ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Overcurrent Relay Settings


Station:
Contract:
Consultant:
Contractor:
Feeder ID:

Outgoing Feeder (Typical)

Relay:

Relay Type:

Numerical

Relay Model:

Delta

Relay Make:

VATECH

CT Ratio

Prim. Current

Sec. Current

Burden, VA

Class

Rct

600/400/1

100

15 - 10

5P15

Fault Current, If

L-L Fault

L-G Fault

CT Data:

Fault Data:

6975

Min. Fault Current, A

699.83

Max. Fault Current, A

FAULT SETTING CALCULATION FOR IDMT O/C


General Data:
Overload Current:

75.6

PMS (Plug Multiplier Setting):

(125% of Full load current of Protected Object)

0.756

Curve Selected:

Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


[(PSM)0.02 - 1]:

1.48 sec

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated
Current/PMS)]

1.09

92.26

Assuming Prot. Op. time, sec:


(0.3sec)

0.1 sec

Grading Margin (0.3sec)

0.5 sec

Hence TMS: ('= (0.3+0) / (Result


from Eq.1)

.........Eq. 3

0.5

Operating time at TMS 0.125, sec


'=0.14*0.125/[(PSM)0.02 - 1]:

0.739 sec

Operating time at TMS 0.2, sec


'=0.14*0.2/[(PSM)0.02 - 1]:

0.296 sec

PMS:

0.756

TMS:

0.5

High Set
(I>>):
Is settings co-ordinated with downstream side:

273240108.xls/IDMT OC-Outgoing

.........Eq. 2

0.406

Final TMS set at:

Adopted Settings:

.........Eq. 1

(for Sample)

10xIn
Yes/No

1/3

ADDC Testing and Protection Section


Is settings co-ordinated with upstream side:

273240108.xls/IDMT OC-Outgoing

Yes/No

2/3

ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Earth Fault Relay Settings


Station:
Contract:
Consultant:
Contractor:
Feeder ID:

Outgoing Feeder (Typical)

Relay:

Relay Type:

Numerical

Relay Model:

Delta

Relay Make:

VATECH

CT Ratio

Prim. Current

Sec. Current

Burden, VA

Class

Rct

600/400/1

100

15 - 10

5P15

Fault Current, If

L-L Fault

L-G Fault

CT Data:

Fault Data:

6975

Min. Fault Current, A

699.83

Max. Fault Current, A

FAULT SETTING CALCULATION FOR IDMT O/C


General Data:
Earth Fault Current:

0.189

PMS (Plug Multiplier Setting):

0.189

Curve Selected:

Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


[(PSM)0.02 - 1]:

1.87 sec

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated
Current/PMS)]

.........Eq. 2

0.1 sec

Grading Margin (0.3sec)

0 sec

Hence TMS: ('= (0.3+0) / (Result


from Eq.1)

0.054

Final TMS set at:

.........Eq. 3

0.2

Operating time at TMS 0.2, sec


'=0.14*0.2/[(PSM)0.02 - 1]:

0.374 sec

PMS:

0.189

TMS:

0.2

High Set
(I0>>):

8xIn

Is settings co-ordinated with downstream side:

Yes/No

Is settings co-ordinated with upstream side:

Yes/No

273240108.xls/IDMT EF-Outgoing

.........Eq. 1

1.07

37.03

Assuming Prot. Op. time, sec:


(0.3sec)

Adopted Settings:

(25% of OC PMS)