
Workshop Area Panel (STBD)

48.0 KW
40.0 KW

20.00
14.81

415 V
415 V

0.85
0.95

0.8
0.9

98
65

CONTINUOUS
INTERMITTENT

100%
50%

Main Marine Panel


PP - 4

FEEDER
FEEDER

NA
NA

107.8
71.5

118
78

125 AT
80 AT

160 AF
100 AF

0.8
0.9

NA
NA

35
35

3C x 70 mm2+E
3C x 35 mm2+E

3
3

1
1

133.28
86.632

0.34
0.66

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

LQ SWITCHBOARD CABLE SIZING


LQ Switchboard I/C
UV Sterilizer A
Demineralised Water Maker
Demineralised Water Pump A Motor
Hot Water Circulation pump A
Clean Diesel Pump-A
Electric Water Heater B
Potable Water Maker A
Potable Water Pump A Motor
Sanitary pump B
UV Sterilizer B
Demineralised Water Pump B Motor
Hot Water Circulation pump B
Sanitary pump A
Sewage treatment plant
Clean Diesel Pump-B
Electric Water Heater A
Potable Water Maker B
Potable Water Pump B Motor

212.6 KW
10.0 KW
3.7 KW
5.5 KW
0.6 KW
3.7 KW
48.0 KW
26.0 KW
3.0 KW
3.0 KW
10.0 KW
5.5 KW
0.6 KW
3.0 KW
10.0 KW
3.7 KW
48.0 KW
26.0 KW
3.0 KW

78.74
4.17
1.54
1.93
0.23
0.63
20.00
8.96
1.25
1.11
4.17
2.29
0.23
1.11
3.70
0.56
20.00
8.75
1.25

415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V

0.95
0.9
0.9
0.95
0.95
0.9
0.9
0.9
0.9
0.95
0.9
0.85
0.9
0.95
0.9
0.9
0.9
0.91
0.91

0.9
0.8
0.8
0.95
0.95
0.8
0.8
0.8
0.8
0.9
0.8
0.8
0.8
0.9
0.9
0.9
0.8
0.8
0.8

346
19
7
8
1
3
93
42
6
5
19
11
1
5
17
3
93
40
6

CONTINUOUS
INTERMITTENT
INTERMITTENT
INTERMITTENT
INTERMITTENT
INTERMITTENT
STAND BY
INTERMITTENT
INTERMITTENT
STAND BY
STAND BY
STAND BY
STAND BY
CONTINUOUS
CONTINUOUS
STAND BY
CONTINUOUS
STAND BY
STAND BY

100%
50%
50%
50%
50%
50%
10%
50%
50%
10%
10%
10%
10%
100%
100%
10%
100%
10%
10%

Emergency Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard
LQ Switchboard

FEEDER
FEEDER
FEEDER
DOL
DOL
DOL
FEEDER
FEEDER
DOL
DOL
FEEDER
DOL
DOL
DOL
FEEDER
DOL
FEEDER
FEEDER
DOL

NA
NA
NA
8.8
1.1
3.3
NA
NA
6.6
5.5
NA
12.1
1.1
5.5
NA
3.3
NA
NA
6.6

380.5
20.9
7.7
9.2
1.15
3.45
102.3
46.2
6.9
5.75
20.9
12.65
1.15
5.75
18.7
3.45
102.3
44
6.9

417
22
8
10
1
4
107
48
7
6
22
13
1
6
20
4
107
46
7

425 AT
25 AT
10 AT
16 AT
10 AT
10 AT
125 AT
50 AT
10 AT
10 AT
25 AT
16 AT
10 AT
10 AT
25 AT
10 AT
125 AT
50 AT
10 AT

630 AF
100 AF
100 AF
100 AF
100 AF
100 AF
160 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
160 AF
100 AF
100 AF

0.9
0.8
0.8
0.3
0.3
0.3
0.8
0.8
0.3
0.3
0.8
0.3
0.3
0.3
0.9
0.3
0.8
0.8
0.3

NA
NA
NA
52
6.5
19.5
NA
NA
39
32.5
NA
71.5
6.5
32.5
NA
19.5
NA
NA
39

35
35
70
70
35
35
35
35
35
35
35
70
35
35
35
35
35
35
35

3R x 3C x 95 mm2+E
3C x 6 mm2+E
3C x 4 mm2+E
3C x 10 mm2+E
3C x 4 mm2+E
3C x 4 mm2+E
3C x 70 mm2+E
3C x 16 mm2+E
3C x 4 mm2+E
3C x 4 mm2+E
3C x 6 mm2+E
3C x 10 mm2+E
3C x 4 mm2+E
3C x 4 mm2+E
3C x 6 mm2+E
3C x 4 mm2+E
3C x 70 mm2+E
3C x 16 mm2+E
3C x 4 mm2+E

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

482.307
28.322
22.491
39.151
22.491
22.491
133.28
53.312
22.491
22.491
28.322
39.151
22.491
22.491
28.322
22.491
133.28
53.312
22.491

0.24
3.89
5.87
2.30
5.87
5.87
0.34
1.45
5.87
5.87
3.89
2.30
5.87
5.87
3.89
5.87
0.34
1.45
5.87

1
2
3
4
5
6
7
8
9
10

EMERGENCY MARINE SWITCHBOARD LOWER DECK CABLE SIZING


Bilge & Ballast pump A
Fire Pump-B
HVAC MCC Switchboard Room
HVAC MCC LQ
Galley Distribution Board
Laundry Distribution Board
Emergency Lighting Transformer
Oily Water Seperator
Leg jetting pump A
Waste Oil Discharge Pump

45.0 KW
75.0 KW
200.3 KW
166.0 KW
108.0 KW
61.0 KW
150.0 KW
2.0 KW
55.0 KW
2.2 KW

16.67
27.78
74.19
61.48
40.00
22.59
55.56
0.83
22.92
0.92

415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V

0.95
0.95
0.95
0.95
0.90
0.90
0.95
0.91
0.91
0.91

0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.8
0.8
0.8

73
122
326
270
185
105
244
4
105
4

STAND BY
STAND BY
CONTINUOUS
CONTINUOUS
INTERMITTENT
INTERMITTENT
CONTINUOUS
CONTINUOUS
INTERMITTENT
CONTINUOUS

10%
10%
100%
100%
50%
50%
100%
100%
50%
100%

Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard

DOL
DOL
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
DOL
DOL

81
134
NA
NA
NA
NA
NA
NA
116
5

84.2
140.3
358.5
297.1
204.0
115.3
268.5
4.2
120.9
4.8

84
140
393
325
224
126
294
5
121
5

100 AT
150 AT
400 AT
350 AT
225 AT
150 AT
300 AT
10 AT
125 AT
10 AT

100 AF
160 AF
400 AF
400 AF
250 AF
160 AF
400 AF
100 AF
160 AF
100 AF

0.3
0.3
0.9
0.9
0.9
0.9
0.9
0.8
0.3
0.3

475.95
793.25
NA
NA
NA
NA
NA
NA
683.20
27.33

35
35
35
35
75
75
75
75
75
76

3C x 50 mm2+E
3C x 95 mm2+E
3R x 3C x 95 mm2+E
3R x 3C x 70 mm2+E
2R x 3C x 70 mm2+E
3C x 95 mm2+E
2R x 3C x 95 mm2+E
3C x 4 mm2+E
3C x 70 mm2+E
3C x 4 mm2+E

3
3
3
3
3
3
3
3
3
3

1
1
6
3
2
1
2
1
1
1

107.457
160.769
482.307
399.84
266.56
160.769
321.538
22.491
133.28
22.491

0.49
0.24
0.24
0.34
0.34
0.24
0.24
5.87
0.34
5.87

1
2
3
4

EMERGENCY MARINE SWITCHBOARD MAIN DECK CABLE SIZING


24V DC UPS Supply - 1
Air Compressor A Motor
Diesel Distribution Pump A Motor
Helifuel Transfer Pump A

16.0 KW
160.0 KW
11.0 KW
5.7 KW

6.67
66.67
4.58
2.38

415 V
415 V
415 V
415 V

0.85
0.85
0.9
0.91

0.8
0.8
0.8
0.8

33
327
21
11

CONTINUOUS
INTERMITTENT
CONTINUOUS
INTERMITTENT

100%
50%
100%
50%

Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard

FEEDER
DOL
DOL
DOL

NA
359.7
23.1
12.1

36.3
376.05
24.15
12.65

40
376
24
13

50 AT
400 AT
32 AT
16 AT

100 AF
400 AF
100 AF
100 AF

0.8
0.3
0.3
0.3

NA
2125.50
136.50
71.50

100
60
35
35

3C x 16 mm2+E
3R x 3C x 95 mm2+E
3C x 10 mm2+E
3C x 2.5 mm2+E

3
3
3
3

1
3
1
1

53.312
482.307
39.151
16.66

1.45
0.24
2.30
9.45

PROJECT :
PROJECT NO.

Load Details
Sr.No.

Description

DOC NO. : SSCP-1381-GLND-EL-DWG-020


REVISION : 2

APPENDIX - B - CABLE SIZING CHART (AC LOADS)

OCD042

Breaker Setting Details

Rating (KW)

KVA/Phase

Voltage

Efficiency

P.F.

Rated
Amp

Type of Load

Demand
Factor

FROM

TYPE
MAX Thermal
DOL/VFD/FEED
Overload
ER
Rating

Overload Range
(103%) for Gen &
Xmer 110%

Cable Sizing Calculation

Nearest AT ( 3%
Overload & 10% Amper Trip Amper Frame
Gen Trans)

Starting
Power
Factor

Starting Current

Length
Mtr

Cable Size

No of
Core

Cables
Runs/
Phase

Diversified
cable rating

Resistance
/km

5
6
7
8
9
10
11
12
12
13

Sprinkler Pump
Life boat (PORT) Winch
Life boat (STBD) Winch
Seawater Lift Pump B Motor
Emergency Lighting Transformer
110V DC UPS
240V AC UPS
24V DC UPS For Topside F&G Supply - 1
Bilge & Ballast pump B
Fire Pump-A

55.0 KW
22.0 KW
22.0 KW
75.0 KW
150.0 KW
7.0 KW
10.0 KW
3.0 KW
45.0 KW
75.0 KW

20.37
8.15
8.15
12.96
55.56
2.59
3.70
1.25
16.67
27.78

415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V

0.9
0.95
0.95
0.9
0.95
0.85
0.9
0.85
0.95
0.95

0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.8
0.9
0.9

94
36
36
129
244
13
17
6
73
122

INTERMITTENT
INTERMITTENT
INTERMITTENT
CONTINUOUS
CONTINUOUS
INTERMITTENT
INTERMITTENT
CONTINUOUS
INTERMITTENT
INTERMITTENT

50%
50%
50%
100%
100%
100%
50%
100%
10%
100%

Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard
Emergency Switchboard

DOL
FEEDER
FEEDER
DOL
FEEDER
FEEDER
FEEDER
FEEDER
DOL
DOL

104
NA
NA
142
NA
NA
NA
NA
81
134

108.6
39.6
39.6
148.1
268.5
14.0
18.9
6.8
84.2
140.3

109
43
43
148
294
15
21
7
84
140

125 AT
50 AT
50 AT
150 AT
300 AT
20 AT
25 AT
10 AT
100 AT
150 AT

160 AF
100 AF
100 AF
160 AF
400 AF
100 AF
100 AF
100 AF
100 AF
160 AF

0.3
0.9
0.9
0.3
0.9
0.9
0.9
0.8
0.3
0.3

614.04
NA
NA
837.32
NA
NA
NA
NA
475.95
793.25

65
100
100
100
40
50
50
50
35
65

3C x 70 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 95 mm2+E
2R x 3C x 95 mm2+E
3C x 4 mm2+E
3C x 6 mm2+E
3C x 4 mm2+E
3C x 50 mm2+E
3C x 95 mm2+E

3
3
3
3
3
3
3
3
3
3

1
1
1
1
2
1
1
1
1
1

133.28
53.312
53.312
160.769
321.538
22.491
28.322
22.491
107.457
160.769

0.34
1.45
1.45
0.24
0.24
5.87
3.89
5.87
0.49
0.24

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

MAIN LIGHTING AND POWER DISTRIIBUTION SWITCHBOARD CABLE SIZING


Normal Lighting DB 1
7.4 KW
Normal Lighting DB 2
7.4 KW
Power DB
16.5 KW
NLP-1
10.4 KW
NLP-2
9.8 KW
NLP-3
8.4 KW
NLP-4
11.5 KW
GDB-2
28.4 KW
Emergency lighting DB 1
5.4 KW
Emergency lighting DB 2
5.0 KW
LQ Emergency lighting DB
2.8 KW
LQ PAGA
5.2 KW
LQ F & G
1.0 KW
LQ LAN System
1.0 KW
LQ Entertainment system
1.0 KW
Space heater DB
4.0 KW
NLP-5
5.7 KW
Jacking Control panel
6.0 KW
Sprinkler Pump
4.0 KW

3.08
3.08
6.88
4.35
4.07
3.51
4.78
11.82
2.25
2.08
1.18
2.17
0.42
0.42
0.42
1.67
2.35
2.50
1.67

240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

22
22
50
31
29
25
34
85
16
15
9
16
3
3
3
12
17
18
12

CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS

100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%

Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB
Main Lighting DB

FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER
FEEDER

NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

24.2
24.2
55
34.1
31.9
27.5
37.4
93.5
17.6
16.5
9.9
17.6
3.3
3.3
3.3
13.2
18.7
19.8
13.2

27
27
60
37
35
30
41
102
19
18
11
19
4
4
4
14
20
22
14

25 AT
25 AT
50 AT
32 AT
32 AT
25 AT
40 AT
100 AT
16 AT
16 AT
10 AT
16 AT
6 AT
6 AT
6 AT
10 AT
20 AT
20 AT
10 AT

100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF
100 AF

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

20
20
20
100
100
100
100
100
35
35
100
100
100
100
100
35
100
35
75

3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 25 mm2+E
3C x 25 mm2+E
3C x 25 mm2+E
3C x 25 mm2+E
3C x 70 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 4 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E
3C x 16 mm2+E

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

53.312
53.312
53.312
69.972
69.972
69.972
69.972
133.28
53.312
53.312
53.312
53.312
22.491
53.312
53.312
53.312
53.312
53.312
53.312

1.45
1.45
1.45
0.92
0.92
0.92
0.92
0.34
1.45
1.45
1.45
1.45
5.87
1.45
1.45
1.45
1.45
1.45
1.45

NOTE : 1. All loads kW ratings, Cable Sizes and Cables Lengths are subject to change upon approved final Vendor Data and Equipment Locations.

DOC NO. : SSCP-1381-GLND-EL-DWG-020


REVISION : 2

DATE

5/2/2013

Cable Sizing Calculation


Reactance
/km

Running (V)
Voltage Drop

Starting (V)
Voltage Drop

% Running
voltage Drop

% Starting voltage
drop

0.073
0.103
0.09
0.084
0.075
0.09
0.073
0.073
0.103
0.075
0.08
0.096
0.096
0.076
0.103
0.076
0.08

5.61
5.18
3.86
5.27
2.45
3.64
3.87
2.7
6.73
3.67
2.41
4.93
4.03
4
7.07
4.12
3.03

20.74
11.55
8.88
13.97
8.74
NA
14.29
10.51
15.01
12.28
NA
NA
NA
NA
NA
NA
NA

1.35%
1.24%
0.93%
1.26%
0.59%
0.87%
0.93%
0.65%
1.62%
0.88%
0.58%
1.18%
0.97%
0.96%
1.70%
0.99%
0.73%

4.99%
2.78%
2.13%
3.36%
2.10%
NA
3.44%
2.53%
3.61%
2.95%
NA
NA
NA
NA
NA
NA
NA

0.094
0.076
0.076
0.076

3.86
2.1
2.1
2.43

NA
6.34
6.34
7.34

0.93%
0.50%
0.50%
0.58%

NA
1.52%
1.52%
1.76%

0.094
0.076
0.076
0.076

3.86
2.1
2.1
2.43

NA
6.34
6.34
7.34

0.93%
0.50%
0.50%
0.58%

NA
1.52%
1.52%
1.76%

0.076
0.096
0.096
0.079
0.079

1.12
0.64
1.29
2.55
2.55

NA
NA
NA
NA
NA

0.26%
0.15%
0.31%
0.61%
0.61%

NA
NA
NA
NA
NA

0.076
0.096
0.079
0.079

1.09
0.96
2.55
2.55

NA
2.18
NA
NA

0.26%
0.23%
0.61%
0.61%

NA
0.52%
NA
NA

0.075
0.076

1.86
2.47

NA
NA

0.44%
0.59%

NA
NA

0.075
0.076

1.86
2.47

NA
NA

0.44%
0.59%

NA
NA

0.073
0.09
0.096
0.084
0.096
0.096
0.075
0.08
0.096
0.096
0.09
0.084
0.096
0.096
0.09
0.096
0.075
0.08
0.096

0.87
3.64
4.03
2.14
0.33
0.86
1.77
3.07
1.72
1.61
3.64
2.52
0.28
1.61
3.64
0.96
1.77
2.92
1.72

NA
NA
NA
4.86
0.72
2.18
NA
NA
4.37
3.64
NA
6.68
0.72
3.64
NA
2.18
NA
NA
4.37

0.20%
0.87%
0.97%
0.51%
0.07%
0.20%
0.42%
0.73%
0.41%
0.38%
0.87%
0.60%
0.06%
0.38%
0.87%
0.23%
0.42%
0.70%
0.41%

NA
NA
NA
1.17%
0.17%
0.52%
NA
NA
1.05%
0.87%
NA
1.60%
0.17%
0.87%
NA
0.52%
NA
NA
1.05%

0.076
0.073
0.073
0.075
0.0375
0.073
0.073
0.096
0.075
0.096

2.1
1.85
0.82
1.83
3.85
3.42
3.98
2.35
4.29
2.63

6.32
6.86
NA
NA
NA
NA
NA
NA
15.32
6.66

0.50%
0.44%
0.19%
0.44%
0.92%
0.82%
0.95%
0.56%
1.03%
0.63%

1.52%
1.65%
NA
NA
NA
NA
NA
NA
3.69%
1.60%

0.08
0.073
0.084
0.103

6.9
2.7
2.4
5.07

NA
10.51
6.37
12.7

1.66%
0.65%
0.57%
1.22%

NA
2.53%
1.53%
3.06%

DOC NO. : SSCP-1381-GLND-EL-DWG-020


REVISION : 2

DATE

5/2/2013

Cable Sizing Calculation


Reactance
/km

Running (V)
Voltage Drop

Starting (V)
Voltage Drop

% Running
voltage Drop

% Starting voltage
drop

0.075
0.08
0.08
0.073
0.073
0.096
0.09
0.096
0.076
0.073

3.57
8.35
8.35
5.6
2.12
5.86
5.26
2.52
2.1
3.45

11.93
NA
NA
20.71
NA
NA
NA
NA
6.32
12.75

0.86%
2.01%
2.01%
1.34%
0.51%
1.41%
1.26%
0.60%
0.50%
0.83%

2.87%
NA
NA
4.99%
NA
NA
NA
NA
1.52%
3.07%

0.08
0.08
0.08
0.079
0.079
0.079
0.079
0.075
0.08
0.08
0.08
0.08
0.096
0.08
0.08
0.08
0.08
0.08
0.08

0.92
0.92
2.09
4.19
3.92
3.38
4.59
4.63
1.17
1.09
1.88
3.34
2.46
0.62
0.62
0.87
3.55
1.31
1.88

NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

0.38%
0.38%
0.87%
1.74%
1.63%
1.40%
1.91%
1.92%
0.48%
0.45%
0.78%
1.39%
1.02%
0.25%
0.25%
0.36%
1.47%
0.54%
0.78%

NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

PROJECT CABLE DATA


Cu/XLPE/FRLS/ARMOURED
45

CABLE TYPE
CABLE RATING TEMPERATURE
AMBIENT TEMPERATURE
INSULATION TEMPERATURE ALLOWABLE
TEMPERATURE DERATING FACTOR
TYPE OF LAYING FACTOR (GROUPING FACTOR)
OVERALL RATING FACTOR

45
85
0.98
0.85
0.833
3

(DATA BASED ON ABS CABLES)


o
C
o

C
C

CABLE
RATING
(amp)

MATCH NO

CABLE
SIZE
(sq mm)

DIVERSIFIED
CABLE RATING
(AMP)

15

3C x 1.5 mm2+E

12.495

20

3C x 2.5 mm2+E

16.66

27

3C x 4 mm2+E

22.491

34

3C x 6 mm2+E

28.322

47

3C x 10 mm2+E

39.151

64

3C x 16 mm2+E

53.312

84

3C x 25 mm2+E

69.972

104

3C x 35 mm2+E

86.632

129

3C x 50 mm2+E

107.457

160

10

3C x 70 mm2+E

133.28

193

11

3C x 95 mm2+E

160.769

208

12

2R x 3C x 35 mm2+E

173.264

258

13

2R x 3C x 50 mm2+E

214.914

320

14

2R x 3C x 70 mm2+E

266.56

386

15

2R x 3C x 95 mm2+E

321.538

480

16

3R x 3C x 70 mm2+E

399.84

579

17

3R x 3C x 95 mm2+E

482.307

638

18

2R x 3(1C x 120) mm2

531.454

957

19

3R x 3(1C x 120) mm2

797.181

1276

20

4R x 3(1C x 120) mm2

1062.908

1595

21

5R x 3(1C x 120) mm2

1328.635

1914

22

6R x 3(1C x 120) mm2

1594.362

2233

23

7R x 3(1C x 120) mm2

1860.089

2552

24

8R x 3(1C x 120) mm2

2125.816

2871

25

9R x 3(1C x 120) mm2

2391.543

3190

26

10R x 3(1C x 120) mm2

2657.27

3509

27

11R x 3(1C x 120) mm2

2922.997

3828

28

12R x 3(1C x 120) mm2

3188.724

4147

29

13R x 3(1C x 120) mm2

3454.451

4785

30

15R x 3(1C x 120) mm2

3985.905

5423

31

17R x 3(1C x 120) mm2

4517.359

6380
20R x 3(1C x 120) mm2
31
on ambinet for IEEE Cables for Rating in table @ 45 Deg.C

5314.54

Maximum
conductor
tempearat
ure
Ambient air temperature ( T 0 C)
85
90
105*

30
1.1
1.1
1.08

40
1..06
1.05
1.04

45
1.00
1.00
1.00

47
0.98
0.98
0.99

*Shore Power cable


319

CABLE
RATING
(amp)

16

3(1C x 120) mm2

4/0 AWG

265.727

MATCH NO

CABLE
SIZE
(sq mm)

CABLE SIZE (AWG)

DIVERSIFIED
CABLE RATING
(AMP)

3C+E x 120 + 120 mm2

4/0 AWG

193.256

232

Conductor-DC resistance
Maximum
Nominal
resistance
crossHence resistance of Plain
of Plain
sectional
copper at 90o C
Copper
at
area (mm2
Ohm/Km
20o C
)
Ohm/Km
1.5

13.3

15.6

2.5

7.98

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

4.95
3.3
1.91
1.21
0.78
0.554
0.386
0.272
0.206
0.161
0.129
0.106
0.0801
0.0641
0.0486
0.0384
0.0287

9.64
5.99
3.97
2.35
1.48
0.936
0.675
0.499
0.344
0.249
0.196
0.161
0.128
0.0972
0.0774
0.0596
0.0463
0.0359

Hence resistance of Plain


copper at 90o C
Ohm/Km

Ambient
Temperature
(o C)
20
25

0.12
0.112
0.105
0.099
0.098
0.094
0.093
0.092
0.09
0.088
0.088
0.088
0.087
0.086
0.085

30
35
40
45
50
55
60
65
70
75
80
85
90

DATA

ATA BASED ON ABS CABLES)

CABLE
RESISTANCE at 85 Deg.
(ohm/kM)

CABLE
REACTANCE
(ohm/kM)

15.28

0.11

9.45

0.103

5.87

0.096

3.89

0.09

2.30

0.084

1.45

0.08

0.92

0.079

0.66

0.076

0.49

0.076

0.34

0.075

0.24

0.073

0.66

0.076

0.49

0.076

0.34

0.0375

0.24

0.073

0.34

0.075

0.24

0.073

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

0.19

0.094

50
0.94
0.94
0.96

55
0.87
0.9
0.92

0.153

0.091

CABLE
RESISTANCE
(ohm/kM)

CABLE
REACTANCE
(ohm/kM)

0.153

0.091

Correction factor

1.000
1.020
1.039
1.059
1.079
1.098
1.118
1.138
1.157
1.177
1.196
1.216
1.236
1.255
1.275

Sr.No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14

HOME PAGE
1 As no.of conductors are not >4
7

10

11

Cable OD

Cable
Weight
(kg/km)

NO.
OF
CORES

9.6

110

1R x 1.5 mm2

M20

#VALUE!

#VALUE!

1.5

Earthing single
core

Gland
Type

12

13

14

SC
Cable
AWG/MCM mm2 ( KA)
Runs
( KA)

15

Earthing
Lug Size

10.4

140

1R x 2.5 mm2

M20

#VALUE!

#VALUE!

2.5

11.7

200

1R x 4 mm2

M20

#VALUE!

#VALUE!

13.1

270

1R x 6 mm

M20

#VALUE!

#VALUE!

15.5

420

1R x 10 mm2

M32

#VALUE!

#VALUE!

10

17.9

620

1R x 16 mm2

M32

#VALUE!

#VALUE!

16

21.9

970

1R x 16 mm2

M40

#VALUE!

#VALUE!

16

24.8

1300

1R x 25 mm2

M40

#VALUE!

#VALUE!

25

28.3

1710

1R x 25 mm

M50

#VALUE!

#VALUE!

25

33.2

2430

1R x 35 mm2

M50

#VALUE!

#VALUE!

35

37.8

3290

1R x 50 mm2

M50

#VALUE!

#VALUE!

50

24.8

2600

1R x 35 mm2

M40

#VALUE!

#VALUE!

35

28.3

3420

2R x 25 mm2

M50

#VALUE!

#VALUE!

25

33.2

4860

2R x 35 mm2

M50

#VALUE!

#VALUE!

35

8730

2R x 50 mm

M50

#VALUE!

#VALUE!

50

33.2

7290

3R x 35 mm2

M50

#VALUE!

#VALUE!

35

37.8

9870

3R x 50 mm2

M50

#VALUE!

#VALUE!

50

24.2

3060

2R x 70 mm

M32

#VALUE!

#VALUE!

70

24.2

4590

3R x 70 mm2

M32

#VALUE!

#VALUE!

70

24.2

6120

4R x 70 mm

M32

#VALUE!

#VALUE!

70

24.2

7650

5R x 70 mm2

M32

#VALUE!

#VALUE!

70

9180

6R x 70 mm

M32

#VALUE!

#VALUE!

70

24.2

10710

7R x 70 mm2

M32

#VALUE!

#VALUE!

70

24.2

12240

8R x 70 mm2

M32

#VALUE!

#VALUE!

70

24.2

13770

9R x 70 mm

M32

#VALUE!

#VALUE!

70

24.2

15300

10R x 70 mm2

M32

#VALUE!

#VALUE!

10

70

24.2

16830

11R x 70 mm

M32

#VALUE!

#VALUE!

11

70

24.2

18360

12R x 70 mm2

M32

#VALUE!

#VALUE!

12

70

19890

13R x 70 mm

M32

#VALUE!

#VALUE!

13

70

24.2

22950

13R x 70 mm2

M32

#VALUE!

#VALUE!

15

70

24.2

26010

13R x 70 mm2

M32

#VALUE!

#VALUE!

17

70

24.2

30600

15R x 70 mm

M32

#VALUE!

#VALUE!

20

70

60
0.79
0.82
0.86

70
0.61
0.67
0.76

37.8

24.2

24.2

24.2

1530

1R x 70 mm2

M32

10

11

Cable OD

Cable
Weight
(kg/km)

NO.
OF
CORES

45

6000

Earthing single
core
1R x 120 mm2

Gland
Type
M75

#VALUE!
12

#VALUE!
13

70

14

15

SC
Cable
AWG/MCM mm2 ( KA)
Runs
( KA)
#VALUE!

#VALUE!

Earthing
Lug Size
120

Recommended Trip Size of Circuit Breaker (AT)


Recommended Frame Size of Circuit Breaker
Amper
5400
3780
2880
2250
1800
1440
1080
720
567
360
225
144
90
80

Frame Size
6000
4200
4200
3200
2500
2000
1600
1200
800
630
400
250
160
100

Sr.No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Amper

320
200
128
80
64
50.4
40
25.6
20
12.8

TRIP SIZE
2500
2000
1600
1200
800
630
400
250
160
100
80
63
50
32
25
16

16

17

Main cable
MCT Module
current

Type of Prysmian
Catlogue

Order Qty

15

RM20

LM-HF

#N/A

20

RM20

LM-HF

27

RM20

LM-HF

34

RM20

LM-HF

850

47

RM30

LM-HF

2000

64

RM30

LM-HF

1750

3307

84

RM30

LM-HF

114

104

RM30

LM-HF

1605

129

RM40

LM-HF

1605

160

RM40

193

RM60

LM-HF

208

RM30

LM-HF

1605

258

RM40

LM-HF

13294

320

RM40

LM-HF

550

386

RM60

LM-HF

480

RM40

LM-HF

579

RM60

LM-HF

638

RM30

LM-HF

957

RM30

LM-HF

1276

RM30

LM-HF

1595

RM30

LM-HF

1914

RM30

LM-HF

2233

RM30

LM-HF

2552

RM30

LM-HF

2871

RM30

LM-HF

3190

RM30

LM-HF

3509

RM30

LM-HF

3828

RM30

LM-HF

4147

RM30

LM-HF

4785

RM30

LM-HF

5423

RM30

LM-HF

6380

RM30

LM-HF

13294

RM30

16

17

LM-HF

Main cable
MCT Module
current
2

RM30

VFD

Sr.No,

Amper

AT Size

AT Size2

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

5
9
15
18
23
29
36
45
57
65
73
82
91
105
114
123
136
150

10
15
20
25
40
40
60
60
80
80
100
100
115
115
150
150
150
185

6
10
16
20
25
32
40
50
63
72
80
90
100
115
125
135
150
165

Breaker (AT)
DOL@225

FOR FEEDER /VFD@120

You might also like